IndustrialIT System 800xA

S800 I/O System

Data Sheet

S800 I/O is a compre- General specifications CI840 For redundant PROFIBUS-DP/V1. Hot Confi-
hensive, distributed guration in Run & HART® pass-through. GSD file
Power supply: 24V d.c. (19.2 - 30V) provided.
and modular process Temperature range: 0…55°C TB840 Optical cluster modem for redundant Modulebus.
I/O system that com- Protection class: IP20 Installed on TU840/TU841. Used with AC 800M.
municates with par- Standards complied with:
ent controllers over Electrical safety: EN 3810, EN 5017-8, IEC 61131-2,
Module Termination Units (MTU:s)
industry-standard UL508, CSA 22.2 No. 142-M1987 Compact, 50V applications
Hazardous locations (Class 1, Div. 2): TU810 With screw terminals.
field buses. Thanks to CSA 22.2 No. 213-M1987, FM 3600, FM 3611, UL 1604
TU812 With 25 pin D-sub connector.
its broad connectivity Corrosive gases: ISA Class G2 (G3 pending)
TU814 With 3 crimp snap-in connectors.
it fits a wide range of Isolation test voltage: 500/2000V a.c.
Compact, 250V applications
process controllers TU811 With screw terminals.
Communication media
from ABB and others. TU813 With 3 crimp snap-in connectors.
Advant Fieldbus 100. Twisted pair screened/coaxial/fiber-
optic cable. Up to 79 stations per bus. Up to 32 per Compact for intrinsic safety
By permitting installa-
twisted-pair segment. Bus length: Up to 750m TU89X With screw terminals & isolated power supply.
tion in the field, close (2 460ft.) per twisted-pair segment overall up to: Extended, 50V applications
to sensors and actua- 15km (9.3 miles). TU830 / TU835 / TU838
tors, S800 I/O re- Profibus DP. Twisted pair screened/fiber-optic cable. Up to With screw terminals, pwr. distribution & fuse.
99 stations per bus. Up to 32 per twisted-pair TU833 With spring-cage term., pwr. distribution & fuse.
duces the installation segment. Bus length: Up to 1200m (3937ft.) per
twisted-pair segment. Extended, 250V applications
cost by reducing the
TU831 / TU836 / TU837
cost of cabling. And Communication interfaces With screw terminals, pwr. distribution & fuse.
thanks to features Redundancy, 50V applications
CI810 For Advant Fieldbus 100. Supports dual bus-cable
such as “hot swap” of redundancy. TU842 / 843 (horiz./vert. mounting) w. screw terminals.
modules, “on-line” CI801 For PROFIBUS-DP/V1. Hot Configuration in Run & TU844 / 845 (horiz./vert. mounting)
HART® pass-through. GSD-file provided. With screw terminals and shunt sticks, TY80X.
reconfiguration and
TB820 / 825 / 810 / 811 / 842. Optical cluster modem/ports TU805 For DI801 & DO801. With field power distribution
redundancy options, for ModuleBus/drives integration. screw terminals.
it contributes to
Redundant interface Station layouts
keeping production –
CI820 For redundant Advant Fieldbus 100 in combination
and thereby profits – No. of I/O modules:
with Advant Controller 400 series controllers.
Up to 24 per I/O station.
up. TB815 Interconnection Unit. An electrical and optical
Extension cable:
ModuleBus interface for coordination of the two
Plug-in, lengths: 0.3, 0.6 and 1.2m (1, 2 & 4ft).
parallell CI820 needed.
(continued overleaf)
Dimensions in mm (in.)
Optical ModuleBus: Up to 7 I/O clusters and/or 24 I/O resolution: 12 bits + sign, load: ≤500Ω (current) /
modules. Max length: 15 or 200m (49 or 656ft). ≥2kΩ (voltage), short-circuit-proof. CI810
84 (3.3) 127.5 (5.0)
S800 I/O modules I/O modules with intrinsic-safety interface
DI890 digital inputs with wire-fault detection

162 (6.4)
Digital input modules 8 ch., separate returns, 24V d.c., current sink.
DI810 16 channels, 2 groups of 8 ch., 24V d.c., current DO890 digital outputs with wire-fault detection
sink. 4 ch., separate returns, load 150-5000Ω, 11V @
DI811 16 ch., 2 groups of 8 ch., 48V d.c., current sink. 40mA, current source, short circuit-proof. CI820, TB815
DI814 16 ch., 2 groups of 8 ch., 24V d.c., current source. AI890 Analog inputs. 8 ch., single-ended, 0(4)-20mA, 12 58 (2.3) 127.5 (5.0)
bits, transmitter power supply
DI820 8 ch., separate returns, 110V d.c., 120V a.c.
AI893 TC/RTD inputs. 8 ch., TC: 7 + ref. junction, sep.

