MATLAB Based Simulations Model For Three Phase Power System Network
MATLAB Based Simulations Model For Three Phase Power System Network
MATLAB Based Simulations Model For Three Phase Power System Network
net/publication/310625062
MATLAB based Simulations model for Three phase Power System Network
CITATION READS
1 1,593
4 authors, including:
K. Nithiyananthan
CMR Institute of Technology
78 PUBLICATIONS 671 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by K. Nithiyananthan on 21 December 2016.
ABSTRACT
The primary aim of this research work is to build up a MATLAB based Simulation model for 3
phase symmetrical and unsymmetrical faults. This paper ways to deal with the MATLAB
programming in which transmission line model is composed and different issues has been
reenacted utilizing tool compartment. Fault Analysis for different sorts of faults has been done
and it impacts are appeared in simulation output, for example, voltage, current, control
alongside the positive, negative and zero grouping segments of voltage and current output as far
as waveforms.
KEYWORDS: L-L –Line to Line fault, Single Line to Ground fault, 2L-G Double Line to
Ground fault, MATLAB Simulations.
1. INTRODUCTION
Presently a-days the requests of power are builds step by step this outcomes to transmit more
power by expanding the transmission line limit from one place to the next place. Be that as it
may, amid the transmission a few faults are happened in the framework, for example, L-L fault
(line to line), L-G fault (single line to ground) and 2L-G fault (twofold line to ground). These
faults influence the power framework types of gear which are associated with it. Now –a – days
due to continuous expansion of Power System Network, controlling and monitoring of Power
systems is unavoidable. Solutions through advanced data communications model are in evident.
[1-26] When different types of fault occurs in power system then in the process of transmission
line fault analysis, determination of bus voltage and the rms line current are possible. While
consulting with the power system the terms bus voltage and rms current of line are very
important. In case of three phase power system mainly two faults occurs, three phase balance
fault and unbalance fault on transmission line of power system, such as double line to ground
fault, line to ground fault and double line fault. The transmission line fault analysis helps to
select and develop a better for protection purpose. For the insurance of transmission line has
been placed the circuit breakers and its rating is depends on triple line fault. The reason behind
is that the triple line fault current is very high as compare to other fault current. Hence by using
MATLAB simulation in computer, the analysis of transmission line fault can be easily carried
out. The principle reason for this paper is to study the general fault types which are balance and
unbalance faults of transmission line in the power system. Also to perform the analysis and
obtain the result of various parameters (voltage, current, power etc) from simulation on those
types of fault using MATLAB [27].A new modeling framework for analysis and simulation of
unbalance fault in power system is procedure includes the frequency information in dynamical
models and produces approximate non linear models that are well adopted for analysis and
simulation[28] .
The transformer display incorporates saturation. The parameters have been acquired from
reasonable or exploratory estimations. From the study it is seen that sags can create transformer
saturation when voltage recovers [29]. This prompts deliver an inrush current that is like inrush
current created amid the transformer energizing. The study call attention to that the voltage
recovery moment can take just discrete value, since the fault clearing is delivered if there should
arise an occurrence of regular current zeros. The moment of voltage recovery compares to the
moment of fault clearing. For phase to phase fault and single phase fault, a solitary point-on-
wave of voltage recovery can be defined [30]. Then again for two-phase to-ground and three-
phase fault, the recovery happens in a few stages. In petrochemical industry, the establishing and
ground fault security are critical factors [31]. For that first it is essential to have the correct
framework establishing for the specific framework application, and alongside this it is similarly
critical to have the best possible assurance against the ground-fault.
written in different dialects. In spite of the fact that MATLAB is proposed fundamentally for
numerical registering a discretionary tool compartment utilizes the MuPAD typical processing
capacities. An extra bundle, Simulink, includes graphical multi-space recreation and model
based plan for dynamic and installed framework. MATLAB clients originate from different
foundations of designing, science and financial aspects. MATLAB is broadly utilized as a part
of scholarly and research organizations and also mechanical ventures. Additionally MATLAB
gives an alluring domain with several dependable and precise inherent capacities. MATLAB
family cooperate with Simulink programming to display electrical, mechanical and control
systems[32].A result of The Math-Works, Inc. MATLAB began life as a program intended to
perform framework science, yet throughout the years it has developed into an adaptable
processing framework equipped for taking care of basically any specialized issue. MATLAB
can control and transform huge frameworks and can be utilized as a part of numerous numerical
applications. MATLAB's capacities can be reached out with expansion called SIMULINK, a
program which is ordinarily utilized as a part of the investigation and combination of present
day systems [33].
system Block set (PSB) is used to create tweaked show libraries for educating protective
relaying ideas.
