ELECTRICAL CALCULATIONS
F OR
JO/EWO
JAN.2015 14C0207
DATE
SHADED WAREHOUSE
@TANAJIB TOOL HOUSE FOR RIG SAR-201
00A
NO.
REV
DISCIPLINE
ENGINEER
AMO
(EWO. #: 14C207)
JAN2015
DATE:
PROJECT
ENGINEER
HAB
DATE:
JAN2015 PLANT NO. M #13
CERTIFIED
NKH
JAN2015
DATE:
CONSTRUCTION
AGENCY
DESIGN CONTRACTOR
TNB
JAN2015
DATE:
OPERATIONS
ARK
DATE:
JAN2015
KELLOGG BROWN & ROOT
CONTROL NUMBER
DATE:
BY:
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
00A
OF THIS DRAWING IS COVERED, FOR ALL
ELECTRICAL CALCULATIONS DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
DATE:
DATE:
DATE:
DATE:
DATE:
THIS INDICATES THAT REV. NO.__________
00A JAN.2015 14C0207 ISSUED FOR CONSTRUCTION NKH HAB
OF THIS DRAWING IS COVERED, FOR ALL
CONTROL NUMBER
NKH
ARK
TNB
AMO
HAB
APPROVAL/CERTIFICATION REQUIREMENTS,
AGENCY
BY:
PROJECT
BY DRAWING COMPLETION CERTIFICATE
ENGINEER
ENGINEER
DISCIPLINE
JAN2015
JAN2015
CERTIFIED
JAN2015
JAN2015
JAN2015
OPERATIONS
CONSTRUCTION
_____________________
(DCC) NO. 10-00452.0004 DATE:
TANAJIB
2.0
1.0
Saudi Aramco 2616-ENG (03/99)
SECTION
SHADED WAREHOUSE
ELECTRICAL CALCULATIONS
DESCRIPTION
SAUDI ARABIA
TOTAL LOAD CONSUMPTION ( LP - 02).
M13
JO / EWO:
TABLE OF CONTENTS
P
DWG.TYPE PLANT NO. INDEX
SAUDI ARABIAN OIL COMPANY
14C207
CALCULATION FOR 30 KVA TRANSFORMER ( XFR - 01 ) .
DRAWING NO.
CALC-P-001
5
2
Of
SHT.NO.
4
3
PAGE
00A
EDSD/2616-0399.doc
REV.NO.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
Saudi Aramco 2616-ENG (03/99)
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
PMT OPRNS
SAUDI ARABIAN OIL COMPANY
A - PRIMARY SIDE:
B - SECONDARY SIDE:
Use 100AF/ 50 AT, 3P, Main breaker of the lighting panel LP-02.
DATE
DISCIPLINE
ENGINEER
AMO
JAN2015
DATE: 3.1 VOLTAGE DROP (FOR 30 KVA TRANSFORMER);
PROJECT
ENGINEER
HAB A - PRIMARY SIDE:
JAN2015
DATE:
CERTIFIED FLA= 45 Amp, Cable length (L) = 4 Meter
NKH
JAN2015
DATE: Is neglected as the cable size from is 35 mm2 copper conductor,
CONSTRUCTION
AGENCY Distance between CB-001 and the transformer is max. 4 meters.
TNB
JAN2015
DATE: B- SECONDARY SIDE:
OPERATIONS
ARK FLA= 54 Amp, Cable length (L) = 4 Meter
JAN2015
DATE:
CONTROL NUMBER
C - VOLTAGE DROP (FOR 95 MM2 FEEDER CABLE) FROM CB-001 TO SUSTATION #4.
DATE:
BY:
REVISIONCERTIFICATION
ELECTRICAL CALCULATIONS DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
PMT OPRNS
SAUDI ARABIAN OIL COMPANY
2.47 %
Hence, voltage drop across the selected cable is less than 5% of the System Nominal Voltage
ISSUED FOR CONSTRUCTION
A- PRIMARY SIDE:
Equipment grounding conductor sized based on NEC Table 250-122. For 70Amp Over
Current protection, the minimum size of the grounding conductor is # 8 AWG Copper
B- SECONDARY SIDE:
JO/EWO
JAN.2015 14C0207
Equipment grounding conductor sized based on NEC Table 250-122. For 70Amp Over
Current protection, the minimum size of the grounding conductor is # 8 AWG Copper
DATE
DISCIPLINE
ENGINEER
AMO
JAN2015
DATE: 3.3 CONDUIT SIZING.
PROJECT
ENGINEER
HAB For cable ( 1- 4/C X 35 mm2 CU/XLPE/PVC +1/C 25mm2 CU/PVC ).
JAN2015
DATE:
CERTIFIED From (Saudi Cable Catalogue section 4- Page 29 & §ion 2- Page: 9).
NKH
= (25.2)²+(11.9)² /0.4
JAN2015
DATE: Minimum Conduit Size Requirement
CONSTRUCTION
AGENCY
TNB
= 43mm
JAN2015
DATE: = 2 IN
OPERATIONS
Use 2”// DIA. Rigid Steel Conduit.
ARK
JAN2015
DATE: .
CONTROL NUMBER
AC LOAD = 6000VA
DATE:
APPROVAL/CERTIFICATION REQUIREMENTS,
ELECTRICAL CALCULATIONS DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
PMT OPRNS
SAUDI ARABIAN OIL COMPANY
TOTAL LOAD = 23100VA
NKH HAB
Equipment grounding conductor sized based on NEC Table 250-122. For 70Amp Over
JAN.2015 14C0207
Current protection, the minimum size of the grounding conductor is # 8 AWG Copper
DATE
DISCIPLINE
ENGINEER
AMO
For cable (1- 4/C X 16mm2 CU/XLPE/ PVC + 1/C 16mm2 CU/PVC (GROUND) ) .
JAN2015
DATE:
PROJECT From (Saudi Cable Catalogue section 5 - Page 35 & §ion 2- Page: 9).
ENGINEER
HAB
JAN2015 Minimum Conduit Size Requirement = (23.9) ²+(9.1) ² /0.4
DATE:
CERTIFIED
NKH = 40 mm
DATE:
JAN2015 = 2 IN
CONSTRUCTION Use 2”// DIA. Rigid Steel Conduit.
AGENCY
TNB
JAN2015
DATE:
OPERATIONS
ARK
JAN2015
DATE:
CONTROL NUMBER
VERIFICATION
EDSD
DATE:
BY:
REVISIONCERTIFICATION
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE
00A
OF THIS DRAWING IS COVERED, FOR ALL
ELECTRICAL CALCULATIONS DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION