Water: Verification of Calculation Method Using Monte Carlo Method For Water Supply Demands of Office Building
Water: Verification of Calculation Method Using Monte Carlo Method For Water Supply Demands of Office Building
Water: Verification of Calculation Method Using Monte Carlo Method For Water Supply Demands of Office Building
Article
Verification of Calculation Method Using Monte
Carlo Method for Water Supply Demands of
Office Building
Guang-Zheng Wu 1, *, Kyosuke Sakaue 2 and Saburo Murakawa 3
1 Department of Architecture and Environmental Design, College of Architecture and Environmental Design,
Kanto Gakuin University, 1-50-1, Mutsuura-Higasi, Kanazawa-ku, Yokohama 236-8501, Japan
2 Department of Architecture, School of Science and Technology, Meiji University, Second School Building
4-4301, 1-1-1, Higashimita, Tama-ku, Kanagawa, Kawasaki 214-8571, Japan; [email protected]
3 The Institute for Sustainable Science and Development, Hiroshima University, 1-3-2 Kagamiyama,
Higashi-Hiroshima City Hiroshima, Hiroshima 739-8511, Japan; [email protected]
* Correspondence: [email protected]; Tel.: +81-045-786-7820
Abstract: In Japan, there are four methods of calculating water supply demands for office buildings
based on SHASE-S 206 and two methods based on the design standard of Ministry of Land,
Infrastructure, Transport and Tourism (MLIT). However, these methods were found to produce
overestimated values when applied to recent sanitary fixtures with advanced water saving features.
To cope with this problem, Murakawa’s Simulation for Water Consumption (MSWC), which utilizes
the Monte Carlo method to calculate water usage dynamically has been developed. In this study,
we evaluated the validity of MSWC on water consumption of an office building. Actual water
consumption data were collected from a six story office building. Water consumption estimates
calculated by the six conventional methods and MSWC were compared with the actual measurement
values. Though the calculations based on the conventional methods significantly deviated from the
actual measurement values, those made by MSWC closely resembled them.
Keywords: water supply demand; calculating method; office building; Monte Carlo method
1. Introduction
In Japan, the design standard of Ministry of Land, Infrastructure, Transport and Tourism
(MLIT) [1] (referred to as “the Design Standard”) and The Society of Heating, Air-Conditioning
and Sanitary Engineers of Japan Standard 206 [2] (referred to as “SHASE-S 206”) have been used since
the 1970s as water load calculation methods. However, the traditional water load calculation methods
such as the Design Standard and SHASE-S 206, especially the worldwide used Hunter-based method,
was proved with a risk of overestimation if they are applied to modern sanitary fixtures with advanced
water-saving features, mentioned by Murakawa (1985) [3] and Wu (2013) [4].
On the other hand, Murakawa et al. (1976) mentioned a method to calculate the water supply
load based on Monte-Carlo simulation [5,6], and with the known probability of demand and demand
flow rate in every hour, daily demand time series can be obtained by Monte-Carlo simulations
mentioned by Holmberg (1987) [7], the Monte-Carlo simulations for the calculation of water supply
load was considered provide more accurate results. According to that, more research was taken on the
Monte-Carlo simulations for water supply loads. Murakawa et al. (2005) [8] developed the simulation
tool Murakawa’s Simulation for Water Consumption (MSWC), which is based on the Monte-Carlo
simulation, enabled to dynamically calculate various water usages in buildings by applying them to
probability models. Blokker et al. (2011) [9] developed Simulation of water Demand, an End-Use Model
(SIMDEUM) based on probability distribution functions for occupancy, frequency of use, duration
and flow per water-use event, occurrence over the day for end-uses such as flushing the toilet, doing
the laundry, washing hands, etc. to predict water demands at 1-s time step. Wong et al. (2017) [10]
integrated a Monte-Carlo simulated demand time series for optimized inflow rate of tanked water
supply system.
In this paper, we take up and evaluated the MSWC tool. The former researches discussed the
using case of MSWC on apartment houses by S. Murakawa (2002, 2003) [11,12] on restaurants by
D. Takahashi (2004) [13], and on hotels by H. Takata (2005) [14], the result shows that the MSWC
method was effective on these cases. In the case of office building, previous studies by G.Z. Wu (2014,
2015) [15,16], K. Sakamoto (2016) [17] and S. Kurisu (2016) [18] indicated that the conventional methods
were found to produce overestimated values, while highly accurate calculation of water supply load is
made possible by using MSWC. In this study, we measured water consumption and the number of
occupants in another office building (flush valve was installed as the discharge system), and compared
and analyzed daily water consumption (referred to as Qday below) and instant peak flow rate (referred
to as Qmax below) in order to further examine the validity of MSWC. Lastly, we correct the basic fixture
unit of conventional methods based on the measurement results, compared the calculation results with
the conventional methods using conventional basic fixture unit, and the results based on MSWC.
Possible Calculated
Calculation Method Abbr.
Water Supply Demand
Facilities design Calculation method based on personnel PM Qday
criteria of MLIT [1] Calculation method based on sanitary fixture FM Qmax
Calculation method based on Water use time
WFM
rate and Fixture unit for water supply
SHASE-S 206 [2] Method based on newer water supply Qmax
NWM
demand unit
prediction of fixture usage PFM
Method based on water supply load unit of
SLM
fixture
2.1.1. Facilities Design Criteria of Ministry of Land, Infrastructure, Transport and Tourism (MLIT)
The Facilities Design Criteria stipulates as a rule that water consumption shall be calculated based
on the personnel to use the subject building. On the other hand, the proviso of the criteria stipulates
that if calculation based on the personnel is not appropriate, the water consumption may be calculated
based on a number of water supply fixtures. Figure 1 shows the calculation flow by the personnel
Water 2017, 9, 376 3 of 21
method, and Figure 2 shows the calculation flow by the fixture-method. Tables 2 and 3 show each
parameter
Water 2017,of
9, the
376 personnel method and the fixture-method. 3 of 21
Water 2017, 9, 376 3 of 21
Calculation of average probable hourly demand of water supply by type of personnel: qh (L/h)
qh = qofd/twater supply by type of personnel: qh (L/h)
Calculation of average probable hourly demand
where qd: daily water consumption by personnel
qh = type
qd/t (L/d); t: Daily operating time
corresponding
where qd: dailyto personnel
water type. by personnel type (L/d); t: Daily operating time
consumption
corresponding to personnel type.
Table 2. Volume and time of water consumption per person based on intended use of building.
Table 3. Volume and time of water consumption per person based on intended use of building.
2.1.2. SHASE-S206
Table 4 shows characteristics of each calculation method of SHASE-S206.
1. Calculation Method Based on Water Use Time Rate and Fixture Unit for Water Supply
Based on the number of the installed fixtures, the Formula (1) and (2) by the type of the fixture are
used, or Table 4 is used to calculate Qmax . The standard value of water use time η and the fixture unit
for water supply are shown in Table 5.
