CP850/1000/1350/1500AVRLCD User's Manual: Product Registration

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

1.

Power Switch
Used as the master on/off switch for equipment connected to the battery power supplied outlets. (Please refer to the Function Setup Guide
for more information.)
CP850/1000/1350/1500AVRLCD 2. Power On Indicator
This LED is illuminated when the utility power is normal and the UPS outlets are providing power, free of surges and spikes.
User’s Manual K01-0000501-02 3. LCD module display
The LCD display shows all the UPS information using icons and messages. For more information please review the “Definitions for Illuminated
LCD Indicators” section below.
PRODUCT REGISTRATION 4. Display/Select Button
Thank you for purchasing a CyberPower product. Please take a few minutes to register your product in Registration section at The button can be used to select the LCD display contents including Input Voltage, Output Voltage, and Estimated Run Time. Short press the
www.cyberpower.com/registration. Registration certifies your product's warranty, confirms your ownership in the event of a product loss or theft button to scroll down the function menu. Pressing the button for 3 seconds will keep the LCD display always on or turn the LCD display off while
and entitles you to free technical support. Register your product now to receive the benefits of CyberPower ownership. in AC/Utility power mode. For more information, please refer to the Function Setup Guide.
5. Mute/Enter Button
IMPORTANT SAFETY INSTRUCTIONS Holding the button for more than 3 seconds will silence the alarm. Short press the ENTER button to confirm the setting. After the setting has
been confirmed, the LCD screen will stop flashing. For more information, please refer to the Function Setup Guide
(SAVE THESE INSTRUCTIONS) 6. Battery and Surge Protected Outlets
This Manual Contains Important Instructions that should be followed during Installation and Maintenance of the UPS and batteries. The UPS has battery powered/surge suppression outlets for connected equipment to ensure temporary uninterrupted operation of your
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area free of conductive contaminants. equipment during a power failure. (DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum, sump pump or other
(Please see specifications for acceptable temperature and humidity range). large electrical devices into the “Battery and Surge Protected Outlets”. The power demands of these devices may overload and
CAUTION! To reduce the risk of electric shock, do not remove the cover except to service the battery. Turn off and unplug the unit before servicing damage the unit.)
the batteries. There are no user serviceable parts inside except for the battery. 7. Full-Time Surge Protection Outlets
CAUTION! Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected. The UPS has surge suppression outlets.
CAUTION! The UPS must be connected to an AC power outlet with fuse or circuit breaker protection. Do not plug into an outlet that is not 8. Circuit Breaker
grounded. If you need to de-energize this equipment, turn off and unplug the unit. Located on the back of the UPS, the circuit breaker serves to provide overload and fault protection.
CAUTION! To avoid electric shock, turn off the unit and unplug it from the AC power source before servicing the battery. 9. Serial/USB Ports to PC
CAUTION! Not for use in a computer room as defined in the Standard for the Protection of Electronic Computer/Data Processing Equipment, The USB port allows connection and communication between the USB port on the computer and the UPS unit.
ANSI/NFPA 75. 10. Communication Protection Ports
CAUTION! To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit over current protection in Communication protection ports, bi-directional, will protect a 10/100/1000 Ethernet connection (RJ45).
accordance with the National Electric Code, ANSI/NFPA 70. 11. Wiring Fault Indicator (red)
DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! CyberPower Systems does not sell products for life support or medical This LED indicator will illuminate to warn the user that a wiring problem exists, such as bad ground, missing ground or reversed wiring. If this is
applications. DO NOT use in any circumstance that would affect the operation and safety of life support equipment, medical applications, or patient illuminated, disconnect all electrical equipment from the outlet and have an electrician verify the outlet is properly wired. The UPS will not provide
care. surge protection without being plugged into a grounded and properly wired wall outlet.
DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire or electric shock, do not use with or near an aquarium. Condensation 12. Coax/Cable/DSS Surge Protection
from the aquarium can cause the unit to short out. The Coax/Cable/DSS protection ports will protect any cable modem, CATV converter, or DSS receiver.
DO NOT USE THE UPS ON ANY TRANSPORTATION! To reduce the risk of fire or electric shock, do not use the unit on any transportation such as 13. Outlets Designed for AC Adapters
airplanes or ships. The effect of shock or vibration caused during transit and the damp environment can cause the unit to short out. The unit has two outlets spaced to allow AC power adapter blocks to be plugged into the UPS without blocking adjacent outlets.
