Geotechnical Design of Shallow Foundations
Geotechnical Design of Shallow Foundations
Geotechnical Design of Shallow Foundations
GEOTECHNICAL DESIGN OF
SHALLOW FOUNDATIONS
9.1 INTRODUCTION
235
236 GEOTECHNICAL DESIGN OF SHALLOW FOUNDATIONS
Figure 9.1 Photograph from Mexico City showing conference attendees standing
next to a well casing showing subsidence over many years.
9.3 DESIGNS TO ACCOMMODATE CONSTRUCTION 237
ferential settlement. The authors are reluctant to present such guidelines be-
cause of special circumstances that apply to many such structures.
Subsidence due to lowering of the water table has affected other places,
including Ottawa, Canada (Bozuzuk and Penner, 1971), the Gulf Coast of
Texas (Dawson, 1963), Venice (Berghinz, 1971), and London (Wilson and
Grace, 1939). Surface and near-surface facilities such as roads, streets, and
pipelines have been adversely affected (Zeevaert, 1980). In addition, fractures
have been observed near the edges of the area of subsidence where the change
in ground surface elevation was severe. Fracturing due to subsidence from
the lowering of the water table is difficult and perhaps impossible to predict,
but the geotechnical engineer must be aware of the chance of such occur-
rences.
Subsidence is a potential problem in areas of abandoned mines (Gray and
Meyers, 1970) and in areas of karstic geology. Location of underground cav-
ities emphasizes the need for a proper investigation of the soil at a site and
suggests the possible use of geophysical techniques.
9.4.1 Introduction
As noted in Chapter 6, designers of footings on sand must be aware of the
possible settlement due to dynamic loads. Many investigators have studied
the problem, with most concern focusing on the design of compaction equip-
ment. Brumund and Leonards (1972) performed tests in the laboratory with
a tank of Ottawa sand at a relative density of 70%. A plate with a diameter
of 4 in. was vibrated and a settlement of approaching 1 in. was measured.
The relative density of sand deposits and all relevant properties of the sand
must be considered when designing the foundations for vibrating machinery.
Data provided by the machine’s manufacturer must be accessed in making
such a design.
The discussion in Chapter 4 indicated that sampling deposits of sand with-
out binder below the water table is not possible without extraordinary mea-
sures, such as freezing, and in situ techniques for investigating the sand are
normally required. The two principal tools for obtaining data on the charac-
teristics of sand are the SPT and the static cone, sometimes termed the Dutch
cone. The cone consists of a 60⬚ hardened steel point, a projected end area
of 10 cm3, and a rate of advancement of 2 cm/sec. Data from the static cone,
if obtained in the recommended manner, are reproducible because the resis-
tance along the push rods is eliminated, the force of penetration is measured
with a calibrated load cell, and the rate of penetration is standard.
The SPT has been used widely in the United States for many years and is
the usual technique for determining the in situ characteristics of sand. Testing
with the static cone is popular in Europe but has been slow in gaining pop-
ularity in the United States; however, many U.S. geotechnical firms can now
perform the cone test.
Data from the SPT, described in Chapter 4, can vary widely from one
operator to another and during the performance of a particular test. Robertson
and Campanella (1988) have referenced other authors and have noted that the
energy delivered to the driving rods during an SPT can vary from about 20%
to 90% of the theoretical maximum, with the variation related to the number
of turns of rope around the cathead, the height of fall, the type of drill rig,
and the operator. They concluded that an energy ratio of 55% to 60% is the
average energy level employed in the field, suggesting that SPT values have
some degree of uncertainty.
9.4 SHALLOW FOUNDATIONS ON SAND 239
In the two sections that follow, two methods are presented for obtaining
the immediate settlement of shallow foundations on sand. The first is based
on the static-cone test and the second is based on the SPT.
p
z (1 )[(1 2v)A F] (9.1)
E
240 GEOTECHNICAL DESIGN OF SHALLOW FOUNDATIONS
USE Es = 2.5 qc
IIP = 0.5 + 0.1 Δp .....(1)
σVP
B
PLANE STRAIN
L/B > 10
3B
(a) Modified strain influence
factor distributions
4B
B
Δp = p – p´o
p
p´o
B/2 (oxisym)
B (pl. str.) σ´vp
DEPTH TO IIP
Figure 9.2 Recommended modified values for strain influence factor diagrams and
matching sand moduli (from Schmertmann et al., 1978).
where
C1 1 0.5 冉冊p0
⌬p
(9.4)
where
The values of Iz, shown in Figure 9.2, must be modified by increasing the
value of Izp from 0.5 to 0.69. The revised diagram for Iz is shown in Figure
9.3 along with assumed values of qc from the cone test, following the pattern
of values employed by Schmertmann in the original example.
The results from the computations for the revised example are shown in
Table 9.1. The stratum was divided into layers, as shown in Figure 9.3, de-
pending on values of qc, except where a layer was adjusted to fit the peak
value of qc. The table extends below the footing to a depth of 4B or (4)(2.60)
10.4 m. Eleven layers are shown in Table 9.1 with pertinent values of the
relevant parameters. For a layer of a given thickness and with the correspond-
ing value of qc, an average value of Iz was obtained by taking values at the
top and bottom of each layer. The value of Es for the plane-strain case was
taken as 3.5 times qc. The values of C1 and C2, for a period of 5 years, were
computed:
C1 1 0.5 冉 冊
31.4
149
1.11
C2 1 0.2 log冉 冊 5
0.1
1.34
Figure 9.3 Modified strain-influence factor and assumed values of qc from the cone
test.
9.4 SHALLOW FOUNDATIONS ON SAND 243
TABLE 9.1
⌬Z qc Es ZL ⌬p ⌬z
Layer (m) (MPa) (MPa) (m) Iz C1 C2 (MPa) (m 103)
1 1.0 2.50 8.75 0.50 0.295 1.11 1.34 0.149 7.5
2 1.6 3.50 12.25 1.80 0.540 1.11 1.34 0.149 15.6
3 0.4 3.50 12.25 2.80 0.673 1.11 1.34 0.149 4.9
4 0.5 7.00 24.50 3.25 0.633 1.11 1.34 0.149 2.9
5 1.0 3.00 10.50 4.00 0.568 1.11 1.34 0.149 12.0
6 0.5 8.50 29.75 4.75 0.500 1.11 1.34 0.149 1.9
7 1.5 17.00 59.50 5.75 0.410 1.11 1.34 0.149 2.3
8 1.0 6.00 21.00 7.00 0.300 1.11 1.34 0.149 3.2
9 1.0 10.00 35.00 8.00 0.213 1.11 1.34 0.149 1.3
10 1.5 4.00 14.00 9.25 0.103 1.11 1.34 0.149 2.4
11 0.4 6.50 22.75 10.20 0.018 1.11 1.34 0.149 0.1
Sum
54.1 mm
qa Cw(0.41)NSPT S (9.6)
Dw
Cw 0.5 0.5 (9.7)
Dƒ B
where
244 GEOTECHNICAL DESIGN OF SHALLOW FOUNDATIONS
The authors included Figure 9.4 to correct NSPT to account for pressure from
the overburden, ⬘0 (the dependence on units should be noted).
The example of a footing on sand is shown in Figure 9.5. The footing is
3 ft by 3 ft2 and placed l.2 m below the ground surface. The unit weights of
the sand above and below the water table are shown. The corrected value of
NSPT is given as 20. The above equations are used to find the value of qa
where the value of S is 25 mm.
1.2
Cw 0.5 0.5 0.64
1.2 3
qa 0.64(0.41)(20)(25) 131 kPa
The bearing capacity of the footing in Figure 9.5 will be studied in the next
section as a means of evaluating the answer shown above.
Figure 9.4 Factor used to multiply by NSPT to obtain the corrected value accounting
for pressure from overburden (from Peck et al., 1974).
9.4 SHALLOW FOUNDATIONS ON SAND 245
Figure 9.5 Example of a computing settlement where the value of NSPT is available.
NSPT is given as 20. Figure 9.6 shows a correlation between the corrected
value of NSPT and ⬘, where ⬘ is the friction angle from effective stress
analysis. If data are available from the cone test, Figure 9.7 shows the cor-
relation between the value of qc from the cone test and ⬘ for uncemented
quartz sand, taking the vertical effective stress into account.
For a corrected value of NSPT of 20, Figure 9.6 shows the value of the
friction angle ⬘ to be 33⬚. Table 7.1 shows the value of Nq to be 26.1 and
Figure 9.6 Correlation between corrected NSPT and friction angle from effective stress
(from Peck et al., 1974).
246 GEOTECHNICAL DESIGN OF SHALLOW FOUNDATIONS
Figure 9.7 Suggested correlation between qc from the cone test and peak friction
angle ⌽⬘ for uncemented quartz sands considering vertical effective stress (from Rob-
ertson and Campanella, 1983).
the value of N␥ to be 24.4. The requisite formula is Eq. 7.7 for the case in
Figure 9.5:
Qd 1
qd ␥BN␥ s␥ d␥ ␥DƒNqsqdq
A 2
1
qd (7.5)(3)(24.4)(0.6)(1) (17.3)(1.2)(26.1)(1.54)(1.37)
2
165 1143 1308 kPa
9.5 SHALLOW FOUNDATIONS ON CLAY 247
water; the stratum of clay will likely have a degree of nonuniformity, and
average values must be used in the analyses; the stiffness of a structure will
affect the distribution of stress and the differential settlement; and settlement
can be shown to depend to some extent on the value of the pore-pressure
coefficient A (Skempton and Bjerrum, 1957). In spite of the limitations noted
above, the equations for total settlement and time rate of settlement of shallow
foundations on saturated clay can be used with some confidence.
Skempton and Bjerrum (1957) include data on the final settlement of four
structures on normally consolidated clay where settlement was significant and
where the computed settlement can be compared with the observed settlement
(Table 9.2). The data are undoubtedly for the portion of the structure where
the settlement was largest. The computed settlement includes an estimate of
the initial settlement, as discussed in the following section.
The data in Figure 9.8 are remarkable where the time rate of settlement is
shown for three of the structures listed in Table 9.2 and where measurements
were made over many years. Excellent agreement is indicated between ob-
served and computed settlements over much of the life of each structure.
The procedures presented in Chapter 7 for the computations of total set-
tlement and time rate of settlement can be used with confidence in many
instances. Limitations on the theory are noted above, and implementation
of the procedures can be expensive and time-consuming. Foundation investi-
gation and laboratory studies must be of high quality, and even then the
geotechnical engineer is faced with difficult decisions about relevant soil
properties.
The settlement due to consolidation of clay will be illustrated using Figure
7.9a. The following assumptions are made with regard to depths and soil
properties: the top of the clay layer is at 8 ft below the bottom of the footings,
the clay layer has a thickness of 4 ft, the footings are embedded 2 ft into
the upper sand, the upper 2 ft of the sand are saturated by capillarity, the
water table is at the base of the footings, the total unit weight of the sand
below the water table is 120 lb/ft3, and the total unit weight of the clay is
110 lb/ft3.
The effective stress at the mid-height of the clay layer prior to construc-
tion the footing may be computed as follows:
Time – years
0 5 10 15 20 25 30
end of
construction
MASONIC TEMPLE
Net Settlement – inches
calc.
10
obs.
15
Time – years
0 10 20 30 40 50 60
end of
construction
MONADNOCK BLOCK
Net Settlement – inches
10
calc.
20
obs.
35
Time – years
10 20 30 40 50 60
0
end of
construction
AUDITORIUM TOWER
Net Settlement – inches
10
calc.