In addition, in the case where different types of fixtures coexist, Qmax is calculated by adding the
highest value among Qmax values of each fixture to the half value of Qmax of other fixtures. However,
continuous flow is to be added without halving its Qmax value.
√
Ymax = cρη + b cρη + ∆, (1)
where Ymax : maximum number of fixtures used simultaneously with reject rate k (unit); c: number of
installed fixtures (unit); ρ: usage rate; η: Water use time rate; b, ∆: constant determined by k.
where Qmax : peak flow rate of water supply (simultaneously used water consumption) (L/min); Ymax :
maximum number of fixtures used simultaneously (unit); q: fixture unit for water supply.
Water 2017, 9, 376 5 of 21
Table 4. Cont.
Table 5. Fixture unit for water supply and standard value of water use time η.
Drain Cock
Connection Fixture Unit for
Fixture Water Supply System Unit for Water Use Time η
Diameter (A) Water Supply
Water Supply
Siphon-type flush valve/male 25 9 - 0.03 (10/300)
0.15 (15/100) with
Siphon-type with flush
25 9 - sound imitating device:
valve/female
0.1 (10/100)
Closet bowl Washing-type flush valve/male 25 6 - 0.03 (10/300)
0.15 (15/100) with
Washing-type flush valve/female 25 6 - sound imitating device:
0.1 (10/100)
Flushing water tank/male 13 1 - 0.15 (15/100)
Flushing water tank/female 13 1 - 0.5 (50/100)
Tank-less type/male/6 L 13 1.4 - 0.08 (22/300)
0.33 (33/100) with
Tank-less type/female/6 L 13 1.4 - sound imitating device:
0.22 (22/100)
Tank-less type/male/8 L 13 1.4 - 0.09 (27/300)
0.41 (41/100) with
Tank-less type/female/8 L 13 1.4 - sound imitating device:
0.27 (27/100)
Flush valve 13 2 - 0.3 (13/40)
Urinal
Flushing water tank 13 0.5 - 1.0 (continuous flow)
Lavatory faucet for water saving
13 1 0.5 0.5
washing
Basin Mixed use for water pouring
13 1 0.5 0.5
washing
Automatic faucet with continuous
13 0.2 - 0.5
flow valve
Automatic faucet without
13 0.5 - 0.5
continuous flow valve
Note: The flow rate for water saving washing consuming 14 L per hour in a basin with standard water pressure
100 kPa was used as the standard flow rate, and this standard flow rate was specified as one fixture unit for
water supply.
Considering that even if the fixtures are occupied simultaneously, there is still unoccupied time
for switch of users, the usage rate was specified as 0.9. Under the assumption that a slight decrease
in water pressure due to the simultaneous use is acceptable, the reject rate was specified as k = 0.05,
and b = 1.6 and ∆ = 0.8 were employed. Figures 3 and 4 and Table 7 shows relationship between the
rejection rate k, and b, and ∆.
Water 2017, 9, 376 8 of 21
Water 2017, 9, 376 8 of 21
Water 2017, 9, 376 8 of 21
simultaneously
of fixtures
Random use
Number of occupants
Number of occupants
Figure Adjustment
4. 4.
Figure ofof
Adjustment number ofof
number fixtures (random
fixtures use).
(random use).
Figure 4. Adjustment of number of fixtures (random use).
Table
Table Number
7. 7. ofof
Number fixtures and
fixtures usage
and rate.
usage rate.
Table 7. Number of fixtures and usage rate.
k 0.1 0.05 0.02 0.01 0.005 0.002 0.001 0.0001
k 0.1 k0.050.1 0.02 0.02 0.01
0.05 0.0050.002 0.002
0.01 0.005 0.001
0.001 0.0001 0.0001
b 1.28 1.64 2.05 2.33 2.58 2.88 3.09 4.26
b Δ 1.28 1.64 2.05 2.33 2.58 2.88 3.09 4.26
b 1.28 1.64 0.6 2.05
0.8 0.9 2.331.0 2.58 1.3 2.881.4
1.11 3.09
1.7 4.26
Δ 0.6 0.8 0.9 1.0 1.11 1.3 1.4 1.7
2. Method ∆ Based
0.6 on Newer
0.8 Water0.9 Supply1.0Demand 1.11
Unit [18]1.3 1.4 1.7
2. Method Based on Newer Water Supply Demand Unit [18]
The newer water supply demand unit of each fixture is chosen in Table 8 below, and the water
2. The newer
Method water
Based onsupply
Newer demand unit ofDemand
Water Supply each fixture
Unit is chosen in Table 8 below, and the water
[18]
load is calculated by using the sum of the newer water supply demand unit of each fixture and the
load is calculated by using the sum of the newer water supply demand unit of each fixture and the
load curve shown in supply
Figure 5.
load The
curvenewer
shownwater
in Figure 5. demand unit of each fixture is chosen in Table 8 below, and the water
load is calculated by using the sum of the newer water supply demand unit of each fixture and the
load curve shown in Figure 5.
Water 2017, 9, 376 9 of 21
Water 2017, 9, 376 9 of 21
Figure Calculation
5. 5.
Figure Calculation Qmax
ofof Qmaxofofthe
theMethod
MethodBased
Basedon
onNewer
NewerWater
WaterSupply
SupplyDemand
DemandUnit
Unit[2,21,22].
[2,21,22].
3.3. Method
MethodBased
Basedon
onFixture
FixtureUsage
Usage
Thewater
The waterload
loadis
is calculated
calculated bybychoosing
choosingthe thenumber
number of of
thethe
fixtures used
fixtures simultaneously
used simultaneouslyin Table
in
9 and the peak flow rate of water supply of each fixture in Table 10, then by multiplying
Table 9 and the peak flow rate of water supply of each fixture in Table 10, then by multiplying the the number
of the fixtures
number with the
of the fixtures withpeak
the flow
peak rate. If theIfnumber
flow rate. of the
the number of fixtures is not
the fixtures indicated
is not in Table
indicated 9, the
in Table 9,
the intermediate value is obtained by proportional distribution. However, if usage of the fixture is is
intermediate value is obtained by proportional distribution. However, if usage of the fixture
estimated
estimated with
with highhigh accuracy,
accuracy, the usage
the usage ratefixtures
rate of the of theused
fixtures used simultaneously
simultaneously should be
should be specifically
specifically estimated without referring
estimated without referring to this table. to this table.
Table
Table 9. 9. Number
Number ofof fixtures
fixtures andand usage
usage rate.
rate.
