Digital Voltage Regulator Installation and Omm
Digital Voltage Regulator Installation and Omm
Digital Voltage Regulator Installation and Omm
3
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
CONTENTS cont.
Instantaneous Field Over Current Shutdown............................................................ 19
Regulator Over Temperature Shutdown................................................................... 19
Generator Under Frequency Alarm.......................................................................... 20
Generator Reverse Power Flow Alarm...................................................................... 21
Loss of CAN Communication Alarm......................................................................... 21
SECTION 4 – INSTALLATION
General................................................................................................................................ 22
Mounting.............................................................................................................................. 22
Connections......................................................................................................................... 25
Preliminary Set-up on Generator......................................................................................... 35
Preliminary Set-up on Bench............................................................................................... 36
SECTION 5 – HUMAN-MACHINE INTERFACE
General................................................................................................................................ 37
Front Panel Display.............................................................................................................. 38
Making Settings Changes.................................................................................................... 39
SECTION 6 – GRAPHICAL USER INTERFACE
Header Buttons.................................................................................................................... 40
Administration........................................................................................................... 40
Login......................................................................................................................... 40
Load Factory Settings............................................................................................... 40
Save to EEPROM...................................................................................................... 40
Load Config.............................................................................................................. 40
Save Config.............................................................................................................. 41
Connect.................................................................................................................... 41
Parameter Screen Selection Buttons................................................................................... 41
Metering Tab............................................................................................................. 41
Configuration Tab..................................................................................................... 42
Operating Modes Sub Panel.................................................................................... 42
Set Points Sub Panel................................................................................................ 43
Protection Settings Sub Panel.................................................................................. 44
CAN Bus Configuration Sub Panel........................................................................... 45
Identification Tab...................................................................................................... 45
SECTION 7 – MAINTENANCE AND TROUBELSHOOTING
Preventative Maintenance................................................................................................... 46
Troubleshooting................................................................................................................... 46
SECTION 8 – CAN BUS INTERFACE
Message Format.................................................................................................................. 53
Outbound Messages From DVR®2000E+.......................................................................... 55
Inbound Messages From ECU1 or ECU2 or ECU3............................................................. 70
APPENDIX A
Alarm Codes........................................................................................................................ 74
Fault Codes.......................................................................................................................... 74
APPENDIX B
Connector Pin-out Figures and Tables................................................................................ 75
APPENDIX C
Quick Start Programming Guide.......................................................................................... 78
4
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
SECTION 1 - OVERVIEW
:Use caution when working around the component side of the DVR®2000E+. Voltage levels
may be present at the exposed components and contacts when the unit is energized.
GENERAL
The DVR®2000E+ is a microprocessor-based control device that regulates the output voltage of a brushless, ac
generator by controlling the current into the generator exciter field. Input power to the DVR®2000E+ is derived
from a single phase, multi-pole, high-frequency, permanent magnet generator (PMG).
The DVR®2000E+ is supplied in an encapsulated package designed for behind-the-panel mounting. The
DVR®2000E+ is held in place by thread-forming screws that thread into its plastic shell. The front panel display
annunciates regulator status and system conditions. DVR®2000E+ connections are made through four types of
connectors:
• Ten quarter-inch, quick-connect terminals for generator connections
• Two 12-pin Deutsch (DTC style) connectors for current transformer (CT) and system
interface connections
• One 3-pin Amp/Tyco Mini Mate-N-Lok receptacle for CAN bus interface.
• One 9-pin DB-9 type connector for communication between the DVR®2000E+ and a
Windows® compatible PC.
FEATURES
DVR®2000E+ has the following features:
• Three regulation modes: single phase automatic voltage regulation (AVR1), three phase
automatic voltage regulation (AVR3) and field current regulation (FCR)
• Preset stability settings
• Adjustable soft start in AVR1 or AVR3 regulation modes
• Under frequency (volts/hertz) regulation
• Three-phase or single-phase generator voltage (RMS) sensing
• Three-phase or single-phase generator current (RMS) sensing
• True three-phase power metering
• Field current sensing
• Field voltage monitoring
• Contact inputs for system interface capability
5
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
• Contact output for fault indication
• Generator paralleling with reactive droop compensation and reactive differential compensation
• Front-panel human-machine interface (HMI) for status and configuration
• MODBUS protocol via RS232 for external communication
• DVR®2000E+ Windows® based software for configuration and monitoring
• Controller Area Network (CAN) interface with CAN 2.0B J1939 protocol for metering and control
• “Power on” LED indicator
• Configurable auxiliary input for metering and control
PROTECTIONS
DVR®2000E+ has the following protection features:
• Field Over Excitation Shutdown
• Generator Over Voltage Shutdown
• Generator Under Voltage Shutdown
• Generator Voltage Imbalance Shutdown
• Loss of Generator Sensing Shutdown
• Field Current Limiting Shutdown
• Instantaneous Field Over Current Shutdown
• Regulator Over Temperature Shutdown
• Generator Under Frequency Alarm
• Generator Reverse Power Flow Alarm
• Loss of CAN Communication Alarm
WARRANTY
When supplied on a generator, the DVR®2000E+ carries the same warranty as the generator. (a) Marathon
warrants Standby Duty Generators manufactured by or for it to be free from defects in materials and workmanship
and to conform to Marathon’s written specifications for a period of 24 months from date of startup or 30 months
from date of shipment or 1000 hours in use, whichever period shall expire first. (b) Marathon warrants Continuous
Duty Generators manufactured by or for it to be free from defects in materials and workmanship and to conform
to Marathon’s written specifications for a period of 12 months from data of startup or 18 months from date of
shipment, whichever period shall expire first.
