Modeling and Simulation of Inverse Time Overcurrent Relay
Modeling and Simulation of Inverse Time Overcurrent Relay
Abstract—Overcurrent relay is an important relay used to measured in multiples of current setting or pickup current.
protect transmission and distribution feeders, transformer, bus When used in coordination with other overcurrent relays such
coupler etc. It can be used as main or backup protection relays. as to protect radial feeders, it can be coordinated with upstream
The modeling of overcurrent relay and other protection relays is or downstream relays easily by the use of Time Multiplier
important in the research on the effects of network parameters
and configurations on the operation of these relays. This research
Setting, TMS [3].
deal with modeling and simulation of inverse time overcurrent There are many works had been done to model and
relay using commonly used Matlab/Simulink software. The simulate protection relays using Matlab/Simulink software. As
developed model was tested with single line to ground fault and in [5], Matlab/Simulink was used to model Inverse Definite
phase to phase fault with various fault locations and fault Minimum Time (IDMT) overcurrent relay which based on
resistances to evaluate phase and earth detectors in sensing the digital signal processor (DSP). After the developed Simulink
fault current. Simulations results show the feasibility of the model was tested using simulation, the developed model then
software to be used to develop the relay. was embedded in TMS320F2812 DSP board. Simulink also
had been used to model overcurrent relay which used to
Index Terms—Overcurrent relay, inverse time, Matlab,
Simulation. protect the Photovoltaic (PV) system for irrigation [6]. The
developed model was investigated at normal conditions,
starting of the motor as well as at faulty conditions.
I. INTRODUCTION
Graphical user interface (GUI) of distance relay was
Protection relay is used to reduce harmful damage to both developed and linked with the model of distance relay created
electrical equipment and personnel when an electrical fault using Simulink [7]. The GUI was used to ease the
occurs. Protection relay is designed based on the basis of understanding among electrical engineering students on the
selectivity, reliability, speed and sensitivity [1]. One of operation of distance relay. Finally, Matlab/Simulink was used
protection relays used to protect the circuits in power system is to model the conventional distance relay as in [8]. The relay
overcurrent relay. When there is a fault in power system, model then was simulated, analyzed and evaluated in real time
overcurrent relay will detects and isolate the faulty section using Opal-RT’s Real-Time LABoratory (RT-LAB). The
from the rest of the system by measuring the value of current. authors also successfully evaluated the effects of in feed
It can be used as main or backup protection to protect the current for protection at zones 1 and 2.
transmission or distribution feeders, transformers, bus coupler
etc [2]. When it is used to protect the feeders and transformers, II. SCOPES OF THE PROJECT
it normally will be coordinated in sequence so that the relay The purpose of this research is to model, simulate and
nearest to the fault location will operate first. There are two evaluate inverse time ovecurrent relay using Matlab/Simulink
types of overcurrent relay operating speed which are software. If the results prove the feasible use of the software to
instantaneous time and delayed time [3]. The weakness of model and simulate the relay, the model can be extended to be
instantaneous type is it can’t discriminate the operation when used in further research in the future. Matlab/Simulink is
fault current at two or more locations is the same [4]. chosen because of the widespread use of this software as
For delayed time type, it can be divided into two categories research platform and its’ capability to model power system
which are definite time and inverse time. For definite time components [9]. To ease the modeling of the relay, the model
overcurrent relay, the operating time is independent of current has been simplified and bounded by limitation where only
where relay closest to the fault has shortest operating time. The standard inverse (SI) curve was modeled and simulated in this
problem with this type is the longest operating time is at the research.