REPLACING THE BATTERY
INSTALLING YOUR UPS SYSTEM Replacement of batteries located in an OPERATOR ACCESS AREA.
1. When replacing batteries, replace with the same number of the following battery: CyberPower / RB1290 for the CP850/1000AVRLCD;
INTRODUCTION
CyberPower / RB1290X2 for the CP1350/1500AVRLCD
Thank you for selecting a CyberPower Systems UPS product. This UPS is designed to provide unsurpassed power protection, operation and
2. CAUTION! Risk of Energy Hazard, 12 V, maximum 9 Ampere-hour battery for CP850/1000AVRLCD; 24 V, maximum 9 Ampere-hour battery
performance during the lifetime of the product.
for CP1350/1500AVRLCD. Before replacing batteries, remove conductive jewelry such as chains, wrist watches, and rings. High energy

UNPACKING conducted through these materials could cause severe burns.

Inspect the UPS upon receipt. The box should contain the following: 3. CAUTION! Do not dispose of batteries in a fire. The batteries may explode.
4. CAUTION! Do not open or mutilate batteries. Released material is harmful to the skin and eyes. It may be toxic.
(a) UPS (b) User’s manual (c) USB A+B type cable (d) Function Setup Guide
5. CAUTION: A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when
*PowerPanel® Personal Edition software is available on our website. Please visit www.cyberpower.com and go to the Software Section for
free download. working on batteries:
1) Remove watches rings, or other metal objects.
OVERVIEW 2) Use tools with insulated handles.
The CP850/1000/1350/1500AVRLCD provides complete power protection from utility power that is not always consistent. CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE OF USED BATTERIES ACCORDING TO
The CP850/1000AVRLCD features 1080 Joules and the CP1350/1500AVRLCD features 1500 Joules of surge protection. LOCAL REGULATIONS.
The unit provides long lasting battery backup during power outages with maintenance free batteries. BATTERY REPLACEMENT PROCEDURE:
The CP850/1000/1350/1500AVRLCD ensures consistent power to your computer system and includes
CP850/1000/1500AVRLCD
software that will automatically shut down your computer system during a utility power loss.
1. Turn off and unplug all connected equipment.
AUTOMATIC VOLTAGE REGULATOR 2. Turn the UPS off and unplug it from the AC power source.
The CP850/1000/1350/1500AVRLCD stabilizes inconsistent utility power voltage to nominal levels that are 3. Turn the UPS on its side.
4. Remove the front panel retaining screws located on the bottom of the UPS.
safe for equipment. Inconsistent incoming utility power may be damaging to important data files and hardware,
5. Slide the battery compartment cover (front panel) completely off of the unit.
but with Automatic Voltage Regulation (AVR), damaging voltage levels are corrected to safe levels. AVR
6. Disconnect the battery wires from the batteries.
automatically increases low utility power or decreases high utility power to a consistent and safe 110/120
7. Remove the batteries from the compartment.
volts. 8. CP850/1000AVRLCD: Install the replacement batteries by connecting the red wire (+) and black wire (-) to the same color connectors.
9. CP1500AVRLCD: Install the replacement batteries by connecting the red wire (+) and black wire (-) to the same color connectors from both the
HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT
upper and lower battery pack. Note: Only use new batteries for replacement and both batteries should be replaced at the same time to ensure
1. Ensure that the equipment plugged into the outlet does not exceed the UPS’s rated capacity (850VA/510W for CP850AVRLCD,
maximum life span.
1000VA/600W for CP1000AVRLCD, 1350VA/815W for CP1350AVRLCD, 1500VA/900W for CP1500AVRLCD. If the rated capacity of the unit is
10. Put the batteries back into the compartment.
exceeded, an overload condition may occur and cause the UPS to shut down or the circuit breaker to trip. 11. Slide back the battery compartment cover and tighten the retaining screws.
2. There are many factors that can affect the amount of power that your computer system will require. It is suggested that the load placed on the 12. Recharge the UPS for 8-16 hours to fully charge the battery.
battery outlets not exceed 80% of the unit’s capacity.
CP850/1000AVRLCD
HARDWARE INSTALLATION GUIDE
1. Your new UPS may be used immediately upon receipt. However, after receiving a new UPS, to ensure the
battery’s maximum charge capacity, it is recommended that you charge the battery for at least 8 hours.
Your UPS is equipped with an auto-charge feature. When the UPS is plugged into an AC outlet, the
battery will automatically charge whether the UPS is turned on or off.