No. of Fixtures c 1 2 4 8 12 16 24 32 40 50 70
No. of Fixtures c 1 2 4 8 12 16 24 32 40 50 70
Closet Bowl (Flush Valve) 100 50 50 40 30 27 23 19 17 15 12
100 50
Closet Bowl (Flush Valve)
General Fixture 10050 10040 70 3055 27
48 4523 42 19
40 17
39 38 15 35 12
General Fixture 100 100 70 55 48 45 42 40 39 38 35
Water 2017, 9, 376 10 of 21
Table 10. Usage rate and Qmax of each plumbing fixture and faucet.
Quantity Peak Flow Rate
Fixture Consumption Per ofPeak
Water Supply
Flow Remarks
Quantity
Use (L) Rate(L/min)
of Water
Fixture Consumption Remarks
Closet bowl with flush valve 6–13 105
Supply
Closet bowl coupled with low tank Per Use (L)
6–10 10
(L/min) It is assumed that users wash the fixture
ClosetCloset
bowl with
bowllow
withtank onvalve
flush the flat wall 8–116–13 10510 once per use. In public toilets, males
Closet bowl with low tank on corner 8–11 10 wash the fixture about 1.5 times per use,
Closet bowl coupled with low tank 6–10 10
Closet bowl integrated with low tank It is
andassumed that users
fames wash wash
it about 2.0the
times per
Closet bowl with low tank on the flat wall 168–11 1010
(single unit type) use. once per use.
fixture
ClosetCloset bowl with
bowl without tanklow tank on corner 6–88–11 10
20 In public toilets, males wash the
ClosetCloset bowl integrated
bowl without tank (smallwith low tank
tank fixture about 1.5 times per use, and
5–5.516 10
10–13
included)
(single unit type)
fames wash it about 2.0 times per
UrinalCloset bowlvalve
with flush without tank 4–66–8 2030 The required flow rate for a plunge bath
use.
UrinalCloset bowl without
with automatic tank (small
Flushing tank
water tank 4–65–5.5 8–13
10–13 is calculated based on the time spent to
Basin included) 10 10 fill the bath tab with water.
Urinal with flush valve 4–6 30 The required flow rate for a plunge
Urinal with automatic Flushing water tank 4–6 8–13 bath is calculated based on the time
4. Method
Basin Based on Water Supply Load Unit 10 of Fixture [19]
10 spent to fill the bath tab with water.
Water Supply
Water Load
Supply UnitUnit
Load of Fixture
of Fixture
Fixture
Fixture Faucet
Faucet Public Use Private Use
Public Use Private Use
Closet bowls Flush valve 10 6
Closet bowls
Closet bowls Flush
Flushing valve
water tank 5 10 3 6
ClosetUrinal
bowls Flushing water tank
Flush valve 5 5 - 3
Urinal
Urinal Flush
Flushing valve
water tank 3 5 - -
Urinal
Basin Flushing water tank
Faucet 2 3 1 -
Basin Faucet 2 1
Peak flow rate of water supply (L/min)
Water supply load unit of fixture Water supply load unit of fixture
(a) (b)
FigureFigure 6. Calculation
6. Calculation of Qofmax
Qmax
ofofthe
theMethod
MethodBased
Based on
on Water
WaterSupply
SupplyLoad Unit
Load of of
Unit Fixture [2,23].
Fixture (a) Peak
[2,23]. (a) Peak
flow rate
flow rate of water
of water supply[L/min];
supply [L/min]; (b)(b)
Peak flowflow
Peak rate of water
rate of supply
water [L/min]
supply(Partial
[L/min]expansion
(Partialof (a)).
expansion
of (a)).
2.2. Water Load Calculation Method Using Murakawa’s Simulation for Water Consumption (MSWC)
2.2. Water
2.2.1. Load Calculation
Outline of MSWCMethod Using Murakawa’s Simulation for Water Consumption (MSWC)
MSWC
2.2.1. Outline is a simulation tool that makes it possible to forecast water supply demand in
of MSWC
chronological order by using the Monte Carlo technique. As shown in Figure 7, this method is used
MSWC is a simulation
for plumbing toolthe
fixtures, but that makes itratio
frequency possible
of thetomean
forecast
valueswater supply
of the demand
simulation in chronological
conditions such
orderasbyuse
using the Monte Carlo technique. As shown in Figure 7, this method is used
frequency [24], discharge flow rate [25], discharge time of the fixture [26,27], temperature for plumbing
of
fixtures,
waterbut
to the frequency
be used ratio
[8,28–30], andofusers’
the mean values
occupation timeof ofthe
thesimulation conditions
fixture [1,31] suchinas
is cumulated a use
frequency [24], discharge flow rate [25], discharge time of the fixture [26,27], temperature of water
to be used [8,28–30], and users’ occupation time of the fixture [1,31] is cumulated in a probability
Water 2017, 9, 376 11 of 21
Erlang distribution K = 10
Erlang distribution
Exponential K = 10
distribution
Probability
Hyperexponential distribution
Exponential distribution
Probability
Hyperexponential distribution
building, the number of users in the whole building is to be entered, and when calculating the water
load 2.2.2.
of oneCalculation
floor of theConditions
subject building,
of MSWC the number of users on the floor is to be entered. Figure 9
shows the operation screen of MSWC.
Table 12 shows the simulation conditions of MSWC [4,32]. The subject number means a number
respectively of male or female Table
users.12.
When calculating
Simulation the water load of all the floors of the subject
conditions.
building, the number of users in the whole building is to be entered, and when calculating the water
Male Female
load of one floor of the subject building, the number of users on the floor is to be entered. Figure 9
Simulation Model Closet Lavatory
shows the operation screen of MSWC. Urinal Basin Basin
Bowl Pan
Arrival rate by time
Arrival-to-fixture To be set by fixture and time zone
Table 12. Simulation conditions.
(person/min)
model
Arrival rate distribution Poisson distribution
Fixture occupation Male Female
Simulation
No. Model
of fixtures to be set (unit) To be set based on the subject building
time model Lavatory
Average occupation timeCloset (s) Bowl 260 Urinal 37 Basin
12 110
Pan
Basin
17
Type of occupation
Arrival rate by time time
Discharge quantity
Arrival-to-fixture Erl.3 To beErl.7 Hyp.2
set by fixture Erl.3
and time zone Hyp2
distribution
(person/min)
model
modelFixture Arrival rate distribution Poisson distribution
occupation time Average discharge time (s) 17.2 5 6 17.2 11
No. of fixtures to be set (unit) To be set based on the subject building
model Type of discharge
Average occupation time (s) time 260 37 12 110 17
Exp. Exp.10 Erl.3 Exp. Erl.3
distribution
Type of occupation time
Discharge Erl.3 Erl.7 Hyp.2 Erl.3 Hyp2
distribution
Average discharge quantity
quantity model 49.8 30 5 49.8 5
Average discharge time (s) 17.2 5 6 17.2 11
Fixture operation (L/min)
Type of discharge time
model Type of discharge quantity Exp. Exp.10 Erl.3 Exp. Erl.3
Fixture
distribution Erl.6 Erl.10 Erl.10 Erl.6 Erl.10
distribution
Average discharge quantity
operation model 49.8 30 5 49.8 5
Average (L/min)
number of times for
Type of discharge quantity 1.37 1 1 1.17 1
washing (time)
distribution
Erl.6 Erl.10 Erl.10 Erl.6 Erl.10
Subject number
Water 2017, x, x(No.Average
of users, tenants
number andfor
of times rooms) To be entered based on the subject building 7 of 22
1.37 1 1 1.17 1
washing (time)
Subject number (No. of users, tenants and rooms) To be entered based on the subject building
Note: As there is no English version of MSWC at present, the right figure was translated depends on the left one.