When supplied as a separate component, Marathon warrants the DVR®2000E+ to be free from defects in
materials and workmanship and to conform to Marathon’s written specifications for a period of 12 months from
date of shipment.
6
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
SECTION 2 – SPECIFICATIONS
Operating Power
Type: 1-phase, ungrounded PMG
Range: 180 to 240 Vac, 250 to 300 Hz
Burden: 350 VA
Fuse Type : Time delay 250 V/4.0 A
Terminals: 3, 4
Contact Inputs
Type: Dry Contact
Input Pull-Up Voltage: 3.3 Vdc
Terminals: DROOP_OFF: J1-10, J1-4
UP: J1-2, J1-4
DOWN: J1-3, J1-4
EXCITATION_OFF: J1-11, J1-4
Field Output
Continuous Rating: 75 Vdc, 3.0 Adc
10 Second Forcing Rating
200 Vac Power Input: 150 Vdc, 7.5 Adc
Field Resistance: 18 to 35 Ohms
Terminals: F+, F-
7
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
AVR1 and AVR3 Operating Modes
Range: 100.0 to 630.0 Vac
Voltage Regulation: ±0.25 % over load range at rated power factor
and constant generator frequency.
Temperature Drift: ±0.0125 %/degree C
Under frequency (V/Hz)
Slope: 1.00 to 3.00 PU
Knee: 40.0 to 70.0 Hz
Parallel Compensation
Modes: Reactive Droop and
Reactive Differential (cross-current)
Droop
Range: 0.0 to 10.0 %
8
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Generator Over Voltage Protection
Threshold: 5.0 to 20.0 %
Timer: 0.75 seconds
Soft-Start Function
Range: 2 to 120 seconds
Auxiliary Input
Auxiliary – Controller (AVR3 or AVR1 regulation)
Voltage Range: -3 Vdc to +3 Vdc
Set point Range: -30 % to +30 % shift
Burden: 2260 Ohms
Terminals: J1-1 (+), J1-12 (-)
9
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Metering
Accuracy of all metering values assumes 25° C, 50/60 Hz and less than 20 % THD.
Regulator-side Metering
Generator Voltage
Range: 10 Vac to 600 Vac
Accuracy: 0.5 %
Generator Current
Range: 0.1 to 5.000 Aac (5 Aac CTs)
Accuracy: 0.5 %
Power (Apparent, Real and Reactive)
Range: 0 to 5200 VA and W
0 to 4160 VAR leading/lagging
Accuracy: 3.0 %
Power Factor
Range: 0.6 to 1.0 leading/lagging
Accuracy: 0.02
Frequency
Range: 40 to 75 Hz
Accuracy: 0.2 Hz
Field Voltage
Range: 0 to 200 Vdc
Accuracy: 5.0 %
Field Current
Range: 0 to 8.0 Adc
Accuracy: 0.5 %
10
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Environmental
Operating Temperature: -40° C to +70° C (-40° F to +158° F)
Storage Temperature: -40° C to +85° C (-40° F to +185° F)
Relative Humidity: < 95 %, non-condensating
Ingress Protection: IP52 (front side mounted in conduit box)
IP10 (rear side with protective cover)
Environmental Tests
Humidity: Tested per MIL-STD-705B, Method 711-D
Salt Fog: Tested per MIL-STD-810E
Electromagnetic Compatibility
Immunity: Meets EN 61000-6-2: 2005 Electromagnetic compatibility (EMC) – Part
6-2: Generic standards – Immunity for industrial environments
Emission: Meets EN 61000-6-4: 2007 Electromagnetic compatibility (EMC) – Part
6-4: Generic standards – Emission standard for industrial environments
Mechanical Tests
Shock: 20 Gs in 3 perpendicular planes
Vibration: 2.5 Gs at 5 to 26 Hz
0.050” double amplitude (27 to 52 Hz)
7 Gs at 53 to 500 Hz
Physical
Weight: 3 lb. (1361 g)
Mating Connectors
J1: Mating Plug Housing: Deutsch DT06-12SB-P012
Mating Plug Wedge Lock: W12S-P012
Mating Plug Terminals: 0462-201-16141
11
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
SECTION 3 – FEATURES AND PROTECTION
INTRODUCTION
This section describes how the DVR®2000E+ functions and explains its operating features. DVR®2000E+
functions are illustrated in the block diagram of Figure 3-1.
