User’s Manual

ACS550-CC Packaged Drive with Bypass


Supplement for ACS550-01/U1 Drives User’s Manual
ii ACS550-CC Packaged Drive with Bypass

ACS550 Drive Manuals


GENERAL MANUALS

ACS550-01/U1 Drives User's Manual (1…550 HP)


• Safety
• Installation
• Start-Up
• Embedded Fieldbus
• Fieldbus Adapter
• Diagnostics
• Maintenance
• Technical Data
ACS550-PC/PD Drive with Disconnect
Supplement to ACS550-01/U1User’s Manual
• Safety
• Installation
• Start-Up
• Technical Data
ACS550-CC Packaged Drive with Bypass
Supplement for ACS550-01/U1 User’s Manual
• Safety
• Installation
• Start-Up
• Maintenance
• Technical Data

© 2007 ABB Inc. All Rights Reserved.


ACS550-CC Packaged Drive with Bypass 1

Safety

WARNING! The ACS550 adjustable speed AC drive with Bypass should ONLY
be installed by a qualified electrician.
WARNING! Even when the motor is stopped, dangerous voltage is present at
the Power Circuit terminals U1, V1, W1 and U2, V2, W2 and, depending on the
frame size, UDC+ and UDC-, or BRK+ and BRK-.
WARNING! Dangerous voltage is present when input power is connected.
After disconnecting the supply, wait at least 5 minutes (to let the intermediate
circuit capacitors discharge) before removing the cover.
WARNING! Even when power is removed from the input terminals of the
ACS550, there may be dangerous voltage (from external sources) on the
terminals of the relay outputs.
WARNING! When the control terminals of two or more drive units are
connected in parallel, the auxiliary voltage for these control connections must
be taken from a single source which can either be one of the units or an
external supply.
WARNING! The ACS550 will start up automatically after an input voltage
interruption if the external run command is on.
WARNING! When the ACS550 with Bypass is connected to the line power, the
Motor Terminals T1, T2, and T3 are live even if the motor is not running. Do not
make any connections when the ACS550 with Bypass is connected to the line.
Disconnect and lock out power to the drive before servicing the drive. Failure
to disconnect power may cause serious injury or death.

Note! For more technical information, contact the factory or your local ABB sales
representative.

Safety
2 ACS550-CC Packaged Drive with Bypass

Use of Warnings and Notes


There are two types of safety instructions throughout this manual:
• Notes draw attention to a particular condition or fact, or give information on a
subject.
• Warnings caution you about conditions which can result in serious injury or death
and/or damage to the equipment. They also tell you how to avoid the danger. The
warning symbols are used as follows:
Dangerous voltage warning warns of high voltage which can cause physical
injury and/or damage to the equipment.
General warning warns about conditions, other than those caused by
electricity, which can result in physical injury and/or damage to the equipment.

Safety
ACS550-CC Packaged Drive with Bypass 3

Table of Contents

Safety
Use of Warnings and Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Table of Contents

Installation
Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Bypass Features and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Installation Flow Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Preparing for Installation (Supplement to ACS550-01/U1 User’s Manual) . . . . . 7
Preparing for Installation (Supplement to ACS550-01/U1 User’s Manual) . . . . . 8
Installing the Drive (Supplement to ACS550-01/U1 User’s Manual) . . . . . . . . . 9
Installing the Wiring (Supplement to ACS550-01/U1 User’s Manual) . . . . . . . 10

Maintenance
Maintenance Interval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Technical Data
Ratings (Supplement to ACS550-01/U1 User’s Manual) . . . . . . . . . . . . . . . . . 18
Input Power Connections (Supplement to ACS550-01/U1 User’s Manual) . . . 18
Motor Connections (Supplement to ACS550-01/U1 User’s Manual) . . . . . . . . 25
Motor Connection Specifications – R7/R8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Cooling – R7/R8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Dimensions and Weights (Supplement to ACS550-01/U1 User’s Manual) . . . 27
Applicable Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Index

Table of Contents
4 ACS550-CC Packaged Drive with Bypass

Installation

Study these installation instructions carefully before proceeding. Failure to observe


the warnings and instructions may cause a malfunction or personal hazard.

WARNING! Before you begin read "Safety" on page 1.

WARNING! When the ACS550 with Bypass is connected to the line power, the
Motor Terminals T1, T2, and T3 are live even if the motor is not running. Do not
make any connections when the ACS550 with Bypass is connected to the line.
Disconnect and lock out power to the drive before servicing the drive. Failure
to disconnect power may cause serious injury or death.

Application
This manual is a supplement to the ACS550-01/U1 User’s Manual and documents
Bypass configurations.

Bypass Features and Functions


The ACS550 with Bypass is an ACS550 AC adjustable frequency drive in an
integrated UL Type/NEMA 1, UL Type/NEMA 12, or UL Type/NEMA 3R package
with a bypass function configured entirely of standard industrial control components.
The ACS550 with Bypass provides:
• Main circuit breaker with door mounted control lever. The lever can be padlocked
in the OFF position (padlock not supplied).
• Electrically interlocked Bypass and drive output contactors
• Class 20 motor overload protection.
• ACS-CP-A drive control panel
– Cover mounted - UL Type/NEMA 1 and 12 enclosures
– Drive mounted - UL Type/NEMA 3R enclosures
• Bypass cover mounted control
– Drive-Off-Bypass selector switch
• Provisions for external control connections.
• Optional drive service switch (drive input disconnect), the functional equivalent of
a three-contactor bypass arrangement.

Installation
ACS550-CC Packaged Drive with Bypass 5

The following shows the front view of a typical ACS550 Bypass wall mount
configuration, and identifies the major components.

ACS-CP-A
l Control Panel

Operating handle for


Circuit Breaker

Cover Control

The following shows the front view of a typical ACS550 Bypass floor mount
configuration, and identifies the major components.

ACS-CP-A
Control Panel

Operating handle for


Circuit Breaker

Cover Control

Installation
6 ACS550-CC Packaged Drive with Bypass

The following is a typical power diagram.