Figure 9.The
Theoperation
operationscreen
screenof
of Murakawa’s
Murakawa’s Simulation
Simulation for
forWater
Water Consumption
Consumption(MSWC).
(MSWC).
FigureFigure
9. The9.operation screen of Murakawa’s Simulation for Water Consumption (MSWC).
The indication
The indication of each of each numbered
numbered zonezone on Figure
on Figure 10 is10
as is as follows.
follows.
In theIn facility
the facility selection
selection section
section in in area“①”,
area “
”,
1 thethe subject
subject building
buildingisisselected.
selected.InInthis research,
this “Office”
research,
waswas
“Office” selected for research
selected of an
for research ofoffice building
an office (the(the
building subject building
subject cancan
building also be be
also selected from
selected thethe
from file list
file list on the bottom of the screen by selecting the file and clicking “Read selected file”
on the bottom of the screen by selecting the file and clicking “Read selected file” in area “ ”). in area “⑪”).
Next, the condition file to be edited is selected to rewrite and store the file.
The overall conditions are described as follows.
distribution
Average number of times for
1.37 1 1 1.17 1
washing (time)
o. of users, tenants and rooms) To be entered based on the subject building
Water 2017,
2017,9,9,
Water2017, 376
9,376
376 13 of 21
Water 1313
ofof
2121
Next, the condition file to be edited is selected to rewrite and store the file.
Next, the condition file to be edited is selected to rewrite and store the file.
The
In the overall
“Analysis conditions are described
unit” section in area “as
”,
2 follows.
it is recommended to choose the 0.1-s analysis, because
The overall conditions are described as follows.
the 1-sIn analysis
the “Analysis may cause unit”errorsection
(taking in area
too long“②”, timeit isforrecommended
the analysis). to choose the 0.1-s analysis,
In the “Analysis unit” section in area “②”, it is recommended to choose the 0.1-s analysis,
because the 1-s
In area “
”,3 analysis may cause
the result name error can be (taking
giventoo longfile
to the time of for
thethe analysis).result. If the number
calculation
because the 1-s analysis may cause error (taking too long time for the analysis).
In areathe
exceeding “③”,number the result
of thename fixtures canchosen
be given to the
in the areafile
“
” 6of the
on thecalculation result. If error
right is entered, the number
will be
In area “③”, the result name can be given to the file of the calculation result. If the number
exceeding
caused during the number of the fixtures
the calculation. Hence, the chosen in the
“Fixture areasection
type” “⑥” on the right
should not be is changed.
entered, error will be
The “Subject
exceeding the number of the fixtures chosen in the area “⑥” on the right is entered, error will be
caused
number” during
should thebe calculation.
consistentHence, with the thepresent
“Fixture type” section
condition and be should
set bynot be changed.
considering theThe “Subject
situation of
caused during the calculation. Hence, the “Fixture type” section should not be changed. The “Subject
number”
the office.should be consistent with the present condition and be set by considering the situation of
number” should be consistent with the present condition and be set by considering the situation of
the office.
The same operation with the “Set number of fixtures” in area “
” 4 can also be performed in the
the office.
The name”
“Fixture same operation
section inwith areathe 6 “Set
“
” numberthe
to change of fixtures”
number of inthe
area “④” can
subject also be
fixtures, asperformed
well as thein the
“Edit
The same operation with the “Set number of fixtures” in area “④” can also be performed in the
“Fixture
setup number” name” section in area “⑥” “
”.
9 to
Inchange
the “Setthe number
subject of the subject
number” sectionfixtures,
in area “as 4 well
”, theasnumber
the “Edit of
“Fixture name” section in area “⑥” to change the number of the subject fixtures, as well as the “Edit
setup
users andnumber”usagesection of eachinfixture
area “⑨”. in 24Inh the can“Set subject number”
be changed. In the “Set section
water intemperature”
area “④”, thesection,numberthe of
setup number” section in area “⑨”. In the “Set subject number” section in area “④”, the number of
users and usage
temperature of each fixture
of supplied water asinwell 24 hascan thebe changed.
water In the “Set
temperature at eachwater temperature”
fixture can be changed.section, the
users and usage of each fixture in 24 h can be changed. In the “Set water temperature” section, the
temperature
In the “Start of supplied watersection
calculation” as wellinasarea the “water
”, thetemperature
water loadat each fixture can be changed.
atcalculation
each fixturesimulation based on any
5
temperature of supplied water as well as the water temperature can be changed.
In the “Start
calculation condition calculation” section inby
can be performed area “⑤”, the water load
choosing calculation simulation based on
In the “Start calculation” section in area “⑤”, the“Rewrite”,
water load“Store new file”
calculation and the based
simulation file foronthe
any calculation
calculation before condition
clicking canthe be performed
“Start”. By by choosing
clicking “Finish” “Rewrite”,
in area “Store
“
”,
5 newentry
data file” can
andbe thefinished
file for
any calculation condition can be performed by choosing “Rewrite”, “Store new file” and the file for
the calculation
without performing beforethe clicking
waterthe the
load “Start”. By clicking
calculation simulation.“Finish” in area “⑤”, data entry can be finished
the calculation before clicking “Start”. By clicking “Finish” in area “⑤”, data entry can be finished
operation screen of withoutIn
Murakawa’s performing
the “Remark”
Simulation the water
section inload
area calculation
“
”,
7 DEMO simulation.
on the data can be entered.
without performing the for
waterWater loadConsumption
calculation(MSWC). simulation.
In the “Remark”
“Set value” section
section ininarea
area “⑦”,
“ 8 DEMO
”, 11 on the data
calculation can be entered.
conditions for each fixture can be shown.
In the “Remark” section in area “⑦”, DEMO on the data can be entered.
In the
the “Set
“Edit value” section
setassection
value” in area “⑧”,
section in area 11 “calculation
”, conditionsconditions
11 calculation for each fixturefor eachcan be shown.
f each numbered zone Inon Figure 10 is follows. can befixture
shown.can
9
the “Set value” in area “⑧”, 11 calculation conditions for each fixture
be
election section in area In the
changed.
“①”, “Edit
theset set value”
subject section in area “⑨”, 11 calculation conditions for each fixture can be changed.
In the “Edit value”building
section inisarea selected.