2. ATP/EMTP is intended to reenact the physical procedures of transmission lines and
transformers rapidly and helpfully however MATLAB/SIMULINK offers more conceivable
outcomes in power electronics, signal processing and control.
3. Clients can without much of a stretch make new relay model with MATLAB/SIMULINK,
though EMTP/ATP doesn't have such limit.
4. MATLAB/SIMULINK envelops preferable realistic capacity apparatuses over EMTP/ATP of
pc plot, plot xy etc.
additionally given. The Power Electronics aggregate contains basic semiconductor devices.
Every component in this gathering (with the exception of Diode) has a SIMULINK gating
control input and a SIMULINK output returning switch current and voltage. Mat Power Tool kit
is a bundle for explaining power stream and ideal power stream issues. This bundle is intended
to give the most ideal execution while keeping the code easy to comprehend and change. Power
System Analysis Tool stash is for electric power framework investigation and control. It
incorporates control stream, ceaseless power stream, ideal power stream, little flag security
investigation and time area reproduction. Voltage stability Tool stash breaks down voltage
security issues and gives data to power system arranging, operation and control. Additional
library comprise of Control squares, discrete control pieces, discrete estimations and phasor
library.
utilized at chose focuses as a part of the circuit to change over electrical signs into SIMULINK
signals.
The implementation deals with the model made in MATLAB using the Sim Power Systems®
Tool, the GUI. Through this advanced data simulation model fault analysis of any power system
network can be simulated with ease and its fault analysis can be carried out. [33-43].
Figure 2 indicates the relay circuit sub system for the proposed three phase model in a matlab
environment.
3. 2 SIMULATION RESULTS
In this particular case, the Distribution system model is runs for a Three Phase to Ground Fault.
The simulation is done for 1 sec, so that the waveforms can be seen more clearly. The sampling
frequency is taken to be 10 kHz. The system voltage is taken as 33 kV and the line length is
taken as 10 kms, with fault occurring at 5 kms. Fault is started at 0.2 secs and cleared at 0.7 secs
as shown in Figure 3. These parameters have been kept constant for other test cases as well.
Fig.3 and Fig 4, indicates the current and voltage waveforms for the given specifications. Upon
injecting these signals to the relay it has been seen that the relay trips after 47.51 ms and the
status of its coil is shown in the simulated results. As this is a self-reset relay, the trip status
comes back to 0 upon clearing the fault, but for a manual reset relay, it stays 1 till the reset
button is pressed manually. The proposed matlab model can be ran standalone or on the GUI to
view the plots.
Figure 5 shows the simulation results of current wave form for the induced double line to
ground fault in the proposed model.
CONCLUSION The simulation and analysis of three phase fault to achieve results of the
transmission line parameter is convenient by using MATLAB software. In this paper simulation
of three phase transmission line fault analysis system is proposed. Single Line to Ground fault,
Double Line fault etc in transmission line is also simulated. This system opens the way to
redesign the bus system of the power system according to its results. The proposed work can
able to implement for a larger power systems geographically apart.
REFERENCES
1 Nithiyananthan.K, Pransujain,(2015) ‘Logixpro Based Scada Simulation Model For
Packaging System In Dry Ice Plant’ International Journal of Electrical And Computer
Engineering, Asia.Vo1 5, No2.443-453.
[5] Nithiyananthan.K and S.Nithya, (2015) ‘Analysis of Energy consumption for Digital
Serial Interfaces in low Embedded Systems Processors’ International Journal for
Electronics and Electrical Engineering,USA, Vol 3, No1,pp 1-6 Feb 2015.
[6] Nithiyananthan.K and Ramachandran.V (2014) ‘Effective Data compression model for
online power system applications’, International Journal of Electrical Energy, USA,
Vol2, No2, pp 138-145 June 2014.
