3G3JZ Manual Basic
3G3JZ Manual Basic
XA
Single-phase 200 V AC R/L1 U/T1
3-phase 200 V AC S/L2 V/T2 M
3-phase 400 V AC T/L3 W/T3
400V AC use
200V AC transformator
Multi-function output 1
(Fault output)
MA a contact
MB b contact
MB
MC Common ˄Fault output˅
OFF ON MC
XA
XA SA
MB MC
(Fault output)
Multi-function input 1(Forward/Stop)
S1
Multi-function input 2(Reverse/Stop)
S2
Multi-function input 3(External fault)
S3
Multi-function input 4(Fault reset)
S4 AM
Multi-function input 5(Multi-step speed reference1) Ć1 Multi-function analog output
S5 ˄AC˅
Multi-function input 6(Multi-step speed reference2) Analog common Ć4
S6
Sequence input common
SC
Frequency reference power
Frequency +V˄10VDC 20mA˅
Frequency reference input
reference A1˄0̚+10V˅Ć2
adjuster
Analog common
AC
A:4p
RS485 Communication Ć3
B:5p
※ 1.Contorl circuit terminal shows the NPN wiring as the default setting. By using Sequence Input Method SW,
PNP input can be selected.
※ 2.Multi-function analog input shows the current input A1 as the default setting. By using Multi-function analog input
Method SW.
※ 3.Use standard connector wires(for Ethernet) to wiring RS485.
※ 4.Analog input common is the same as analog output common termainal.Analog output is the PWM wave which the car-
rier frequency is 1KHz,and it could connect to analog input directly.
2-11
10 Chapter 10
● List of Parameters ●
10
Chapter 10 List of Parameters
In order to make easier settings of 3G3JZ parameters, parameters are divided into 11 groups based on the
functions and are descripted below.
Parameter Name Description Reference
No. page
Select the environment group, such as control mode selection.
Environment
n0 settings
Parameter write-prohibit and change of monitor range of parameters are 10-2
also included in this function group.
V/f mode and
acceleration/ Set the basic characteristics for the inverter.
n1 deceleration time Set V/f mode, acceleration/deceleration conditions. 10-4
settings
Set the operation mode for the inverter.
Operation mode
n2 settings
Set the input mode by selecting frequency command or operation 10-5
command.
Output function Set the control circuit output functions for the inverter.
n3 settings Select multi-function output or analog output and adjust the set value. 10-8
Input function Set the control circuit input functions for the inverter.
n4 settings Select multi-function input or analog input and adjust the set value. 10-10
10-1
Chapter 10 List of Parameters
Reference page
Changes during
Parameter No.
Register No.
Default setting
Unit of setting
Setting range
(Hex)
operation
n0.00 0000 Inverter Display the power supply specifications and capacity — 1 — — 3-7
capacity for the inverter.
being Applicable specification/capacity for each inverter is as
moni- follows.
tored
※ Only Power supply Power supply
Value
Value
for refer- specification/ specification/
capacity capacity
ence
0 Single-phase/3-phase 9 3-phase 400VAC/2.2kW
200VAC/0.2kW
1 Not used 10 Single-phase/3-phase
200 VAC/3.7 kW
2 Single-phase/3-phase 11 3-phase 400 VAC/3.7kW
200VAC/0.4 kW
3-phase 400VAC/
3 0.4kW
Single-phase/3-phase
4 200 VAC/0.75 kW
3-phase 400VAC/
5 0.75kW
Single-phase/3-phase
6 200 VAC/1.5 kW
3-phase 400VAC/
7 1.5kW
Single-phase/3-phase
8 200 VAC/2.2 kW
n0.02 0002 Parame- Prohibit parameters to be written and reset parameters to 0 1 0 × 5-1
ter write- default values. ~
prohibit 0: All parameters can be set and displayed 10
selec- 1: Parameter n0.02 can be set only, and other parameters
tion/ can be displayed.
parame- 8: Operation button unable
ter initial- 9: Initializes at the maximum frequency of 50Hz.
ization 10: Initializes at the maximum frequency of 60Hz
n0.03 0003 Items Set the items desired to display immediately when power 0 1 0 ○ 3-6
being ON. ~
moni- 0: Frequency command 4
tored 1: Output frequency
selection 2: Output current
when 3: Items being monitored set in n0.04
power 4: FWD (forward rotation)/REV (reverse rotation)
ON
10-2
Chapter 10 List of Parameters
Name Description
Reference page
Changes during
Parameter No.