“⑨”, 11 Incalculation
this research, conditions for each fixture can be changed.
for research of an office In the “Progress bar” in area “⑩”, progress of the calculation can be viewed.
InIn the“Progress
building
the “Progress
(the subjectbar”in
bar” inarea
area“⑩”,
building “can”,progress
progress
also ofofthe
be selected thefrom
calculation
the can
calculation canbe beviewed.
viewed.
of the screen by selecting Bytheusing
file the “Read
and clicking chosen
“Read file”
selected section
file” inin area
area “⑪”,
“⑪”). the name of the set value can be shown in
ByByusing
usingthe the“Read
“Readchosenchosenfile” file”section
sectionininarea area“⑪”,“ ”,the thenamenameofofthe thesetsetvalue
valuecan canbebeshown
showninin
the “Set value name” section by choosing and clicking a file in the file list. By using the “Store chosen
the
the“Set
“Setvalue
valuename” name”sectionsectionby bychoosing
choosingand andclicking
clickinga afile fileininthethefile
filelist.
list.ByByusing
usingthe the“Store
“Storechosen
chosen
file” section, the chosen file can be stored. In the “Store new file” section, a new file can be stored in
file”
file”section,
section,the thechosen
chosenfile filecan
canbebestored.
stored.InInthe the“Store
“Storenew newfile” file”section,
section,a anew newfilefilecan
canbebestored
storedinin
the name used in the “Set value name” section, and the file name can also be changed in this section.
the
thename
nameused usedininthe the“Set
“Setvalue
valuename”name”section, section,and andthe thefile
filename
namecan canalso alsobebechanged
changedininthis thissection.
section.
In the “File list” section in area “⑫”, the calculation can be performed by checking the box on
InInthe
the“File“Filelist”list”section
section in in area
area “⑫”,
“ ”, the the calculation
calculationcan canbe beperformed
performedbybychecking checking the
the box
box ononthe
the left of each file listed as the files that can be used for the calculation.
the left of each file listed as the files that can be
left of each file listed as the files that can be used for the calculation. used for the calculation.
The water load calculation simulation is conducted for 24 h for each fixture type and is
The
Thewater
water load load calculation
calculationsimulation
simulation is conducted
is conducted for 24 forh for
24 each
h forfixtureeach type
fixtureandtype and is
is aggregated
aggregated every second to produce basic files for water, hot water and heat quantity. The simulation
aggregated
every second every second to
to produce produce
basic files for basic fileshot
water, forwater
water,and hotheat
water and heat
quantity. Thequantity.
simulation Theissimulation
completed,
is completed, when some of such basic files are displayed.
iswhen
completed, when some of such
some of such basic files are displayed. basic files are displayed.
Note: As there is no English version of MSWC at present, the right figure was translated depends on the left one.
Figure10.
Figure 10.The
The operation
operation screen
screen of
of MSWC.
MSWC.
3. Measurement
M WC 6F
W WC
Hot water supply room office
M WC 5F
D W WC
Hot water supply room office
Ultrasonic flow meter C M WC 4F
W WC
Hot water supply room office
M WC 3F
B W WC
Hot water supply room office
M WC 2F
W WC
Hot water supply room Law office
M WC 1F
W WC Medical office
GL Hot water supply room
A WC
B1F
Parking place
Water meter
Ultrasonic flow meters were placed in the water supply main near the outlet of the pump (A); in
Qday and Qmax on each floor obtained from calculation based on the measured data by ultrasonic
the water supply main between the floors 3 and 4 (B); 4 and 5 (C); and 5 and 6 (D) from Wednesday,
flow meters during the measuring period: 5–6 August, and 12 November 2015 are shown in Table 13.
5 August to Thursday, 6 August, and on Thursday, 12 November 2015, and water flow rate was
In Chapter 5, data obtained on 6 August, when Qday calculated from the ultrasonic flow meter data
measured
were the every
largestsecond.
were used.
Qd ay and Qmax on each floor obtained from calculation based on the measured data by ultrasonic
flow meters during the measuring Table
period:
13.5–6
QdayAugust,
and Qmaxand 12 November
on each floor. 2015 are shown in Table 13.
In Chapter 5, data obtained on 6 August, when Qday calculated from the ultrasonic flow meter data
were the largestPeriod Classification Whole Building 6F
were used. 5F 4F B1F~3F
8/5 Qday (L/day) 9361 1434 2357 2017 3552
(Wed.) Qmax (L/min) 86.7 28.6 66.2 85.3 69.5
Table 13. Qday and Qmax on each floor.
8/6 Qday (L/day) 9701 1558 2649 1827 3667
Period
(Thu.) Classification
Qmax (L/min) Whole Building
79.0 6F
45.4 5F 73.3 52.94F 70.7B1F~3F
11/12 Qday (L/day) 9493 1574 2438 2182 3298
Q (L/day) 9361 1434 2357 2017 3552
(Thu.) Q dayQ(L/min)
8/5 (Wed.) max (L/min)
86.7
67.1 28.6
38.1 66.2
58.4 53.785.3 67.1 69.5
max
Qday (L/day) 9518 1522 2481 2009 3506
Ave. Qday (L/day) 9701 1558 2649 1827 3667
8/6 (Thu.) Qmax (L/min) 77.6 37.4 66.0 64.0 69.1
Qmax (L/min) 79.0 45.4 73.3 52.9 70.7
Qday (L/day) 9493 1574 2438 2182 3298
3.2. The11/12 (Thu.)
Number of Occupants
Qmax (L/min) 67.1 38.1 58.4 53.7 67.1
To determine Qdaynumber
the (L/day) of occupants
9518 1522in the 2481
present rooms in2009 3506 during the
T-building
Ave.
measurement period,Qthe
max (L/min) 77.6
occupants of T-building 37.4
were 66.0
asked to fill out 64.0 69.1
questionnaires and their
Water 2017, 9, 376 15 of 21
The number of occupants in the rooms by gender was counted every 30 min during the
presence in the rooms every 30 min on the days’ measurements were made were investigated. To
measurement period: Wednesday, 5 August to Friday, 7 August; Wednesday, 11 November to Friday,
further validate the accuracy of the questionnaires, security cameras were used [15,16].
13 November 2015.
The number of occupants in the rooms by gender was counted every 30 min during the
People entering and exiting T-building were monitored by security cameras placed at the front
measurement period: Wednesday, 5 August to Friday, 7 August; Wednesday, 11 November to
and back entrances during the measurement period: Wednesday, 11 November to Friday, 13 November
Friday, 13 November 2015.
2015; andPeople
the number of people was counted by gender every 5 min.
entering and exiting T-building were monitored by security cameras placed at the front
The back
and number of occupants
entrances during registered for T-building
the measurement period: isWednesday,
shown in Table 14. The movements
11 November to Friday, 13of
people obtained by questionnaire on Thursday, 12 November and an example
November 2015; and the number of people was counted by gender every 5 min. of the fluctuation of
occupants captured by a security camera on Thursday, 12 November in Figure 12.
