Hart P&F
Hart P&F
HART Interface
Solutions
11/2010
908837 (US) / 208599 (EU)
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Interface Solutions Introduction
At the core of HART Interface Solution (HIS), the HART Multiplexer acts like a gateway device, routing communications
between the maintenance workstation PC and the HART field devices. Pepperl+Fuchs supports several different platforms HART
(K-System, H-System).
Time
K-System 526
Master/slave system for up to 7,936 field devices
Compact design, DIN rail mounting
Network up to 31 Multiplexers via RS 485
Compatible with operating and asset management software
(AMS, PDM, FieldCare, PACTware™)
Suitable for loop integrity up to SIL3
H-System 550
Stand-alone Multiplexer for up to 992 field devices
Termination Board solution
Network up to 31 Multiplexers via RS 485
Compatible with operating and asset management software
(AMS, PDM, FieldCare, PACTware™)
Suitable for loop integrity up to SIL3
11/2010
908837 (US) / 208599 (EU)
Edition
HART
K-System
HART K-System
Multiplexers
HART
Termination
Boards
HART Loop
Converters
Accessories
11/2010
908837 (US) / 208599 (EU)
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Interface Solutions Table of Contents
HART Multiplexers
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 535
K-System
Product Data Sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 537
Termination Boards
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 535
Multiplexers
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 535
HART
Product Data Sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 545
Accessories
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 536
Termination
Boards
Product Data Sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 548
HART Loop
Converters
Accessories
11/2010
908837 (US) / 208599 (EU)
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description HART Interface Solutions
The K-System HART Multiplexer works as a master/slave • Up to 16 field devices can be KFD0-HMS-16
system and when fully occupied can drive up to 256 HART connected 1
field devices. Up to 15 additional slaves can be connected to • Used with HART Multiplexer Master
K-System
32
30
28
26
24
22
20
18
16
14
12
10
2
Termination
X1
Boards are designed to
31
29
27
25
23
21
19
17
15
13
11
1
establish the connection of a
C15
C13
C11
C9
C7
C5
C3
C1
Figure 1 K-System HART communication 1 2
KFD*-HM*-16 HART
C16
C14
C12
C10
C8
C6
C4
C2
Multiplexer to up to 16 field X2
R16
R15
R14
R13
R12
R11
R10
R9
R8
R7
R6
R5
R4
R3
R2
R1
devices.
Components
25 26
HART Multiplexer
32
30
28
26
24
22
20
18
16
14
12
10
2
found in the data sheet of the
HART Loop
Converters
29
27
25
23
21
19
17
15
13
11
1
Board.
• HART field device inputs
• 16 field devices and up to 15
KFD0-HMS-16 slave units can Figure 4 HART Termination Board
KFD2-HMM-16
be connected 1
3 4
OK
• Configurable by keypad
908837 (US) / 208599 (EU)
Figure 5 40 mm housing
(KFD2-HLC-Ex1.D.4S)
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Interface Solutions System Description
Topology
HART
HART Multiplexer
A wide variety of Termination Boards are available. For additional information about topology, refer to HART Multiplexer System
manual.
Multiplexer Master and Slaves are connected to Termination Boards, which transmits the control signals via screw terminals. In
K-System
this case the Termination Board provides a parallel connection to the Multiplexer or Slave. This assembly method is completely
independent of DCS.
For hazardous location applications, the intelligent field device must be isolated from the safe area via a K-System isolator. The
isolated signals are then connected to Termination Boards, where a parallel connection to the Multiplexer or Slave is made via a
26-pin ribbon cable.
HART
HART
HART
Multiplexers
HART
Isolated
DCS barriers
16 32 32 16 16 32 32 16
Up to
16
Termination
field devices
Boards
1 17 17 1 1 17 17 1
X2 X1 X2 X1
2 26 2 26
IDC connector IDC connector
1 25 1 25
X3 X3
Termination
Board
Power Rail insert
Management
software 26-pin ribbon cable
1 2 3
HART Loop
4 5 6
Converters
KFD2-EB2 KFD2-HMM-16 KFD0-HMS-16
ON
ERR PWR ON
S1 I II
5 AT
13 14 15 16 17 18
19 20 21
7 8 9
10 11 12
13 14 15
Converter
14-pin ribbon cable DIN Rail
RS 232
Accessories
RS 485 up to 15 HART Multiplexer Slaves per Master
24 VDC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description HART Interface Solutions
Active input
Transmitter supply
The active input is used for supply of a transmitter. The
measured value is transmitted via the HART communication 1 2
4 5
3
6
1 2 3 4 5 6
not via the 4 mA ... 20 mA signal. The field device KFD2-HLC-
Ex1.D.4S KFD2-STC4-Ex1.2O.H
1 2
PWR
RS232
OK
7 8 9 10 11 12
13 14 15 16 17 18
Multiplexers
19 20 21 22 23 24
7 8 9
HART 10 11 12
HART
13 14 15
1 2 3 4 5 6
Boards
KFD2-HLC-
Ex1.D.4S
PWR
IN /
CH K
1
1 2
Connection to field device with active current output
OUT
ESC
RS232
HART
Passive input
Accessories
OK
7 8 9 10 11 12
13 14 15 16 17 18
19 20 21 22 23 24
11/2010
908837 (US) / 208599 (EU)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Interface Solutions System Description
K-System
Power Rail
The Power Rail is a plastic insert into a standard DIN rail and
contains two leads that deliver power to the modules. Power
is sent through the rail by a power feed module that delivers
24 V DC at 4 A. The module uses a 5 A fuse to protect the
barriers. The Power Rail virtually eliminates the risk of wiring
faults and facilitates easy expansion. Power Rail is available
in two versions:
• UPR-03: 3-lead version supplies two leads for power and
one lead for error signal
Multiplexers
• UPR-05: 5-lead version supplies two leads for power, one
HART
lead for error signal and two leads for serial data
exchange.
Termination
Boards
Figure 10 Universal Power Rail UPR-05
HART Loop
Converters
Accessories
Figure 12 Improper K-System mounting
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description HART Interface Solutions
7 8 9 7 8 9 7 8 9 7 8 9
10 11 12 10 11 12 10 11 12 10 11 12
respective data sheet.
Protection of operating personnel and the system is not
ensured if the product is not used in accordance with its
intended use.