20
obs.
30
Figure 9.8 Observed and calculated settlement of buildings on Chicago clay (from
Skemptom and Bjerrum, 1957).
250 GEOTECHNICAL DESIGN OF SHALLOW FOUNDATIONS
Figure 7.12 shows that the value of v was 0.580 k/ft2 at the top of the clay
layer due to the imposition of the footing loads. A similar exercise used the
Newmark chart, and the value of v at the bottom of the clay layer was 0.423
k/ft2. The value of v at the mid-height of the clay layer was 0.502 k/ft2.
It is assumed that consolidation tests have been performed for the clay in
the layer between the sand strata. The clay was found to be normally con-
solidated, and the following values were obtained: e0 0.7, cc 0.36, and
cr 0.04 ft2 /day.
From Eq. 7.36,
S
4
1 0.7冋0.36 log
0.796 0.502
0.796 册
0.286 ft
Referring to Figure 7.14, data can be obtained for preparing a table showing
settlement as a function of time, as shown below. The time for a specific
amount of settlement to occur may be obtained from Eq. 7.44, as shown for
time for 50% of the settlement to occur.
U, % Tv S, ft t, days
11 0.01 0.032 1.0
20 0.03 0.057 3.0
30 0.066 0.086 6.6
40 0.12 0.114 12.0
50 0.197 0.143 19.7
60 0.28 0.172 28.0
70 0.38 0.200 38.0
80 0.48 0.229 48.0
90 0.85 0.243 85.0
100 0.289 Infinite
Information such as that in the table above can be of great value to the
engineer and other professionals in planning the design of a structure of sat-
urated clay.
1 2
qBI (9.8)
E
where
q qd 1 2
I (9.9)
B qd su E/su
where
Making the substitutions, the following equation was obtained for a circular
footing on the surface of saturated clay:
1 4 q
(9.10)
B E/su qd
Skempton noted that for footings at some depth below the ground surface,
the influence value of I decreases but the bearing capacity factor Nc increases;
therefore, to a first approximation, the value of I Nc is constant, and Eq, (9.10)
applies to all circular footings. In the axial compression test for undrained
specimens of clay, the axial strain for the deviator stress of (1 3) is given
by the following expression:
(1 3)
(9.11)
E
252 GEOTECHNICAL DESIGN OF SHALLOW FOUNDATIONS
where E is the secant Young’s modulus at the stress (1 3). The above
equation may be written more conveniently as follows:
1 3 (1 3)t 1
(9.12)
(1 3)t su E/su
But in saturated clay with no change in water content under the applied stress,
(1 3)t
2.0; thus, the following equation may be written:
su
2 (1 3)
(9.13)
E/su (1 3)t
Comparing Eq. 9.10 with Eq. 9.13 shows that, for the same ratio of applied
stress to ultimate stress, the strain in the loading test is related to that in the
compression test by the following equation:
1
2 (9.14)
B
The equation states that the settlement of a circular footing resting on the
surface of a stratum of saturated clay can be found from the stress-strain
curve of the clay. Skempton performed some tests with remolded London
clay and found that Eq. 9.14 could be used to predict the results of the footing
q
tests except for high values of . He further noted that the values of I
qd
increased from 0.73 for a circle to 1.26 for a footing with a ratio of length
to width of 10⬊1, while the bearing capacity factor Nc decreased from 6.2 to
5.3 for the same range of dimensions. Skempton concluded that the proposed
formulation could be used with a degree of approximation of 20% for any
shape of footing at any depth.
the observed movement at the top of the shafts. The instrumentation with
interpretation allowed load-settlement curves to be produced for each of the
four tests.
