MainsPro Datasheet
MainsPro Datasheet
MainsPro Datasheet
Datasheet
Product description
l Protection relay for mains connected applications
like generator sets, renewable energy sources,
cogeneration, micro turbines, etc.
l Adjustable voltage, frequency and loss of mains
protections to safeguard both the distribution
network and the generators
Key features
l True RMS measurement Order code: MAINSPRO
l Vector Shift and Rate of change of frequency
(ROCOF) protection in one unit
l Symmetrical components for better detection of
voltage asymmetry failures
l Two stage settings of voltage and frequency
protections
l Adjustable time delay of Automatic fault reset
l Free assignment of 5 relay outputs
l Free assignment of 4 binary switches
l Support of 3-phase and 1-phase applications
Application overview
l Last 5 trips record providing evidence of cause of
trip
l Universal power supply
l Suitable for standard DIN rail installation or door-
mount (optional)
l Integrated mechanical lock to secure user settings
l Breaker failure protection
l Full and easy configuration through the front panel
- no other tool is needed
|MainsPro Datasheet |Related HW ver: 1.2 |Related SW ver: 1.5 |Date of issue: 6.3.2015 1
Technical data
Power Supply Binary inputs
8-40 VDC Number 4 non-isolated
Power supply range 85-263 VAC Input resistance 4.2 kΩ
110-370 VDC 0-2 VDC close contact
Close/Open indication
Maximal power 600 mA / 10 VDC 0-36 VDC open contact
consumption 90 mA / 370 VAC Display
Operating conditions Build-in monochromatic
Type
Operating Temperature -20 ... 70 °C Resolution 4 lines X 20 symbols
Voltage measurement
Measurement
3 phase mains voltage
inputs
Measurement
True RMS
type
120-230 V Ph-N
Voltage range
400 V Ph-Ph
Maximal voltage
130 % Un
range
1 % from nominal value at 50 Hz ±
Voltage 10% and 25 °C
accuracy 1,5 % within the complete
temperature range
Measurement
input 400 kΩ
impedance
Frequency measurement
Max switched
voltage / 250 V / 4 A
current
Resistive load:
1000 VA AC
Max switched 200 W DC
power Inductive load
50 VA AC
25 W DC
Resistive load
250 V / 4 A AC
Rated voltage 200 V / 0 A, 1A; 24 V / 4A DC
/ current relay Inductive load
250 V / 2 A AC
200 V / 0 A, 1A; 24 V / 3A DC
MainsPro Datasheet 2
Dimensions, terminals and mounting
MainsPro can be also mounted into panel doors as a standalone unit. For this way of installation is
recommended to use MainsPro Frame.
MainsPro Datasheet 3
Related information
Related products
Product Description Order code
Vector shift 78
l VDE V 0126-1-1
l IEC 60255
l UL508
l CEI 0-21
l IEn NR 005/2012
l VDE-A-RN 4105
EMC
Description Code Description Code
IEC 60255-22-4
Electromagnetic
EN 50263 Electrical fast transient/burst immunity EN 61000-4-4
compatibility
IEEE C37.90.1
IEC 60255-22-5
Safety standard IEC 61010-1 Surge immunity test
EN 61000-4-5
IEC 60255-3 IEC 60255-22-6
Electrical relays Immunity to conducted disturbances induced by
IEC 60255-5 IEC EN 61000-4-6
test radio-frequency field
60255-6 IEEE C37.90.2
Sine vibration
IEC 60255-21-1 Test of power frequency magnetic field IEC 61000-4-8
tests
Shock and IEC 60255-22-7
IEC 60255-21-2 Power frequency immunity tests
impact test EN 61000-4-16
MainsPro Datasheet 4
Interruptions to an alternative component (ripple) IEC 60255-11
Seismic test IEC 60255-21-3 in DC auxiliary energizing quantity of measuring EN 61000-4-17
relay EN 61000-4-26
Electromagnetic
Voltage dips, short interruptions and voltage
compatibility IEC 60255-26 IEC 61000-4-11
variations
requirements
IEC 60255-22-1
1 MHz burst
IEC 61000-4-18 Environmental testing (- 30 °C) IEC 60068-2-1
immunity test
IEEE C37.90.1
Damped
oscillatory wave IEC 61000-4-18
Environmental testing (+ 70 °C) IEC 60068-2-2
100 kHz IEEE C37.90.1
immunity test
Ring oscillatory
IEC 61000-4-12 Environmental testing - temperature change (- 25
wave IEC 60068-2-14
IEEE C37.90.1 °C .. + 70 °C)
immunity test
MainsPro Datasheet 5