[7] Nithiyananthan.K, Ramachandran.V (2013) ‘Distributed Mobile Agent model for multi
area power systems on-line state estimation’, International Journal of Computer Aided
Engineering and Technology, Inderscience publications, USA, Vol. 5, No. 4,300-310.
[14] Don Jacob, Nithiyananthan.K, (2009) ‘ Smart and micro grid model for renewable
energy based power system’ International Journal of Engineering Modelling, Croatia,
EUROPE, Vol. 22, No 1-4, pp.89-94.
[15] Nithiyananthan.K, Ramachandran.V, (2008) ‘A plug and play model for JINI based on-
line relay control for power system protection’ International Journal of Engineering
Modelling, Croatia, EUROPE, Vol. 21, No 1-4, pp.65-68.
[17] Don Jacob, Nithiyananthan.K, (2008) ‘Effective Methods for Power System
Grounding’ WSEAS Transactions on Business and Economics, USA. 30-642
[20] Nithiyananthan.K and Ramachandran.V, (2005) ‘RMI based distributed model for
multi-area power system on-line economic load dispatch’ Journal of Electrical
Engineering, Romania, EUROPE Vol 56, No 1-2, PP 41-44.
[23] Nithiyananthan K. and Ramachandran V. (2003), ‘Component Model for Multi - Area
Power Systems on - line Dynamic Security analysis’, Iranian Journal of Electrical and
Computer Engineering, Tehran, IRAN, Vol. 2, No. 2, pp. 103-106. .
Text here
[25] Nithiyananthan K. and Ramachandran V. (2003), ‘Distributed Mobile Agent Model for
Multi - Area on-line Economic Load Dispatch’, Journal of Electrical Engineering,
Romania, EUROPE, Vol. 54, No. 11-12, pp.316-319.
[26] Nithiyananthan K. and Ramachandran V. (2002), ‘EJB based component model for
distributed Load flow monitoring of multi - area power systems’, International Journal of
Engineering Modelling, Croatia, EUROPE, Vol. 15, No 1-4, pp.63-67.
[27] Varun Jadhav, Noah Dias, Arulselvan G, Ganesh Pushpakumar, ‘Fault Simulations on a
Distribution Network through a GUI’,International Journal of Innovative Research in
Electrical, Electronics, Instrumentation and Control Engineering,Vol. 4, Special Issue 2,
April 2016.
[31] M. Stankovic and Timur Aydin,”Analysis of asymmetrical fault in power system using
dynamic phasor”, IEEE transactions on power system, vol.15, p.p. 1062-1068, August
2000.
[32] Gerard us C.Paap,”Symmetrical component in the time domain and their application to
power network calculation,” IEEE Transaction on Power System, vol.15, p.p. 522-528,
May 2000.
[33] The Math-Works, Inc., Power System Blockset,User’s Guide, Version 1, 1999.
[35] SyahrelEmran Bin Siraj, Tan Yong Sing, Raman Raguraman, Pratap Nair,
K. Nithiyananthan, (2016) ‟Application of Cluster Analysis and Association
Analysis Model Based Power System Fault Identification‟, European Journal of
Scientific Research, Europe,Vol No 138, No 1.50-55.
[38] Tan Yong Sing, SyahrelEmran Bin Siraj, Raman Raguraman, Pratap Nair Marimuthu,
K. Gowrishankar, and K. Nithiyananthan (2016) “Cluster Analysis Based Fault
Identification Data Mining Models for 3 Phase Power Systems,” International Journal of
Innovation and Scientific Research, vol. 24, no. 2, pp. 285–292,Asia.
[39] SekethVerma and Nithiyananthan. K (2016) ‘MATLAB Based Simulations Model For
Identification of Various Points in Global Positioning System’, International Journal of
Computer Applications,USA, Vol138, No13.15-18.
[40] PratapNair and Nithiyananthan. K,(2016) ‘Feasibility analysis model for mini hydro
power plant in Tioman Island’, International Journal on Distributed generation &
Alternative Energy, U.K,Europe.Vol No 31 No 2,36-54.
[41] PratapNair and Nithiyananthan. K,(2016) ‘Effective cable sizing model for buildings
and Industries’ International Journal of Electrical and Computer Engineering, Asia,
Vol16, No1,34-39.