C.H. - 0+465.5 Section No5

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 1

NOTES

SECTION No5
C.H. - 0+465.5

#######

Retaining
Concrete Wall

GRP Junction box c/w disconnection


link for testing. For further details
see elevation drawing ME-01-30X 1990 2520 1022 13400
GRP Earthing enclosure c/w disconnetion links for
testing and maintenance to be installed on the wall

Ø50mm hot dipped galvanized


steel conduit drops to connect to
160 PE ducting in the ground

#######
160 Auxiliary earth rod electrodes
Ø50mm hot dipped galvanized Backfill material
installed in concrete manhole 410

545 300 350


steel conduit drop on the wall Exothermic welded connection
to ground level. 95mm² earth to join cable and rod
Ø200 ####### cable buried in
the ground runs
472 300 350

95mm² earth cable embedded in


500

in Ø63mm PE
concrete rise to connect to GRP
Duct
enclosure mounted on the external

300
Backfilling side of the retaining wall

763
to bond the fence and to connect
Auxiliary earth electrode to auxiliary earth rod located outside.
housed in PE Earth Pit 150x150mm stainless steel
junction box
Scale 3:1 @ A1
Exothermic
Welding 95mm2 earth (insulated) cable runs Earth rod

4800
Connection embedded in concrete 20Ømm opening in the concrete length has been sized
countervault structure diaphragm wall (C.H. 0+465.50) for the according to BS7430 and soil
95 mm² earth cable to 95mm² earth cable to pass through the wall resistity tests.
4800

Earth rod run in Ø63mm PE duct in Earth rod


length has been sized the ground to connect to electrode tip
according to BS7430 and soil earth rod
resistity tests. 2000
2951 95mm² earth cable embedded in concrete
Ø50mm stainless steel conduit
runs along the whole length of the retaining wall.
at high level fixed directly to
2000 At this position CH. 0+451,
A T piece will be welded to take off a branch to connect
Min. 90° bend for ducting concrete ceiling Cable ladder 400x85mm
duct connects to back of GRP
to the steel re-bars cast in the concrete to earth system 1770 enclosure
as per detail drawing - MS-01-40X
Cable ladder 400x85mm Cable tray 300x60mm
Earth rod Exothermic Welding Cable / Cable Cable tray 300x60mm Ø63mm PE ducting cast in the
electrode tip concrete slab and retaining Cable tray 300x60mm
wall. 95mm² general earth
Conduit wall fixings to be spaced cable rises to outside in the PE
Conduit wall fixings to be spaced
at a max of 1m ducting
at a max of 1m
Cable tray 300x60mm 95mm2 general earth cable runs in
95mm2 general earth cable runs in Ø50mm Ø50mm Stainless Steel Conduit. The
stainless steel conduit exposed over the fire conduit rises to above ground behind
cladding. fire cladding
Ø63mm PE Ducting cast in
the concrete slab to run earth
cable to above ground
Fire Cladding 150x150mm stainless steel
junction box Fire Cladding
Scale 3:1 @ A1

150x150mm stainless steel


junction box
95mm2 earth (insulated) cable runs Scale 3:1 @ A1
embedded in concrete
countervault structure
Fire Cladding
Fire Cladding

95mm2 general earth (insulated)


cable runs in Ø63mm PE duct cast in
concrete wall. The cable duct rises to
above behind fire cladding
95mm2 general earth (insulated)
cable runs in Ø63mm PE duct cast in
concrete wall. The cable duct rises to
above behind fire cladding
Electrical and
comms ducts
in access chamber
Exothermic Welding Cable / Cable
Exothermic Weldind connection
to join earth cables

Power ducts (A)


Power ducts (D)
Fire mains Power ducts (D)
Main tunnel drainage Fire mains
Power ducts (D)
Comms duct (E)
95mm2 earth (insulated) cable runs Comms duct (E)
embedded in concrete WEST BORE
Drainage
EAST BORE

-7
countervault structure

Exothermic Welding to Structure Reinforcement

PK=0+465,500

GAFAR 2. GIBRALTAR AIRPORT


AND FRONTIER ACCESS ROAD

FOR CONSTRUCTION
CHECKED / ELABORATED APPROVED
VERSION
M&E DESIGN LEADER PROJECT MANAGER

SIGNATURE

DATE 24/10/2018

C01
ELECTRICAL SERVICES
GIBRALTAR AIRPORT AND EARTHING AND LPS INSTALLATION
FRONTIER ACCESS ROAD SECTIONS
C.H. 0+465.5 ME-01-202 C01