162 (6.4)
DI821 8 ch., separate returns, 220V d.c., 230V a.c. returns. TC types B, C, E, J, K, L, N, R, S, T, U,
DI825 With time tagging, 8 ch., sep. returns, 125V d.c. -10…80mV. RTD: Pt50-1000, Ni100-500, Cu10-
DI830 With time tagging. 16 ch., 2 groups of 8 ch., 24V 100, resistor 0-4000Ω, 3-wire. 15 bits + sign.
d.c., current sink. Resolution: <0.5ms. AI895 with intrinsic safety & HART interface Redundant Comm. Modules
DI831 With time tagging. 16 ch., 2 groups of 8 ch., 48V 8 ch., single-ended, 4-20mA, 12 bits, transmitter 123 (4.8) 127.5 (5.0)
d.c., current sink. Resolution: <0.5ms. power supply.
DI885 With time tagging & wire-fault detection. AO890 with intrinsic safety & wire-fault detection

162 (6.4)
8 ch., common return, 24-48V d.c., current sink. 8 ch., common return, 0(4)-20mA, 12 bits, load:
Time tagging resolution: 1ms. 750Ω (short-circuit-proof).
AO895 with intrinsic safety, HART interface & wire-
Pulse input module fault detection. 8 ch., common return, 4-20mA, 12
DP 820 2 channels, separate returns, 0.25Hz - 1.5MHz, bits, load: 750Ω (short-circuit-proof). Compact I/O
signal voltage: 5 / 24V d.c. 58 (2.3) 127.5 (5.0)
S800L I/O modules
Digital output modules

162 (6.4)
DI801 16 channels, 1 group, 24V d.c., current sink.
DO810 16 channels, 2 groups of 8 ch., 24V, max 0.5A d.c., DI802 8 ch., 110V d.c., 120V a.c.
transistor, current source, short-circuit-proof.
DI803 8 ch., 220V d.c., 230V a.c.
DO814 16 ch., 2 groups of 8 ch., 24V d.c., max 0.5A,
transistor, current sink, short-circuit-proof. DO801 16 ch., common return, 24V, max 0.5A d.c.,
transistor, current source, short-circuit-proof. Extended I/O
DO815 8 ch., 2 groups of 4 ch., 24V d.c., max 2A, 120 (4.7) 127.5 (5.0)

transistor, current source, short-circuit-proof. DO802 8 ch., 5-250V, max 2A a.c./d.c., relay (N.O.).

110 (4.3)
DO820 8 ch., separate returns, 5-250V, max 3A a.c./d.c., AI801 8 ch., single-ended, 0(4)-20mA, 12 bits.
relay (N.O.). AO801 8 ch., common return, 0(4)-20mA, 12 bits, load:
DO821 8 ch., separate returns, 5-250V, max 3A a.c./d.c., <750Ω.
relay (N.C.). Intrinsic safety I/O
S800 I/O modules for redundancy & SIL3
58 (2,3) 127.5 (5.0)
Analog input modules DI840 16 channels, common return, 24V d.c., current
AI810 8 channels, single-ended, 0(4)-20mA, 0(2)-10V, 12 sink, extended diagnostics.

194 (7,6)
bits. DI880 16 ch., 24V d.c., current sink, SIL3, extended
AI820 Differential inputs, 4 ch., 0(1)-5V, ±0(2)-10V, diagnostics.
±0(4)-20mA, 14 bits + sign. DP840 8 ch., sep. returns, freq. measurement or pulse
AI825 Galvanically isolated, 4 ch., ±0(2)-10V, ±0(4)- counting, 0.5-20 kHz, 12/24V d.c or NAMUR.
20mA, 14 bits + sign. DO840 16 ch., common return, 24V d.c., max. 0,5A, Redundant I/O
AI830 RTD inputs, 8 ch., Pt100, Ni100, Ni120, Cu10, current source, short-circuit-proof, extended 123 (4.8) 127.5 (5.0)
resistor 0-400Ω, 14 bits, 3-wire. diagnostics.

162 (6.4)
AI835 TC inputs, 8 ch., (7+ ref. junction), separate D0880 16 ch., 24V d.c., max. 0.5A, current source, SIL3,
returns. TC types B, C, E, J, K, N, R, S, T, - short-circuit-proof, extended diagnostics.
30…75mV, 15 bits. AI843 TC input, 8 ch. + ref. junction. TC types: B, C, E, J,
K, L, N, R, S, T, U, -30…75mV, 16 bits, extended
Analog output modules diagnostics. CI801, S800L I/O
AO810 8 channels, common return, 0(4)-20mA, 14 bits, AI845 8 ch., common return, 0(4)-20mA 0(1)-5V, 86 (3.4) 58.5 (2.3)
load: 850Ω (short-circuit-proof). extended diagnostics, HART support.
AO820 Isolated output. 4 ch., separate returns, AI880A 8 ch., common return, 0(4)-20mA, SIL3, extended
136 (5.4)

measuring range: ±0(2)-10V, ±0(4)-20mA, diagnostics, HART support.


AO845 8 ch., common return, 4-20mA, extended
Produced by R&B TeknikTransfer HB, Västerås, Sweden.

diagnostics, HART support.

Automation Technologies Automation Technologies Automation Technologies


Västerås, Sweden Wickliffe, Ohio, USA Mannheim, Germany
Phone: +46 (0) 21 34 20 00 Phone: +1 440 585 8500 Phone: +49 (0) 1805 26 67 76
Fax: +46 (0) 21 13 78 45 Fax: + 1 440 585 8756 Fax: +49 (0) 1805 77 63 29
www.abb.com/controlsystems www.abb.com/controlsystems www.abb.de/controlsystems
e-mail: [email protected] e-mail: [email protected] e-mail: [email protected]

3BSE025986R0401
© Copyright 2005 ABB. All rights reserved. Specifications subject to change without notice. Pictures, schematics and other graphics contained herein are published
for illustration purposes only and do not represent product configurations or functionality. User documentation accompanying the product is the exclusive source for
functionality descriptions. The IndustrialIT wordmark, Aspect Objects, and all above-mentioned names in the form XXXXXXIT are registered or pending trademarks of
ABB. All rights to other trademarks reside with their respective owners.