Data Monitoring and Performance Analysis of A 1.6Kwp Grid Connected PV System in Algeria
Data Monitoring and Performance Analysis of A 1.6Kwp Grid Connected PV System in Algeria
Data Monitoring and Performance Analysis of A 1.6Kwp Grid Connected PV System in Algeria
*Department of Industrial Engineering, Laboratory of Automation and Manufacturing, Hadj Lakhdar University of Batna, 05
avenue Chahid Boukhlouf 05000 Batna, Algeria
**Department of Industrial Engineering, Hadj Lakhdar University of Batna, Algeria, 05 avenue Chahid Boukhlouf 05000
Batna, Algeria
***Department of Electrical Engineering, University Hadj Lakhdar Batna, 05000 Batna, Algeria, 05 avenue Chahid Boukhlouf
05000 Batna
****Department of physics, University Hadj Lakhdar Batna, 05 avenue Chahid Boukhlouf 05000 Batna
([email protected], [email protected], [email protected], [email protected])
‡ Corresponding Author; Adel Ghouari, 05 avenue Chahid Boukhlouf 05000 Batna, Algeria, Tel: +213 (0) 663913860,
[email protected]
Abstract- The present study deals with the performance of a 1.6kWp grid connected PV system installed at Batna University,
in Algeria. The average solar energy received was 5.21 kWh/m².d, the grid connected PV system seems to be a good candidate
for generating electricity in this region. The system was monitored during one year of continuous operation and data analysis to
evaluate the performance of the grid connected PV system. The performance ratio of the system ranged between 51 and 61%.
Furthermore, the total produced energy by the PV array was 1931.7kWh and the supplied energy to the grid was 1705kWh. The
annual final yield was 1065.6kWh/kWp. Moreover, an analysis of the energy losses in the system was performed, this makes it
possible to determine the effect of the capture and system losses on the total energy balance of the system. All the electricity
generated by the system was fed into the internal electrical grid of the university.
Keywords Grid connected PV system; Photovoltaic performance; PV yields and losses analysis; PV system comparative results.
35
INTERNATIONAL JOURNAL of RENEWABLE ENERGY RESEARCH
A. Ghouari et al., Vol.6, No.1, 2016
HG where:
Yr (1)
Gi, STC NOCT: is the Nominal Operating Cell Temperature
(45°C)
Where:
The miscellaneous capture losses LCM summarized the
The reference yield Yr is the ratio between the total in- different types of losses caused by the PV array operation,
plane solar radiation HG and the reference irradiance 1kW/m², during the reference period τ, it contains the losses of wiring,
it indicates the number of peak sun-hours during period τ (d: string diodes, low irradiance, partial shadowing and mismatch
day, m: month or y: year), the measuring unit is kWh/kWp/τ other factors. The measuring unit is kWh/kWp/τ or h/τ. It is
or h/τ. given as follows:
TC Ta Gi
NOCT - 20 (7)
was 1831.4kWh/m², which was found very close to other
regions like Greece, Egypt and Morocco[22—24] and higher
800 than some other Mediterranean locations like Spain [25].
36
INTERNATIONAL JOURNAL of RENEWABLE ENERGY RESEARCH
A. Ghouari et al., Vol.6, No.1, 2016
14 ISC 1,5
1000
Current (A)
12
10 800
Current (A)
IMAX 1
8 PMAX 600
6 I-V old modules
400 I-V New modules
4 0,5
2 200
UMAX UOC
0 0 0
0 10 20 30 40 50 60 70 80 0 31 60 91
Voltage (V) Voltage (V)
Fig. 4. The I-V and PV curves of the PV array Fig. 7. The I-V curves of new and old PV modules at
(PG0=1.6KWp) at 900 W/m² of solar irradiance and the cell 800W/m² and cell temperature 27°C, 12/01/2014.
temperature is 53°C, 11/20/2014.
Table 2. Comparison between old PV modules (G1) used in
the present study and new PV modules (G2) of
PHOTOWATT PW400 type.