electrical source where the fault current is the highest. While
for inverse time overcurrent relay, the higher the fault current III. THEORIES OF INVERSE TIME OVERCURRENT RELAY
level, the faster the operating time will be. Fault current is
Parameters Values
Source Short Circuit Level (VA) 500,000,000
X/R Ratio 5
Source VLL (V) 132,000
Line CT Ratio 1200/1 A
Line Length (km) 50
Line Positive Sequence Resistance, R1 (Ω/km) 0.045531917
Line Zero Sequence Resistance, R0 (Ω/km) 0.151489359
Line Positive Sequence Inductance, L1 (H/km) 0.0006176566224
Line Zero Sequence Inductance, L0 (H/km) 0.001533982723
Line Full Load Current, IFL (A) 1233 A
3 Phase Line Capacity (VA) 282,000,000
Fig. 1. Characteristics of inverse time overcurrent relay [3] Plug Setting (PS) for Phase 1.2
Time Multiplier Setting (TMS) for Phase 0.35
Ip = PS x CTsec (1) Plug Setting (PS) for Earth 0.4
Where; Time Multiplier Setting (TMS) for Earth 0.35
PS = Plug Setting (% or pu) Line VLL (V) 132,000
Network Frequency (Hz) 50
CTsec = Rated Secondary Current of Current Transformer
Type of Curve Standard Inverse
(CT) in Ampere (A). Load Active Power (W) 175,000,000
41
2016 IEEE International Conference on Automatic Control and Intelligent Systems (I2CACIS), 22 October 2016, Shah Alam, Malaysia
current entering them. Figure 4 shows the block properties developed for the phase and earth subsystems.
V. SIMULATION RESULTS
This section discusses the results from the simulation. From
the model, all faults were initiated at 0.5 s. Two types of fault
which are single line to ground (SLG) fault and line to line
(LL) fault were taken to be studied. Faults were simulated at
different locations, FL and with different fault resistances, Rf to
vary the value of fault current. The results which were focused
are the operation times, top for all phases and earth detectors
and whether the fault current, If for each phase and earth is
higher than the pickup current, Ip or not. From the relay setting
parameters, Ip for each phase and earth were calculated as
follows:
i. Earth, Ip = 0.4 x 1200 = 480 A
ii. Phase, Ip = 1.2 x 1200 = 1440 A
Fig. 4. Block properties for phase and earth subsystems
42
2016 IEEE International Conference on Automatic Control and Intelligent Systems (I2CACIS), 22 October 2016, Shah Alam, Malaysia
Table III shows the results of fault current, operation time multiple of earth’s fault current over pickup current (2061/480
and trip signal for faults at different locations and different = 4.294) was higher than for phase (2604/1440 = 1.808). Thus,
fault resistances. Case 1 to 3 are for SLG faults (RG) while the breaker was isolated and tripped at 2.204 s (≈ 0.5 s +
case 4 to case 6 are for LL faults (RY). For case 1, it can be 1.692 s = 2.192 s). Figure 6 and 7 show the rms red phase
seen that both red phase and earth detected the fault due to low current and rms earth return current for case 1 respectively
fault resistance (1 Ω) and both fault currents exceeded the while Fig. 8 shows the trip signal which was sent to trip the
pickup currents. However, the operation time was faster for breaker after the operation time 1.692 s had been elapsed.
earth detector compared with phase detector because the
If = 2604 A
3000
2500
1
CURRENT (A)
2.204s
2000
0 OR 1
1500
0.5
1000
0 0
0 0.5 1 1.5 2 2.5 0 0.5 1 1.5 2 2.5
TIME (s) TIME (s)
Fig. 6. Rms red phase current for case 1 Fig. 8. Trip signal for case 1
NEUTRAL CURRENT (RMS) For case 2, the fault currents for both red phase and earth
4000 detectors were smaller compared with case 1. This was because
OPERATION TIME = 1.692s the fault location for case 2 (in km) was greater than case 1
3000
although the fault resistance value was the same, thus the
2000 impedance for the fault current to flow was higher. However,
both phase and earth fault currents still greater than each
CURRENT (A)
1000
If = 2061 A
pickup current and the breaker was tripped at 3.0041 s (≈
2.487 + 0.5 s = 2.987 s) by the trip signal sent by the earth fault
0
FAULT ISOLATION AT 2.204s
-1000 detector. For case 3, the fault location was still the same with
-2000
FAULT INCEPTION AT 0.5s
case 2. However, the fault resistance was increased to 40 Ω. It
can be seen that, fault currents for both phase and earth
-3000
detectors dropped significantly. Only the earth detector sensed
0 0.5 1
TIME (s)
1.5 2 2.5
the fault because the fault current was still greater than pickup
Fig. 7. Rms earth return current for case 1 current. The breaker was tripped at a very long time which was
23.4691 s (≈ 22.831 s + 0.5 s = 23.331 s).