Actuators
Digitally configurable proportional
push actuator – 160/200 N
IMI TA / Actuators / TA-Slider 160
TA-Slider 160
Digitally configurable actuators with or without KNX Bus communication,
and a wide range of setup options provide extensive flexibility for on-
site parameter adaptation. Fully programmable binary input, relay and
adjustable max. stroke of the valve bring new opportunities for advanced
hydronic control and balancing.
Key features
>> Convenient, reliable setup >> Quick copying of settings
Fully customisable by smartphone via Setup configuration can be copied
Bluetooth using a TA-Dongle. quickly from the TA-Dongle to identical
(Not for KNX versions) TA-Slider actuators.
(Not for KNX versions)
>> Fully configurable
More than 200 setup options allow >> Perfection in connectivity
input and output signals, binary input, A separate version allows configuring
relay, characteristics and many other and communicating via KNX Bus.
parameters to be configured.
Technical description
Function
Setting TA-Slider 160, 160 I/O, 160 Plus LED indication
The actuator can be set by the HyTune app (iOS version 8 or
Status Red (heating) /
later on iPhone 4S or later, Android version 4.3 or later) + the
Blue (cooling)
TA-Dongle device, with or without the actuator power supplied.
The setting configuration can be stored in the TA-Dongle for Fully retracted (actuator stem) Long pulse - (–· –· –·)
setting of one or several actuators. Connect the TA-Dongle to Short pulse
the actuator and press the configuration button. Fully extended (actuator stem) Short pulse - (·– ·– ·–)
HyTune can be downloaded from the App Store or Google Play. Long pulse
Intermediate position Long pulses (– – –)
Moving Short pulses (· · ·)
Calibrating 2 short pulses (·· ·· ··)
Manual mode or no power supply Off
*) Default
Note: A calibration refresh can be automatically repeated
monthly or weekly.
Manual override (not for KNX/KNX R24 versions) Default setting: Off.
By using the TA-Dongle device. No power supply needed.
Self-adjusting force
Automatic valve type detection, the force is set to 160 or 200 N
for IMI TA/IMI Heimeier valves.
Default setting: On.
3
IMI TA / Actuators / TA-Slider 160
Stroke limitation setting I/O, Plus, KNX and KNX R24 versions:
The stroke can be set to a percentage (20-100%) of detected Binary input
valve lift. If the binary input circuit is open, the actuator will go to a set
For some IMI TA/IMI Heimeier valves it can also be set to a stroke or switch to a second stroke limitation setting. See also
Kvmax/qmax. Change-over system detection.
Default setting: No stroke limitation (100%). Default setting: Off
Valve blockage protection Change-over system detection
The actuator will perform a quarter of a full stroke and then back Switching between two different stroke limitation settings by
to desired value if no actuation takes place for one week or one toggling the binary input or using the dual-range input signal.
month. For the KNX versions, this switching may also be made via KNX
Default setting: Off. Bus.
Valve clogging detection KNX and KNX R24 versions:
If actuation stops before the desired value is reached, the
actuator moves back ready to make a new attempt. The Connection interfaces for KNX Bus communication
actuator will move to the configured error safe position after Twisted pair; KNX/TP
three attempts.
Default setting: On.
Diagnostics/logging
The last 10 errors (low power, line break, valve clogging, stroke
detection failure) with time stamps can be read using the
HyTune app + TA-Dongle device. Logged errors will be cleared if
the power is disconnected.
Installation
IP54
X
Ø22.5
Note!
4
Connection diagram
TA-Slider 160 TA-Slider 160 I/O TA-Slider 160 Plus
M M M
L24 M Yv L24 M Yv Xv B L24 M Yv Xv B COM NC NO
Brown
Brown
Brown
Yellow
Brown
White
White
Yellow
Green
Green
White
Green
Black
Grey
Grey
Grey
24 VAC/VDC 24 VAC/VDC 24 VAC/VDC
0 VAC/VDC 0 VAC/VDC 0 VAC/VDC
0(2)..10 VDC 0(2)..10 VDC 0(2)..10 VDC
0(2)..10 VDC 0(2)..10 VDC
M M
- + B M - + B M COM NC NO
Dk Green
Yellow
White
Orange
Black
Yellow
White
Violet
Red
Black
Red
-
-
+ KNX Bus
+ KNX Bus
Terminal Description
L24 Power supply 24 VAC/VDC
M Neutral for power supply 24 VAC/VDC and signals. (For KNX, only used for potential free contact)
YV Input signal for proportional control 0(2)-10 VDC, 47 kΩ
XV Output signal 0(2)-10 VDC, max. 8 mA or min. load resistance 1.25 kΩ
B Connection for potential free contact (e.g. open window detection), max. 100 Ω, max. 10 m cable or shielded
COM Plus version: Common relay contact, max. 250 VAC, max. 5A @ 250 VAC on resistive load, max. 5A @ 30 VDC on resistive load.
KNX R24 version: Common relay contact, max. 30 VAC/VDC, max. 2A on resistive load.
NC Normally closed contact for relay
NO Normally open contact for relay
5
IMI TA / Actuators / TA-Slider 160
Articles
78 24 TA-Slider 160
Input signal: 0(2)-10 VDC
6
78 24 TA-Slider 160 KNX
Twisted pair; KNX/TP
Additional equipment
TA-Dongle
For Bluetooth communication with the EAN Article No
HyTune app, transfer configuration 5901688828632 322228-00001
settings and manual override.
130
(Not for KNX versions)
77 18
Programming magnet
For programming the physical addresses EAN Article No
without contact. 4024052149919 1865-01.433