2. Note: This UPS is designed with a safety feature to keep the system from being turned on during shipment.
The first time you turn the UPS on, you will need to have it connected to AC power or it will not power up. CP1500AVRLCD
3. With the UPS unit turned off and unplugged, connect your computer, monitor, and any other peripherals requiring battery backup into the battery
power supplied outlets. DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum, sump pump or other large electrical
devices into the “Battery and Surge Protected Outlets”. The power demands of these devices may overload and damage the UPS.
4. Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is protected by a fuse or circuit breaker
and does not service equipment with large electrical demands (e.g. air conditioner, copier, etc…).
The warranty prohibits the use of extension cords, outlet strips, and surge strips.
5. Press the power switch to turn the unit on. The Power On indicator light will illuminate and the unit will “beep”. CP1350AVRLCD
If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and unplug at least 1. Turn off and unplug all connected equipment.
one piece of equipment from the battery power supplied outlets. Make sure the circuit breaker is depressed and then turn the UPS on. 2. Turn the UPS off and unplug it from the AC power source.
3. Turn the UPS on its side.
6. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times.
4. Remove two retaining screws located on the bottom of the UPS.
7. To store the UPS for an extended period, cover it and store with the battery fully charged. While in storage, recharge the battery every three
5. Slide the battery compartment cover completely off of the unit.
months to ensure battery life.
6. Remove the battery which is located on the right side from the compartment.
8. Ensure the wall outlet and UPS are located near the equipment being attached for proper accessibility. 7. Disconnect the battery wires from the right side of the battery.
8. Slide the remaining battery from left to right and remove it from the compartment.
BASIC OPERATION 9. Disconnect the battery wires from the remaining battery.
10. Install the "left side" replacement battery by connecting the yellow wire (+) to the red connector from the battery and the black wire (-) to the
DESCRIPTION black connector from the battery. Place the battery into the left side of the compartment.
11. Install the "right side" replacement battery by connecting the red wire (+) to the red connector from the battery and yellow wire (-) to the black
connector from the battery. Place the battery into the right side of the compartment. Note: Only new batteries should be used for replacement
and both batteries should be replaced at the same time to insure maximum life span.
12. Slide back the battery compartment cover and tighten the retaining screws.
13. Recharge the UPS for 8-16 hours to fully charge the battery.

Yellow Wire to (+)Red Connector Red Wire to (+)Red Connector


Black Wire to (-)Black Connector Yellow Wire to (-)Black Connector

REMINDER: Batteries are considered HAZARDOUS WASTE and must be disposed of properly. Most retailers that sell lead-acid batteries collect
CP1500AVRLCD used batteries for recycling, as required by local regulations.
CP850/1000AVRLCD CP1350AVRLCD
DEFINITIONS FOR ILLUMINATED LCD INDICATORS FCC Compliance Statement
FCC Compliance Statement
This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful
interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and
can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the
1. INPUT voltage meter: interference by one or more of the following measures:
This meter measures the AC voltage that the UPS system is receiving from the utility wall outlet. The UPS is designed, through the use of - Reorient or relocate the receiving antenna.
automatic voltage regulation, to continuously correct output voltage to connected equipment to a safe 120 voltage output range. In the event of
- Increase the separation between the equipment and receiver.
a complete power loss, severe brownout, or over-voltage, the UPS relies on its internal battery to supply consistent 110/120 output voltage.
- Connect the equipment to an outlet on a circuit different from that to which the receiver is connected.
The INPUT voltage meter can be used as a diagnostic tool to identify poor-quality input power.
2. OUTPUT voltage meter: - Consult the dealer or an experienced radio/TV technician for help"
This meter measures, in real time, the AC voltage that the UPS system is providing to the computer, such as normal line mode, AVR mode, Warning: Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the
and battery backup mode. (Note: The OUTPUT voltage meter shows the status of the battery backup outlets.) equipment.
3. ESTIMATED RUN TIME: Canadian Compliance Statement
This displays the run time estimate of the UPS with current battery capacity and load. CAN ICES-3 (B)/NMB-3(B)
4. NORMAL icon:
This icon appears when the UPS is working under normal conditions.