Beaumont clay was deposited by the alluvial process in the first Wisconsin
Ice Age and is somewhat heterogeneous, with inclusions of sand and silt. The
liquid limit is around 70 and the plastic limit is around 20, although wide
variations in both indices are common. The formation was preconsolidated
by desiccation, with the indicated preconsolidation pressure at about 4 tons/
ft2. Numerous cycles of wetting and drying produced a network of randomly
oriented and closely spaced fissures. The fissures led to considerable varia-
tions in measured shear strength, as indicated by the shear-strength profile
shown in Figure 9.9. Confining pressure in the performance of the tests was
equal to the overburden pressure. The scatter in the test results is not unusual
and indicates practical problems in sampling and testing of many overcon-
solidated clays. The solid line in the figure was used in interpreting the results
of testing of the foundation.
A stress-strain curve is shown in Figure 9.10 for the upper stratum at
O’Neill’s site. The shear strength was the average of two diameters below the
base of each of the shafts. Significant data for the four test shafts are shown
in Table 9.3. Computed values of the bearing capacity factor for three of the
tests are very close to the Hansen value of 9.0. The overburden pressure and
Figure 9.9 Shear strength profile from triaxial testing (from O’Neill, 1970).
254 GEOTECHNICAL DESIGN OF SHALLOW FOUNDATIONS
Figure 9.10 Stress-strain curves for beaumont clay (from O’Neill, 1970).
the pressure from the weight of the concrete in the drilled shaft were assumed
to be equal in computing the bearing capacity.
Load-settlement curves from the experiments performed by O’Neill are
plotted in Figures 9.11 through 9.14. The stress-strain curve in Figure 9.10
was used in making the Skempton computations. The lack of much better
agreement between the measured and computed values is not surprising in
view of the nature of the soil at the test site. The presence of randomly
oriented and closely spaced fissures means that the soil in the triaxial tests
was less stiff than the soil at the base of the test shafts during the testing.
As shown in Figures 9.11 to 9.14, the values for pile settlement are indi-
cated for a factor of safety of 3 based on the data from the stress-strain curves.
Assuming that the data from load tests were not available, the stress-strain
curves yielded an average settlement value of 0.24 in. for the shafts with a
base diameter of 30 in. and 0.27 in. for the shaft with a base diameter of 90
in. The numbers should not have caused the designer much concern, even
60
Qexp = 52 T
50
40
Load (tons)
30
20
FS = 3, ρ exp = 0.18, ρ ana = 0.22 in.
10
O'Neill
Skempton
0
0 0.5 1 1.5 2 2.5 3
Settlement (in.)
though the corresponding numbers from the load tests were 0.18 in., 0.05 in.,
and 0.09 in. (shafts 1, 3 and 4), average of 0.11 in. and 0.21 in.
500
Qana = 461 T
450 Q exp = 445 T
400
N c = 8.68
350
300
Load (tons)
250
200
100
50 O'Neill
Skempton
0
0 1 2 3 4 5 6 7 8
Settlement (in.)
50
Qana = 46.4 T
45
Q exp = 47 T
40
Nc = 9.12
35
30
Load (tons)
25
20
10
5 O'Neill
Skempton
0
0 0.5 1 1.5 2 2.5 3 3.5 4
Settlement (in.)
Figure 9.13 Load-settlement curves for test shaft S3.
Two procedures may be considered: (1) the use of deep foundations driven
into stable soil with respect to vibration and (2) the use of soil-improvement
methods to make the sand resistant to vibration.
160
Qexp = 142 T
140
120
N c = 12.68
80
60
40
FS = 3, ρ exp = 0.09 in., ρ ana = 0.29 in.
20
O'Neill
Skempton
0
0 0.5 1 1.5 2 2.5 3
Settlement (in.)
lenses. With time, more water rises and additional ice lenses are formed. On
some occasions, a large quantity of ice can collect in a restricted area. The
increased thickness of the ice causes a heave of the shallow foundation, as
shown in Figure 9.16. When warm weather occurs the ice in the soil melts,
leaving the soil with high water content and a low value of bearing capacity.
