Interface Adapter
Interface Adapter
Interface adapter
Block diagram
The interface adapter STA provides electrical
isolation of the signal lines between the central
control cabinet and the additional equipment. The
Additional equipment electrical isolation of the signal lines protects the
CPTronic control system. The following additional
equipment can, for instance, be connected to the
interface adapter:
SAM SEM STA-X1
IR dryer, UV dryer, sheeter, tape inserter, produc-
tion recorder, external powder spray device.
STA
The interface adapter comprises an interface input
STA-X3 ( SM74 only ) STA-X2 module SEM, an interface output module SAM, the
terminal strip STA-X1 and the connector STA-X2
and, for M74, the connector STA-X3.
Printing press
ÁÁ 1S65
Connector STA-X2
The position switch ”Press cycle” 1S65 is con-
nected to the connector STA-X2.
Central control
console
Signal flow
177
Interface adapter Layout, place of installation
Layout
Interface output module SAM Connector STA-X2 for position switch ”Press
Interface input module SEM
cycle” (1S65)
Place of installation
SM52, SM74
The interface adapter STA is located at the
feeder, below the control console on the O.S.
ÎÎ ÎÎÎÎ
ÎÎÎÎ STA
178
Interface adapter Layout, place of installation
SM102, CD102
The interface adapter STA is located outside on
the back panel of the central control cabinet.
The position switch ”Press cycle” 1S65 is fitted
before the 1st printing unit on the O.S.
179
Interface adapter Connector
Connector
Connector STA-X2
Pin Function
1 NO contact,
2 1 2 switching capacity 230V AC, 1A
3 4 3 NC contact,
4 switching capacity 230V AC, 1A
Pin Function
A1 AC 230 V AC
A2 Neutral conductor AC 230 V
A3 DC 24 V
A4 Run
A5 Dryer on / off
A6 Radiators on / off
A7 Paper in PU1
A8 Emergency stop
A9 Printed sheets in the delivery
B2 Feeder on
B3 Powder spray device on / off
B4 Emergency stop
B5 UV dryer in operation
B6 Malfunction UV dryer
Connector STA-X3, coming from the press B7 –
B8 –
C1 –
C2 –
C3 –
C4 AC 21 V
C5 Neutral conductor AC 21 V
C6 –
C7 –
C8 –
C9 –
PE conductor
180
Interface adapter SEM Interface input module
E3 10
14
E4 10
15
E5 10
16
E6 10
17
E7 10
18
E8
X1 X2
Layout of SEM
Block diagram
AC
21 V
DC AC 21 V
12 V
EAK ESK
DC 24 V
REK2 /
REK386
External device SEM FEM / EVM
Principle of SEM
181
Interface adapter SEM Interface input module
Connections
UV dryer
with shutter
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
washing
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
18
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
10 E8
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
17
E7
Not used 10
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
E6
16
E5
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
* 10
E4
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
15
E3
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
10 E2
14 E1
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
Not used 10 +1
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
13
N4
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
10 211
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
12
*
10
Malfunction UV dryer
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
*
11
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
10
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
UV dryer in
operation
* Note:
When connecting additional equipment
– to terminals 10 and 11
– to terminals 10 and 12
Emergency stop
– to terminals 10 and 16
remove the corresponding jumper!
Terminal strip: SEM-X2; connections of the The cables from the additional equipment are
additional equipment connected to terminal strip SEM-X2 of the inter-
face input module SEM.
Terminal strip: SEM-X1; connections to the
central control cabinet ZSG
182
Interface adapter Input signals (SEM)
183
Interface adapter SAM Interface output module
184
Interface adapter SAM Interface output module
Block diagram
REK2 /
REK386
DC 24 V
AC 230 V
ESK EAK
Emergency
stop
Connections
185
Interface adapter SAM Interface output module
186
Interface adapter Output signals (SAM)
187
Interface adapter Output signals (SAM)
Feeder on/off
Control signal e. g. for sheeter.
The control signal is present as long as the feeder is
engaged.
188
Interface adapter EEM Single-fault fail-safe
extension module
Layout
Connector X1
connection to backplane of computer plug-in
unit RER2
Connector X2
ground and connection to SAM
Task/function
The EEM transmits the isolated signal ”Main drive
emergency stop” from the REK2 to the SAM. The
signal transmission path is open-circuit-monitored.
This second signal transmission path ( as
compared to the ”Emergency stop” signal which is
transmitted to the SAM via the EAK ) ensures the
single-fault fail-safe condition.
If a wire is broken or the signal ”Main drive
emergency stop” is transmitted by one of the
SEKs, the corresponding relay on the SAM drops
out.
Block diagram
A10
189
Interface adapter EEM Single-fault fail-safe
extension module
Pin assignment
Connector X2
Pin Function
1 3
1 Connection to ground ( if two SEKs are
used on presses with 8 PUs; other-
wise not connected )
2 Connection to ground ( if one SEK is
Connector EEM-X2 used on presses with 8 PUs; other-
wise not connected )
3 Relay
– if no emergency stop: ground
– if emergency stop: high-resistance
( no ground)
190
Interface adapter 1S65 Position switch ”Press cycle”
Place of installation
SM52
SM74
1S65
ÎÎÎÎÎ
ÎÎ
ÎÎ ÎÎÎÎ
ÎÎ
ÎÎ
Position switch ”Press cycle” in front of 1st PU, O.S.
SM102, CD102
191
Interface adapter 1S65 Position switch ”Press cycle”
Positioning
Remove the defective position switch 1S65.
Fit the new position switch 1S65.
When fitting the position switch, make sure to
1S65 position it in such a way that the NC and NO
contacts are actuated.
21 22
13 14
2mm 1S65
21 / 22 = 0
13 / 14 = 1
13 14