XT+ Releasing Control Panel
XT+ Releasing Control Panel
XT+ Releasing Control Panel
Standard Features
• UL 864 10th Edition Listed
• Up to 2 releasing areas / hazards per XT+ unit
• Dual releasing outputs for each area (configurable as Main/Reserve)
• First and second stage NAC outputs for each area
• First and second stage volt free changeover relays for each area
• Released volt-free relay per area
• Trouble volt-free relay per area
• Programmable releasing delays
• Programmable output duration
• Countdown indicator shows time until release in seconds
• Mode select and manual release controls per area
• Monitored remote manual release input
• Monitored remote abort input
• Monitored remote mode select input
• Monitored remote released pressure switch input
Releasing Module Units Part Numbers
• Serial connections for status units and ancillary boards
VF1711-10 1 Area, Red
VF1711-40 1 Area, Gray
Product Overview
VF1712-10 2 Area, Red
XT+ releasing control units are multi-area releasing control units
VF1712-40 2 Area, Gray containing one or two releasing modules complying with UL 864 10th
All cabinets are equipped with a 5.25A Power edition.
Supply.
Up to 15 releasing modules may be connected to a Elite RS fire alarm
Accessory Part Numbers control panel. Each releasing module can accommodate a separate
VF1832-10/40 Disablement Switch
hazard defined by two specific zones.
VF1823-10/40 Abort Switch
Each XT+ unit is equipped with a 5.25 A power supply (120 VAC or 240
VF1822-10/40 Ancillary Relay Board & VAC) to power releasing modules and attached solenoids / actuators or
Cabinet sequential activators.
VF1821-11/12/13/14 Status Units
41/42/43/44
Each releasing module has a comprehensive set of inputs and outputs
and is configurable via a simple programming interface provided by
Unit Key Lock Part Numbers
Loop Explorer 2. Each releasing module may have up to 7 serially-
901 Enable Access connected status units or ancillary relay boards.
Mode Select
CAT 30 Cabinet Lock
PENDING
VES Fire Detection Systems | 620 Allendale Road | King of Prussia, PA 19406 | 800.270.3066 | www.ves-network.com
July 2019, Version 1.01
2
TECHNICAL SPECIFICATIONS
Construction 1.2mm mild sheet steel
Dimensions 14.5”W x 18.9”H x 4.25” D
IP Rating IP30
Finish Epoxy powder coated
Color Lid & Box: Gray - BS 00 A 05 or Red - RAL 3002
Fascia: RAL7016
Weight 17.6 lbs (Standard Configuration)
Cabling FP200 or equivalent (max capacitance 1uF max inductance 1 mH).
Connect 18 to 14 AWG wiring for all field terminations except AC input.
Connect 14 AWG wiring for line, neutral, and ground terminations of the AC input.
Power Supply 1.83 Amps Max @ 120 V, 50/60 Hz
0.915 Amps Max @ 240 V, 50/60 Hz
Power Supply Fuse 3A (field-replaceable)
Power Supply Rating 1 and 2 Area Units: Regulated 24V DC @ 4A
Maximum Ripple Current 1V Maximum
Standby Battery Type Two 12 VDC, valve-regulated lead acid
Battery Size Recommended battery size is 12 Ah for a typical configuration. Required battery size is mainly dependent on
standby current. To determine the most appropriate battery size, use the battery calculator in LE2.
Battery Charge Voltage 27.6VDC nominal (temperature compensated)
Battery Fuse 10A 3AG (field-replaceable)
Current Draw in Power Fail Condition 54mA per releasing module
Max Current Draw from Batteries 4A
Ground Fault Impedance Value 100 Ohms
Temperature Range 32°F (0°C) - 120°F (49°C)
Relative Humidity up to 93%, non-condensing
Releasing Delay Adjustable 0 to 60 seconds (+/- 10%)
Releasing Duration Adjustable 60 to 300 seconds
Fire Alarm Control Panel Elite RS with Firmware Version 07.002.005 or higher
TOP TERMINALS
24V Power 24V Regulated, continuous (power input)
Aux 24V 24V Regulated @360mA Max, Power-limited
Trouble
1st Stage
2nd Stage
Volt-free contact rated at 30V DC, 1A, Resistive
3rd Stage (Released)
Supv. / Abort
Extract
3rd Stage Alarm
24V Regulated @ 850mA Max, Power-limited
2nd Stage Alarm
Exting. 1 (Main)
24V Regulated @ 1A Max, Power-limited
Exting. 2 (Reserve)
BOTTOM TERMINALS
Class B
Man. Rel
Supervised for opens, shorts, and grounds
Abort
End-of-Line device: 6.8K Ohm resistor (S2027)
Disable
Activation device: 470 Ohm resistor (S2051)
Mode
Maximum Voltage / Current: 24V DC / 50 mA
Rel P. Sw
Maximum Wiring Impedance for Each Circuit: 50 Ohms
Low Press.
Power-limited
CIE Serial Two wire, RS485 connection, Data 3.3 V, current-limited, Class B, supervised
Maximum Line Impedance: 120 Ohms
Status Serial Two wire, RS485 connection, Data 3.3 V, current-limited, Class B, supervised
Maximum Line Impedance: 120 Ohms
Status Pow. 24V Regulated @ 360mA Max, Power-limited
VES Fire Detection Systems | 620 Allendale Road | King of Prussia, PA 19406 | 800.270.3066 | www.ves-network.com