Degradatio
PMAX IMAX UMAX ISC UOC
n ratio
37
INTERNATIONAL JOURNAL of RENEWABLE ENERGY RESEARCH
A. Ghouari et al., Vol.6, No.1, 2016
G 113 1.4 77.3 1.7 92.6 in “Figure 9”. It is obvious that the PV system is affected by
1 W A V A V the site climatic conditions as well as the component
8.3% technology.
G 123 1.6 74.8 1.8 94.5 The month of October of the same year showed the lowest
2 W A V A V performance ratio, which makes this study interesting in a way
to get information about the losses occurring during this
month. These losses are related to thermal capture losses,
4.3. The Inverter, PV generator and system efficiencies miscellaneous capture losses and system losses.
Thus, the daily performance ratio in the month of October,
The inverter efficiency varied between 86.7% and 89.3%
ranged between 49.1% and 59%. Also, the daily average final
with an average value of 88.2%. Also, the PV array efficiency
yield (Yf,d) was 2.83kWh/kWp/d. Moreover the daily average
was found to be between 8.62% and 10.4% with an average
system losses (LS,d) were 0.34kWh/kWp/d, the system losses
value of 9.93%. The system efficiency varied between 7.69%
indicate that the inverter was in good state of operation. The
and 9.13% “Table 3”.
other hand, the daily average value of the capture losses (LC,d)
were found to be 2.26kWh/kWp/d.
4.4. The grid connected PV system normalized indicators
evaluation Yr = 1831.43 ,Ya = 1207.00 & Yf = 1065.58 kWh/kWp
Yr,m = 152 ,Ya,m = 101 & Yf,m = 88.7 kWh/kWp/m
Yr,d = 5.21,Ya,d = 3.44 & Yf,d = 3.03 kWh/kWp/d
“Figure 8” illustrates the variation of the average monthly
and daily values of the reference, array and final yields. The Reference yield Array yield Final yield
monitoring of the system parameters indicated that the
monthly average daily value of the reference yield (Y r,d) was 7
5.21kWh/kWp/d, the total reference yield (Yr) for the year Monthly average Yr, Ya and Yf 6
2013 was 1831.4kWh/kWp with an average of 5
152.6kWh/kWp each month. The monthly average daily
(kWh/kWp/m)
capture losses and system losses). As shown in “Figure 9” the Yf,d = 3.03 kWh/kWp/d
8 PR = 57%
monthly average daily value of the capture losses (LC,d) varied
between 1.233kWh/kWp/d and 2.26kWh/kWp/d. The total of 7 58% 58%
58% 58% 51%
capture losses (LC) through the whole year was 6 59% 58%
610.77kWh/kWp. 5 59% 60% 59%
61% 58%
The main reasons of these losses are the high levels of 4
ambient temperatures during the summer period and the 3
ageing factor related to the PV modules, also, the connections 2
between strings of the PV generator and the wirings are 1
responsible for a part of these losses. The length of each wire 0
used to relate the PV generator to the connection box was up
5 6 7 8 9 10 11 12 1 2 3 4
to 30m with a measured resistance of about 50.4 Ohms.
Month
The monthly average daily value of the system losses (LS,d Fig. 9. Monthly daily average values of the Performance
) ranged between 0,32kWh/kWp/d and 0.54kWh/kWp/d. The ratio, capture losses and system losses for 1.6kWp grid
annual system losses (LS) was 141.33kWh/kWp and the connected PV system at Batna region during the year 2013.
monthly average value was 11.77kWh/kWp/m. These losses
are due mainly to the system conversion (DC-AC).
Thus, the performance ratio (PR) of the system during this
period of the test ranged between 51% and 61% as indicated
38
INTERNATIONAL JOURNAL of RENEWABLE ENERGY RESEARCH
A. Ghouari et al., Vol.6, No.1, 2016
Table 3. The Annual and daily average values of the grid connected PV system parameters at BATNA region for the year 2013,
global solar insolation , ambient temperature , Energies (produced, supplied to the grid), yields (reference, array and final), losses
(capture and system), efficiencies (generator, inverter and system) and performance ratio.