Power supply with Power Rail Installation of the interface devices in the
The Pepperl+Fuchs Power Rail eliminates wiring hassles and safe area
reduces expense. The power feed module mounts on the
Power Rail for easy and reliable distribution of power to all The devices are constructed to satisfy the IP20 protection
connected isolated modules. This method eliminates all of the classification and must be protected from adverse
parallel power wiring necessary on a conventional installation environmental conditions such as water spray or dirt
HART Loop
KFD2-HMM-16 Ex1.D
ERR PWR
Declaration of Conformity or separate certificate of conformity
ON
can be installed in Zone 2/Div. 2.
RS232
ESC
The individual data sheets indicate whether these conditions
are met.
OK
7 8 9 10 11 12
13 14 15 16 17 18 13 14 15 16 17 18
19 20 21 19 20 21 22 23 24
7 8 9
10 11 12
13 14 15
11/2010
908837 (US) / 208599 (EU)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Interface Solutions System Description
For US and Canada installations, in Zone 2/Div. 2 follow the Technical data
NEC and CEC wiring methods. The enclosure must be able to HART
accept Zone 2/Div. 2 wiring methods. The referenced product
certification control drawing must be observed. Electrical data
For all other applications, the devices should be installed in a For electrical data, see data sheets.
switch or junction box that:
Mechanical data
K-System
• meets at least IP54 in accordance to EN 60529.
• meets to the requirements of resistance to light and Mounting
resistance to impact according to EN 60079-0/ • Snap-on 35 mm standard DIN rail acc. to EN 60715. Can
IEC 60079-0. be mounted horizontally or vertically, side by side.
• meets to the requirements of thermal endurance • Panel mount: The lugs on the base of the modules must
according to EN 60079-15/IEC 60079-15. be extended and used for mounting purposes with 3 mm
• must not cause ignition danger by electrostatic charge screws.
during intended use, maintenance and cleaning. • K-MS mounting base for screw attachment
The EC-Type Examination Certificates, standard
certificates/approvals or the manufacturer's Declaration of Mass
Multiplexers
Conformity should be observed. It is especially important to Termination Boards: 200 g to 400 g
HART
observe the "special conditions" if these are included in the
Modules: 100 g to 250 g
certificates.
Housing material
Repair and maintenance Polycarbonate (PC)
The transfer characteristics of the devices remain stable over Dimensions
long periods of time. This eliminates the need for regular
adjustment. Maintenance is not required. Housing drawings please refer to the appendix.
Termination
Protection degree
Boards
Fault elimination
Modules: IP20 acc. to EN 60529
No changes can be made to devices that are operated in
hazardous areas. Repairs on the device are not allowed. Connection
• Removable connector with integrated self-opening device
Isolation coordinates for installations for terminals for leads of up to a max. of 1 x 2.5 mm2
galvanic isolation according to EN 50178 (14 AWG)
and EN 61140 • Signal connection via ribbon cable
HART Loop
Converters
The devices of the K-System are electronic equipment for use Labeling
in secluded electrical operating sites where only skilled
personnel or electrically instructed personnel will have place for labeling on the front side, label: 8 mm x 18 mm
admission or access.
The devices are assessed for pollution degree 2 and
overvoltage category II according to EN 50178.
For additional details, see data sheets.
Accessories
11/2010
908837 (US) / 208599 (EU)
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description HART Interface Solutions
Ambient conditions
HART
Ambient temperature
Modules: -20 °C to 60 °C (-4 °F to 140 °F)
Termination Boards: 0 °C to 55 °C (32 °F to 131 °F)
Storage temperature
K-System
frequency
HART
Shock resistance
acc. to EN 60068-2-27, 15 g, 11 ms, half-sine
11/2010
908837 (US) / 208599 (EU)
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Interface Solutions Selection Tables
HART Multiplexers
HART
Model Number Page
Zone 2/Division 2
Power Rail
Mounting
Channels
K-System
Master
Slave
SIL*
KFD2-HMM-16 16 3 537
KFD0-HMS-16 16 3 538
* see also table Termination Boards
Termination Boards
Multiplexers
Model Number Page
HART
Communication Isolation
Parallel Connection
Zone 2 Mounting
Communication
KFD*-HM*-16)
Connection
Capacitive
Channels
Resistor
Termination
Boards
FI-DO-Y37023 16 2 539
FI-DO-R-Y41610 16 2 540
FI-DO-R-Y49092 16 2 541
FI-PFH-108874 16 3 542
FI-PFH-110469 16 3 543
HART Loop
Converters
FI-PFH-127720 16 3 544
Accessories
Transmitter Supply
Zone 2/Division 2
(Active/Passive)
0/4 mA ... 20 mA
Supply 24 V DC
Channels
Mounting
Signal
Relay
SIL
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Selection Tables HART Interface Solutions
Accessories
HART
K-HM26 HART Connection Cable with Connectors (Master/Slave – Termination Board) 549
Multiplexers
HART
Termination
Boards
HART Loop
Converters
Accessories
11/2010
908837 (US) / 208599 (EU)
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Multiplexer Master KFD2-HMM-16
K-System
Connection 26-pin flat cable for analog connections • Up to SIL3 acc. to IEC 61508
14-pin flat cable for master-slave connection between
KFD2-HMM-16 and KFD0-HMS-16
Function
Leakage current < 3 μA at -20 ... 85 °C (-4 ... 185 °F)
Terminating resistor external 230 ... 500 Ω standard (up to 1000 Ω possible) This HART Multiplexer Master operates
Output voltage ≥ 400 mVpp (with the terminator resistance specified up to 256 analog field instruments. The
above)
built-in slave unit in the HART master
Output resistance 100 Ω or smaller, capacitive coupling
operates the first 16 field instruments. If
Input impedance according to HART specification
more than 16 field instruments are
Input voltage range 0.08 ... 4 Vpp; typ. ± 5.2 V as local reference
required, up to 15 additional HART
Interface
Multiplexers
Multiplexer Slaves KFD0-HMS-16 can be
Transfer rate 9600, 19200, or 38400 Bit/s (selectable with
connected.
HART
DIL switch (2 and 3) by the user)
Type RS 485 2-wire multidrop The slave units are connected to the
Address selection One of 31 possible addresses selectable per master with a 14-pin flat cable. The
DIL switch (4 ... 8) connector for the ribbon cable is found on
Ambient conditions the same housing side as the connectors
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) for the interface and the power supply.