Register No.
Default setting
Unit of setting
Setting range
(Hex)
operation
n0.04 0004 Selecting Select one of the five items displayed via the operator to 0 1 4 ○ 3-5
items change. ~
being Set the items desired to be displayed. 11
moni-
tored Item being Power supply
Set value
Set value
monitored specifications/
capacity
10-3
Chapter 10 List of Parameters
● n1:set v/f mode and acceleration/deceleration time
Name Description
Reference page
Changes during
Parameter No.
Default setting
Register No.
Unit of setting
Setting range
(Hex)
operation
n1.00 0100 Maximum Set basic characteristics for the inverter, i.e. the V/f mode. 50.00 0.01 50.00 × 5-2
frequency ● V/f control mode: Set output voltages for differ- ~ Hz ※1
(FMAX) ent frequencies. 600.0
Maximum ● Vector control mode: Vector control is used to 0.01 50.00 5-2
n1.01 0101 control frequency and voltage, therefore the set- 0.10 ~ ×
voltage fre- 600.0 Hz ※1
quency(FA) tings in n1.03, n1.04, n1.06 are disabled.
Output voltage[V]
n1.02 0102 Maximum 0.1 ~ 0.1V 200.0 × 5-2
voltage 255.0(0.1 (400.0)
(VMAX) n1.02 ~510.0) ※2
※2
n1.03 0103 Middle output 0.10 ~ 0.01 1.5 × 5-2
frequency (FB) 600.0 Hz
n1.04
10-4
Chapter 10 List of Parameters
※ 1. Default value. When n0.02 = 10 [Initialization at the maximum frequency of 60 Hz], the set value will change to 60Hz.
※ 2. Figures in the parentheses are the setting range and default value of 400VAC inverters.
● n2: Inverter operation mode settings
Name Description
Reference page
Changes during
Parameter No.
Register No.
Default setting
Unit of setting
Setting range
(Hex)
operation
n2.00 0200 Fre- Select the method to input frequency command to the 0~4 1 1 ○ 5-6
quency inverter
0: Increment/Decrement key on the operator enabled
com- 1: Frequency command knob on the operator enabled
mand 2: Frequency command input terminal A1 (voltage
selec- input 0~10V) enabled
tion 3: Multi-function analog input terminal A1 (current
input 4~20mA) enabled
4: RS485 communication link frequency command
enabled
※ When UP/DOWN command (set to 10, 11) is used
in multi-function input (n4.05~n4.08), set n2.00 to
0. In this case, input from Increment/Decrement
key on operator is also enabled. The multi-
function input UP/DOWN command however
takes the priority.
※ Multi-step speed command(set to 01, 02, 03) of the
multi-function inputs(n4.05~n4.08) will not be
impacted by n2.00 setting and be enabled all the time.
※ Choose terminal A1 current/voltage input, use the
SW to ACI/AVI.
n2.01 0201 Opera- Select RUN/STOP command input method for the 0~4 1 0 ○ 5-4
tion inverter.
com- 0: RUN/STOP key of operator enabled
mand 1: Control circuit terminal (2-wire or 3-wire) enabled
selec- ※ STOP key on the operator is also enabled.
tion 2: Control circuit terminal (2-wire or 3-wire) enabled
※ STOP key on the operator is also enabled.
3. RS485 communication link operation command
enabled
※ STOP key on the operator is also enabled.
4. RS485 communication link operation command
enabled
※ STOP key on the operator is disabled.
※ Set the multi-function inputs (n4.05~n4.08)
respectively to "18 (operation command
changeover: control terminal)", "19 (operation
command changeover: operator)" and "20
(operation command changeover:
communication)" to switch the operation
commands temporarily.
n2.02 0202 Stop Select the stop mode in case o stop command or 0~3 1 0 × 5-16
mode external fault inputs.
selec- 0: Decelerates to stop upon stop command/Coasts
tion to stop for external fault
1: Coasts to stop upon stop command/Coasts to
stop for external fault
2: Decelerates to stop upon stop command/
Decelerates to stop for external fault
3: Coasts to stop upon stop command/ Decelerates
to stop for external fault
10-5
Chapter 10 List of Parameters
Name Description
Reference page
Changes during
Parameter No.
Register No.
