Actuator SQM40.../SQM41...
Electromotoric actuator up to 10 Nm
Clockwise and counterclockwise variants
Running times from 15 and 30 seconds
Various shaft ends available
Electronic version with analog control input
Internal position indication
Drive shaft can be disengaged
UL approval
The SQM40.../SQM41… and this Data Sheet are intended for use by OEMs which
integrate the actuators in their products!
Use
The SQM40.../SQM41... actuators are suited for driving flow control valves, butterfly
valves, dampers or for use on other applications that require rotary motion.
Areas of application are oil and gas burners of medium to higher capacity as well as
thermal process plants.
The actuators are used primarily for load-dependent control of the flow of gas, oil and
combustion air:
In connection with 3-position or modulating controllers (e.g. 4...20 mA), or
Directly by burner controls
CC1N7817en
Building Technologies Division
07.05.2012 Infrastructure & Cities Sector
Warning notes
To avoid injury to persons, damage to property or the environment, the following
warning notes must be observed!
Only qualified personnel may open, interfere with or modify the actuators!
Read the documentation on the actuators carefully and fully. If not observed,
dangerous situations might occur
All product-related activities (mounting, settings and maintenance) must be
performed by qualified and authorized personnel
Caution!
Risk of electric shock hazard – to disconnect the actuator from power, it may be
necessary to open more than one switch. Before performing maintenance work,
the actuator must be disconnected from power
The electrical connection between the conduit fittings is not made automatically.
It must be established on installation site
The connecting plate is made of plastic and does not provide earthing of the
conduit fittings. Earthing must be ensured by adequate washers and wire links
To provide protection against electric shock hazard, the connecting terminals must
have adequate touch protection. Make certain that non-insulated connections or
wires cannot be touched
Each time work has been carried out (mounting, installation, service work, etc.),
check to ensure that wiring is in an orderly state
Fall or shock can adversely affect the safety functions. Such actuators must not be
put into operation even if they do not exhibit any damage
Static charges must be avoided since they can damage the actuator’s electronic
components when touched.
Recommendation: Use ESD equipment
2/15
SQM40… SQM41…
0° 90°
90° 0°
7546d33/0307
Installation notes
Ensure that the electrical wiring is in compliance with national and local safety
regulation
Make certain that strain relief of the connected cables conforms to the relevant
standards (e.g. as per DIN EN 60730 and DIN EN 60335)
Ensure that spliced wires cannot get into contact with neighboring terminals. Use
adequate ferrules
Unused terminals of the SQM40.../SQM41... must be covered by dummy plugs
When making the wiring, the AC 120 V or AC 230 V section must be strictly
separated from other voltage sections, thus ensuring protection against electric
shock hazard
The mechanical coupling between actuators and controlling elements must be form-
fitted
3/15
SQM4x.x6xxxx/
SQM4x.x4xxxx: SQM4x.x7xxxx:
7817z09e/1109
Note
SELV or PELV depends on the safety class of the connected components. In the
case of PELV, the relevant component is connected to protective earth.
4/15
Note
Potentiometers for adjustment of the modulation limits:
90°
Max.
Min.
0°
7817z10/1009
Note
Usable range for the potentiometers:
90°
Setpoint (I/mA)
max.
(V) (I)
20
18
16
14
12
10
8
6
4
2
Operating angle (°)
0
10 20 30 40 50 60 70 80 90
0° 7817d04e/1109
min.
For use in US/Canada where the power supply lines require a connection facility for
flexible conduit, the actuator's product no. includes type suffix «R» (see following
example). These products are UL-listed.
Example: SQM40.264R10
Disposal notes
The unit contains electrical and electronic components and must not be disposed of
together with domestic waste.
Local and currently valid legislation must be observed.