The number of occupants registered for T-building is shown in Table 14. The movements of
people obtained by questionnaire on Thursday, 12 November and an example of the fluctuation of
occupants capturedTable 14. The number
by a security cameraof
onoccupants
Thursday,registered for T-building.
12 November in Figure 12.
200
Questionnaire
150
100
50
0
0:00 3:00 6:00 9:00 12:00 15:00 18:00 21:00 0:00
Time
Fluctuation of occupants
200
Security cameras
150
100
50
0
0:00 3:00 6:00 9:00 12:00 15:00 18:00 21:00 0:00
Time
MLIT SHASE-S206
Water Consumption
PM FM
WFM NWM PFM SLM
P/A NOR CBU ABU
Whole Qday (L/day) 38,080 16,800 21,120 16,554 - - - -
building Qmax (L/min) 238 105 220 172 474 390 1094 370
Qday (L/day) 18,880 6960 11,040 8650 - - - -
B1F~3F
Qmax (L/min) 118 43.6 103 90.0 280 290 702 380
Qday (L/day) 6480 3331 3360 2635 - - - -
4F
Qmax (L/min) 41 20.8 35 27.4 175 210 355 257
Qday (L/day) 6480 5330 3360 2635 - - - -
5F
Qmax (L/min) 41 33.3 35 27.4 175 210 355 257
Qday (L/day) 6240 1396 3360 2635 - - - -
6F
Qmax (L/min) 39 8.7 35 27.4 175 210 355 267
Water 2017, 9, 376 17 of 21
to as QAday , the ratio of Qday to QAday as Rd, actual measurements of Qmax as QAmax , and the ratio
of Qmax to QAmax as Rm below). In comparison of Qday , the total figure of each floor and the figures
Water 2017, 9, 376 18 of 21
for allWater
floors were
2017, 9, 376used in MSWC. MSWC calculations for the number of occupants were the 18 ofclosest
21
Water 2017, 9, 376 18 of 21
to actual measurements. Compared to the conventional design standards,
actual measurements in Qday and Qmax for all floors. However, they were smaller than actual the personnel method
actual measurements in Qday and Qmax for all floors. However, they were smaller than actual
basedactual
on themeasurements
number
measurements in of occupants
Qmax for
in each
Q
and the
day floor,
and Q
fixturethat
indicating
max for all
method based on actual
the personnel
floors. However,method
basic
and
they were
unit produced
fixture
smallermethod
figures
in the
than actual
measurements in Qmax for each floor, indicating that the personnel method and fixture method in the
closerconventional
to actual measurements
measurements design in Qfloor,
in Qmaxstandards
for each day not Q
areand max for
reliable allthe
when floors. However,
making they
calculations were
andbased smaller
on onlythan
a few actual
conventional design standards are indicating
not reliable that
when personnel method
making calculations fixture
based method
on only ain few
the
measurements
sanitary in Q
fixtures
conventional
sanitary fixtures
for each
installed.
design
max floor, indicating that the personnel method and fixture
standards are not reliable when making calculations based on only a few
installed.
method in the
conventional
sanitary design
fixtures standards
installed. are not reliable when making calculations based on only a few sanitary
fixtures installed.
40,000
40,000
35,000
40,000
35,000
30,000
35,000
30,000
(L/day)
day(L/day)
25,000
30,000
25,000
(L/day)
20,000
25,000
20,000
15,000
20,000
day
15,000
QQ
Qday
10,000
15,000
10,000
5,000
10,000
5,000
0
5,000
0
0 QAday FM FM PM PM MSWC MSWC
QAday FM FM PM PM MSWC MSWC
QAday (P/A)
FM (NOR)
FM (CBU)
PM (ABU)
PM (P/A)
MSWC (NOR)
MSWC
(P/A) (NOR) (CBU) (ABU) (P/A) (NOR)
(P/A) BF~3F
(NOR) 4F (CBU)
5F 6F (ABU) (P/A) (NOR)
BF~3F 4F 5F 6F
BF~3F 4F 5F 6F
Figure 13. Comparison of Qday obtained by each method.
Figure 13. Comparison of Qday obtained by each method.
Figure 13. Comparison of Qday obtained by each method.
Figure 13. Comparison of Qday obtained by each method.
6.0
6.0
6.0
5.0
5.0
5.0
4.0
4.0
4.0
Rd
3.0
RdRd
3.0
3.0
2.0
2.0
2.0
1.0
1.0
1.0
0.0
0.0
FM FM PM PM MSWC MSWC
0.0 FM FM PM PM MSWC MSWC
(P/A) (NOR) (CBU) (ABU) (P/A) (NOR)
(P/A)
FM (NOR)
FM (CBU)
PM (ABU)
PM (P/A)
MSWC (NOR)
MSWC
BF~3F 4F 5F 6F Whole building
(P/A) (NOR)
BF~3F 4F(CBU)
5F 6F (ABU)
Whole building (P/A) (NOR)
BF~3F 4F 5F 6F Whole building
Figure
Figure 14.14. Ratio
Ratio of to actual
ofQQday to actual measurements.
measurements.
Figure 14. Ratio of Q day to actual measurements.
day
Figure 14. Ratio of Qday to actual measurements.
1,200
1,200
1,200
1,000
1,000
(L/min)
(L/min)
1,000
800
(L/min)
800
800
600
Qmax
600
Qmax
600
Qmax
400
400
400
200
200
200
0
0
QAmax PM PM FM FM WFM NWM PFM SLM MSWC MSWC
0 QAmax PM PM FM FM WFM NWM PFM SLM MSWC MSWC
(P/A) (NOR) (CBU) (ABU) (P/A) (NOR)
QAmax (P/A)
PM (NOR)
PM (CBU)
FM (ABU)
FM WFM NWM PFM SLM (P/A)
MSWC (NOR)
MSWC
(P/A) Whole(CBU)
(NOR) building (ABU)BF~3F 4F 5F 6F (P/A) (NOR)
Whole building BF~3F 4F 5F 6F
Whole building BF~3F 4F 5F 6F
Figure Comparison
15. 15.
Figure Comparison ofofQQmax obtained by each method.
max obtained by each method.
Figure 15. Comparison of Qmax obtained by each method.
Figure 15. Comparison of Qmax obtained by each method.
Water 2017, 9, 376 19 of 21
Water 2017, 9, 376 19 of 21
14.0
12.0
10.0
8.0
Rm
6.0
4.0
2.0
0.0
PM PM FM FM WFM NWM PFM SLM MSWC MSWC
(P/A) (NOR) (CBU) (ABU) (P/A) (NOR)
Whole building BF~3F 4F 5F 6F
Figure Ratio
16.16.
Figure ofofQQ
Ratio max to
max actualmeasurements.
to actual measurements.
