POWER SUPPLY SYSTEMS DEHNguard® modular

SPDS TYPE 2 DG M TT 275 FM

Dimension drawing DG M TT ... FM Basic circuit diagram DG M TT ... FM Complete prewired unit for TT systems,
consisting of a base part and plug-in protection
DG M TT ... (FM): Modular surge arrester for TT and TN-S systems ("3+1" circuit) modules

Energy-coordinated within the Red/Line product


family

High discharge capacity due to powerful zinc


oxide varistors/spark gaps

Reliable SPD control due to "Thermo Dynamic


Control"

Operating state/fault indication of every


protective circuit

Multifunctional terminals for connection of


conductors and busbars

Easy exchange of protection modules without


tools by module locking system with releasing
button

Tested for vibration- and shock-proofness acc.


to EN 60068-2

DG M TT 275 FM
SPD according to EN 61643-11 Type 2
SPD according to IEC 61643-1 Class II
Nominal ac voltage [UN] 230/400 V
Max. continuous ac voltage [L-N] [UC] 275 V
Max. continuous ac voltage [N-PE] [UC] 255 V
Nominal discharge current (8/20 µs) [In] 20 kA
Max. discharge current (8/20 µs) [Imax] 40 kA
Lightning impulse current (10/350 µs) [N-PE] [Iimp] 12 kA
Voltage protection level [L-N] [UP] ≤ 1.25 kV
Voltage protection level [L-N] at 5 kA [UP] ≤ 1 kV
Voltage protection level [N-PE] [UP] ≤ 1.5 kV
Follow current extinguishing capability [N-PE] [Ifi] 100 Arms
Response time [L-N] [tA] ≤ 25 ns
Response time [N-PE] [tA] ≤ 100 ns
Max. mains-side overcurrent protection 125 A gL/gG
Short circuit withstand capability at max. mains-side overcurrent 50 kArms
protection
TOV voltage [L-N] [UT] 335 V / 5 sec.
TOV voltage [N-PE] [UT] 1200 V / 200 ms
Operating temperature range [TU] -40°C...+80°C
Cross-sectional area (min.) 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715

page1©2007 DEHN + SÖHNE GmbH + Co. KG Hans-Dehn-Str. 1 Postfach 1640 D-92306 Neumarkt, Germany, Tel. +499181 906-0 www.dehn.de, as at: 2007-08-20
Enclosure material red thermoplastic, UL 94 V-0
Degree of protection IP 20
Dimension 4 mods., DIN 4
Type of remote signalling contact changeover contact
Switching capacity ac 250 V/0.5 A
Switching capacity dc 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible

Ordering information
Type DG M TT 275 FM
Part No. 952 315
Packing unit 1pcs.
Change in form and technology, with masses, weights and materials we reserve ourselves in the sense of the progress of the technology. The illustrations are noncommittal.

page2©2007 DEHN + SÖHNE GmbH + Co. KG Hans-Dehn-Str. 1 Postfach 1640 D-92306 Neumarkt, Germany, Tel. +499181 906-0 www.dehn.de, as at: 2007-08-20