Mechanical specifications The analog signals are separately linked
Protection degree IP20 to a termination board via a 26-pin flat
Termination
Mass approx. 250 g cable for each unit. Sixteen leads are
Boards
Dimensions 40 x 107 x 115 mm (1.6 x 4.2 x 4.5 in), housing type C1 reserved for the HART signal of the
Data for application in connection analog measurement circuits. The
with Ex-areas
remaining 10 leads are sent to ground.
Statement of conformity Pepperl+Fuchs
Group, category, type of protection, ¬ II 3G Ex nA II T4 X This unit is designed with removable
temperature classification terminals and can be connected to the
Power Rail.
HART Loop
Converters
Accessories
Diagrams
Front view
LED red:
KFD2-HMM-16 Fault signal
HART 21 1
ON
...
Termination 1
11/2010
2
Board FI 23 13 GND 3
24 14 T- 4
25 15 T+ LED green: 5
6
26 Power supply 7
1 8 26
908837 (US) / 208599 (EU)
2
13 14 15 16 17 18
KFD0-HMS-16
...
19 20 21
14
17+
18-
24 V DC
LED orange:
Operational
24 V DC Zone 2 Removable terminals
Power Rail Div. 2 green
Edition
14 pin connector
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 537
www.pepperl-fuchs.com [email protected] [email protected] [email protected]
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD0-HMS-16 HART Multiplexer Slave
• 16-channel Supply
Connection via 14-channel flat cable form master KFD2-HMM-16
• No external power required
HART signal channels
• HART field device inputs (intrinsically safe)
• Used with HART Multiplexer Master HART signal channels
KFD2-HMM-16 Connection 26-pin flat cable for analog connections
K-System
• Up to SIL3 acc. to IEC 61508 14-pin flat cable for master-slave connection between
KFD2-HMM-16 and KFD0-HMS-16
Leakage current < 3 μA at -20 ... 85 °C (-4 ... 185 °F)
Function
Terminating resistor external 230 ... 500 Ω standard (up to 1000 Ω possible)
This HART Multiplexer Slave operates up Output voltage 400 mVpp (with the terminator resistance specified
above)
to 16 analog field instruments. It can be
Output resistance 100 Ω or smaller, capacitive coupling
operated only with the HART Multiplexer
Input impedance according to HART specification
Master KFD2-HMM-16 and is powered by
Input voltage range 0.08 ... 4 Vpp; typ. ± 5.2 V as local reference
the master across a 14-pin flat cable
Ambient conditions
connection.
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Multiplexers
Diagrams
Front view
KFD0-HMS-16
Rotary switch
KFD0-HMS-16 1
1
2
1
...
HART HART 2
11/2010
KFD2-HMM-16/
...
Termination
...
23 KFD0-HMS-16
Board FI
24 14
26 25
908837 (US) / 208599 (EU)
26
26 pin
connector
Zone 2
14 pin Div. 2
connector
Edition
538 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected]
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Termination Board FI-DO-Y37023
K-System
Ambient conditions Function
Ambient temperature 0 ... 55 °C (32 ... 131 °F)
Mechanical specifications This HART Termination Board have
Core cross-section 2.5 mm2 (16 AWG) 16 terminal blocks to connect up to
Connection field side: screw terminals 16 HART field devices.
control side: screw terminals It does not have a 250 Ω HART pick-up
multiplexer connection: 26-pin NFP-26A (Yamaichi) resistor built in and can be used only in
Mass approx. 200 g applications that have a 250 Ω resistor in
Dimensions 67 x 50 x 126 mm (2.6 x 1.9 x 5 in) the DCS/PLC or I/O card. It does not
Mounting DIN rail mounting come with terminal blocks for
Multiplexers
Data for application in connection 4 mA ... 20 mA signal to DCS/PLC.
with Ex-areas
HART
Statement of conformity PF 10 CERT 1617 X The Termination Board can be used for
Group, category, type of protection ¬ II 3G Ex nA II T4 general-purpose applications or in
conjunction with intrinsic safety barriers
for hazardous applications.
A 26-pin flat cable K-HM26 is used for
connection of each HART Multiplexers
KFD*-HM*-16 to the Termination Board.
Termination
Other Termination Boards are available.
Boards
Contact Pepperl+Fuchs for details.
HART Loop
Converters
Accessories
Diagrams
Front view
KFD*-HM*-16
I II ... XVI
X2 6 7 23 24 -
X1
FI-DO-Y37023 17
1
... To Connection
11/2010
I
mA mA 25 26
II
16x 16x
...
...
32
16
PEPPERL + FUCHS
XVI
Zone 2
Edition
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 539
www.pepperl-fuchs.com [email protected] [email protected] [email protected]
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
FI-DO-R-Y41610 HART Termination Board
Ambient conditions
Function Ambient temperature 0 ... 55 °C (32 ... 131 °F)
Mechanical specifications
This HART Termination Board have Core cross-section 2.5 mm2 (16 AWG)
16 terminal blocks to connect up to Connection field side: screw terminals
16 HART field devices. control side: screw terminals
multiplexer connection: 26-pin NFP-26A (Yamaichi)
It has a 250 Ω HART pick-up resistor built
Mass approx. 300 g
in, and terminal blocks for the
Dimensions 67 x 70 x 126 mm (2.6 x 2.8 x 5 in)
4 mA ... 20 mA signal to the DCS/PLC.
Mounting DIN rail mounting
The Termination Board can be used for
Multiplexers
general-purpose applications or in
HART
Diagrams
Front view
To
KFD*-HM*-16 KFD*-HM*-16
I II ... XVI
X3 6 7 23 24 -
X3
25 1
IDC connector
26 2
Connection X1 X2 Connection
X1 X2
11/2010
1 17 17 1
Field devices DCS 250 Ω
1+ 1+
I 17- 17- I
mA mA
250 Ω
2+ 2+
908837 (US) / 208599 (EU)
II II
16x 18- 18- 16x
...
...
...
...