Month Meteorological Energies (kWh/d) Yields and energy losses (kWh/kWp/d) PR Efficiencies
parameters %
Hi Ta EDC,d EAC,d Yr,d Ya,d Yf,d LC,d LS,d ηG ηinv ηS
kWh/m °C % % %
²/d
Jan 4.01 7.430 4.40 3.87 4.01 2.74 2.42 1.26 0.32 60 10.26 88.15 9.04
Feb 4.36 6.780 4.67 4.12 4.36 2.92 2.58 1.42 0.34 58 10.05 88.18 8.86
Mar 5.00 12.92 5.53 4.80 5.00 3.46 3.00 1.54 0.45 60 10.37 86.78 9.00
Apr 6.13 14.60 6.42 5.70 6.13 4.01 3.56 2.02 0.45 58 9.820 88.81 8.72
May 5.65 16.82 5.98 5.33 5.65 3.74 3.33 1.84 0.40 59 9.920 89.12 8.84
Jun 6.50 22.72 6.93 6.05 6.50 4.33 3.78 2.17 0.54 58 9.980 87.44 8.72
Jul 6.03 26.95 6.28 5.61 6.03 3.92 3.50 2.10 0.42 58 9.760 89.29 8.72
Aug 5.82 25.42 6.05 5.39 5.82 3.78 3.37 1.97 0.41 57 9.750 89.07 8.68
Sep 5.40 21.87 5.73 4.98 5.40 3.58 3.11 1.75 0.46 57 9.990 86.69 8.66
Oct 5.52 19.72 5.08 4.53 5.52 3.17 2.83 2.26 0.34 51 8.620 89.22 7.69
Nov 4.23 9.480 4.70 4.12 4.23 2.93 2.58 1.28 0.35 59 10.40 87.80 9.13
Dec 3.98 5.520 4.35 3.82 3.98 2.72 2.40 1.20 0.33 58 10.24 87.90 9.00
Annual daily
5.21 15.85 5.51 4.86 5.21 3.44 3.03 1.73 0.4 57 9.93 88.20 8.75
average value
As it is shown in “Figure 10”, the daily average value of performance ratio, thus the daily average cell temperature
the miscellaneous capture losses (LCM,d) ranged between variations during October 2013 in Batna region.
0.63kWh/kWp/d (30th, October) and 2.8kWh/kWp/d (14th,
October), and the daily average thermal losses varied between 5. Results analysis and discussion
-0.004kWh/kWp/d (30th, October) and 0.883kWh/kWp/d
(4th, October). In this section, a regional comparison of the grid
The LCT losses are proportional to the PV module connected photovoltaic systems performances is carried out.
temperature (Tm) which ranged between 23.48°C (7th, The comparison is done on the basis of various parameters.
The final yield (Yf) and the performance ratio PR and system
October) and 55.86°C (4th, October), during these two days,
efficiency are the most normalized factors that are needed to
the LCT were 0.015kWh/kWp/d to 2.045kWh/kWp/d
evaluate and compare PV systems17.
respectively. The miscellaneous capture losses, thermal
capture losses and system losses are estimated to be about The annual daily average final yield of the system under
34%, 8% and 6% respectively. Thus, during this month the study was 3.03kWh/kWp/d and the performance ratio was
final yield accounted for 52% of the total energy balance. found to be about 57% “Table 4”. Thus, the final yield of the
system installed in Batna region was found to be higher than
Final Yield
System Losses
that of the PV grid systems installed in Germany and
8 60 Netherlands (1.8kWh/kWp/d), Italy (2.0kWh/kWp/d) and
daily average Yf, LS, LCT, LCM
49% 51%
52%
52%
yield (3.5kWp/kWh/d) this may be attributed to the higher
6 49% 52% 50 received solar radiation (6.6kWh/m²/d) [28].