5. BATTERY icon: CYBERPOWER GREENPOWER UPS™ TECHNOLOGY
During a severe brownout or blackout, this icon appears and an alarm sounds (two short beeps followed by a pause) to indicate the UPS is
operating from its internal batteries. During a prolonged brownout or blackout, the alarm will sound continuously to indicate the UPS’s batteries Advanced Energy-Saving Patented Bypass Technology
are nearly out of power. You should save files and turn off your equipment immediately or allow the software to shut the system down. CyberPower’s patented GreenPower UPS™ with Bypass Technology reduces UPS energy costs by up to
6. AVR (Automatic Voltage Regulation) icon:
75% compared to conventional UPS models. Even when utility power is normal, conventional UPS models
This icon appears whenever your UPS is automatically correcting low AC line voltage without using battery power. This is a normal, automatic
operation of your UPS, and no action is required on your part. constantly pass power through a transformer. By contrast, under normal conditions the advanced circuitry
7. SILENT MODE icon: of a GreenPower UPS™ bypasses the transformer. As a result, the power efficiency is significantly
This icon appears whenever the UPS is in silent mode. increased while decreasing waste heat, using less energy, and reducing energy costs.
8. OVER LOAD icon:
When an abnormal power condition occurs, the GreenPower UPS™ automatically runs power through its
This icon appears and an alarm sounds to indicate the battery-supplied outlets are overloaded. To clear the overload, unplug some of your
equipment from the battery-supplied outlets until the icon turns off and the alarm stops. transformer to regulate voltage and provide “safe” power. Since utility power is normal over 88% of the time, the GreenPower UPS™ operates
9. FAULT icon: primarily in its efficient bypass mode.
This icon appears if there is a problem with the UPS, Contact CyberPower Systems at for further help and support. The GreenPower UPS™ is also manufactured in accordance with the Restriction on Hazardous Substances (RoHS) directive making it one of the
E01: Charger Fault – Overcharge (Contact CyberPower Systems for support.)
most environmentally-friendly on the market today.
E02: Charger Fault – No Charge (Contact CyberPower Systems for support.)
E11: Battery Overvoltage (Contact CyberPower Systems for support.)
E21: Battery Output Short Fault (Turn on the UPS again.)
E22: Battery Mode or AC/Utility Power Mode Overload Fault (Unplug at least one piece of equipment from battery outlets and turn the UPS Limited Warranty and Connected Equipment Guarantee
on again.)
10. BATT. CAPACITY meter: Read the following terms and conditions carefully before using the CyberPower CP850/1000/1350/1500AVRLCD (the “Product”). By using the
This meter displays the approximate charge level (in 20% increments) of the UPS’s internal battery. During a blackout or severe brownout, the Product you consent to be bound by and become a party to the terms and conditions of this Limited Warranty and Connected Equipment Guarantee
UPS switches to battery power, the BATTERY icon appears, and the charge level decreases. (together referred to as this “Warranty”). If you do not agree to the terms and conditions of this Warranty, you should return the Product for a full
11. LOAD CAPACITY meter: refund prior to using it.
This meter displays the approximate output load level (in 20% increments) of the UPS battery outlets.
Who is Providing this Warranty?
For more information about functions setup, please refer to the Function Setup Guide. Cyber Power Systems (USA), Inc. (“CyberPower”) provides this Limited Warranty.
What Does This Warranty Cover?
TROUBLESHOOTING This warranty covers defects in materials and workmanship in the Product under normal use and conditions. It also covers equipment that was
connected to the Product and damaged because of the failure of the Product.
What is the Period of Coverage?
Problem Possible Cause Solution This warranty covers the Product for three years and connected equipment for as long as you own the Product.
Who Is Covered?
Circuit breaker button is Turn the UPS off and unplug at least one piece of This warranty only covers the original purchaser. Coverage ends if you sell or otherwise transfer the Product.
Circuit breaker has tripped due to an
projecting from the back of the equipment. Wait 10 seconds, reset the circuit breaker by How Do You Get Warranty Service?
overload.
unit. depressing the button, and then turn the UPS on. 1. Before contacting CyberPower, identify Your Product model number, the Purchase Date, and each item of Connected Equipment (E.G.
Computer tower, Computer Monitor, Ink Jet Printer, Cable Modem, etc).
Battery not fully charged. Recharge the battery by leaving the UPS plugged in.
2. Visit our web site at http://www.cpsww.com/support or Call us at (877) 297-6937.
The UPS does not perform
Contact CyberPower Systems about replacement batteries 3. If your product requires warranty service you must provide a copy of your dated purchase receipt or invoice.
expected runtime. Battery is worn out.
at [email protected] How Do You Open A Connected Equipment Claim?
1. Call us at (877) 297-6937 or write to us at Cyber Power Systems (USA), Inc., 4241 12th Ave. E., STE 400, Shakopee, MN 55379, or send us
The on/off switch is designed to an e-mail message at [email protected] for instructions, within 10 days of the occurrence.
Turn the UPS off. Wait 10 seconds and then turn the UPS
prevent damage from rapidly turning 2. When you contact CyberPower, identify the Product, the Purchase Date, and the item(s) of Connected Equipment. Have information on all
on.
it off and on. applicable insurance or other resources of recovery/payment that are available to the Initial Customer and Request a Claim Number.
The unit is not connected to an AC 3. You must provide a dated purchase receipt (or other proof of the original purchase) for the CyberPower unit and connected equipment. You
The unit must be connected to a 120V 60Hz outlet. also need to provide a description of the damage to your connected equipment.
outlet.
The UPS will not turn on. 4. Pack and ship the product to CyberPower and, if requested, the item(s) of Connected Equipment, a repair cost estimate for the damage to the
Contact CyberPower Systems about replacement batteries Connected Equipment, and all claim forms that CyberPower provides to you. Show the Claim Number on the shipping label or include it with
The battery is worn out.
at [email protected] the product. You must prepay all shipping costs, you are responsible for packaging and shipment, and you must pay the cost of the
repair estimate.
Mechanical problem. Contact CyberPower Systems at [email protected] How Long Do I Have To Make A Claim?
All claims must be made within ten days of the occurrence.
Connect the USB cable to the UPS unit and an open USB What Will We Do To Correct Problems?
The USB cable is not connected. port on the back of the computer. You must use the cable CyberPower will inspect and examine the Product.
that came with the unit. If the Product is defective in material or workmanship, CyberPower will repair or replace it at CyberPower's expense, or, if CyberPower is unable to or
decides not to repair or replace the Product (if defective) within a reasonable time, CyberPower will refund to you the full purchase price you paid for
PowerPanel® Personal Edition is The USB cable is connected to the Check the back of the computer for an additional USB port. the Product (purchase receipt showing price paid is required).
inactive (all icons are gray). wrong port. Move the cable to this port. If it appears that our Product failed to protect any equipment plugged into it, we will also send you forms for making your claim for the connected
Shutdown your computer and turn the UPS off. Wait 10 equipment. We will repair or replace the equipment that was damaged because of the failure of our Product or pay you the fair market value (NOT
The unit is not providing battery REPLACEMENT COST) of the equipment at of the time of the damage. We will use Orion Blue Book, or another a third-party valuation guide, or
seconds and turn the UPS back on. This should reset the
power. eBay, craigslist, or other source to establish that amount. Our maximum liability is limited to $250,000 for the CP850AVRLCD; $350,000 for the
unit.
CP1000AVRLCD; $500,000 for the CP1350/1500AVRLCD;
Additional troubleshooting information can be found under “Support” at www.cyberpower.com Who Pays For Shipping?
We pay when we send items to you; you pay when you send items to us.
What isn’t covered by the warranty?
TECHNICAL SPECIFICATIONS 1. This Warranty does not cover any software that was damaged or needs to be replaced due to the failure of the Product or any data that is lost
as a result of the failure or the restoration of data or records, or the reinstallation of software.
2. This Warranty does not cover or apply to: misuse, modification, operation or storage outside environmental limits of the Product or the
Model CP850AVRLCDa CP1000AVRLCDa CP1350AVRLCDa CP1500AVRLCDa equipment connected to it, nor for damage while in transit or in storage, nor if there has been improper operation or maintenance, or use with
items not designed or intended for use with the Product, such as laser printers, appliances, aquariums, medical or life support devices, etc.
What are the Limitations?
Capacity 850VA / 510W 1000VA / 600W 1350VA / 815W 1500VA / 900W
The sole and exclusive remedies of the Initial Customer are those provided by this Warranty.
1. This Warranty does not apply unless the Product and the equipment that was connected to it were connected to properly wired and grounded
Nominal Input Voltage 120V
outlets (including compliance with electrical and safety codes of the most current electrical code), without the use of any adapters or other
connectors.
Input Frequency 60 Hz ± 3 Hz
2. The Product must have been plugged directly into the power source and the equipment connected to the Product must be directly connected
to the Product and not “daisy-chained” together in serial fashion with any extension cords, another Product or device similar to the Product,
On-Battery Output Voltage 120Vac ± 5%
surge suppressor, or power tap. Any such installation voids the Limited Warranty.