250 Ω
16+ 16+
XVI 32- 32- XVI
16 32 32 16
PEPPERL + FUCHS
FI-DO-R-Y41610
Edition
540 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected]
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Termination Board FI-DO-R-Y49092
K-System
Ambient conditions Function
Ambient temperature 0 ... 55 °C (32 ... 131 °F)
Mechanical specifications This HART Termination Board have
Core cross-section 2.5 mm2 (16 AWG) 16 terminal blocks to connect up to
Connection field side: screw terminals 16 HART field devices.
control side: screw terminals It does not have a 250 Ω HART pick-up
multiplexer connection: 26-pin NFP-26A (Yamaichi) resistor built in and can be used only in
Mass approx. 300 g applications that have a 250 Ω resistor in
Dimensions 67 x 70 x 126 mm (2.6 x 2.8 x 5 in) the DCS/PLC or I/O card. It does not
Mounting DIN rail mounting come with terminal blocks for
Multiplexers
4 mA ... 20 mA signal to DCS/PLC.
HART
The Termination Board can be used for
general-purpose applications or in
conjunction with intrinsic safety barriers
for hazardous applications.
A 26-pin flat cable K-HM26 is used for
connection of each HART Multiplexers
KFD*-HM*-16 to the Termination Board.
Termination
Other Termination Boards are available.
Boards
Contact Pepperl+Fuchs for details.
HART Loop
Converters
Accessories
Diagrams
Front view
To
KFD*-HM*-16 KFD*-HM*-16
I II ... XVI
X3 6 7 23 24 -
X3
25 1
IDC connector
26 2
Connection X1 X2 Connection
X1 X2
11/2010
1 17 17 1
Field devices DCS
1+ 1+
I 17- 17- I
mA mA
2+ 2+
908837 (US) / 208599 (EU)
II II
16x 18- 18- 16x
...
...
...
...
16+ 16+
XVI 32- 32- XVI
16 32 32 16
PEPPERL + FUCHS
FI-DO-R-Y49092
Edition
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 541
www.pepperl-fuchs.com [email protected] [email protected] [email protected]
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
FI-PFH-108874 HART Termination Board
Ambient conditions
Function Ambient temperature 0 ... 55 °C (32 ... 131 °F)
Mechanical specifications
This HART Termination Board have Core cross-section 2.5 mm2 (16 AWG)
16 terminal blocks to connect up to Connection field side: screw terminals
16 HART field devices. control side: screw terminals
multiplexer connection: 26-pin NFP-26A (Yamaichi)
The connection board is connected in
Mass approx. 200 g
parallel into the field device loop. The
Dimensions 67 x 50 x 126 mm (2.6 x 1.9 x 5 in)
HART signal is galvanically isolated via
Mounting DIN rail mounting
capacitors.
Multiplexers
Diagrams
Front view
KFD*-HM*-16
I II ... XVI
X2 6 7 23 24 -
X1
C1 C2
17
FI-PFH-108874
C3 C4 1
To Connection ...
11/2010
C5
KFD*-HM*-16 HART Loops
X2
C6
1 2 C7
X1 1+ 17- 2+ 18- 16+ 32-
IDC connector
C8
908837 (US) / 208599 (EU)
PEPPERL + FUCHS
C9 I
25 26 mA mA
C10
II
C11
C12
16x 16x
...
...
C13 C14 32
16
C15 C16
XVI
Zone 2
Edition
542 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected]
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Termination Board FI-PFH-110469
K-System
Ambient conditions • Galvanic isolation of HART signal
Ambient temperature 0 ... 55 °C (32 ... 131 °F)
Mechanical specifications Function
Core cross-section 2.5 mm2 (16 AWG)
Connection field side: screw terminals This HART Termination Board have
control side: screw terminals 16 terminal blocks to connect up to
multiplexer connection: 26-pin NFP-26A (Yamaichi)
16 HART field devices.
Mass approx. 400 g
Dimensions 67 x 100 x 126 mm (2.6 x 3.9 x 5 in)
It has a 250 Ω HART pick-up resistor and
Mounting DIN rail mounting
a ground capacitor built in. It also has
terminal blocks for the 4 mA ... 20 mA
Multiplexers
Data for application in connection
with Ex-areas signal to the DCS/PLC.
HART
Statement of conformity PF 10 CERT 1617 X A 26-pin flat cable K-HM26 is used for
Group, category, type of protection ¬ II 3G Ex nA II T4 connection of each HART Multiplexers
KFD*-HM*-16 to the Termination Board.
Other Termination Boards are available.
Contact Pepperl+Fuchs for details.
Termination
Boards
HART Loop
Converters
Accessories
Diagrams
Front view
KFD*-HM*-16
I II ... XVI
X2 6 7 23 24 -
To
32
30
28
26
24
22
20
18
16
14
12
10
KFD*-HM*-16
X1 X3 Connection X1
250 Ω
11/2010
31
29
27
25
23
21
19
17
15
13
11
1+ 1+ Field devices
I
C15
C13
C11
C9
C7
C5
C3
C1
2- 2- 1 2
C16
C14
C12
C10
C8
C6
C4
C2
mA mA
250 Ω X2
3+ 3+
908837 (US) / 208599 (EU)
Connection
II
R16
R15
R14
R13
R12
R11
R10
R9
R8
R7
R6
R5
R4
R3
R2
R1
16x 4- 4- 16x 25 26
DCS
...
...
...
...
FI-PFH-XXXXXX Y
250 Ω PEPPERL + FUCHS
31+ 31+
32
30
28
26
24
22
20
18
16
14
12
10
29
27
25
23
21
19
17
15
13
11
FI-PFH-110469
Zone 2
Edition
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 543
www.pepperl-fuchs.com [email protected] [email protected] [email protected]
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
FI-PFH-127720 HART Termination Board
Ambient conditions
Function Ambient temperature 0 ... 55 °C (32 ... 131 °F)
Mechanical specifications
This HART Termination Board have Core cross-section 2.5 mm2 (16 AWG)
16 terminal blocks to connect up to Connection field side: screw terminals
16 HART field devices. control side: screw terminals
multiplexer connection: 26-pin NFP-26A (Yamaichi)
The connection board is connected
Mass approx. 400 g
serially into the field device loop to access
Dimensions 67 x 100 x 126 mm (2.6 x 3.9 x 5 in)
the HART signal which is galvanically
Mounting DIN rail mounting
isolated via capacitors.