Default setting
Unit of setting
Setting range
(Hex)
operation
n2.03 0203 Carrier Set the output carrier frequency for the inverter. 2~ 1kHz 8 × 6-3
frequen ※ Generally the default value is used.
cy 15
※ Set to a higher value to reduce the motor noise.
selection ※ Set to a lower value to reduce the effect by
electrical noise.
※ If the carrier frequency set value is higher, the
inverter will be hot. If the set value is higher
than 8 kHz, the rated output current will
decrease.
n2.04 0204 Reverse Select the operation with the reverse command input. 0~2 1 0 × 5-16
rotation- 0: Reverse enabled (forward enabled)
prohibit 1: Reverse disabled (forward enabled)
selection 2: Reverse enabled (forward disabled)
n2.05 0205 Opera- Set the operation commands enabled/disabled input earlier 0~3 1 1 × 5-5
tion after power on or upon operation changeover command.
selection 0: Enabled after power on/disabled upon operation
after changeover command
power on 1: Disabled after power on/ disabled upon operation
/opera- changeover command
tion 2: Enabled after power on/ enabled upon operation
change changeover command
over 3: Disabled after power on/ enabled upon operation
com- changeover command
mand ※ It must be enabled when operation command is input
again after power on or upon operation changeover
command.
n2.06 0206 frequence Set the operation with loss of frequence command input 0~2 1 0 × 5-10
command command.
input When frequence command input occurred at the default
(Termi- input current, loss will be detected if the input current is
nal A1) less than n4.15 set value (the minimum current value
loss of across the frequence command input terminal A1)
detection 0: Decelerate to 0Hz (operates upon command)
selection 1: Detect fault frequence command input signal with
"AErr" (coasts to stop) displayed.
2: Detect exception without "ERR" displayed and
operate under the frequency before disconnection.
※ When the fault frequence command input signal is
detected with "AErr" displayed, it changes to reset
after cause is removed (flash is eliminated).
※ Loss detection is disabled when the frequence
command input set value is changed to 0~20mA or
voltage is input.
10-6
Chapter 10 List of Parameters
Name Description
Reference page
Changes during
Parameter No.
Register No.
Default setting
Unit of setting
Setting range
(Hex)
operation
n2.09 0209 Second- Select the input method of the secondary 0~4 1 2 ○ 5-6
ary fre- frequency command frequency.
※ The secondary frequency command method is
quency used via setting the secondary frequency
com- command operation selection (n2.10).
mand ※ Frequency command input can be changed over
by setting the multi-function input
selection (n4.05~n4.08) to "22 (Secondary frequency
command)".
0: Increment/decrement key of the operator
enabled
1: Frequency command knob of the operator
enabled
2: Frequency command input terminal A1 (input
voltage 0~10V) enabled
3: Multi-function analog input terminal A1 (input
current 4~20mA) enabled
4: RS485 communication link frequency command
enabled
※ When UP/DOWN command (value 10, 11) is
used in the multi-function inputs
(n4.05~n4.08), set n2.09 = 0. Increment/
decrement key of the operator is also enabled.
However, the multi-function input UP/DOWN
command takes the priority.
※ Multi-step speed command (1, 2, 3) of the
multi-function inputs (n4.05~n4.08) will not be
impacted by n2.09 setting and be enabled all
the time.
※ Choose frequence command input current/
voltage, use the switch to ACI/AVI.
n2.10 020A Second Select the operation method for the secondary 00 ~ 02 1 0 ○ 5-6
fre- frequency command.
quency 0: Disabled
com- Actual frequency command = Frequency
mand command (n2.00)
opera- 1: Enabled
tion Actual frequency command = Frequency
selection command (n2.00)+Secondary frequency
command (n2.09)
2: Enabled
Actual frequency command= Frequency
command (n2.00)-Secondary frequency
command (n2.09)
n2.13 020D Opera- Select whether the frequency command sent by operator 0~2 1 0 × 5-8
tor com- and communication link is stored or not.
municati 0:Store the operator frequency command/store 5-13
on fre- communication link frequency command
quency 1:Store the operator frequency command/not store
com- communication link frequency command
mand 2:Not store the operator frequency command/store
memory communication link frequency command
selection ※ When the parameter is set to not store, the frequency
command will operate with "0.00" after power ON.
10-7
Chapter 10 List of Parameters
Reference page
Changes during
Parameter No.