5/15
Couplings Shaft can be disengaged from motor by coupling (pressing coupling pin «K1»)
Automatic reengagement
Electrical RAST3.5 screw terminals are enclosed, depending on the PCB variant
connections RAST5 screw terminals are enclosed, depending on the PCB variant
Optional: Insulation displacement connectors
Wiring through connecting cover
Easy insertion of cables through large openings in the housing
Actuator fixing Fixing holes at housing bottom (drive shaft side), like SQM45.../SQM48... with
screws M5 or, alternatively, SQM10.../SQM20... front mounting with self-tapping
screws M5
6/15
Product no. Direction Torque PCB Shaft no. Regional Operating Potentio-
of rotation version voltage meter
Counterclockwise
Clockwise
Electronic
3-position
2-position
Switches
AC120V
AC230V
Double
Single
Relay
Basic
EU
US
SQM40.141A21 5Nm/15s 3 1
SQM40.144R11 5Nm/15s 3 4
SQM40.145A21 5Nm/15s 3 5
SQM40.145R11 5Nm/15s 3 5
SQM40.161A20 5Nm/15s 6 1
SQM40.164R11 5Nm/15s 6 4
SQM40.165A20 5Nm/15s 6 5
SQM40.165A21 5Nm/15s 6 5
SQM40.165R11 5Nm/15s 6 5
SQM40.171A20 5Nm/15s 5 1 1
SQM40.174R10 5Nm/15s 5 1 4
SQM40.175A21 5Nm/15s 5 1 5
SQM40.241A11 10Nm/30s 3 1
SQM40.241R11 10Nm/30s 3 1
SQM40.241A21 10Nm/30s 3 1
SQM40.244A21 10Nm/30s 3 4
SQM40.244R11 10Nm/30s 3 4
SQM40.245A11 10Nm/30s 3 5
SQM40.245A21 10Nm/30s 3 5
SQM40.245R11 10Nm/30s 3 5
SQM40.247A21 10Nm/30s 3 7
SQM40.261A11 10Nm/30s 6 1
SQM40.261R11 10Nm/30s 6 1
SQM40.261A20 10Nm/30s 6 1
SQM40.261A21 10Nm/30s 6 1
SQM40.261A22 10Nm/30s 6 1
SQM40.264A21 10Nm/30s 6 4
SQM40.264R11 10Nm/30s 6 4
SQM40.265A11 10Nm/30s 6 5
SQM40.265A21 10Nm/30s 6 5
SQM40.265R11 10Nm/30s 6 5
SQM40.265A20 10Nm/30s 6 5
SQM40.267A20 10Nm/30s 6 7
SQM40.271A20 10Nm/30s 5 1 1
SQM40.271R10 10Nm/30s 5 1 1
SQM40.274R10 10Nm/30s 5 1 4
SQM40.275A20 10Nm/30s 5 1 5
SQM40.275A21 10Nm/30s 5 1 5
7/15
Product no. Direction Torque PCB Shaft no. Regional Operating Potentio-
of rotation version voltage meter
Counterclockwise
Clockwise
Electronic
3-position
2-position
Switches
AC120V
AC230V
Double
Single
Relay
Basic
EU
US
SQM41.141A21 5Nm/15s 3 1
SQM41.144R11 5Nm/15s 3 4
SQM41.145A21 5Nm/15s 3 5
SQM41.145R11 5Nm/15s 3 5
SQM41.164R11 5Nm/15s 6 4
SQM41.165R11 5Nm/15s 6 5
SQM41.174R10 5Nm/15s 5 1 4
SQM41.241A11 10Nm/30s 3 1
SQM41.241R11 10Nm/30s 3 1
SQM41.241A21 10Nm/30s 3 1
SQM41.244A21 10Nm/30s 3 4
SQM41.244R11 10Nm/30s 3 4
SQM41.245A11 10Nm/30s 3 5
SQM41.245A21 10Nm/30s 3 5
SQM41.245R11 10Nm/30s 3 5
SQM41.261A11 10Nm/30s 6 1
SQM41.261R11 10Nm/30s 6 1
SQM41.261A21 10Nm/30s 6 1
SQM41.264A21 10Nm/30s 6 4
SQM41.265R11 10Nm/30s 6 5
SQM41.267A21 10Nm/30s 6 7
SQM41.271R10 10Nm/30s 5 1 1
SQM41.274R10 10Nm/30s 5 1 4
SQM41.275A21 10Nm/30s 5 1 5
Note
Not all types of actuators are available ex stock. Additional versions are available on
request.