Multiplexers
Diagrams
Front view
KFD*-HM*-16
I II ... XVI
X2 6 7 23 24 -
To
32
30
28
26
24
22
20
18
16
14
12
10
KFD*-HM*-16
Connection X1 X1 X3
0Ω
11/2010
31
29
27
25
23
21
19
17
15
13
11
Field devices 1+ 1+
I
C15
C13
C11
C9
C7
C5
C3
C1
1 2
2- 2-
C16
C14
C12
C10
C8
C6
C4
C2
mA mA
X2 0Ω
3+ 3+
908837 (US) / 208599 (EU)
Connection
II
R16
R15
R14
R13
R12
R11
R10
R9
R8
R7
R6
R5
R4
R3
R2
R1
25 26
DCS 16x 4- 4- 16x
...
...
...
...
FI-PFH-XXXXXX Y
PEPPERL + FUCHS
0Ω
31+ 31+
32
30
28
26
24
22
20
18
16
14
12
10
29
27
25
23
21
19
17
15
13
11
FI-PFH-127720
Zone 2
Edition
544 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected]
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Loop Converter KFD2-HLC-Ex1.D
K-System
Input
Input signal HART communication, transmitter supply • Configurable by keypad
Open circuit voltage/short-circuit typ. 24 V/28 mA
current Function
Input resistance 250 Ω, 5 % (terminals 2, 3 and with jumper on 5, 6)
Available voltage ≥ 15.5 V at 20 mA, short-circuit proof This isolated barrier is used for intrinsic
Output safety applications. It is a HART loop
Output signal analog converter that provides power to
Current range 4 ... 20 mA, source or sink mode transmitters or can be connected to
Load ≤ 650 Ω, source mode existing HART loops in parallel.
Voltage range 5 ... 30 V, sink mode from external supply
It is able to evaluate up to four HART
Multiplexers
Collective error message Power Rail and LED red
variables (PV, SV, TV, QV). Of those four
Fault signal downscale I ≤ 2 mA, upscale I ≥ 21.5 mA
HART
(acc. NAMUR NE43) or hold measurement value HART variables, the data contained in
Other outputs HART communicator on terminals 22, 24 any three of them can be converted to
Ambient conditions
three different 4 mA ... 20 mA current
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) signals. These loop signals can be
Mechanical specifications connected to display devices or analog
Protection degree IP20
inputs on the process control
Mass 300 g system/control system.
Termination
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in), housing type C3 The unit is easily programmed by the use
Boards
Data for application in connection see page 258 for entity parameters of a keypad located on the front of the
with Ex-areas unit.
EC-Type Examination Certificate BASEEFA 07 ATEX 0174
For additional information, refer to the
Group, category, type of protection ¬ II (1)GD [Ex ia] IIC, [Ex iaD]
manual and www.pepperl-fuchs.com.
Statement of conformity Pepperl+Fuchs
Group, category, type of protection, ¬ II 3G Ex nA II T4 X
temperature classification
HART Loop
Converters
Accessories
Diagrams
Front view
Removable
terminals
blue
KFD2-HLC-Ex1.D
+ LED green:
1+ 7 Power supply
HART 1 2 3 4 5 6
LC display
I
HART
+ + mA 8+ KFD2-HLC-
2+ + V Ex1.D
HART
9- - ERR PWR
- mA - - 13
3- 14+ II LED red:
11/2010
mA + V Fault indication
15- -
4 19 ESC
+ V OK Keypad
5 21- -
908837 (US) / 208599 (EU)
7 8 9 10 11 12
13 14 15 16 17 18
6 19 20 21 22 23 24
22 Programming jack
HART
23+ Removable
24-
24 V DC
terminals
green
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD2-HLC-Ex1.D.2W HART Loop Converter
Input
• 3 analog outputs 4 mA ... 20 mA Input signal HART communication, transmitter supply
• Sink and source mode output Open circuit voltage/short-circuit typ. 24 V/28 mA
current
• Configurable by keypad
Input resistance 250 Ω, 5 % (terminals 2, 3 and with jumper on 5, 6)
Available voltage ≥ 15.5 V at 20 mA, short-circuit proof
Function
Output
Collective error message Power Rail and LED red
This isolated barrier is used for intrinsic
Output I, II
safety applications. It is a HART loop
Output signal relay and LED yellow
converter that provides power to
Mechanical life 107 switching cycles
transmitters or can be connected to
Multiplexers
system/control system. Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
In addition to the current outputs, two Mechanical specifications
form C changeover relay contacts are Protection degree IP20
available and can be programmed to Mass 300 g
operate at trip values from the HART Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in), housing type C3
variables. Data for application in connection see page 258 for entity parameters
with Ex-areas
The unit is easily programmed by the use
EC-Type Examination Certificate BASEEFA 07 ATEX 0174
of a keypad located on the front of the
HART Loop
Converters
Group, category, type of protection ¬ II (1)GD [Ex ia] IIC, [Ex iaD]
unit.
Statement of conformity Pepperl+Fuchs
For additional information, refer to the Group, category, type of protection, ¬ II 3G Ex nA nC II T4 X
manual and www.pepperl-fuchs.com. temperature classification
Accessories
Diagrams
Front view
Removable
terminals
blue
KFD2-HLC-Ex1.D.2W
+ 10
LED green: 1+ 11 I
Power supply
1 2 3 4 5 6
LC display HART 12
HART
KFD2-HLC- + +
Ex1.D.2W
2+ 16
HART
ERR PWR
- mA - -
17 II
LED red: 1 2 3- 18
11/2010
OUT
Fault indication 7
ESC
4 mA 8+ III
+ V
RS232
9- -
LEDs yellow: OK Keypad 13
5
Relay status IV
908837 (US) / 208599 (EU)
7 8 9 10 11 12 mA 14+
+ V
13 14 15 16 17 18
6 15- -
19 20 21 22 23 24
19
mA 20+ V
+ V
21- -
Programming jack 22
HART
Removable 23+
24-
24 V DC
terminals
green
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Loop Converter KFD2-HLC-Ex1.D.4S
K-System
Input
Input signal HART communication, transmitter supply • Sink and source mode output
Open circuit voltage/short-circuit typ. 24 V/28 mA
• Configurable by keypad
current
Input resistance 250 Ω, 5 % (terminals 2, 3 and with jumper on 5, 6)
Function
Available voltage ≥ 15.5 V at 20 mA, short-circuit proof
Output
This isolated barrier is used for intrinsic
Collective error message Power Rail and LED red
safety applications. It is a HART loop
Output I, II, III, IV
converter that provides power to
Output signal relay and LED yellow
transmitters or can be connected to
Mechanical life 107 switching cycles
existing HART loops in parallel.