Register No.
Default setting
Unit of setting
Setting range
(Hex)
operation
n3.00 0300 Multi-func- Select the functions of multi-function output 0 ~ 21 1 8 × 5-18
tion output 1 terminals.
(output termi-
Function Description
nals MA/MB
and MC) Set value
10-8
Chapter 10 List of Parameters
Name Description
Reference page
Changes during
Parameter No.
Register No.
Default setting
Unit of setting
Setting range
(Hex)
operation
8 Fault output ON: Fault output
9 Frequency ON: Output frequency ≥
detection frequency detection level
(n3.02)
12 Stall ON: Stall prevention during
prevention deceleration in progress
during (n6.00)
deceleration
in progress
13 Stall ON: Stall prevention during
prevention acceleration/operation in
during progress (n6.01/n6.02)
acceleration
/operation
in progress
14 Inverter ON: Inverter overheating
overheating alarm (temperature of
alarm radiation fin is above 85 ℃ )
15 Overvoltage ON: Overvoltage alarm
alarm (Voltage on the main circuit
exceeds the alarm voltage)
※ Alarm voltage: The DC
voltage of the main circuit:
200V; 200VAC model: 374V;
400V AC model: 747V
17 Rotating in ON: Rotating in forward
forward
direction direction
10-9
Chapter 10 List of Parameters
Name Description
Reference page
Changes during
Parameter No.
Register No.
Default setting
Unit of setting
Setting range
(Hex)
operation
n3.04 0304 Multi-function To adjust voltage in the multi-function analog 1 ~ 200 1% 100 ○ 5-21
analog output output, set the output voltage gain. When output
gain (output voltage gain is set to 100%, output is determined
terminals AM- by the following equation.
AC) n3.03 = 0: Output frequency being monitored
(0~10V/0~Maximum frequency n1.00)
n3.03 = 1: Output current being monitored (0~10V/
0~250% of the inverter rated output current)
※ If output voltage gain is set to 50%, the output
voltage is 5V under the same conditions.
n3.08 n3.08 Cooling fan Set the cooling fan operation. 0~ 1 1 × 6-13
operation 0: Rotates only when RUN command is input
selection 1: Rotates when the inverter is turned ON (for 3
1 minute after the inverter stops operation)
2: Rotates when the inverter is turned ON
(Stops when the inverter stops)
3: Rotates according to IGBT temperature
conditions (Operates above 60 ℃ and stops
below 40 ℃ )
n3.11 030B External brake Set the control signals for external brake 0.00 0.01 0.0 × 6-6
release fre- operations. Set the external brake release/ ~ Hz 0
quency external brake operation time according to 20.00
the inverter output frequency.
n3.12 030C External brake ※ Set the multi-function output (n3.00) to 0.00 0.01 0.0 × 6-6
operation fre- "21 (external brake output)" to connect ~ Hz 0
quency with external brake. 20.00
※ Set the brake operation value coincident
with the inverter output status value Hz
in order to prevent the vertical shaft from
dropping.
Reference page
Changes during
Parameter No.
Register No.
Default setting
Unit of setting
Setting range
(Hex)
operation
n4.04 0404 Multi-function Input the control circuit terminal operation 0~2 1 0 × 5-4
input 1/2 command from the multi-function input 1/2. Set
selection the input method according to actual application.
(Input terminal 0: 2-wire sequence (Forward /stop (Terminal S1),
S1/S2) Reverse/stop (Terminal S2))
1: 2-wire sequence (Run/stop (Terminal S1),
Forward/Reverse (Terminal S2))
2: 3-wire sequence
※ When n4.04 = 2, even if 3-wire sequence input is set,
3-wire sequence allocation is performed while the
multi-function input 3 (n4.05) set value is disabled.
STOP Switch RUN switch
(b connection) (a connection) S1 RUN input (Operates with the stop
switch and RUN switch closed)
S3 STOP input (Stops with the stop
Direction switch switch opened)
Direction switch
S2 Forward/Reverse command (Forward
with the direction switch opened and reverse
with the direction switch closed)
SC Sequence input common terminal
10-10
Chapter 10 List of Parameters
Name Description
Reference page
Changes during
Parameter No.
Register No.
