7XG3130 - ReyArc Catalogue Sheet
7XG3130 - ReyArc Catalogue Sheet
7XG3130 - ReyArc Catalogue Sheet
Protection
Devices
7XG3130 – ReyArc30
Optical Arc Fault Sensor
Energy Management
7XG3130 - RA30 Description
Optical Arc Fault Sensor
The RA30(ReyArc30) is an optical sensor that responds to the
flash of light emitted during the incidence of an arcing fault.
Onset of the light flash & detection by the RA30 occurs in a
few ms.
Each arc fault sensor consists of one or two silicon PIN photo
diode light detectors mounted on a circuit board together
with the associated detection circuit (Figures 1 & 2). The
detector monitors a wide space angle. A broad spectral re-
sponse in the visible region is provided as depicted in figure
5.
Sensitivity of the arc sensor has been set to a low level to
reduce the possibility of mal operation under high ambient
lighting conditions. This is made possible due the high in-
tensity of light emitted under arc fault conditions. Additional
security can be incorporated by way of a current check
stage.
In standby mode the RA30 sensor presents a high resistance
to the 12V DC control signal provided by the Arc Fault Moni-
tor. This allows a small circulating current to flow for contin-
uous supervision of the RA30 connection circuit. When an
arc is detected, the resistance presented by the RA30 drops
to a level where the current flow increases to approximately
20mA. This increased current flow is instantaneously detect-
ed by the Arc Fault Monitor & its trip output contacts closed.
Features Refer to the RA20 Arc Fault Monitor Catalogue sheet for
further details.
Application
Arc fault protection is a technique employed for the fast clear- Figure 1:
ance of arcing faults on busbars & within metal clad switch-
gear & associated cable boxes. The arc is detected using an
optical sensor & the signal input to a protection device which
also monitors the load current on the system. A trip signal can
be achieved in less than 10ms using arc detection.
While the high intensity flash caused by an electrical arc will be
reflected within the metal clad switchgear, it is recommended
that one or more sensors be mounted in each enclosed
switchgear compartment.
For busbar protection applications multiple sensors are re-
quired to achieve adequate coverage along the length of the
bar. A sensor version with two optical detectors “looking” in
opposite directions is available for this purpose (Refer figure 3
for generic layout).
Figure 4:
For the RA30 single detector version the front detector only
is fitted. In this configuration the RA30 will be insensitive to
white light incident on the rear surface of the case up to a
Figure 2: level of 200,000 Lux.
As the illuminace of diffuse ambient sunlight falls in the
range 5,000 to 10,000 Lux, this will not normally be suffi-
Detector range cient to trigger the RA30 sensor. The luminous intensity from
the sun at noon at the equator however is ~100,000 Lux
A detection range along the 100% relative sensitivity curve which will be sufficient to trigger the RA30 sensor so
shown in figure 3 is approximately 3m. Single detector ver- measures should be made to avoid this situation.
sions therefore need to be placed at a maximum spacing of Direct sunlight incident on the rear of the RA30 single sensor
5-6m. The dual detector versions may be placed at a maxi- model will not cause it to pick up. This attribute provides a
mum spacing of 8-10m to provide adequate detection over- significant safety margin to avoid nuisance tripping when
lap. In switchgear the light caused by the arc is reflected the option of mounting the sensor externally on switchgear
from the walls & therefore, the mounting of the sensor is not as depicted in figure 6 is employed.
critical.
While the high intensity flash caused by an electrical arc will be Detector directional characteristics
reflected within the metal clad switchgear, it is recommended
that one or more sensors be mounted in each enclosed
switchgear compartment. Detector sensitivity falls to ~40% of the nominal level at
inclination angles up to 70 degrees from the normal for
white light.
100%
90%
Relative Sensitivity
Figure 3: 80%
70%
60%
50%
600 700 800 900 1,000 1,100 1,200
Wavelength (nm)
Internal partition
between switchgear
compartments
Figure 6:
RA30 shown mounted on the outside of a switchgear panel
Detector oriented to ‘look’ through a hole into the switch-
gear
Figure 9: RA30 shown mounted on the inside of a switchgear
panel. This configuration combines the functions described
in Figures 6 & 7 with the application of a single
dual detector arc fault sensor
Optical detector 2 x M4
protruding through self threading
hole in panel mounting screws
(Supplied)
Optical detector 2 x M4
facing away self threading
from panel mounting screws
(Supplied)
Hole in panel
to allow detector
to ‘look’ into
switchgear
chamber
Temperature range
Operating: -5 to +55oC
Right angle
Storage: -25 to +75oC
mounting
bracket Sensor Connections
Order Code
Serial No.
Optional second
optical detector
‘looks’ forward
through front
label window
EMEA-C10068-00-76GB
March 2016
www. siemens.com/energy