Max. Load for UPS Outlets 3. The Product and equipment connected to it must have been used properly in a suitable and proper environment and in conformance with any
850VA / 510W 1000VA / 600W 1350VA / 815W 1500VA / 900W
(5 Outlets) license, instruction manual, or warnings provided with the Product and the equipment connected to it.
Max. Load for Full-Time 12 Amp 12 Amp 12 Amp 4. The Product must have been used at all times within the limitations on the Product’s VA capacity.
Surge Protection outlets (9 outlets) (10 outlets) (12 outlets) The Product was designed to eliminate disrupting and damaging effects of momentary (less than 1ms) voltage spikes or impulses from lightning or
On-Battery Output Wave other power transients. If it can be shown that a voltage spike lasting longer than 1ms has occurred, the occurrence will be deemed outside the
Simulated Sine Wave rated capabilities of the Product and the Limited Warranty is void. CyberPower Does Not Cover or Undertake Any Liability in Any Event for Any of the
Form
Following:
Operating Temperature + 32°F to 104° F / 0° C to 40° C 1. Loss of or damage to data, records, or software or the restoration of data or records, or the reinstallation of software.
2. Damage from causes other than AC Power Line Transients, spikes, or surges on properly installed, grounded and code-compliant 120 volt
Operating Relative Humidity 0 to 90% non-condensing power lines in the United States and Canada; transients, surges or spikes on standard telephone land lines, PBX telephone equipment lines or
Base 10T Ethernet lines, when properly installed and connected. (This exclusion applies, for example, to fluctuations in data transmission or
3.9" x 9.8" x 13.7" 3.9" x 11" x 14"
Size (W x H x D) 3.9" x 9.0" x 10.2" (100*227.5*260mm) reception, by CATV or RF transmission or fluctuations, or by transients in such transmission.)
(99 x 249 x 348 mm) (100 x 280 x 355 mm)
3. Damage from any circumstance described as excluded above with respect to the Product.
Net Weight 15.0lbs / 6.8kg 22.2lbs / 10.1kg 25lbs / 11.3kg 4. Damages from fire, flood, wind, rain, rising water, leakage or breakage of plumbing, abuse, misuse or alteration of either the product or the
Connected Equipment.
Battery Type CyberPower / RB1290 CyberPower / RB1290X2 CyberPower / RB1290X2 5. CyberPower excludes any liability for personal injury under the Limited Warranty and Connected Equipment Guarantee. CyberPower excludes
any liability for direct, indirect, special, incidental or consequential damages, whether for damage to or loss of property [EXCEPT FOR (AND
Typical Battery Recharge
8 hours ONLY FOR) the specific limited agreement of CyberPower to provide certain warranty benefits regarding "Connected Equipment" under this
Time
Warranty], loss of profits, business interruption, or loss of information or data. NOTE: Some States or Provinces do not allow the exclusion or
Typical Battery Life 3 to 6 years, depending on number of discharge/recharge cycles limitation of incidental or consequential damages, so the above limitation may not apply to you.
6. The Product is not for use in high-risk activities or with aquariums. The Product is not designed or intended for use in hazardous environments
Recommended Battery Sealed Maintenance Free Lead Acid Battery requiring fail-safe performance, or for use in any circumstance in which the failure of the Product could lead directly to death, personal injury,
or severe physical or property damage, or that would affect operation or safety of any medical or life support device (collectively, "High Risk
Safety Approvals UL1778(UPS), cUL107., FCC/DoC Class B Activities"). CyberPower expressly disclaims any express or implied warranty of fitness for High Risk Activities or with aquariums. CyberPower
does not authorize use of any Product in any High Risk Activities or with Aquariums. ANY SUCH USE IS IMPROPER AND IS A MISUSE OF
THE PRODUCT.
SYSTEM FUNCTIONAL BLOCK DIAGRAM Where Can I Get More Information?
The application of the United Nations Convention of Contracts for the International Sale of Goods is expressly excluded.
EMI Surge CyberPower is the warrantor under this Limited Warranty.
Input Filter Suppressor AVR Output
For further information please feel free to contact CyberPower at Cyber Power Systems (USA), Inc. 4241 12th Ave E., STE 400, Shakopee, MN 55379;
call us at (877) 297-6937; or send us an e-mail message at [email protected].

Charger Cyber Power Systems (USA), Inc. encourages environmentally sound methods for disposal and recycling of its UPS products.
AC/DC Inverter
Please dispose and/or recycle your UPS and batteries in accordance to the local regulations of your state.
Normal Mode
All rights reserved. Reproduction without permission is prohibited.
Battery Mode
Battery