Default setting
Unit of setting
Setting range
(Hex)
operation
n4.05 0405 Multi-function Select the functions of multi-function input 0 ~ 22 1 14 × 5-17
input 3 selec- terminals 3 through 6.
tion (Input ter-
minal S3)
n4.06 0406 Multi-function Function Description 5 × 5-17
Set value
input 4 selec-
tion (Input ter-
minal S4)
10-11
Chapter 10 List of Parameters
Name Description
Reference page
Changes during
Parameter No.
Register No.
Default setting
Unit of setting
Setting range
(Hex)
operation
18 Operation ON: Operation command 5-17
command sent by control circuit
changeover terminal enabled
(Control OFF: Operation command
circuit selection (n2.01) enabled
terminal)
19 Operation ON: RUN/STOP key on 5-17
command the operator enabled
changeover OFF: Operation command
(Operator) selection (n2.01) enabled
20 Operation ON: Communication 5-17
command link operation command
changeover enabled
(communic OFF: Operation
ation) command selection
(n2.01) enabled
22 Secondary ON: Secondary 5-17
frequency frequency command
command (n2.09) enabled
n4.09 0409 Multi-func- Select the multi-function input from a 0~ 1 0 × 6-5
tion input a connection (NO) or b connection (NC). 63
connection/b When b connection (NC) is set to 1, the
connection binary value is converted to decimal value.
input selec- "11" = 000000001011
tion → Multi-function inputs 1, 2, 4 are set by b
connection (NC) input
0:a connection(N.O.)
1 1 1 1 1 1 1:b connection(N.C.)
Multi-function inpu1(S1)
Multi-function inpu2(S2)
Multi-function inpu3(S3)
Multi-function inpu4(S4)
Multi-function inpu5(S5)
Multi-function inpu6(S6)
n4.10 040A Input termi- Set the input response time for input 1~ 1(2 1 × 6-6
nal response terminals. 20 ms
time Generally it is not required to set. Set the )
parameter to a higher value to prevent relay
vibration or electrical noise in unit of 2ms.
10-12
Chapter 10 List of Parameters
Name Description
Reference page
Changes during
Parameter No.
Register No.
Default setting
Unit of setting
Setting range
(Hex)
operation
n4.11 040B Frequency command Change and adjust the frequency command 0.0 0.1 0.0 × 5-10
input terminal A1 min- input (terminal A1) analog input ~ V
imum voltage input characteristics. 10.0
Set the characteristics desired to be changed
n4.12 040C Frequency command according to the following figure. 0.0 0.1 0.0 × 5-10
input terminal A1 min- ※ Command value is set with the maximum ~ %
imum voltage com- frequency (n1.00) being 100%, in unit of 100.0
mand value 0.1%.
n4.13 040D Frequency command input ※ Choose A1 input current/voltage, use the 0.0 0.1 10.0 × 5-10
terminal A1 maximum switch to ACI/AVI. ~ V
voltage input ACI: current input(4 ~ 20mA) 10.0
Frequency command AVI: voltage input(0 ~ 10V) 0.0 0.1 100.0 5-10
n4.14 040E ×
input terminal A1 ~ %
maximum voltage Command value
100.0
command value 100%
Maximum frequency(n1.00)
n4.17 0411 Frequency command input 0V n4.11 n4.13 10V 0.0 0.1 20.0 × 5-10
terminal A1 maximum cur- 0mA n4.15 n4.17 20mA ~ m
rent input 20.0 A
n4.18 0412 Frequency command 0.0 0.1 100.0 × 5-10
input terminal A1 ~ %
maximum current 100.0
command value
n4.27 041B Input termi- Allocate the input terminals to internal inputs, 0~ 1 00 × 6-4
nal internal which allows the internal inputs to be set to a fixed 63
input selec- status. This parameter is available when starting the
tion inverter in fixed status after power ON without
wiring.
n4.28 041C Internal input ※ Set the input terminal internal input selection 0~ 1 00 ○ 6-4
status selection (n4.27) to allocate to the internal inputs. Set the 63
values with internal input status of 1 and
displayed after being converted from binary to
decimal.
※ Set in the internal input status selection (n4.28)
the fixed status of internal inputs. Set the input
fixed status (a connection is ON) to 1, with the set
values converted from binary values to decimal
values. For example: Value "11"=000000001011
n4.27 → multi-function inputs 1, 2 and 4
are allocated to the internal input setting
n4.28 → multi-function inputs 1, 2 and 4 are
in input fixed status (a connection is ON)
n4.27=1:Internal input setting
1 11 11 1 n4.28=1:Input fixed status
Multi-function input1(S1)
Multi-function input2(S2)
Multi-function input3(S3)
Multi-function input4(S4)
Multi-function input5(S5)
Multi-function input6(S6)
10-13
Chapter 10 List of Parameters
Reference page
Changes during
Parameter No.