Multiplexers
Energized/De-energized delay approx. 20 ms/approx. 20 ms
Output V, VI, VII It is able to evaluate up to four HART
HART
Output signal analog variables (PV, SV, TV, QV). Of those four
Current range 4 ... 20 mA, source or sink mode HART variables, the data contained in
Load ≤ 650 Ω, source mode any three of them can be converted to
Voltage range 5 ... 30 V, sink mode from external supply three different 4 mA ... 20 mA current
Fault signal downscale I ≤ 2 mA, upscale I ≥ 21.5 mA signals. These loop signals can be
(acc. NAMUR NE43) or hold measurement value connected to display devices or analog
Other outputs HART communicator on terminals 22, 24 inputs on the process control
Termination
Ambient conditions system/control system.
Boards
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) In addition to the current outputs, four
Mechanical specifications form A normally open relay contacts are
Protection degree IP20 available and can be programmed to
Mass 300 g operate at trip values from the HART
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in), housing type C3 variables.
Data for application in connection see page 258 for entity parameters
The unit is easily programmed by the use
with Ex-areas
of a keypad located on the front of the
EC-Type Examination Certificate BASEEFA 07 ATEX 0174
unit.
HART Loop
Converters
Group, category, type of protection ¬ II (1)GD [Ex ia] IIC, [Ex iaD]
Statement of conformity Pepperl+Fuchs For additional information, refer to the
Group, category, type of protection, ¬ II 3G Ex nA nC II T4 X manual and www.pepperl-fuchs.com.
temperature classification
Accessories
Diagrams
Front view
Removable
terminals
blue
KFD2-HLC-Ex1.D.4S
+ 10 I
1+ 11 LED green:
HART 12 II Power supply
1 2 3 4 5 6
LC display
HART
+ + KFD2-HLC-
2+ 16 III
Ex1.D.4S
HART
mA 17 1 PWR
- - -
3- 18 IV LED red:
IN /
CH K
1 2
11/2010
OUT
7 Fault indication 3 4
4 mA 8+ V ESC
+ V
9- -
RS232
mA 14+
+ V 7 8 9 10 11 12
6 15- - 13 14 15 16 17 18
19 20 21 22 23 24
19
mA 20+ VII
+ V
21- -
22 Programming jack
HART
23+ Removable
24-
24 V DC
terminals
green
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Accessories HART Interface Solutions
HART Filter
HART
HISHF-AI-02 Technical data
HART signal channels
Features (intrinsically safe)
HART signal channels
• 2-channel Isolation 30 V DC
• Ideal for retrofitting existing Ambient conditions
K-System
Function
The unit is a stand-alone HART analog
input filter. It is designed to complement
the I/O Termination Boards. It filters the
Multiplexers
control loop.
This unit mounts on DIN rail, has
removable terminal blocks, and includes
connections for HART communicators.
HART Filter
Technical data
Termination
HISHF-AO-02
Boards
Function
This unit is a stand-alone HART analog
output filter. It is designed to complement
the I/O Termination Boards. It filters the
HART signal from the 4 mA ... 20 mA
Accessories
control loop.
This unit mounts on DIN rail, has
removable terminal blocks, and includes
connections for HART communicators.
11/2010
908837 (US) / 208599 (EU)
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Interface Solutions Accessories
HART Filter
HART
K-22μ
Ø10
Features
18
28 • 1-channel
• Parallel connection to HART loop
K-System
• Filters HART signal from control
Technical data loop
Electrical specifications
Capacitance 22 μF, 16 V Function
Damping 20 μA, at 250 Ω
Mechanical specifications
The capacitor is used to filter or suppress
Dimensions Ø10 x 28 mm (0.4 x 1.1 in)
HART communication.
Multiplexers
Connectors
K-HM14
HART
14-pin IDC connector (female)
Termination
Boards
Master Slave 1 Slave 2 ........... Slave 14 max. Slave 15 Function
KFD2-HMM-16
The connection cable K-HM14 is used for
KFD0-HMS-16
connection of a HART Multiplexer Master
KFD2-HMM-16 to up to
Technical data 15 HART Multiplexer Slaves KFD0-HMS-
Ambient conditions 16.
Ambient temperature 0 ... 55 °C (32 ... 131 °F)
The connection cable has 16 connectors
Mechanical specifications
HART Loop
and a length of 0.45 m. Other cable
Converters
Connection 14-pin IDC female connector
lengths (max. 8 m) are available upon
Cable length 0.45 m
request.
Note distance of plugs 3 cm (1.2 in)
Accessories
26-pin IDC connector (female)
Features
• K-System accessory
• Connection cable for KF*-HM*-16 to
Termination Board
• 26-pin flat cable
26
Function
Master KFD2-HMM-16/ Termination Board FI
11/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H-System HART Interface Solutions
HART
H-System
HART H-System
Multiplexers
HART
Termination
Boards
Accessories
11/2010
908837 (US) / 208599 (EU)
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Interface Solutions Table of Contents
HART Multiplexers
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 557
H-System
Product Data Sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 558
Termination Boards
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 557
Accessories
Multiplexers
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 557
HART
Product Data Sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 563
Termination
Boards
Accessories
11/2010
908837 (US) / 208599 (EU)
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description HART Interface Solutions
RS 485 interface.
ON
FAULT HART TX
32 Channel
Multiplexer
2700
MUX
Hart
PWR
ON
OFF
Figure 3 HART Communication Board
Topology
This figure illustrates a typical H-System solution. It contains a
Termination Board, Fault Indication Board and HART
Communication Board. One HART Communication Board is
Multiplexers
OFF ON
Termination
Multiplexer
Hart
32 Channel
2700
MUX
Boards
ON
PWR
Internal
fault bus
Components
HART Multiplexer HART
Accessories
Ch. 1 ... 8
• Compact 18 mm housing
• HART field device inputs
PWR
ON Control Fault output Power supply 1
• Termination Board mounted FAULT HART TX
system (relay contact) Power supply 2
• DIP switch settings for RS 485 Figure 4 H-System topology
MUX
2700
32 Channel
Hart
Mounting
Multiplexer
• Place the Termination Board onto the DIN rail (Figure 5).