51% 51% 53%
52% 52% 56% In terms of performance ratio, the investigated system was
4 49% 59% 40
52% found to be in a good agreement with the results obtained and
reported in other countries. In fact, in the case of Germany, the
2 30 PR of 106 systems varied between 42% and 85%, with an
average value of 67%. In the same way, Austria reported an
0 20 average performance ratio related to 22 systems to be in the
1 6 11 16 21 26 31 order of 63% and 69% for 62 investigated systems in
Day Switzerland.
Fig. 10. The normalized daily final yield, system losses,
Furthermore, the overall efficiency of the system
thermal capture losses, miscellaneous capture losses and
investigated was found to be very close to the results of PV
39
INTERNATIONAL JOURNAL of RENEWABLE ENERGY RESEARCH
A. Ghouari et al., Vol.6, No.1, 2016
systems reported in literature, especially with those using
similar technology (MC-Si).
Table 4. The comparison of the performance of various grid connected PV systems thought the world and the results obtained
from the present work in Algeria (PS).
Location PV type Yields and losses kWh/kWp/d PR Efficiency % Ref
Yf,d Yr,d Ya,d LC,d LS,d % ηG ηinv ηs
18
MC-Si 2.4 2.8 2.6 0.2 0.2 81.5 14.9 89 12.6
Dublin, Ireland 29
MC-si 1.6-1.7 2.6-2.9 1.8-2 0.3-1.3 0.08-0.4 60-62 7.5-10 87 6–9
MC-Si 2.74 4.27 3.10 1.16 0.37 65 9.21 87 8.08
MC-Si 2.32 4.01 2.42 1.59 0.10 58 7.5 95 7.20 25
Jaén, Spain
MC-Si 2.74 4.20 3.35 0.85 0.61 65 9.96 80 8.04
PC-Si 1.60 3.26 1.83 1.43 0.24 49 5.71 87 4.96
30
Phitsanulok, Thailand - 3.84 5.21 4.32 0.90 0.47 73 - - -
31
Poland A-Si - - - - - 60-80 4-5 91-99 -
32
Bangi, Malaysia A-Si - - - - - 93-101 - - -
PC-Si 3.8-4.3 - - - 67-89 - 11.8 8-11
33
Selangor, Malaysia A-Si 1.9-3 4.2-5.5 - - - 88-102 - 9.8 6.1-6.9
MC-Si 1-3.8 - - - 72-85 - 6.5 9.9-11.7
MC-Si - - - - - 75.1 10.1 89 9.0
PC-Si - - - - - 63.3 9.2 86 7.9 34
Daejeon, Korea
MC-Si - - - - - 67.3 9.5 83 7.9
PC-Si - - - - - 71.8 9.5 87 8.3
Austria - - - - - - 42-79 - - -
Germany - - - - - 42-85 - - -
35
Italy - - - - - - 44-82 - - -
Netherlands - - - - 58-79 - - -
Switzerland - - - - - - 49-85 - - -
23
Cairo, Egypt - 4.35 5.6 - - - - 4.22 94.5 4.02
France - - - - - - 52-75 - - -
17
Belgium - - - - - - 52-93 - - -
Taiwan - - - - - - 30-90 - - -
22
Crete, Greece PC-Si 1.9-5.0 5.43 2-6.6 0.5-1.3 0.2-1.5 58-73 - - -
MC-Si 78
MC-Si 79
36
Jayapura, Indonesia
A-Si 91
MC-Si 54
38
Jodhpur, India 16-98
PS
Batna, Algeria MC-Si 3.03 5.21 3.44 1.73 0.4 57 9.9 88.2 8.75
40
INTERNATIONAL JOURNAL of RENEWABLE ENERGY RESEARCH
A. Ghouari et al., Vol.6, No.1, 2016
value of 3.038kWh/kWp/d. It accounted for 59% of the total [15] H. Haeberlin, Ch. Beutler. “Normalized
PV system energy balance. Representation of Energy and Power for Analysis of
Performance and One-line Error Detection in PV-
The results of the survey of previous work undertaken
Systems”, 13th EU PV Conference on Photovoltaic Solar
elsewhere and reported in literature show that a good
Energy Conversion, Nice, France,1995.