6. Conclusions
6. Conclusions
In this study, the accuracy of water load calculation based on the conventional method and
In this study, the accuracy of water load calculation based on the conventional method and MSWC
MSWC simulation were compared and validated.
simulation were compared and validated.
The conventional water load calculation methods were found to overestimate water load except
The
Qmaxconventional
for each floor water
in the load calculation
personnel methodmethods were
and fixture foundQto
method. overestimate water load except
max for all floors and Qday in the
Qmax for each floor in the personnel method and fixture
personnel and fixture methods using actual basic unit produced method. Q max for all floors
figures closerandto Qactual
day in the
personnel and fixture
measurements methods
than using actual
the conventional basicdid.
methods unit produced figures closer to actual measurements
than the conventional
MSWC calculationsmethods did.
with the number of occupants were the closest to actual measurements. It
was confirmed
MSWC that obtaining
calculations with the accurate
number number of people was
of occupants wereimportant as the
the closest tosimulation based on
actual measurements.
personnel/area produced larger than actual measurements than the simulation
It was confirmed that obtaining accurate number of people was important as the simulation based on the number
based on
of occupants. The comparison between the conventional methods with and
personnel/area produced larger than actual measurements than the simulation based on the number without the correction
of the basic fixture unit based on the measurement results proved that the conventional basic fixture
of occupants. The comparison between the conventional methods with and without the correction of
unit should be modified [23].
the basic fixture unit based on the measurement results proved that the conventional basic fixture unit
To further refine and validate the accuracy of MSWC, our next step will be to compare the results
shouldofbe modified
each water load[23].
calculation method with actual measurements based on detailed measurement of
To further
water refine and
consumption validate
and countingtheofaccuracy
the number of of
MSWC,
peopleour next stepfor
in buildings will be to compare
multiple uses. the results
of each water load calculation method with actual measurements based on detailed measurement of
Author Contributions: Kyosuke Sakaue conceived and planned the research/measurement; Saburo Murakawa
watercontributed
consumption andtheory
the basic counting of the number
and provided of people
the simulation in buildings
tool; Guang-Zheng Wufor multipletheuses.
performed investigation,
analyzed the data and wrote the paper.
Author Contributions: Kyosuke Sakaue conceived and planned the research/measurement; Saburo Murakawa
Conflicts
contributed theofbasic
Interest: the and
theory authors declare the
provided no conflict of interest.
simulation tool; Guang-Zheng Wu performed the investigation,
analyzed the data and wrote the paper.
References
Conflicts of Interest: The authors declare no conflict of interest.
1. Ministry of Land, Infrastructure, Transport and Tourism. Facilities Design Criteria; MLIT: Tokyo, Japan,
References pp. 447–454.
2006;
2. The Society of Heating, Air-Conditioning and Sanitary Engineers of Japan; SHASE-S206-2009; SHASE: Tokyo,
1. Ministry 2009. Infrastructure, Transport and Tourism. Facilities Design Criteria; MLIT: Tokyo, Japan, 2006;
of Land,
Japan,
pp.
3. 447–454.
Murakawa, S. Study on the method for calculating water consumption and water uses in multi-story flats.
2. In Proceedings
The Society of the
of Heating, 13th International
Air-Conditioning Symposium
and of CIB W062,
Sanitary Engineers Tokyo,SHASE-S206-2009;
of Japan; Japan, 9–10 April 1985; pp. 1–19.
SHASE: Tokyo,
4.
Japan,Wu,
2009.G.Z.; Sakaue, K.; Kojima, K.; Fujimura, K.; Murakawa, S.; Hayakawa, K. Examinations on Water
3. SupplyS.
Murakawa, Load Calculation
Study Methodsfor
on the method of Office Building:
calculating Comparison
water between
consumption andConventional
water usesDesign Methods flats.
in multi-story
and the Simulation Methods. In Proceedings of the 39th International Symposium of CIB W062, Nagano,
In Proceedings of the 13th International Symposium of CIB W062, Tokyo, Japan, 9–10 April 1985; pp. 1–19.
Japan, 17–19 September 2013; pp. 529–540.
4. Wu, G.Z.; Sakaue, K.; Kojima, K.; Fujimura, K.; Murakawa, S.; Hayakawa, K. Examinations on Water Supply
5. Murakawa, S. Investigation of the Method of calculation of Water Consumption in the Designing of
Load Calculation Methods of Office Building: Comparison between Conventional Design Methods and the
Building Equipments: Part 1 The Theory of Calculation and Analyses of the Use of Water in Multi-storey
Simulation Methods.
Flats. Transact. In Proceedings
Archit. Inst. Jpn. 1976,of the71–80.
246, 39th (In
International
Japanese) Symposium of CIB W062, Nagano, Japan,
17–19 September 2013; pp. 529–540.
5. Murakawa, S. Investigation of the Method of calculation of Water Consumption in the Designing of Building
Equipments: Part 1 The Theory of Calculation and Analyses of the Use of Water in Multi-storey Flats.
Transact. Archit. Inst. Jpn. 1976, 246, 71–80. (In Japanese).
Water 2017, 9, 376 20 of 21
6. Murakawa, S. Investigation of the Method of calculation of Water Consumption in the Designing of Building
Equipments: Part 4 Calculation of Water Load and Analysis of Simultaneous Uses. Transact. Archit. Inst. Jpn.
1976, 253, 103–112. (In Japanese).
7. Holmberg, S. Computer dimensioning of water supply systems with use of continuous field measurements
as input data. In Proceedings of the 15th International Symposium of CIB W062, Sao Paulo, Brazil,
14–18 September 1987.
8. Yamane, Y.; Murakawa, S.; Takata, H.; Sakamoto, K. Analysis on The Water Usage in Office Buildings:
A study on the calculating method for cold and hot water supply demands based on the analysis of water
usage in the time series (Part 2). J. Environ. Eng. Trans. AIJ 2005, 70, 65–72. (In Japanese). [CrossRef]
9. Blokker, E.J.M.; Pieter-Quirijns, E.J.; Vreeburg, J.H.G.; van Dijk, J.C. Simulating nonresidential water demand
with a stochastic end-use model. J. Water Res. Plan. Manag. 2011, 137, 511–520. [CrossRef]
10. Wong, L.T.; Mui, K.W.; Zhou, Y. Energy Efficiency Evaluation for the Water Supply Systems in Tall Buildings.
Available online: http://journals.sagepub.com/doi/abs/10.1177/0143624417699857?journalCode=bsea&
(accessed on 23 May 2017).
11. Murakawa, S.; Takata, H. Development of the calculating method for cold and hot water consumption based
on the fixture usage in the time series through a day: A case study of apartment houses. In Proceedings
of the International Symposium of CIB/W62 on Water Supply and Drainage for Buildings, Iasi, Romania,
18–19 September 2002; pp. 1–13.
12. Murakawa, S.; Hiroshi, T. Development of the calculating method for the loads of clod and hot water
consumption in the apartment houses. In Proceedings of the International Symposium of CIB/W62 on Water
Supply and Drainage for Buildings, Ankara, Turkey, 11–12 September 2003; pp. 281–295.
13. Takahashi, D.; Murakawa, S.; Nishina, D.; Takada, H. Development of the calculating method of cold and hot
water consumption based on the fixture usage in the time series through a day (Part 4) Analysis on the loads
of water supply demands in the restaurants of a complex commercial building. In Summaries of Technical
Papers of Annual Meeting; Architectural Institute of Japan: Tokyo, Japan, 2004; Volume D-1.
14. Takata, H.; Murakawa, S.; Nishina, D.; Tanaka, A. An Analysis on the Loads of Hot Water Consumption of
Guest Rooms in a Hotel. In Proceedings of the International Symposium of CIB/W62 on Water Supply and
Drainage for Buildings, Brussels, Belgium, 14–16 September 2005; pp. 1–9.
15. Wu, G.Z.; Sakaue, K.; Hayakawa, K.; Murakawa, S. Comparison between the traditional methods and the
simulation method in water supply load calculation methods for office building. In Proceedings of the 40th
International Symposium of CIB W062, Sao Paulo, Brazil, 8–10 September 2014; pp. 35–44.
16. Wu, G.Z.; Sakaue, K.; Hayakawa, K.; Murakawa, S.; Inada, Y. Verification of calculating method using
the Monte Carlo method for water supply demands: The water consumption of mixed-use building for
rent. In Proceedings of the 41th International Symposium of CIB W062, Beijing, China, 17–20 August 2015;
pp. 306–318.
17. Sakamoto, K.; Murakawa, S.; Takada, H.; Toyosada, K.; Yoshikawa, H. Development of the calculating
method for the loads of water consumption in office buildings: Dynamic estimation for the loads of water
demands for design of water supply system. Archit. Inst. Jpn. 2016, 39, 475–478. (In Japanese).
18. Kurisu, S.; Sakaue, K.; Murakawa, S.; Wu, G.Z.; Fujimura, K. Verification of calculation method using Monte
Carlo method for water supply demands: The water consumption of an office building. In Proceedings of
the 42th International Symposium of CIB W062, Kosice, Slovakia, 29 August–1 September 2016; pp. 306–318.
19. Okada, K. Some Problems on the Probability of Simultaneous Usage of Building Equipments (Scientefic
Basis of Planning Building). Archit. Inst. Jpn. 1957, 57, 65–68. (In Japanese).
20. Kanasaki, T.; Murakawa, S. Fundamental Study on the Appropriate Number of scale of Plumbing Fixture:
Part 5 The Number of Appropriate Fixtures at Office Building. Archit. Inst. Jpn. 1983, 151. (In Japanese).
21. Murakawa, S.; Yamate, T. Investigation of Calculating Method for Flow Rates Design and Water Uses in
Multi-storey Flats. Soc. Heat. Air-Cond. Sanit. Eng. Jpn. 1982, 20, 11–27.
22. Murakawa, S. New Design Method of plumbing and drainage systems of Revenue House. Jpn. Soc.
Plumb. Eng. 1990, 7, 23–26. (In Japanese).
23. Hunter, R.B. Building Materials and Structures Report No.65; U.S. Department of Commerce: Washington, DC,
USA, 1940.
Water 2017, 9, 376 21 of 21
24. Takada, H. Analysis on the Uses and Cold-Hot Water Consumption of Toilet and Hot-Water Service Room
in the Office Building: Part 1 Using frequency of sanitary fixtures. Archit. Inst. Jpn. 2003, 26, 533–536.
(In Japanese).
25. Takada, H.; Murakawa, S.; Nishina, D.; Sakamoto, K.; Yamaoka, M.; Yamane, Y. A Study on the Cold and Hot
Water Consumption based on the Time Series Analysis: Part 2 The Usage of Fixtures in the Office Building’s
Toilets. In Summaries of Technical Papers of Annual Meeting; Architectural Institute of Japan: Tokyo, Japan,
2003; pp. 455–456. (In Japanese)
26. Yamane, Y.; Murakawa, S.; Nishina, D.; Sakamoto, K.; Yamaoka, M.; Takada, H. A Study on the Cold and Hot
Water Consumption based on the Time Series Analysis: Part 3 Analysis on the Cold-Hot Water Demands in
the Office Building’s Toilets. In Summaries of Technical Papers of Annual Meeting; Architectural Institute of
Japan: Tokyo, Japan, 2003; pp. 457–458. (In Japanese)
27. Takada, H.; Murakawa, S.; Nishina, D.; Yamane, Y. A Study on the Cold and Hot Water Consumption based
on the Time Series Analysis: Part 6 Cold Water Demands in the Office Building’s Toilets. In Summaries
of Technical Papers of Annual Meeting; Architectural Institute of Japan: Tokyo, Japan, 2004; pp. 559–560.
(In Japanese)
28. Sakamoto, K.; Murakawa, S.; Koshikawa, Y.; Takada, H.; Yamane, Y. Development of the Calculating Method
of Cold and Hot Water Consumption based on the Fixture Usage in the Time Series through a Day: Part 5
Analysis on the Loads of Water Supply Demands in the Office Buildings. In Summaries of Technical Papers of
Annual Meeting; Architectural Institute of Japan: Tokyo, Japan, 2005; pp. 416–451. (In Japanese)
29. Yamane, Y.; Murakawa, S.; Nishina, D.; Takada, H.; Nagae, M. Analysis on the Uses and Cold-Hot Water
Consumption of Toilet and Hot-Water Service Room in the Office Building: Part 3 The usage in hot-water
service room and basin. Archit. Inst. Jpn. 2004, 27, 533–536. (In Japanese).
30. Takada, H.; Murakawa, S.; Yamane, Y.; Sakamoto, K. Analysis on The Water Usage in Office Buildings:
A study on the calculating method for cold and hot water supply demands based on the analysis of water
usage in the time series (Part 3). J. Environ. Eng. Trans. AIJ 2005, 71, 51–58. (In Japanese). [CrossRef]
31. Koshikawa, Y. Analysis of the Adult’s Uses and Consciousness of Lavatories. Soc. Heat. Air-Cond. Sanit.
Eng. Jpn. 1997, 65, 41–52. (In Japanese).
32. Wu, G.Z.; Sakaue, K.; Fujimura, K.; Murakawa, K.; Kojima, K.; Hayakawa, K. Examinations on Water Supply
Load Calculation Methods of Office Building: Comparison between Traditional Design Methods and the
Simulation Tool. Tech. Pap. Annu. Meet. Soc. Heat. Air-Cond. Sanit. Eng. Jpn. 2013, 1, 1–4. (In Japanese).
© 2017 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).