Drive with Bypass
Drive Output
Circuit Breaker Contactor

3 Phase ACS550
Drive Motor
Input Power

Service Switch Bypass


(Optional) Contactor

Installation Flow Chart


The installation of Bypass Configurations for ACS550 drives follows the outline
below. The steps must be carried out in the order shown. At the right of each step
are references to the detailed information needed for the correct installation of the
unit.
Reference in ACS550-01/U1
Task User’s Manual “Installation” Reference in this Manual
section
PREPARE for installation “Preparing for Installation” Floor Mounted: “Lifting the Drive” on
Page 7
“Drive Identification” on Page 8
“Suitable Mounting Location” on page 8

PREPARE the Mounting “Prepare the Mounting Location” Prepare the Mounting Location - Floor
Location Mounted Enclosures” on page 9
“Dimensions and weights” on page 27

REMOVE the front cover “Remove Front Cover” --

MOUNT the drive “Mount the Drive” --

INSTALL wiring “Wiring Overview” and Installing the Wiring starting on page 10
“Install the Wiring”

CHECK installation “Check Installation” --

RE-INSTALL the cover “Re-install Cover” --

APPLY power “Apply Power” --

START-UP “Start-Up” --

Installation
ACS550-CC Packaged Drive with Bypass 7

Preparing for Installation

Lifting the Drive


Floor Mounting

Warning! Handle and ship floor mounted enclosures


only in the upright position. These units are not
designed to be laid on their backs.

1. Use a pallet truck to move the package/enclosure to the


installation site.
2. Remove any bolts that secure the cabinet to the shipping PC00005
pallet.

Warning! Use the lifting lugs/bars at the top of the unit


to lift floor mounted drives.
30o

3. Use a hoist to lift the drive. (Do not place drive in final
position until mounting site is prepared.

PC00003

Installation
8 ACS550-CC Packaged Drive with Bypass

Preparing for Installation

Drive Identification
To identify the type of device you are installing, refer to the type code number on the
device identification label.
• Wall mounting base drives – label attached on the side surface of the heat sink.
• Packaged drive with screw cover – label attached to outside surface on the left
side of the enclosure.
• Enclosure with hinged cover/door – label on inside surface of the cover/door.
Type Code Number
Use the following to interpret the type code found on the identification label.

ACS550-U1-015A-4 +…+…
AC Drive = 550 Product Series
Construction
U1 or U2 = Base Drive
CC = Bypass with circuit breaker
PC = Drive with circuit breaker
PD = Drive with disconnect switch

Output current rating (See ratings chart for details)


Voltage rating
2 = 208…240 VAC
4 = 380…480 VAC
6 = 500…600 VAC
Enclosure protection class
No specification = UL Type/NEMA 1
+B055 = UL Type/NEMA 12
+B058 = UL Type/NEMA 3R
Power options
+F267 = Service switch
Input/Output option modules
+L502 = Pulse encoder interface
+L511 = Relay output extension
+L512 = 115/230 V digital input interface
Fieldbus adaptors
+K451 – DeviceNet Adaptor
+K452 = LonWorks Adaptor
+K457 = CANopen Adaptor
+K462 = ControlNet Adaptor
+K466 = Ethernet Adaptor
+K467 = PROFINET IO Adaptor
Miscellaneous Options
+P919 = Bypass Cover Control Option

Suitable Mounting Location (Supplement to ACS550-01/U1 User’s Manual)


For selecting a suitable mounting location for Drive with Bypass units, refer to:
• Preparing for installation in the ACS550-01/U1 User’s Manual, and
• The Technical Data section of this manual for information on dimensions and
weights

Installation
ACS550-CC Packaged Drive with Bypass 9

Installing the Drive

Warning! Metal shavings or debris in the enclosure can damage electrical


equipment and create a hazardous condition. Where parts, such as conduit
plates require cutting or drilling, first remove the part. If that is not practical,
cover nearby electrical components to protect them from all shavings or
debris.

Prepare the Mounting Location – Floor Mounted Enclosures


The ACS550 should only be mounted where all of the requirements defined in
“Preparing for Installation” are met.

Installation
10 ACS550-CC Packaged Drive with Bypass

Installing the Wiring

WARNING!
• Metal shavings or debris in the enclosure can damage electrical equipment
and create a hazardous condition. Where parts, such as conduit plates
require cutting or drilling, first remove the part. If that is not practical, cover
nearby electrical components to protect them from all shavings or debris.
• Do not connect or disconnect input or output power wiring, or control
wires, when power is applied.
• Never connect line voltage to drive output Terminals T1, T2, and T3.
• Do not make any voltage tolerance tests (Hi Pot or Megger) on any part of
the unit. Disconnect motor wires before taking any measurements in the
motor or motor wires.
• Make sure that power factor correction capacitors are not connected
between the drive and the motor.

Wiring Requirements
Refer to the “Wiring Requirements” Section in the ACS550-01/U1 User’s Manual.
The requirements apply to all ACS550 drives. In particular:
• Use separate, metal conduit runs for the following different classes of wiring:
– Input power wiring.
– Motor wiring.
– Control/communications wiring.
• Properly and individually ground the drive, the motor and cable shields.

Installation
ACS550-CC Packaged Drive with Bypass 11

Wiring Overview
Connection Diagrams –
ACS550-CC units are configured for wiring access from the top or the bottom. The
following figures show the wiring connection points. Refer to the ACS550-01/U1
User's Manual for control connections to the drive.

Typical Wall Mount Typical Floor Mount

Installation
12 ACS550-CC Packaged Drive with Bypass

Install the Line Input Wiring


Line Input Connections – Bypass Configurations
Connect input power to the terminals of the circuit breaker. Connect the equipment
grounding conductor to the ground lug at the top of the enclosure. The figures below
show the connection points for typical configurations. Units are configured for wiring
access from the top or the bottom.
Typical Wall mount Typical Floor mount

WARNING! Check the motor and motor wiring insulation before connecting
the ACS550 to line power. Follow the procedure in the ACS550-01/U1 User’s
Manual. Before proceeding with the insulation resistance measurements,
check that the ACS550 is disconnected from incoming line power. Failure to
disconnect line power could result in death or serious injury.

Installation
ACS550-CC Packaged Drive with Bypass 13

Install the Motor Wiring


Motor Connections – Bypass Configurations
Connect the motor cables to the motor overload relay output terminals; see the
figures below. The motor grounding conductor can be connected to the ground lug
near the motor overload relay.
Typical Wall mount Typical Floor mount

O V E R LO A D
R E LA Y
OU T PU T
OVE RL OAD
T ER M IN A LS R E LA Y
O UT PUT
T E R M IN A L S

M OT OR
G R OU N D L U G M O TO R
GROUN D LUG

Install the Control Wiring (Supplement to ACS550-01/U1 User’s Manual)


Connect control wiring to the terminal block 1TB located on the back panel toward
the bottom of the enclosure and terminal block x1 inside the drive.

Control Wiring
The control wiring includes connections to an analog speed command signal and
start/stop relay contact for controlling the drive in the AUTO mode. There may also
be connections to external run enable interlock contacts and a connection from the
Motor Run contact to an external status indicating circuit.

Wiring Practices
The external control wiring must not be run in the same conduit or raceway with any
high power wiring. The external speed reference signal must be wired using a
shielded, twisted pair cable. The shield connection must be terminated at the ground
terminal provided (x1:3). The other end of the shield should be cut and taped back at
the signal source.

Installation
14 ACS550-CC Packaged Drive with Bypass

Terminal Block 1TB

Connection Points
Basic control connections are made to 1TB, which is a din-rail terminal block on the
back panel at the bottom of the enclosure. 1TB includes screw clamp terminals rated
for #22-10 AWG stranded or solid wire. Recommended tightening torque is 4.4 - 7.1
in-lbs.
Terminals 1TB:7 and 1TB:8 are 120 VAC control circuit terminals connected to 120
VAC control power supplied by the control circuit transformer provided. Terminals
1TB:9 and 1TB:10 are powered at 24VDC to accept an external contact closure to
start the drive. Terminals 1TB:13 and 1TB:14 are connected to un-powered relay
contacts provided for use with externally powered customer control circuits.

Additional Connections
The low voltage speed reference signal input, analog outputs, additional relay
outputs, and additional digital input connections are available on Terminal Block X1
inside the ACS550. Note that the Bypass control circuitry uses inputs and outputs
DI1,DI4 and R02. These inputs are not available for any other purpose and must not
be reconfigured. Output RO2 is wired to the terminal block, 1TB. AI1, AI2, DI3, DI5,
DI6, RO1, and R03 are available for use. Refer to the ACS550-01/U1 User’s Manual
for information about control connections on Terminal Block X1. When making
connections to Terminal Block X1, be careful not to disturb the factory installed wiring
between X1 and the Bypass control circuitry.
Analog Input
The external “Auto” speed reference is to be connected to ACS550 analog input
AI1. The analog input can accept a voltage signal (0 – 10 VDC) or a current signal (0
– 20 mA). Jumper J1, located on the Control Board in the ACS550, determines the
signal type. J1 can be set in either the voltage or current position according to the
type of external signal that will be connected. Refer to the ACS550-01/U1 User’s
Manual.

Run Enable Interlocks


Run Enable interlocks are normally closed un-powered contacts connected in series
between 1TB:7 and 1TB:8. When any of these contacts opens, the motor will stop,
whether in DRIVE or BYPASS. The unit is shipped with a jumper installed from
1TB:7 to 1TB:8. This jumper must be removed before connecting external contacts.

Installation
ACS550-CC Packaged Drive with Bypass 15

Auto Start Contact


To start the ACS550 by means of an external un-powered contact (maintained),
connect the contact to 1TB:9 and 1TB:10. Closing this contact will start the motor
when the drive is in the AUTO mode.

Relay Contact Output


A “Motor Running” relay contact output is provided at terminals 1TB:13 and 1TB:14
for external indication of the motor status. The output consists of a normally open
auxiliary contact on the bypass contactor and a normally open “Drive Running”
contact from the ACS550. The two contacts are connected in parallel so that a
contact closure is provided whenever the motor is running.
Refer to “Control Connections” in the ACS550-01/U1 User’s Manual Technical Data
where relay contacts are used to control inductive loads.

Installation
16 ACS550-CC Packaged Drive with Bypass

Motor Overload Relay


The ACS550 with Bypass includes a motor overload relay to provide thermal motor
protection. It is connected in both drive and bypass modes of operation. For motor
full load currents up to 80 amperes, the Motor Overload Relay is an adjustable trip,
bimetallic overload relay with a class 20 trip characteristic. Above 80 amperes, the
Motor Overload Relay is an adjustable trip, electronic overload relay with selectable
class 10, 20 or 30 trip characteristic.

Suggested Settings
Current
Set the current adjustment to the value of the full load current shown on the motor
nameplate.

Auto/Man
It is recommended the overload relay be set to the Manual Reset mode of operation.
In the Auto Reset mode, the Overload Relay contacts re-close automatically when
the bi-metals of bi-metallic versions cool or when the timer function within the
electronic versions times out. If power is applied and the switches and contacts in
the control circuit are commanding the motor to run, the motor will start as soon as
the overload relay resets.

Class
The class 20 setting on the electronic overload relays would be the appropriate
choice for the majority of the motors used in North America.

Resetting the Overload Relay


In the event an overload relay set in the Manual Reset mode trips, it is necessary to
open the door of the enclosure and push the Reset button on the front of the
overload relay to reset it.

WARNING: If power is applied and the switches and contacts in the control
circuit are commanding the motor to run, the motor will start as soon as the
overload relay resets. Use caution when manually resetting the overload relay
to make sure it is safe to start the motor.

Installation
ACS550-CC/CF Packaged Drive with Bypass 17

Maintenance

Maintenance Interval
If installed in an appropriate environment, the drive requires very little maintenance.
The table lists the routine maintenance intervals recommended by ABB. The
information shown below is supplemental and in addition to that shown in the
ACS550-01/U1 User’s Manual.

Maintenance Application Interval

Check/replace enclosure inlet air UL Type/NEMA 12 and 3R enclosures Check every 3 months. Replace as
filter needed
Check/replace enclosure exhaust air UL Type/NEMA 12 and 3R enclosures Check every 6 months. Replace as
filter needed.
Replace enclosure vent fan(s). UL Type/NEMA 12 and 3R enclosures Every three years

Replace enclosure air circulation fan Frames R4 through R6 in UL Type/ Every three years
NEMA 1 enclosures

Maintenance
18 ACS550-CC Packaged Drive with Bypass

Technical Data

Ratings

Note! The ratings listed below are additions to the ratings listed in the ACS550-01/
U1 User’s Manual.

Ratings, 380…480 Volt Drives


Type Code Valid up to 40°C (104 °F)
Normal Use Heavy-Duty Use
Frame Size
ACS550-Cx-see I2N PN I2hd Phd
below A HP A HP
-245A-4 245 200 192 150 R7
-316A-4 316 250 240 200 R8
-368A-4 368 300 302 250 R8
-414A-4 414 350 368 300 R8
-486A-4 486 400 414 350 R8

Input Power Connections


Branch Circuit Protection
Input power is connected to the ACS550 with Bypass through a circuit breaker that
provides the branch circuit short circuit and ground fault protection for the motor
operating in the bypass mode.

Fuses
Drive input fuses are provided to disconnect the drive from power in the event that a
component fails in the drive’s input power circuitry. The drive’s electronic protection
circuitry is designed to clear drive output short circuits and ground faults without
blowing the drive input fuses. Drive input fuses are shown in the following tables.

NOTE! Although fuses listed are similar in functional characteristics to fuses listed in
the ACS550-01/U1 User’s Manual, physical characteristics may differ. Fuses from
other manufacturers can be used if they meet the functional characteristics of those
shown in the tables.

Technical Data
ACS550-CC Packaged Drive with Bypass 19

208…240 Volt Fuses


208… 240 Volt Drive Input Fuse Ratings
Frame
Size Amps Bussmann
HP Identification
(600V) Type
1 ACS550-CC-04A6-2 R1 15 KTK-R-15
1.5 ACS550-CC-06A6-2 R1 15 KTK-R-15
2 ACS550-CC-07A5-2 R1 15 KTK-R-15
3 ACS550-CC-012A-2 R1 15 KTK-R-15
5 ACS550-CC-017A-2 R1 30 KTK-R-30
7.5 ACS550-CC-024A-2 R2 30 KTK-R-30
10 ACS550-CC-031A-2 R2 50 JJS-50
15 ACS550-CC-046A-2 R3 80 JJS-80
20 ACS550-CC-059A-2 R3 80 JJS-80
25 ACS550-CC-075A-2 R4 100 JJS-100
30 ACS550-CC-088A-2 R4 110 JJS-110
40 ACS550-CC-114A-2 R4 150 JJS-150
50 ACS550-CC-143A-2 R6 200 JJS-200
60 ACS550-CC-178A-2 R6 250 JJS-250
75 ACS550-CC-221A-2 R6 300 JJS-300
100 ACS550-CC-248A-2 R6 350 JJS-350

Technical Data
20 ACS550-CC Packaged Drive with Bypass

380…480 Volt Fuses


380… 480 Volt Drive Input Fuse Ratings
Frame
Size Amps Bussmann
HP Identification
(600V) Type
1/1.5 ACS550-CC-03A3-4 R1 15 KTK-R-15
2 ACS550-CC-04A1-4 R1 15 KTK-R-15
3 ACS550-CC-06A9-4 R1 15 KTK-R-15
5 ACS550-CC-08A8-4 R1 15 KTK-R-15
7.5 ACS550-CC-012A-4 R1 15 KTK-R-15
10 ACS550-CC-015A-4 R2 30 KTK-R-30
15 ACS550-CC-023A-4 R2 30 KTK-R-30
20 ACS550-CC-031A-4 R3 50 JJS-50
25 ACS550-CC-038A-4 R3 50 JJS-50
30 ACS550-CC-045A-4 R3 100 JJS-100
30 ACS550-CC-044A-4 R4 100 JJS-100
40 ACS550-CC-059A-4 R4 100 JJS-100
50 ACS550-CC-072A-4 R4 100 JJS-100
60 ACS550-CC-078A-4 R4 100 JJS-100
75 ACS550-CC-097A-4 R4 125 JJS-125
75 ACS550-CC-096A-4 R5 125 JJS-125
100 ACS550-CC-125A-4 R5 175 JJS-175
100 ACS550-CC-124A-4 R6 175 JJS-175
125 ACS550-CC-157A-4 R6 200 JJS-200
150 ACS550-CC-180A-4 R6 250 JJS-250
200 ACS550-CC-246A-4 R6 400 JJS-400
200 ACS550-CC-245A-4 R7 400 JJS-400
250 ACS550-CC-316A-4 R8 400 JJS-400
300 ACS550-CC-368A-4 R8 400 JJS-400
350 ACS550-CC-414A-4 R8 600 JJS-600
400 ACS550-CC-486A-4 R8 600 JJS-600

Technical Data
ACS550-CC Packaged Drive with Bypass 21

Fuses, 500…600 Volt, Fuses


500…600 Volt Drive Input Fuse Ratings
Frame
Size Amps Bussmann
HP Identification
(600V) Type
2 ACS550-CC-02A7-6 R2 15 KTK-R-15
3 ACS550-CC-03A9-6 R2 15 KTK-R-15
5 ACS550-CC-06A1-6 R2 15 KTK-R-15
7.5 ACS550-CC-09A0-6 R2 15 KTK-R-15
10 ACS550-CC-011A-6 R2 30 KTK-R-30
15 ACS550-CC-017A-6 R2 30 KTK-R-30
20 ACS550-CC-022A-6 R3 50 JJS-50
25 ACS550-CC-027A-6 R3 50 JJS-50
30 ACS550-CC-032A-6 R4 100 JJS-100
40 ACS550-CC-041A-6 R4 100 JJS-100
50 ACS550-CC-052A-6 R4 100 JJS-100
60 ACS550-CC-062A-6 R4 100 JJS-100
75 ACS550-CC-077A-6 R6 100 JJS-100
100 ACS550-CC-099A-6 R6 150 JJS-150
125 ACS550-CC-125A-6 R6 175 JJS-175
150 ACS550-CC-144A-6 R6 200 JJS-200

Technical Data
22 ACS550-CC Packaged Drive with Bypass

Power Connection Terminals


The following tables show maximum wire size and required tightening torque for
incoming power and motor terminals, and grounding terminal lug information.
208…240 Volt, Terminals
208…240 Volt, Power Connection Terminal Data
208…240 Volt Base Power Wiring Size
Drive
Frame Circuit Overload Ground
HP Type Code
Size Breaker Relay Lugs

1 ACS550-CC-04A6-2 R1
1.5 ACS550-CC-06A6-2 R1
#10
2 ACS550-CC-07A5-2 R1 #10
35 in-lbs
3 ACS550-CC-012A-2 R1 13 in-lbs
5 ACS550-CC-017A-2 R1 #2
7.5 ACS550-CC-024A-2 R2 15 in-lbs
#6
#8 (#14 - #12)
10 ACS550-CC-031A-2 R2 45 in-lbs
21 in-lbs 40 in-lbs
(#10 - #6)
15 ACS550-CC-046A-2 R3 #3 #3
50 in-lbs
20 ACS550-CC-059A-2 R3 50 in-lbs 36 in-lbs
(#4 - #2)
#1 #2
25 ACS550-CC-075A-2 R4
50 in-lbs 36 in-lbs
30 ACS550-CC-088A-2 R4 #2/0
#2/0
300 in-lbs
40 ACS550-CC-114A-2 R4 274 in-lbs

50 ACS550-CC-143A-2 R6 #2/0
250 MCM 275 in-lbs
300 MCM
300 in-lbs (#6 - #2)
60 ACS550-CC-178A-2 R6 274 in-lbs
375 in-lbs
(#1 - #2/0)
75 ACS550-CC-221A-2 R6 2 x 250 MCM 2 x 250 MCM 350 MCM
100 ACS550-CC-248A-2 R6 275 in-lbs 375 in-lbs 100 in-lbs

Technical Data
ACS550-CC Packaged Drive with Bypass 23

380…480 Volt, Terminals


380…480 Volt, Power Connection Terminal Data
380…480 Volt Base Power Wiring Size
Drive
Frame Circuit Overload
HP Type Code Ground Lugs
Size Breaker Relay

1/1.5 ACS550-CC-03A3-4 R1
2 ACS550-CC-04A1-4 R1 #10
3 ACS550-CC-06A9-4 R1 35 in-lbs
#10
5 ACS550-CC-08A8-4 R1
13 in-lbs
7.5 ACS550-CC-012A-4 R1
10 ACS550-CC-015A-4 R2 #6
15 ACS550-CC-023A-4 R2 45 in-lbs
#2
#8 15 in-lbs
20 ACS550-CC-031A-4 R3 #3 21 in-lbs (#14 - #12)
50 in-lbs
25 ACS550-CC-038A-4 R3 #3 40 in-lbs
30 ACS550-CC-045A-4 R3 36 in-lbs (#10 - #6)
50 in-lbs
30 ACS550-CC-044A-4 R4
(#4 - #2)
40 ACS550-CC-059A-4 R4
#1 #2
50 ACS550-CC-072A-4 R4
50 in-lbs 36 in-lbs
60 ACS550-CC-078A-4 R4
75 ACS550-CC-097A-4 R4
75 ACS550-CC-096A-4 R5
100 ACS550-CC-125A-4 R5
100 ACS550-CC-124A-4 R6 300 MCM 250 MCM
125 ACS550-CC-157A-4 R6 274 in-lbs 300 in-lbs #2/0
275 in-lbs
(#6 - #2)
150 ACS550-CC-180A-4 R6
375 in-lbs
(#1 - #2/0)
200 ACS550-CC-246A-4 R6
2 x 250 MCM 2 x 250 MCM
200 ACS550-CC-245A-4 R7
275 in-lbs 375 in-lbs
250 ACS550-CC-316A-4 R8 350MCM
300 ACS550-CC-368A-4 R8 100 in-lbs
2 x 500 MCM 2 x 500MCM
350 ACS550-CC-414A-4 R8
275 in-lbs 375 in-lbs
400 ACS550-CC-486A-4 R8

Technical Data
24 ACS550-CC Packaged Drive with Bypass

500…600 Volt, Terminals


500…600 Volt, Power Connection Terminal Data
500…600 Volt Base Power Wiring Size
Drive
Frame Circuit Overload Ground
HP Type Code
Size Breaker Relay Lugs

2 ACS550-CC-02A7-6 R2
3 ACS550-CC-03A9-6 R2
5 ACS550-CC-06A1-6 R2 #6
#10
7.5 ACS550-CC-09A0-6 R2 62 in-lbs
13 in-lbs #2
10 ACS550-CC-011A-6 R2
15 in-lbs
15 ACS550-CC-017A-6 R2 (#14 - #12)
20 ACS550-CC-022A-6 R3 #3 40 in-lbs
25 ACS550-CC-027A-6 R3 62 in-lbs #8 (#10 - #6)
21 in-lbs 50 in-lbs
30 ACS550-CC-032A-6 R4
#1 (#4 - #2)
40 ACS550-CC-041A-6 R4
62 in-lbs
50 ACS550-CC-052A-6 R4 #2
60 ACS550-CC-062A-6 R4 36 in-lbs
75 ACS550-CC-077A-6 R6
100 ACS550-CC-099A-6 R6
125 ACS550-CC-125A-6 R6 300 MCM #2/0
250 MCM 275 in-lbs
200 in-lbs
300 in-lbs (#6 - #2)
150 ACS550-CC-144A-6 R6
375 in-lbs
(#1 - #2/0)

Technical Data
ACS550-CC Packaged Drive with Bypass 25

Motor Connections

Motor Terminals
See preceding “Power Connection Terminal Data” tables.

Bypass Contactors
The bypass circuit in the ACS550 Bypass includes two contactors. One contactor is
the bypass contactor (2M) that can be used to connect the motor directly to the
incoming power line in the event that the ACS550 is out of service. The other
contactor is the ACS550 output contactor (1M) that disconnects the ACS550 from
the motor when the motor is operating in the Bypass mode. The drive output
contactor and the bypass contactor are electrically interlocked to prevent “back
feeding,” applying line voltage to the ACS550 output terminals.

Motor Overload Protection


The ACS550 with Bypass includes a motor overload relay to provide thermal motor
protection. It is connected in both drive and bypass modes of operation. For motor
full load currents through 80 amperes, the Motor Overload Relay is an adjustable
trip, bimetallic overload relay with a class 20 trip characteristic. Above 80 amperes,
the Motor Overload Relay is an adjustable trip, electronic overload relay with
selectable class 10, 20 or 30 trip characteristic. The class 20 setting on the
electronic overload relays is the appropriate choice for the majority of the motors
used in North America.

WARNING: If power is applied and the switches and contacts in the control
circuit are commanding the motor to run, the motor will start as soon as the
overload relay is reset.
Use caution when resetting the overload relay to make sure it is safe to start
the motor.

Technical Data
26 ACS550-CC Packaged Drive with Bypass

Motor Connection Specifications – R7/R8


Motor Connection Specifications
Max. Motor Cable Length*
Maximum Motor Cable Frame Size
fsw = 1 or 4 kHz fsw = 8 kHz or 12 kHz
Length
R7…R8 300 m 980 ft Does not apply
* Warning! Using a motor cable longer than specified in the
chart above may cause permanent damage to the drive.

Cooling – R7/R8
Cooling Specifications
Method Internal fan, flow direction from bottom to top.
Requirement Allow 4 to 6 inches at the sides of enclosure for venting.

Air Flow, 380…480 Volt Drives – R7/R8


The following table lists heat loss and air flow data for 380…480 Volt drives.
Drive Heat Loss Air Flow
ACS550-xx- Frame Size W BTU/Hr m3/h ft3/min
-245A-4 R7 3850 13000 300 540
-316A-4 R8 5300 18000 700 1220
-368A-4 R8 6850 23000 700 1220
-414A-4 R8 7000 24000 700 1220
-486A-4 R8 7600 26000 700 1220

Technical Data
ACS550-CC Packaged Drive with Bypass 27

Dimensions and Weights

Dimensional References
The following tables contain dimensional references that will be needed to identify
the dimensional information applying to a given device type code.

208/230V Bypass Packages


UL Type UL Type UL Type
(NEMA) 1 (NEMA) 12 (NEMA) 3R
HP Type Code Amp Frame Dim. Ref. Page 29 Dim. Ref. Page 30 Dim. Ref. Page 31
1 ACS550-CC-04A6-2 4.6 R1 CX1-1 CX12-1 CX3R-1
1.5 ACS550-CC-06A6-2 6.6 R1 CX1-1 CX12-1 CX3R-1
2 ACS550-CC-07A5-2 7.5 R1 CX1-1 CX12-1 CX3R-1
3 ACS550-CC-012A-2 12 R1 CX1-1 CX12-1 CX3R-1
5 ACS550-CC-017A-2 17 R1 CX1-1 CX12-1 CX3R-1
7.5 ACS550-CC-024A-2 24 R2 CX1-3 CX12-3 CX3R-3
10 ACS550-CC-031A-2 31 R2 CX1-3 Cx12-3 CX3R-3
15 ACS550-CC-046A-2 46 R3 CX1-4 CX12-5 CX3R-5
20 ACS550-CC-059A-2 59 R3 CX1-4 CX12-5 CX3R-5
25 ACS550-CC-075A-2 75 R4 CX1-6 CX12-6 CX3R-6
30 ACS550-CC-088A-2 88 R4 CX1-9 CX12-7 CX3R-7
40 ACS550-CC-114A-2 114 R4 CX1-9 CX12-7 CX3R-7
50 ACS550-CC-143A-2 143 R6 CX1-10 CX12-10 CX3R-10
60 ACS550-CC-178A-2 178 R6 CX1-10 CX12-10 CX3R-10
75 ACS550-CC-221A-2 221 R6 CX1-11 CX12-10 CX3R-10
100 ACS550-CC-248A-2 248 R6 CX1-11 CX12-10 CX3R-10

Technical Data
28 ACS550-CC Packaged Drive with Bypass

480V Bypass Packages

UL Type UL Type UL Type


(NEMA) 1 (NEMA) 12 (NEMA) 3R
HP Type Coxe Amp Frame Dim. Ref. Page 29 Dim. Ref. Page 30 Dim. Ref. Page 31
1 ACS550-CC-03A3-4 3.3 R1 CX1-1 CX12-1 CX3R-1
1.5 ACS550-CC-03A3-4 3.3 R1 CX1-1 CX12-1 CX3R-1
2 ACS550-CC-04A1-4 4.1 R1 CX1-1 CX12-1 CX3R-1
3 ACS550-CC-06A9-4 6.9 R1 CX1-1 CX12-1 CX3R-1
5 ACS550-CC-08A8-4 8.8 R1 CX1-1 CX12-1 CX3R-1
7.5 ACS550-CC-012A-4 12 R1 CX1-1 CX12-1 CX3R-1
10 ACS550-CC-015A-4 15 R2 CX1-2 CX12-2 CX3R-2
15 ACS550-CC-023A-4 23 R2 CX1-2 CX12-2 CX3R-2
20 ACS550-CC-031A-4 31 R3 CX1-4 CX12-4 CX3R-4
25 ACS550-CC-038A-4 38 R3 CX1-4 CX12-4 CX3R-4
30 ACS550-CC-045A-4 44 R3 CX1-4 CX12-5 CX3R-5
40 ACS550-CC-059A-4 59 R4 CX1-5 CX12-6 CX3R-6
50 ACS550-CC-072A-4 72 R4 CX1-5 CX12-6 CX3R-6
60 ACS550-CC-078A-4 78 R4 CX1-5 CX12-6 CX3R-6
75 ACS550-CC-097A-4 96 R4 CX1-6 CX12-7 CX3R-7
100 ACS550-CC-125A-4 124 R5 CX1-7 CX12-8 CX3R-8
125 ACS550-CC-157A-4 157 R6 CX1-10 CX12-9 CX3R-9
150 ACS550-CC-180A-4 180 R6 CX1-10 CX12-9 CX3R-9
200 ACS550-CC-246A-4 245 R6 CX1-11 CX12-10 CX3R-10
250 ACS550-CC-316A-4 316 R8 CX1-12 CX12-11
300 ACS550-CC-368A-4 368 R8 CX1-13 CX12-12
Consult Factory
350 ACS550-CC-414A-4 414 R8 CX1-13 CX12-12
400 ACS550-CC-486A-4 486 R8 CX1-13 CX12-12

600V Bypass Packages

UL Type UL Type UL Type


(NEMA) 1 (NEMA) 12 (NEMA) 3R
HP Type Code Amp Frame Dim. Ref. Page 29 Dim. Ref. Page 30 Dim. Ref. Page 31
2 ACS550-CC-02A7-6 2.7 R2 CX1-2 CX12-2 CX3R-2
3 ACS550-CC-03A9-6 3.9 R2 CX1-2 CX12-2 CX3R-2
5 ACS550-CC-06A1-6 6.1 R2 CX1-2 CX12-2 CX3R-2
7.5 ACS550-CC-09A0-6 9 R2 CX1-2 CX12-2 CX3R-2
10 ACS550-CC-011A-6 11 R2 CX1-2 CX12-2 CX3R-2
15 ACS550-CC-017A-6 17 R2 CX1-2 CX12-2 CX3R-2
20 ACS550-CC-022A-6 22 R3 CX1-4 CX12-4 CX3R-4
25 ACS550-CC-027A-6 27 R3 CX1-4 CX12-4 CX3R-4
30 ACS550-CC-032A-6 32 R4 CX1-5 CX12-6 CX3R-6
40 ACS550-CC-041A-6 41 R4 CX1-5 CX12-6 CX3R-6
50 ACS550-CC-052A-6 52 R4 CX1-5 CX12-6 CX3R-6
60 ACS550-CC-062A-6 62 R4 CX1-5 CX12-6 CX3R-6
75 ACS550-CC-077A-6 77 R6 CX1-8 CX12-9 CX3R-9
100 ACS550-CC-099A-6 99 R6 CX1-8 CX12-9 CX3R-9
125 ACS550-CC-125A-6 125 R6 CX1-10 CX12-9 CX3R-9
150 ACS550-CC-144A-6 144 R6 CX1-10 CX12-9 CX3R-9