The conditions shown in Figure 9.15 can lead to failures of roadway pavement
that can be dangerous to vehicular traffic. A remedy to the problem illustrated
in Figure 9.16 is to place a layer of coarse granular soil in the zone of
capillary rise to prevent the upper flow of capillary water.
In northern climates, the soil may remain permanently frozen, a condition
termed permafrost. The construction of light structures and other facilities in
such regions is aimed at preventing the thawing of the permafrost. Structures
are supported on posts or short piles so that air circulation beneath the struc-
ture and above the frozen soil is allowed to continue.
Figure 9.15 Maximum anticipated depths of freezing as inferred from city building
codes. Actual depths may vary considerably, depending on cover, soil, soil moisture,
topography, and weather (from Spangler and Handy, 1982).
Figure 9.17 Distribution of potentially expansive soils in the United States (from Nelson and Miller, 1992).
262 GEOTECHNICAL DESIGN OF SHALLOW FOUNDATIONS
water. The permeability of clay is so low that the slurry will not readily
penetrate it.
If the stratum of clay is so thick that it cannot be removed or treated, then
the engineer usually considers the use of a stiffened slab on grade, such as
the BRAB slab (Building Research Advisory Board, 1968). The site is graded
with deepened sections at relatively close spacing where reinforcing steel is
placed to form beams into the foundation. The depth of the beams and the
spacing depend on the judgment about shrinkage potential. The purpose of
the beams is to make the slab so stiff that differential settlement is minimal.
Over time, moisture will collect under the center of the slab because of re-
stricted evaporation, but the edges of the slab will respond to changes in
weather. Some homeowners have used plantings or other means to prevent
shrinkage of the soil around a stiffened slab.
In some cases, a founding stratum may occur below the expansive clay.
Drilled shafts can be installed with bells and designed to sustain the uplift
from the expanding clay. If drilled shafts are used, a beam system should be
employed to provide a space above the surface of the clay to allow swelling
to occur without contact with the beams and floor system. Further, the bond
between the expanding clay and the shaft should be eliminated or the shaft
should be heavily reinforced to sustain uplift forces.
the soil is of the same sort but with widely varying properties, or two or more
layers exist in the zone beneath the foundation. Settlement may be computed
with procedures that have been presented, but questions arise when selecting
the bearing capacity. If the additional cost is minor, the bearing capacity may
be based on the weakest stratum in the founding stratum. The second possi-
bility is that settlement will control the design, as shown earlier in this chapter,
rather than bearing capacity.
In some studies, the shapes of the failure surfaces have been modified to
reflect the presence of layers with different characteristics (Meyerhof, 1978;
Meyerhof and Hanna, 1974). A more favorable approach is to employ FEM,
as demonstrated by the material in the following section. A number of codes
are available. Such codes will continue to be important in the analytical work
of engineering offices.
assumed to be 120 pcf. The Mohr-Coulomb model was used to represent the
nonlinear behavior of the soil.
The result from the FEM computation, where a series of deformations of
the footing was used as input, is shown in Figure 9.19. The analysis assumed
a rough footing because the soil was not allowed to spread at the base of the
footing. As may be seen, the unit value of the ultimate bearing capacity (qu)
of the footing was predicted as 185 psi. The Terzaghi equation for bearing
capacity, Eq. 7.3, is re-written to obtain the unit value of ultimate bearing
capacity and shown in Eq. 9.15.
1
qu ␥BN␥ ␥DƒNq cNc (9.15)
2
The footing is resting on the soil surface, so the value of Dƒ is 0. The prop-
erties of the soil show above were employed, along with the following values
of the bearing capacity factors (see Chap 7): N␥ 3.64, Nc 17.69, and the
value of qu was computed as follows
1
qu (0.0694)(120)(3.64) (10)(17.69) 15.2 176.9 192.1 psi.
2
The FEM yielded a value quite close to the result from the Terzaghi equations.