Register No.
Default setting
Unit of setting
Setting range
(Hex)
operation
n5.00 0500 Frequency Set the internal frequency commands. 0.0 0.01 0.00 ○ 5-9
command 1 ※ Select the internal frequency commands with the
0 Hz
multi-function inputs (n4.05~n4.08) set to multi-step ~
n5.01 0501 Frequency 600.0 0.00 ○
command 2 speed command (set value 01, 02, 03).
Frequency
command 5 ○ × ○ ×
Frequency
command 6 × ○ ○ ×
Frequency
command 7 ○ ○ ○ ×
Register No.
Default setting
Unit of setting
Setting range
(Hex)
operation
n6.00 0600 Operation Set the operation level under which deceleration 0.0、 0.1V 390.0 × 6-9
level for time function automatically stops in order to 330.0 ~ (780.0)
stall preven- prevent overvoltage (OV) during deceleration. Set 410.0
with the voltage value of DC power supply of the ※2
tion during (0.0,
deceleration main circuit. Generally it is not required to change
the set value. 660.0 ~
※ When stall prevention during deceleration is 820.0)
enabled, overvoltage is detected, set the ※2
parameter to a lower value.
If the parameter is set too low, the inverter can
not deceleration, causing the stop duration very
long, which should be attended to.
10-14
Chapter 10 List of Parameters
Name Description
Reference page
Changes during
Parameter No
Register No.
Default setting
Unit of setting
Setting range
(Hex)
operation
n6.01 0601 Operation Set the operation level under which the 0,20 1% 170 × 6-9
level for acceleration function automatically stops to avoid ~
stall the stall status during acceleration. Set the 250
prevention parameter in unit of % with the inverter rated
during output current referred to 100%.
acceleration ※ When the parameter is set to "0.0", stall prevention
during acceleration function is disabled.
n6.02 0602 Operation Set the operation level under which the acceleration 0,20 1% 170 × 6-10
level for stall function automatically stops to avoid the stall status ~
prevention during running. Set the parameter in % with the 250
during inverter rated output current referred to 100%.
running ※ When the parameter is set to "0.0", stall
prevention during running function is disabled.
n6.03 0603 Overtorque Enable or disable the overtorque detection and 0~4 1 0 × 6-7
detection how to process after overtorque is detected.
selection 0: Overtorque detection disabled.
1: Only detection in speed consistency/Continue
to run with overtorque being detected
(detection alarm)
2: Only detection in speed consistency/Stop
output with overtorque being detected (fault
detection)
3: Detection during running/Continue to run with
overtorque being detected (detection alarm)
4: Detection during running/Stop output with
overtorque being detected (fault detection)
※ Exceeding the overtorque detection level
(n6.04) continues to exist for certain of
duration after the overtorque detection time
(n6.05) lapses will be detected.
※ When overtorque is being detected, if it is error
detect, "OL2" is displayed, flash until stop output. If
it is alarm detect, "OL2" is displayed, flash until no
overtorque is being detected.
※ If the multi-function output (n3.00) is set to
"04 (overtorque being detected)", output to
external is enabled.
n6.04 0604 Level for Set the level under which overtorque is being 10 ~ 1% 150 ○ 6-7
overtorque detected with the inverter rated output current 200
being detected being 100%, and % as the setting unit.
n6.05 0605 Time for over- Set the duration for overtorque being detected. 0.1 0.1s 0.1 × 6-7
torque being ~
detected 60.0
n6.06 0606 Motor pro- Set the overload prevention characteristics for 0~2 1 0 × 6-11
tection connecting with motor (electronic temperature
function sensitive characteristics).
selection 0: Protection operation corresponding to the
general induction motor
1: Protection operation corresponding to the
special motor for inverter
2: Motor overload prevention function disabled
※ Motor rated current (n7.00) must be set in order to
enable the electronic temperature sensitive function
to detect the motor overload (OL1) properly.
※ If 2 or above motors are connected to the same
inverter, set the n6.06 to 2.
n6.07 0607 Motor pro- Set the electronic temperature sensitive protection for 30 ~ 1s 60 × 6-11
tection motor overload being detected (OL1) with seconds. 600
operation The default setting is 150% withhold 1 minute.
duration ※ Generally, it is not necessary to change the
default setting.
10-15
Chapter 10 List of Parameters
Name Description
Reference page
Changes during
Parameter No
Register No.
Default setting
Unit of setting
Setting range
(Hex)
operation
n6.08 0608 Error his- 2 error history records can be stored at the most. — 1 0 × 3-7
tory record This parameter is used for analysis of fault cause.
1 (before 1 The error history records are stored with the
time) following codes.
n6.09 0609 Error history No. Function No. Function — 1 0 — 3-7
record 2 0 (No error) 21 Overvoltage
(before 2 detection circuit
times) error "HPF2"
1 Overcurrent 22 Grounding short
(hardware circuit detection
being detected) error "HPF3"
"OC"
2 Overvoltage 23 Overcurrent detec-
"ov" tion circuit error
"HPF4"
3 Radiation fin 24 U phase circuit
overheated error "cF3.0"
"oH1"
4 Power supply 25 V phase circuit
base overheated error "cF3.1"
"oH2"
5 Inverter 26 W phase circuit
overload "oL" error "cF3.2"
6 Motor overload 27 Voltage control
"oL1" circuit error
"cF3.3"
7 Overtorque 28 Temperature
detection "oL2" detector 1 error
"cF3.5
8 External fault 29 Temperature
"EF" detector 2 error
"cF3.5"
9 Overcurrent 32 Multi-function
during analog input sig-
acceleration nal error "AErr"
"ocA"
10 Overcurrent
during
deceleration
"ocD"
11 Overcurrent in
normal status
"ocn"
12 Grounding fault
"GFF"
13 Low voltage on
main circuit
"Lv"
※ Not stored
14 Input power
phase loss
"PHL"
15 External base
block "bb"
※ Not stored
10-16
Chapter 10 List of Parameters
Name Description
Reference page
Changes during
Parameter No
Register No.
Default setting
Unit of setting
Setting range
(Hex)
operation
EEPROM (CB)
18 writing error
"cF1.0"
EEPROM (CB)
19 reading error
"cF2.0"
Current
20 limiting circuit
error "HPF1"
※ 13: Main circuit low voltage "LV" and 15:
External base block "bb" are not stored in the
error history record.
※ 2. Figures in the parentheses are the setting range and default value for 400VAC models.
● n7: Motor parameter settings
Name Description
Reference page
Changes during
Parameter No
Register No.
Default setting
Unit of setting
Setting range
(Hex)
operation
n7.00 0700 Rated Set the rated motor current (A). ※4 0.1A ※5 ○ 5-2
motor Rated motor current is default to the standard
current current of motor overload detection (OL1) or
vector control algorithm parameters.
n7.01 0701 Motor no Set the motor no load current (A). ※6 0.1A ※7 ○ 6-1
load cur-
rent
n7.02 0702 Torque Set the torque compensation gain. 0.0 ~ 0.1 1.0 ○ 6-2
compen- ※ Generally it is not necessary to change the 10.0
sation default value. When torque is insufficient, set
gain the parameter to a higher value.
※ When several motors are connected to the
same inverter, current will increase, in this
case, set the parameter to "0.0" to disable the
function.
n7.03 0703 Slip Set the slip compensation gain. Slip compensation 0.00 ~ 0.01 0.00 ○ 6-1
compen- function requires setting of rated motor current 10.0
sation (n7.00), motor no load current (n7.01).
gain ※ This function is disabled by setting the
parameter to 0.0.
※ 4. The setting range varies with the inverter capacity within 30~120% of the rated inverter output current.
※ 5. The default value varies with the inverter capacity, about 75% of the rated inverter output current.
※ 6. The setting range varies with the inverter capacity within 0~99% of the rated inverter output current.
※ 7. The default value varies with the inverter capacity, about 40% of the rated inverter output current.
10-17
Chapter 10 List of Parameters
Reference page
Changes during
Parameter No
Register No.