Technical Data
ACS550-CC Packaged Drive with Bypass 29

Dimensions: ACS550-CC NEMA 1 R1 through R8 Frame Size

W
D

H
H1

W1

CX1-1 to CX1-11 Wall Mounted CX1-12 to CX1-13 Free Standing

H1 W1 Height (H) Width (W) Depth (D) Weight


CX1-1 920 208 948 348 349 35
[36.2] [8.2] [37.3] [13.7] [13.7] [76]
CX1-2 920 208 948 348 349 37
[36.2] [8.2] [37.3] [13.7] [13.7] [82]
CX1-3 1352 254 1380 414 371 49
[53.2] [10] [54.3] [16.3] [14.6] [107]
CX1-4 1352 254 1380 414 371 61
[53.2] [10] [54.3] [16.3] [14.6] [135]
CX1-5 1352 254 1380 414 371 76
[53.2] [10] [54.3] [16.3] [14.6] [168]
CX1-6 1568 330 1596 491 489 90
[61.7] [13] [62.8] [19.3] [19.2] [198]
CX1-7 1568 330 1596 491 489 119
[61.7] [13] [62.8] [19.3] [19.2] [262]
CX1-8 1568 330 1596 491 489 154
[61.7] [13] [62.8] [19.3] [19.2] [339]
CX1-9 Free Free 1883 889 527 126
Standing Standing [74.1] [35] [20.7] [277]
CX1-10 Free Free 1883 889 527 190
Standing Standing [74.1] [35] [20.7] [418]
CX1-11 Free Free 1829 914 584 247
Standing Standing [72] [36] [23] [543]
CX1-12 Free Free 2134 914 847 579
Standing Standing [84] [36] [33.4] [1273]
CX1-13 Free Free 2134 1524 847 662
Standing Standing [84] [60] [33.4] [1456]
CX1-9 through CX1-11 are a wall mount configuration with 12 inch high mounting feet.
Feet are removable.
Allow 4-6 inches between enclosures for venting.

Technical Data
30 ACS550-CC Packaged Drive with Bypass

Dimensions: ACS550-CC NEMA 12 R1 through R8 Frame Size

D W

H
H1

W1

CX12-1 to CX12-10 Wall


H1 Mounted
W1 CX12-11
Height (H) Width (W) to CX12-12
Depth (D) Free Standing
Weight
CX12-1 648 419 686 457 369 36
[25.5] [16.5] [27] [18] [14.5] [78]
CX12-2 648 419 686 457 369 38
[25.5] [16.5] [27] [18] [14.5] [84]
CX12-3 800 572 838 610 369 51
[31.5] [22.5] [33] [24] [14.3] [113]
CX12-4 800 572 838 610 369 64
[31.5] [22.5] [33] [24] [14.3] [141]
CX12-5 953 724 991 762 369 78
[37.5] [28.5] [39] [30] [14.3] [172]
CX12-6 953 724 991 762 369 93
[37.5] [28.5] [39] [30] [14.3] [205]
CX12-7 1257 724 1304 914 572 118
[49.5] [28.5] [51.4] [36] [22.5] [259]
CX12-8 1257 724 1304 914 572 147
[49.5] [28.5] [51.4] [36] [22.5] [323]
CX12-9 1257 724 1304 914 572 182
[49.5] [28.5] [51.4] [36] [22.5] [400]
CX12-10 Free Free 1829 914 584 247
Standing Standing [72] [36] [23] [543]
CX12-11 Free Free 2134 914 847 579
Standing Standing [84] [36] [33.4] [1273]
CX12-12 Free Free 2134 1524 847 662
Standing Standing [84] [60] [33.4] [1456]
CX3R-10 is a wall mount configuration with 12 inch high mounting feet.
Feet are removable.
CX3R-12 enclosure is double door construction.
Allow 4-6 inches between enclosures for venting.

Technical Data
ACS550-CC Packaged Drive with Bypass 31

Dimensions: ACS550-CC NEMA 3R R1 through R6 Frame Size

W1

CX3R-1 to CX3R-9 Wall Mounted CX3R-10 Free Standing

Height Width Width Width Depth


H1 W1 (H) (W) (W2) (W3) (D) Weight
CX3R-1 572 419 610 457 89 N/A 359 37
[22.5] [16.5] [24] [18] [3.5] N/A [14.1] [82]
CX3R-2 572 419 610 457 89 N/A 359 40
[22.5] [16.5] [24] [18] [3.5] N/A [14.1] [88]
CX3R-3 724 572 762 610 89 N/A 359 53
[28.5] [22.5] [30] [24] [3.5] N/A [14.1] [117]
CX3R-4 724 572 762 610 89 N/A 359 66
[28.5] [22.5] [30] [24] [3.5] N/A [14.1] [145]
CX3R-5 876 725 914 762 89 89 359 82
[34.5] [28.5] [36] [30] [3.5] [3.5] [14.1] [180]
CX3R-6 876 725 914 762 89 89 359 97
[34.5] [28.5] [36] [30] [3.5] [3.5] [14.1] [213]
CX3R-7 1181 876 1219 914 89 89 562 121
[46.5] [34.5] [48] [36] [3.5] [3.5] [22.1] [267]
CX3R-8 1181 876 1219 914 89 89 562 151
[46.5] [34.5] [48] [36] [3.5] [3.5] [22.1] [331]
CX3R-9 1181 876 1219 914 89 89 562 186
[46.5] [34.5] [48] [36] [3.5] [3.5] [22.1] [408]
CX3R-10 Free Free 1829 914 89 89 584 251
Standing Standing [72] [36] [3.5] [3.5] [23] [553]

CX3R-10 is a wall mount configuration with 12 inch high mounting feet.


Feet are removable.

Technical Data
32 ACS550-CC Packaged Drive with Bypass

Applicable Standards
Drive compliance with the following standards is identified by the standards “marks”
on the type code label.
Mark Applicable Standards
UL 508C and UL Standard for Safety, Power Conversion Equipment, and
C22.2 No. 14 CSA Standard for Industrial Control Equipment

UL 508A UL Standard for Safety, Industrial Control Panels

C22.2 No. 14 CSA Standard for Industrial Control Equipment

Compliance is valid with the following provisions:


• The motor and control cables are chosen as specified in this manual.
• The installation rules of this manual are followed.