The methods presented herein do not allow a check to be made of the initial
slope of the load-settlement curve in Fig. 9.19. The deformation field of soil
in the vicinity of the strip footing generated by the FEM output is presented
in Fig. 9.20 which is consistent with the theory introduced in Chapter 7.
The excellent comparison between results from the FEM for a solution of
a straightforward problem indicates that the method can be applied to complex
problems in bearing capacity including response to eccentric loading and be-
havior of shallow foundations on layered soils. However, in the solution of
Figure 9.19 Load-settlement curve for a strip footing from analysis by FEM.
PROBLEMS 265
Figure 9.20 Deformation field for soil near a strip footing from analysis by FEM.
the example, the engineer faced the problem of selecting a constitutive model
for the soil, the size and number of the elements, the distance to each of the
boundaries, and appropriate restraint at the boundaries. Experience in using
the method is valuable, but different trials by varying the parameters in the
solution may be necessary. Many engineering offices are routinely employing
codes for the FEM and more use is expected in the future.
PROBLEMS
P9.1. Cummings (1947) described the nature of the clay in the Valley of
Mexico and showed the results of consolidation tests performed at
Harvard, where the void ratios were extremely high and unusual.
The e-log-p plot in Figure 9.21 is patterned after the test results
reported by Cummings. Using that plot and estimating the settlement
at a location in Mexico City from the photograph in Figure 9.1, com-
pute the amount the water table must be lowered to cause the settle-
ment indicated. Assume the clay stratum to be 150 ft thick, the initial
void ratio to be 6.60, the initial compressive stress to be 0.9 tsf, and
that the clay remains saturated by capillarity as the water table is
lowered. The answer may be surprising.
P9.2. The plot in Figure 9.22 shows values of qc from the cone penetration
test at a site where a footing is to be constructed. Use the Schmert-
266 GEOTECHNICAL DESIGN OF SHALLOW FOUNDATIONS
5
Void Ratio
0
0.01 0.1 1 10
Pressure, tsf
Figure 9.21 Plot of e versus log-p for soil similar to that in the Valley of Mexico.
Figure 9.22 Example of the result of the cone penetration test (from Robertson and
Campanella, 1988).
P9.3. Use the data from Problem P9.2 to compute the bearing capacity for
the footing. Use Figure 9.23 in selecting a value of for use in
bearing-capacity computations, and consider the low value qc at the
base of the footing and the significant increase with depth below the
base. Assume a factor of safety of 3 and compute the value of the
safe bearing capacity. Compare the safe bearing capacity with the unit
load used in Problem P9.2. Discuss the allowable load or safe load
you would select. (Check construction on figure and modify as
necessary.)
P9.4. Estimate the settlement of a footing 10 ft2 resting at a depth of 2 ft
below the surface of a coarse sand and subjected to a total load of
400 kips. The water table is at a depth of 2 ft, and the corrected value
of NSPT is 30.
P9.5. Compute the unit bearing capacity in kips per square foot of the foot-
ing in Problem P9.4, assuming that the total unit weight of the sand
is 122 pcf. Compute the factor of safety for the load of 400 kips.
268 GEOTECHNICAL DESIGN OF SHALLOW FOUNDATIONS
Figure 9.23 Suggested correlation between qc from the cone test and peak friction
angle ⌽⬘ for uncemented quartz sands considering vertical effective stress (from
Robertson and Campanella, 1983).
P9.8. Assume that consolidation tests were performed on the clay in Prob-
lem P9.7, that the soil is normally consolidated, and that the following
values were obtained for the clay: ␥sat 120 pcf; e0 1.10; cc
0.40; cv 0.025 ft2 /day; sand, ␥ 125 pcf. Compute the settlement
in inches at the center and edge of the tank.
P9.9. Plot curves showing the settlement of the center of the tank as a
function of time.
P9.10. Plot a curve showing the distribution of excess porewater pressure in
the clay stratum for consolidation of about 50% (use Tv 0.2).
P9.11. If the differential settlement of the tank is judged to be a problem,
list three steps that may be taken to reduce it.