The HART Communication Board can interface with HART
enabled H-System Termination Boards. It contains one slot to • Tighten the fastening screws (Figure 6).
mount the 32-channel HART Multiplexer type HiDMux2700. The Termination Board is now properly mounted and secured.
The HiACA-UNI-FLK34-*. cables provide easy connection
between the HiD/HiC (H-System) Termination Boards and the
HART Communication Board.
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Interface Solutions System Description
Module
Hi D Mux 2 7 0 0
H-System
Model number
2700
DIN mounting rail
Type
Figure 5 Proper mounting of the H-System Termination Board Mux HART Multiplexer
Housing
Fastening screw
D 18 mm module
Hi H-System
Multiplexers
HART
HART Communication Boards
ON
FAULT HART TX
32 Channel
Multiplexer
2700
MUX
Hart
PWR
ON
OFF
HiATB 01 – HART –
Figure 6 Top view of the H-System HART Communication Board
Termination
Mounting the module on the Termination
Boards
Board
• Ensure that the red Quick Lok Bar (1) is in the upper
position Number of connectors and
• Center the pins over the contacts on the Termination terminals
Board and observe the plug orientation of the device 2X16 with 2 connectors of
• Carefully press the device into the contacts 16 channels each
Accessories
• Press the red Quick Lok Bar (1) down on either side of the 4X8 with 4 connectors of
device (see Figure 7) 8 channels each
1
11/2010
908837 (US) / 208599 (EU)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description HART Interface Solutions
Safety information For US and Canada installations, in Zone 2/Div. 2 follow the
HART NEC and CEC wiring methods. The enclosure must be able to
The corresponding data sheets, the Declaration of accept Zone 2/Div. 2 wiring methods. The referenced product
Conformity, the EC-Type Examination Certificate and certification control drawing must be observed.
applicable certificates (see data sheet) are an integral part of
For all other applications, the devices should be installed in a
this document.
switch or junction box that:
H-System
power engineering, unless this is specifically referred to in the Conformity should be observed. It is especially important to
HART
respective data sheet. observe the "special conditions" if these are included in the
certificates.
Protection of operating personnel and the system is not
ensured if the product is not used in accordance with its Repair and maintenance
intended use.
The transfer characteristics of the devices remain stable over
Installation and commissioning long periods of time. This eliminates the need for regular
adjustment. Maintenance is not required.
Termination
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Interface Solutions System Description
H-System
Each module is protected internally. The Termination Boards
have redundant power supply connections with fuses that can Relative humidity:
be replaced by the customer. max. 95 % no moisture condensation
Multiplexers
Protection degree
HART
• Termination Boards: IP20 with modules plugged in Conformity with standards and directives
(IP00 without modules)
General
• Modules: IP20
• EMC acc. to NAMUR NE21 and EN 61326
Mass
• LEDs acc. to NAMUR NE44
Termination Boards:
• Software acc. to NAMUR NE53
• HiATB01 approx. 150 g
Termination
Modules:
Boards
• HiDMux2700 approx. 140 g
Material
Modules: Polycarbonate
Termination Boards: Polycarbonate, fiber glass reinforced
Dimensions
Accessories
Termination Boards (height inclusive module assembly):
• HiATB01: 50 x 190 x 200 mm
Modules:
• HiD module: 18 x 106 x 130 mm
Housing drawings please refer to the appendix.
Labeling
A plastic label holder is available on the front of the module:
• HiD module: 35 x 10.5 mm
A large label carrier kit HiALC-… for the Termination Boards is
available as an option.
Fire protection class
Housing: V2 according to UL 94 standard. (Unless stated
otherwise all details relate to the reference conditions.)
11/2010
908837 (US) / 208599 (EU)
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Notes HART Interface Solutions
HART
H-System
Multiplexers
HART
Termination
Boards
Accessories
11/2010
908837 (US) / 208599 (EU)
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Interface Solutions Selection Tables
HART Multiplexers
HART
Model Number Page
RS 485 Connection
Zone 2/Division 2
Supply 24 V DC
Channels
Mounting
H-System
HiDMux2700 32 558
Termination Boards
RS 485 Connection
Multiplexers
Zone 2/Division 2
2 x 16 Channels
Supply 24 V DC
HART
4 x 8 Channels
Power Supply
Redundant
Mounting
Channels
HiATB01-HART-2X16 32 559
Termination
HiATB01-HART-4X8 32 560
Boards
HISHPSM/32/MM-01 32 561
HISHPSM/32/TB-02/HF32 32 562
Accessories
Accessories
Model Number Description Page
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HiDMux2700 HART Multiplexer Master
• 32-channel Supply
Rated voltage 20.4 ... 30 V DC via Termination Board
• 24 V DC supply
Power loss 0.7 W at 24 V
• HART field device inputs HART signal channels
• RS 485 interface (intrinsically safe)
• Up to SIL3 acc. to IEC 61508 HART signal channels
H-System
Number of channels 32
Function Signal range 0.12 Vpp < signal < 1.5 Vpp
Leakage current < 3 μA at -20 ... 85 °C (-4 ... 185 °F)
The HART Multiplexer Master provides Terminating resistor external 230 ... 500 Ω standard (up to 1000 Ω possible)
32 signal channels for connection to Output voltage ≥ 400 mVpp (with the terminator resistance specified
SMART transmitters or control devices above)
supporting digital communication Output resistance 100 Ω or smaller, capacitive coupling
according to the HART standard. DC isolation dual capacitor each channel
Common mode voltage up to 30 V
Full three-port isolation is included and
Input impedance > 5 kΩ, according to HART specification
each input channel has dual capacitor
Multiplexers
Each HART Multiplexer Master is Differential mode clamping ± 5.2 V, for transient or AC signals
networked simply by connecting the high- Common mode clamping ± 10 V, for transient or AC signals
speed RS 485 output in a multidrop Device type DC isolated bus device
configuration. Data link type HART primary and secondary
The device interrogates each field device, Field multi point support option available upon request
under the supervision of the workstation, Interface
retrieving information for storage in its Transfer rate 9600 MBit/s, 19200 MBit/s or 38400 MBit/s,
Termination
Diagrams
Front view
LED green:
Power supply
HiDMux2700
PWR
ON
RS 485
...