Technical Data
ACS550-CC Packaged Drive with Bypass 33

Index

Numerics F
208/230V bypass packages . . . . . . . . . . . . . . . . 27 Floor mount
480V bypass packages . . . . . . . . . . . . . . . . . . . . 28 installing the line input wiring . . . . . . . . . . . . . 12
600V bypass packages . . . . . . . . . . . . . . . . . . . . 28 typical configuration, front view . . . . . . . . . . . . 5
wiring overview. . . . . . . . . . . . . . . . . . . . . . . . 11
A Fuses, drive
208 to 240 volt drives . . . . . . . . . . . . . . . . . . . 22
Air flow. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 380 to 480 volt drives . . . . . . . . . . . . . . . . . . . 23
Analog inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 500 to 600 volt drives . . . . . . . . . . . . . . . . . . . 20
Auto start contact. . . . . . . . . . . . . . . . . . . . . . . . . 15
Automatic start-up warning . . . . . . . . . . . . . . . . . . 1 G
Auto/Man setting . . . . . . . . . . . . . . . . . . . . . . . . . 16
Grounding requirements . . . . . . . . . . . . . . . . . . . . 10
Auto/Man setting, overload relay . . . . . . . . . . . . . 16
H
B
Heat loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Branch circuit protection . . . . . . . . . . . . . . . . . . . 19
Bypass I
contactors, description . . . . . . . . . . . . . . . . . 25
diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Identifying the drive type . . . . . . . . . . . . . . . . . . . . . 8
features and functions. . . . . . . . . . . . . . . . . . . 4 Input power
branch circuit protection . . . . . . . . . . . . . . . . . 19
C cable/wire requirements . . . . . . . . . . . . . . . . . 18
Installation
Cable requirements, input power. . . . . . . . . . . . . 18 control wiring . . . . . . . . . . . . . . . . . . . . . . . . . 13
Class setting, overload relay . . . . . . . . . . . . . . . . 16 flow chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Connection points . . . . . . . . . . . . . . . . . . . . . . . . 14 line input wiring. . . . . . . . . . . . . . . . . . . . . . . . 12
Contactor bypass, description . . . . . . . . . . . . . . . 25 motor wiring . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Contacts, auto start . . . . . . . . . . . . . . . . . . . . . . . 15 preparation . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 8
Control wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 wiring requirements . . . . . . . . . . . . . . . . . . . . 10
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Installer warning . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Current settings . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Interlocks, run enable . . . . . . . . . . . . . . . . . . . . . . 15

D L
Dangerous voltage warning. . . . . . . . . . . . . . . . . . 1 Line connection warning . . . . . . . . . . . . . . . . . . . . . 1
Dimensional references. . . . . . . . . . . . . . . . . 27–28 Location, mounting . . . . . . . . . . . . . . . . . . . . . . . . . 8
208/230V bypass packages . . . . . . . . . . . . . 27
480V bypass packages . . . . . . . . . . . . . . . . . 28 M
600V bypass packages . . . . . . . . . . . . . . . . . 28
Maintenance schedule . . . . . . . . . . . . . . . . . . . . . 17
Dimensions
NEMA 1 R1-R8 frame size . . . . . . . . . . . . . . 27 Manuals for ACS550 drive . . . . . . . . . . . . . . . . . . . ii
NEMA 12 R1-R8 frame size . . . . . . . . . . . . . 27 Metal conduit runs. . . . . . . . . . . . . . . . . . . . . . . . . 10
NEMA 3R R1- R6 frame size . . . . . . . . . . . . 27 Motor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Drive cable, maximum length . . . . . . . . . . . . . . . . . 26
identification . . . . . . . . . . . . . . . . . . . . . . . . . . 8 connection specifications . . . . . . . . . . . . . . . . 26
proper lifting . . . . . . . . . . . . . . . . . . . . . . . . . . 7 connections . . . . . . . . . . . . . . . . . . . . . . . . . . 25
standards, compliance to . . . . . . . . . . . . . . . 32 protection, overload relay . . . . . . . . . . . . . . . . 25
running, relay contact output . . . . . . . . . . . . . 15
wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
E Mounting locations . . . . . . . . . . . . . . . . . . . . . . . . . 8
Enclosure protection class code . . . . . . . . . . . . . . 8 Mounting locations, preparing. . . . . . . . . . . . . . . . . 9

Index
34 ACS550-CC Packaged Drive with Bypass

N T
NEMA 1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . 18–32
code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Terminal block 1TB. . . . . . . . . . . . . . . . . . . . . . . . 14
R1-R8 frame size dimensions. . . . . . . . . . . . 27 Terminals, power, wire sizes . . . . . . . . . . . . . . . . 22
NEMA 12
code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 W
R1-R8 frame size dimensions. . . . . . . . . . . . 27
NEMA 3R Wall mount
code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 installing the line input wiring . . . . . . . . . . . . . 12
installing the motor wiring. . . . . . . . . . . . . . . . 13
R1- R6 frame size dimensions . . . . . . . . . . . 27
typical configuration, front view . . . . . . . . . . . . 5
wiring overview. . . . . . . . . . . . . . . . . . . . . . . . 11
O Warning
Overload relay automatic start-up . . . . . . . . . . . . . . . . . . . . . . 1
motor protection . . . . . . . . . . . . . . . . . . . . . . 25 dangerous voltages . . . . . . . . . . . . . . . . . . . . . 1
resetting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 parallel control connections . . . . . . . . . . . . . . . 1
qualified installer . . . . . . . . . . . . . . . . . . . . . . . 1
P Wire requirements, input power . . . . . . . . . . . . . . 18
Parallel control connections warning. . . . . . . . . . . 1 Wiring
Power connection terminals . . . . . . . . . . . . . . . . 22 conduits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Protection control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
branch circuit . . . . . . . . . . . . . . . . . . . . . . . . 19 line input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
motor overload . . . . . . . . . . . . . . . . . . . . . . . 25 motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
requirements . . . . . . . . . . . . . . . . . . . . . . . . . 10
shielded cable . . . . . . . . . . . . . . . . . . . . . . . . 13
Q wall and floor mount overviews . . . . . . . . . . . 11
Qualified installer requirement. . . . . . . . . . . . . . . . 1

R
R7/R8
cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
motor connection specifications . . . . . . . . . . 26
Relay
motor running contact output . . . . . . . . . . . . 15
overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Requirements
grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
input power cables . . . . . . . . . . . . . . . . . . . . 18
metal conduit runs . . . . . . . . . . . . . . . . . . . . 10
wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
wiring, input power . . . . . . . . . . . . . . . . . . . . 18
Resetting the overload relay . . . . . . . . . . . . . . . . 16
Run enable interlocks . . . . . . . . . . . . . . . . . . . . . 15
Running, relay contact output . . . . . . . . . . . . . . . 15

S
Safety warnings. . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Specifications
208 to 240 volt power connection . . . . . . . . . 22
380 to 480 volt power connection . . . . . . . . . 23
500 to 600 volt power connection . . . . . . . . . 24
cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
input power connections . . . . . . . . . . . . . . . . 19
motor connections . . . . . . . . . . . . . . . . . . . . 26
power connection terminals . . . . . . . . . . . . . 22
Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
C22.2 No. 14. . . . . . . . . . . . . . . . . . . . . . . . . 32
UL 508C . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Index