8/15
Front cover For making the connections for the power supply lines
(on request) - For 1/2" NPT protective sleeve AGA45.11
- For metric cable gland AGA45.12
Note
Connecting covers are used depending on the application. The actuators come with
the covers prefitted.
Terminal kits
- For replacement
- For SQM4x.x4x.xxx AGA45.4
- For SQM4x.x6x.xxx and SQM4x.x7x.xxx AGA45.6
9/15
1) At 60 Hz frequency, running times are about 17 % shorter and torques lower by the same rate.
10/15
11/15
7817d03/0212
Mains voltage terminals Design
VI 4
V X2-1 Opening (I) Input AC 120 V/AC 230 V
0041a
I VI V X2-2 Startup in low-fire (V) Input AC 120 V/AC 230 V
X2-3 Position reached Output AC 120 V/AC 230 V
I
M max. 10 mA
X2-4 Closing/ignition (VI) Input AC 120 V/AC 230 V
X2-5 Controller release Input AC 120 V/AC 230 V
X2-6 Neutral Input AC 120 V/AC 230 V
Range adjustment Adjust the range of the analog signal to match the switch positions (min. and max.
position):
1. Set cam I to the required high-fire position (e.g. 85°; position is indicated on the scale
next to the cam).
2. Set cam V to the required low-fire position (e.g. 20°).
3. Preset the signal at the analog input according to the required high-fire position
(e.g. 20 mA).
4. Turn the potentiometer for maximum angular rotation
a) clockwise, if the actuator has not yet reached its maximum angular rotation, or
b) counterclockwise until the actuator starts
5. Preset the signal at the analog input according to the low-fire position (e.g. 4 mA).
6. Turn the potentiometer for minimum angular rotation
a) counterclockwise, if the actuator has not yet reached its minimum angular
rotation, or
b) clockwise until the actuator starts
Min.
0°
7817z08e/1109
12/15
7817d01/1108
6 Mains voltage terminals Design
VI
V X3-1 AUX (VI) NO Output AC 120 V/AC 230 V
0039a
I II III max. 1 A
IV
III X3-2 AUX (VI) NC Output AC 120 V/AC 230 V
M II max. 1 A
I X3-3 AUX (VI) Input AC 120 V/AC 230 V
IV V VI
X2-1 AUX (V) Input AC 120 V/AC 230 V
X2-2 AUX (V) NO Output AC 120 V/AC 230 V
max. 1 A
X2-3 Open position reached Output AC 120 V/AC 230 V
32 6 4 5 1 X1 543 12 X2 231 max. 1 A
X2-4 Closed position reached Output AC 120 V/AC 230 V
max. 1 A
X2-5 Ignition position reached Output AC 120 V/AC 230 V
max. 1 A
I II III max. 1 A
IV
III X3-2 AUX (VI) NC Output AC 120 V/AC 230 V
M II max. 1 A
I X3-3 AUX (VI) Input AC 120 V/AC 230 V
IV VI
K-A X2-1 Mains voltage Input AC 120 V/AC 230 V
a1
X2-2 Opening/closing Input AC 120 V/AC 230 V
(changeover switch)
X2-3 Open position reached Output AC 120 V/AC 230 V
32 6 4 5 1 X1 543 12 X2 231 max. 1 A
X2-4 Closed position reached Output AC 120 V/AC 230 V
max. 1 A
X2-5 Ignition position reached Output AC 120 V/AC 230 V
max. 1 A
13/15
7817z06e/1109 7817z05e/1109
VI 30°
V 30°
IV 30°
III 10°
II 0°
I 90°
Zero position
90
R 00
Zero position
Note!
The setting of the switch position must be checked.
14/15
SQM40.../SQM41…
5 deep
Shaft no.
SQM4x.xx4xxx Square 4
SQM4x.xx5xxx D-shaft 5