Default setting
Unit of setting
Setting range
(Hex)
operation
n8.00 0800 DC braking Apply DC current to brake the induction motor. Set DC 0~ 1% 50 × 6-8
current braking current as percentage based on the rated 100
inverter output current as 100% and in unit of %.
n8.01 0801 DC braking 0.0 ~ 0.1s 0.0 × 6-8
time during Frequency[Hz]
n8.02 60.0
startup
n8.03
n8.02 0802 DC braking
n1.05 0.0 ~ 0.1s 0.5 × 6-8
time during 60.0
stop Time
n8.03 0803 DC braking n8.01 0.00 0.01 0.00 × 6-8
starting fre- ※ DC braking changes over with the minimum output ~ Hz
quency dur- frequency (n1.05) when startup. 600.0
ing stop ※ This parameter is used to stop large moment load or
decelerate to avoid FAN regeneration.
n8.04 0804 Operation Select the process method for instant power loss. 0~2 1 0 × 6-12
selection after 0: STOP
recovery from 1: Continue to run (restart according to the speed search
instant stop sent by frequency command)
2: Continue to run (restart according to the speed search
sent by minimum output frequency)
※ Continue to run until the time set in the instant
power loss compensation time (n8.05) lapses.
n8.05 0805 Instant power Set the maximum duration when the process method 0.1 ~ 0.1s 2.0 × 6-12
loss compen- after instant power loss is set to "continues to run". 5.0
sation time ※ When the instant power loss is longer than the preset
time, "Lv" error will be detected.
※ If a too long time is set that the inverter internal
power supply decreases completely, speed will not
be searched and ordinary startup is be conducted.
n8.09 0809 Upper limit of Set the leaping frequency to avoid mechanical resonance 0.00 0.01 0.00 × 6-13
leaping fre- frequency. ~ Hz
quency 1 600.0
n8.10 080A Lower limit Output frequency[Hz] 0.00 0.01 0.00 × 6-13
of leaping fre- ~ Hz
quency 1 n8.09 600.0
n8.10
n8.11 080B Upper limit of n8.11
0.00 0.01 0.00 × 6-13
leaping fre- ~ Hz
quency 2 n8.12
600.0
n8.12 080C Lower limit 0.00 0.01 0.00 × 6-13
of leaping fre- Command frequency[Hz] ~ Hz
quency 2 600.0
※ Parameters must set to meet the following condition:
n8.09 ≥ n8.10 ≥ n8.11 ≥ n8.12.
※ The functions are disabled by setting the parameters
to 0.00.
n8.15 080F Number of The function can restart by automatic reset in case 0~ 1 0 × 6-13
fault retry of overvoltage (ov) and overcurrent (oc). 10
※ Set the maximum number of restarts.
10-18
Chapter 10 List of Parameters
Name Description
Reference page
Changes during
Parameter No
Register No.
Default setting
Unit of setting
Setting range
(Hex)
operation
n8.17 0811 Energy-sav- Enable or disable the energy-saving control. 0,1 1 0 × 6-14
ing control 0: Disabled
selection 1: Enabled
※ Control the electric power required for load
operation in automatic control mode when the motor
power factor is satisfied.
※ 2. Figures in the parentheses are the setting range and default value for 400VAC models.
● n9: RS485 communication settings
Name Description
Reference page
Changes during
Parameter No
Register No.
Default setting
Unit of setting
Setting range
(Hex)
operation
n9.00 0900 RS485 com- Set the slave address (Slave unit number) for 0~ 1 0 × 7-2
munications communications. 254
slave address ※ RS485 communication is disabled by setting
the parameter to 0.0.
n9.01 0901 RS485 baud Set the baud rate for communications. 0~3 1 1 × 7-2
rate selection 0: 4800 bps
1: 9600 bps
2: 19200 bps
3: 38400 bps
n9.02 0902 Operation Select the operations when a communication error 0~3 1 2 × 7-2
selection (CE □ ) is detected.
upon RS485 0: Continues to run with alarm displayed
communica- 1: Decelerates to stop with alarm displayed
tions error 2: Coasts to stop with alarm displayed
detected 3: Continues to run (no alarm displayed)
n9.04 0904 RS485 send Set the waiting period for returning a response 0~ 1(2 0 × 7-2
wait time after the DSR (data-send-request) message is 200 ms)
received from the Master with a setting increment
of 2ms.
n9.05 0905 RS485 com- Set the detection period for communication time- 0.0 0.1s 1.0 × 7-2
munications out. ~
time-out Set the detection period according to the 120.0
detection communication program.
period ※ Communication time-out detection is disabled
by setting the parameter to 0.0.
10-19