Activity 4B Impedance of RLC Circuits: Parallel RLC Circuit: Electrical Engineering Department
Activity 4B Impedance of RLC Circuits: Parallel RLC Circuit: Electrical Engineering Department
ACTIVITY 4B
b. ability to design and conduct experiments, as well as to analyze and interpret data
d. ability to function on multidisciplinary teams
e. ability to identify, formulate, and solve engineering problems
g. ability to communicate effectively
1. compute the reactances, total current, branch currents, impedance and phase angle in a
parallel RLC circuit at various frequencies by using standard electronic formulas.
In a parallel RLC circuit, the resistance, inductance and capacitance are all connected
directly across the AC supply voltage, as shown in figure 4.2-1.Each component forms
one branch of the circuit, and each branch draws a current from the AC supply based
upon the applied voltage and the resistance or reactances. Using the values in Figure 4.2-
1, you can calculate the reactances as follows.
The sum of the individual branch currents in parallel RLC circuits equal to the total current
drawn from the source (IT). Because of the different phase shifts in the parallel circuit, the
individual branch current cannot be added directly. Instead, they must be added with
phasors by the following equation:
Figure 4.2-2
Figure 4.2-3 (a and b) shows the current waveforms in the circuit. Because the currents
through the inductor and capacitor are 180 degrees out of phase with one another, they
naturally oppose and cancel one another. The resulting current (IC) is capacitive because
the capacitor current is higher than the inductor current at this frequency. The way to tell
if a parallel RLC circuit is inductive or capacitive is to examine the reactance or branch
currents. The component with the lowest reactance or with the highest current dominates.
Figure 4.2-3
The equivalent of the parallel RLC circuit is 3.9 K resistor in parallel with a capacitor that
draws IC’ or IC2 – IL2 (3.equivalent capacitor 45 – 1.59 = 1.86 mA). We can compute the
equivalent capacitor by first finding its reactance.
XC = Vac / IC
XC = 5 / 1.86 mA
XC = 2, 688 Ω
Figure 4.2-4
Knowing the total circuit current and the applied voltage, you can compute the total circuit
impedance by using Ohm’s Law.
Z = Vac / IT
Z = 5/2.25 mA
Z = 2,222 Ω
Because the circuit is capacitive, the current leads the applied voltage by some phase angle
between 0 and 90˚. The phase angle can be computed from the current amplitudes in the
phasor diagram of Figure 4.2-2. The phase angle A is:
A = arctan (IC/IR)
A = arctan (1.86 mA/ 1.28 mA)
A = arctan (1.45)
A = 55.50o
The current in this circuit leads the applied voltage (Vac) by 55.50˚.
Varying the frequency will change the reactances, branch currents, total current,
impedance, and phase angles. At the lower frequencies, XL will be lower than XC’ so the
circuit will be inductive. At the higher frequencies, XC will be lower than XC so the circuit
will be capacitive.
4B.6 Procedure/s
1. Adjust the dc power sources to + 15 Vdc and – 15 Vdc. Turn the power sources off.
Insert the AC 2 FUNDAMENTALS circuit board into the base unit. Turn on the power
sources.
2. Locate the RLC/RESONANCE/POWER circuit block, and connect the circuit shown in
Figure 4.2-5. If your generator does not have 50 Ω output impedance, plug the
GENERATOR BUFFER into the AC 2 FUNDAMENTALS circuit board, and connect the
buffer between your generator and the circuit.
Figure 4.2-5
3. Set the sine wave generator frequency to 50 kHz. Rather than rely on the generator dial,
use you oscilloscope to set the correct period.
4. Adjust the amplitude of the generator signal (VGEN) for a VAC of 5 Vpk-pk directly across
the parallel network of figure 4.2-5.
Note: Shorting R1 = 4.7k Ω V. Adjust VGEN so that Vac is 5 Vpk-pk
5. Measure IT, IR6, IL2, and IC2. Record your measurements in Table 4.2-1.
IT IR6 IL2 IC2
50 kHz
Step 5
Table 4.2-1.
6. Compute the impedance value of the parallel circuit by using the value of IT that
you measured in step 5 ( Z = Vac / IT ). Z = _________ Ω
7. Measure the phase angle between IT and Vac by using the phase relationship
measurement method.
Note: Connect the probe of channel 1 to the voltage across R6 (Vac) not to the generator
output.
What is the phase angle? Is total current leading or lagging the applied voltage?
Phase angle = _________ degrees , __________
8. Is IL greater or less than IC? Does this cause the circuit to be capacitive or inductive?
________________________________________________________________________
10. Is IL greater or less than IC? Does this cause circuit to be capacitive on inductive?
________________________________________________________________________
12. Using the oscilloscope, set the sine wave generator frequency to 20 kHz. Readjust the
amplitude of the voltage across the parallel RLC circuit (Vac) to 5 Vpk-pk
13. Given the following values, compute the remaining circuit values at 20 kHz. Record
your values in Table 4.2-2.
Vac
X 12 2fL 1256 I R6
R6
1 Vac
XC2 3619 I L2
2fC X 12
Vac
R6 3900 I C2
XC2
I T I R2 6 ( I L I C 2 ) 2
14. Measure IT’ IR6’ and IC2. Record your results in Table 4.2-2.
15. Is IL greater or less than IC? Does this cause the circuit to be capacitive or inductive?
________________________________________________________________________
16. Compute the impedance of the parallel RLC circuit using the values you measured
in step 14 (Z = Vac/ IT). Z = _________ Ω
17. Measure and record the phase shift between total circuit current and the applied
voltage. Does the current lead or lag the voltage (Vac)?
NOTE: Do not compare the current to VGEN. Compare the current to Vac.
Phase shift = ________ degrees , ________
18. Set CM switch 12 in the ON position to change the value of C2 from 0.0022mF to
0.0044mF. Readjust the voltage (Vac) across the RLC circuit to 5 Vpk-pk.
19. Measure and record the values of IL2’ IC2’ and the phase angle. Does IT lead or lag
the applied voltage (Vac)?
IL2 = ________ A, IC2 = ________ A, Phase angle = ______ degrees
4B.7.1 Calculations