...
MUX
2700 32
908837 (US) / 208599 (EU)
32 Channel
Hart
Multiplexer
ON OFF
+
-
24 V DC
Switch 1 ... 8
Zone 2
Div. 2
Edition
558 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected]
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Communication Board HiATB01-HART-2X16
H-System
Power loss ≤ 500 mW, without module Boards
Reverse polarity protected yes
• LED indicator for supply status
Redundancy
Supply Redundancy available. Each supply is decoupled and
fused (500 mA).
Function
Ambient conditions
This HART Communication Board can
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
interface with two, 16-channel H-System
Mechanical specifications
Termination Boards.
Protection degree IP20
Connection screw terminal for max. 2.5 mm2, fixed It contains one slot to mount the 32-
channel HART Multiplexer Master type
Multiplexers
Mass approx. 150 g
Dimensions 50 x 200 x 163 mm (1.97 x 7.9 x 6.42 in), HiD Mux2700.
HART
height including module assembly HART interface cables provide easy
Mounting DIN rail mounting connection between the HiD/HiC
Accessories Termination Boards and the HART
Designation optional accessories: Communication Board.
- HART Multiplexer Master HiDMux2700
- HART connection cable HiACA-... It offers fused redundant power supply
connections with LED indication. RS 485
terminals are redundant and can be daisy
Termination
chained.
Boards
Accessories
Diagrams
24 V DC (I),
HART 1 ... 8, 9 ... 16 HART 17 ... 24, 25 ... 32 24 V DC (II)
+ - + -
Supply II Supply I
11/2010
RS 485
GND
NET A
NET B
908837 (US) / 208599 (EU)
ON
FAULT HART TX
32 Channel
Multiplexer
2700
MUX
Hart
PWR
ON
OFF
Zone 2
Edition
Div. 2
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HiATB01-HART-4X8 HART Communication Board
• 4 x 8-channel Supply
Rated voltage 24 V DC, in consideration of rated voltage of used
• 24 V DC supply isolated barriers
• Suitable for HART communication Voltage drop 0.9 V, voltage drop across the series diode on the
• Dual RS 485 connections Termination Board must be considered
• Used with HiD/HiC Termination Ripple ≤ 10 %
H-System
The HART interface cable provides easy height including module assembly
connection between the HiD/HiC Mounting DIN rail mounting
Termination Boards and the HART Accessories
Communication Board. Designation optional accessories:
- HART Multiplexer Master HiDMux2700
It offers fused redundant power supply - HART connection cable HiACA-...
connections with LED indication. RS 485
terminals are redundant and can be daisy
Termination
chained.
Boards
Accessories
Diagrams
Supply II Supply I
11/2010
RS 485
GND
NET A
NET B
908837 (US) / 208599 (EU)
ON
FAULT HART TX
32 Channel
Multiplexer
2700
MUX
Hart
PWR
ON
OFF
Zone 2
Edition
Div. 2
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Termination Board HISHPSM/32/MM-01
H-System
HART signal channels
(intrinsically safe) • Slot for HART Multiplexer
HART signal channels
Number of channels 32 unbalanced signal loops Function
Redundancy
Supply yes This HART Termination Board has
Ambient conditions 32 terminal blocks to connect up to
Ambient temperature -20 ... 55 °C (-4 ... 131 °F) 32 HART field devices.
Mechanical specifications It contains one slot to mount the 32-
Core cross-section 2.5 mm2 (16 AWG) channel HART Multiplexer Master type
Connection field side: fixed screw terminals HiDMux2700.
Multiplexers
control side: fixed screw terminals
RS 485 interface: removable screw terminals The Termination Board can be used for
HART
power: removable screw terminals general-purpose applications or in
Mass approx. 500 g conjunction with intrinsic safety barriers
Dimensions 222 x 122 x 208 mm (8.7 x 4.8 x 8.2 in), for hazardous applications.
height including module assembly
It offers fused redundant power supply
Mounting DIN rail mounting
connections. RS 485 terminals are
redundant and can be daisy chained.
Termination
Boards
Accessories
Diagrams
A+ +A
32 B B 32
C- -C
908837 (US) / 208599 (EU)
J2 C C J1
RS 485
RS 485
HiDMux2700
+ 24 V DC
-
+ 24 V DC
-
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HISHPSM/32/TB-02/HF32 HART Termination Board
• 32-channel Supply
Rated voltage 20 ... 30 V DC
• 24 V DC supply
Fusing 100 mA, 5 x 20 mm (0.2 x 0.8 in)
• For analog output cards Power loss 0.7 W, with Multiplexer
• HART output filters Reverse polarity protected yes
• Interface for serial or parallel wiring
H-System
wiring.
Boards
Diagrams
HISHPSM/32/TB-02/HF32
32x 32x
A+ +A
1 C R L C
mA C mA
B- -B 1
DSUB/1
+3
-2
11/2010
A+ +A
32 C R L C
C -B
DSUB/2
B- 32
+36
908837 (US) / 208599 (EU)
-35
RS 485
RS 485
HiDMux2700
+ 24 V DC
-
+ 24 V DC
-
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HART Interface Solutions Accessories
H-System
Features
• H-System accessory
• Connection cable between HART
Communication Board and
Technical data Termination Board
Ambient conditions
• 34-pin cable
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Function
Mechanical specifications
Connection 34-pin FLK connector (female) The HART connection cable is used for
Mass HiACA-UNI-FLK34-FLK34-0M5: approx. 150 g connection of a HART Communication
Multiplexers
HiACA-UNI-FLK34-FLK34-2M0: approx. 600 g Board to a H-System Termination Board.
HART
HiACA-UNI-FLK34-FLK34-3M0: approx. 900 g
HiACA-UNI-FLK34-FLK34-6M0: approx. 1800 g
Cable length HiACA-UNI-FLK34-FLK34-0M5: 0.5 m
HiACA-UNI-FLK34-FLK34-2M0: 2 m
HiACA-UNI-FLK34-FLK34-3M0: 3 m
HiACA-UNI-FLK34-FLK34-6M0: 6 m
Termination
Boards
Accessories
11/2010