agreement is found in terms of energy yields and system
components efficiency. [16] G. Blaesser, D. Munro, “Guideline for the
Assessment of Photovoltaic Plants Document B. Analysis
The future works will be focused on the energy
and Presentation of Monitoring Data. Report EURO
management in smart home concept and the economic
16339”, Joint Research Center, European
evaluation.
Comission,1993.
References [17] Photovoltaic power systems programme, “Analytical
Monitoring of Grid-connected Photovoltaic Systems Good
[1] Document, Ministry of energy, “National energy balance Practices for Monitoring and Performance Analysis”, IEA-
for the year 2008”, edition 2010, available from : PVPS T13-03, 2014.
http://www.mem-algeria.org.
[18] L. M. Ayompe, A. Duffy, S.J. McCormack, M.
[2] Document, Ministry of energy, “National energy balance Conlon, “Measured performance of a 1.72 kW rooftop grid
for the year 2013”, edition 2014, available from : connected photovoltaic system in Ireland”, Energy
http://www.mem-algeria.org. Conversion and Management, Vol. 52, pp.16-825, 2011.
[3] Document, The regulation commission for electricity and [19] P. Bhattacharya, S. Dey, B. Mustaphi, “Some
gas, “Activity rapport 2008”, 2009, available from analytical studies on the performance of grid connected
http://www.creg.gov.dz. solar photovoltaic system with different parameters”,
Procedia Mater Sci Vol. 6, pp.1942–50, 2014,.
[4] Document, The regulation commission for electricity and
gas, “Activity rapport 2013”, available from [20] S. Ghazi, K. Ip, “The effect of weather conditions on
http://www.creg.gov.dz. the efficiency of PV panels in the southeast of UK”,
Renewable Energy, vol. 69, pp. 50-59, 2014.
[5] A. Ghouari, Ch. Hamouda and A. Chaghi, “Performance
Analysis of Grid connected PV system in the perspective [21] P. M. Congedo, M. Malvoni, M. Mele, M.G. De
of use in a smart house in Algeria”, International Giorgi, “Performance measurements of monocrystalline
Renewable and Sustainable Energy Conference, silicon PV modules in South-eastern Italy”, Energy
Ouarzazate, Morocco, 7-9 March 2013. Conversion and Management, vol. 68, pp.1-10, 2013.
[6] Energy potential in Algeria, available from: [22] M. Drif, P. J. Pérez, J. Aguilera, et al, “Univer
http://www.mem-algeria.org/fr/enr/pot.html. Project. A grid connected photovoltaic system of 200 kWp
at Jaén University. Overview and performance analysis”,
[7] SKTM, Company of Electricity and renewable Energy, Solar Energy Materials and Solar Cells. vol. 91, pp. 670-
http://www.sktm.dz. 683, 2007.
[8] Photovoltaic solar module. PW-P400 40W-12V datasheet, [23] E. Kymakis, S. Kalykakis, T. M. Papazoglou,
PHOTOWATT. “Performance analysis of a grid connected photovoltaic
[9] NEG inverter 1600 user manual. park on the island of Crete”, Energy Conversion and
Management, vol. 50, pp.433-438, 2009.
[10] Precision power meter LMG310 User Manual. ZES
ZIMMER Electronic Systems, 1995. [24] A. S. Elhodeiby, H. M. B. Metwally, M. A. Farahat,
“Performance analysis of 3.6 kW rooftop grid connected
[11] M. A. Hamouda et al, “Study and implanting of an photovoltaic system in Egypt”, International conference
intelligent electrical power supply system of urban on energy systems and technologies,. Cairo, Egypt, 2011.
housing with feeding into the grid”, Review of renewable
energy, vol. 14, pp. 187-202, Jun 2011, available from: [25] A. Barhdadi, A. S. Zakey, “Performance assessment
http://www.cder.dz/download/Art14-2_1.pdf of the first grid-connected photovoltaic micro power in
Africa: the PVGIS approach”, Moroccan Journal of
[12] Datataker DT50 User’s Manual. Connected Matter, vol. 12, pp. 14-19, 2010.
[13] IEC, Photovoltaic system performance monitoring – [26] U. Jahn et al, “International energy agency TASK II
guidelines for measurement, data exchange and analysis. database on photovoltaic power systems: statistical and
in: IEC 61724, International Electrotechnical Committee: analytical evaluation of PV operational data”, 2nd World
Geneva, 1998. Switzerland. conference on photovoltaic solar energy conversion,
[14] H. Haeberlin, Ph. Schaerf, “long-term Behaviour of Vienna, Austria, 1998.
Grid-Connected PV systems over more than 15 Years, [27] U. Jahn, W. Nasse, “Operational performance of
25th European Photovoltaic Solar Conference / 5th World grid-connected PV systems on buildings in Germany”,
Conference on Photovoltaic Energy Conversion”, Progress in Photovoltaics: Research and Applications, vol.
Valencia, Spain, 2010. 12, pp.441-448, 2004.
41
INTERNATIONAL JOURNAL of RENEWABLE ENERGY RESEARCH
A. Ghouari et al., Vol.6, No.1, 2016
[28] J. D. Mondol, Y. Yohanis, M. Smyth, B. Norton,
“Long term performance analysis of a grid connected
photovoltaic system in Northern Ireland”, Energy
Conversion and Management, vol.47, pp.2925-2947,
2006.
[29] A. Chimtavee, N. Ketjoy, “PV generator
performance evaluation and load analysis of the PV
microgrid system in Thailand”, In: Procedia Engineering,
vol.32, pp.384-391, 2012.
[30] S. M. Pietruszko, M. Gradzki, “Performance of a grid
connected small PV system in Poland”, Applied Energy,
vol. 74, pp. 177-184, 2003.
[31] R. A. Rahman, S.I. Sulaiman, A.M. Omar, S. Shaari,
Z.M. Zain, “Performance analysis of a grid-connected PV
system at malaysian energy centre”, 4th International
Power Engineering and Optimization Conference,
Malaysia,2010.
[32] M. Z. Hussin et al, “Performance of grid-Connected
photovoltaic system in equatorial rainforest fully humid
climate of Malaysia”, International Journal of Applied
Power Engineering, pp.105–142013.
[33] J.H. So, Y.S Jung, G.J. Yu, J.Y. Choi, J.H. Choi,
“Performance results and analysis of 3kW grid-connected
PV systems”, Renewable Energy, vol.32, pp.1858-
1872,2007.
[34] U. Jahn, W. Nasse, T. Nordmann, L. Clavadetscher,
D. Mayer, “Achievements of task 2 of IEA PV power
systems performance: final results on PV system
performance”, 19th EUPVSECParis, France, 2004.
[35] A. J. Veldhuis, A.H.M.E. Reinders, “Performance of
34 kWp Grid-Connected PV System in Indonesia –
Acomparison of Tropical and European PV system”, 40th
IEEE Photovoltaic Specialist Conference, Denver,
Colorado, 2014.
[36] D. C. Jordan, B. Sekulic, B. Marion, S.R. Kurtz,
“Performance and aging of a 20-year-old silicon PV
system”, IEEE J. Photovoltaics, vo.5, pp.744-751, 2015.
[37] J. Wohlgemuth, S.R. Kurtz, “Photovoltaic module
qualification plus testing”, 40th IEEE Photovoltaic
Specialist Conference, Denver, Colorado, 2014.
[38] S. Singh, R. Kumar, V. Vijay, “Performance analysis
of 58 kW grid-connected roof-top PV systems”, 6th IEEE
Power India International Conference, Delhi, India, 2014.
42