Generator Voltage
Generator voltage is measured at terminals E1 (A-phase), E2 (B-phase), and E3 (C-phase). Nominal voltages of up
to 600Vac may be sensed at these terminals. Voltage applied to these inputs is scaled, conditioned and applied
to the controller.
Line Currents
Generator line currents (IA, IB, IC) are measured via current transformers (CTs) at connector J2 or terminals CT1
and CT2. Current up to 5 Arms may be monitored at these terminals. These currents are scaled, conditioned and
applied to the controller. Refer to Specifications in Section 1 for connector pin assignments.
Field Voltage
Voltage across the regulator field is monitored at terminals, F+ and F-.
Field Current
Current through the exciter field winding is measured at terminal F+. Field current is scaled, conditioned and
applied to the input of the controller.
UP
Closing the UP contact across terminals J1-2 and J1-4 causes the active operating set point to increase. Keeping
the contact closed will continue to increase the operating set point until the limit is reached. The limit is determined
by the value entered in the Maximum Voltage Adjust field of the Windows® software. This field is adjustable in
0.1% increments and allows an input range of 0.0% to 15.0%. The effect the UP and DOWN contacts are having
on the set point is displayed in the Windows® software.
12
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Figure 3-1. Simplified Block Diagram
DOWN
Closing the DOWN contact across terminals J1-3 and J1-4 causes the active operating set point to decrease.
Keeping the contact closed will continue to decrease the operating set point until the limit is reached. The limit
is determined by the value entered in the Maximum Voltage Adjust field of the Windows® software. This field is
adjustable in 0.1% increments and allows an input range of 0.0% to 15.0%. The effect the UP and DOWN contacts
are having on the set point is displayed in the Windows® software.
Note: If power is removed from the DVR®2000E+, the settings from the remote UP/DOWN contacts will be lost.
DROOP_OFF
Closing the DROOP_OFF contact across terminals J1-10 and J1-4 disables voltage droop. An open contact
enables voltage droop. This function enables reactive load sharing between generators operating in parallel.
EXCITATION_OFF
Closing the EXCITATION_OFF contact across terminals J1-11 and J1-4 disables field excitation. An open contact
enables field excitation. This function enables removal of excitation without removing power to the regulator.
Opening the EXCITATION_OFF contact will initiate a soft start and clear any alarm or fault conditions.
Communication Port
The communication port provides an isolated interface for user programming (setup) of the DVR®2000E+ through
the Windows® communication software. Connection is made to the female RS-232 (DB-9) connector with a user-
supplied, standard 9-pin cable. A Null modem cable is unacceptable.
13
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Controlled Area Network (CAN) Port
The CAN port provides an isolated interface for communication with and control of the DVR®2000E+. This permits
the integration of the DVR®2000E+ as a node on a CAN network. Connection is made to the J3 connector with a
user-supplied Amp/Tyco Mini Mate-N-Lok plug (see Section 2 – Specifications). The communication is powered
from a transformer-isolated supply.
Controller
The controller portion of the DVR®2000E+ includes the microprocessor and performs measurement, computation,
control and communication functions by the use of its embedded programming and the nonvolatile settings stored
in its memory.
Power Supply
The internal switch-mode power supply is fed from the power input stage and supplies power at the required DC
voltage levels to the internal circuitry of the DVR®2000E+.
14
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
DVR®2000E+ OPERATING FEATURES
Regulation Modes
The DVR®2000E+ provides three modes of regulation selectable through the HMI or through the Windows®
communication software.
Auxiliary Input
Functionality of the auxiliary input is dependent on the configuration of the modes described below. The auxiliary
input is set to the Auxiliary - Off mode by default and can be set to the Auxiliary - Control or Auxiliary - Meter
modes through the HMI or the Windows® communication software. The effect of the auxiliary input on the set point
is displayed in the Windows® communication software.
Auxiliary - Off
In this mode, any signal applied to the analog input will be displayed in the Windows® communication software,
but will have no effect on the set point of the regulator.
Auxiliary - Control
This mode allows modification of the regulation set point by the application of a positive or negative DC voltage
across terminals J1-1 (+) and J1-12 (-). A voltage up to +/- 3 Vdc may be applied at this input. The circuit imposes
a 2260-ohm burden on the DC source.
In AVR1 or AVR3 regulation modes, the application of a +/- 3 Vdc signal corresponds to a +/- 30% offset to the set
point. This offset is not limited by the Maximum Voltage Adjust field of the Windows® communication software. For
example, with a programmed regulation set point of 480 Vrms, an input of -1 Vdc will result in a –48 Vrms offset to
the set point. Therefore the regulator will regulate to a reference voltage of 432 Vrms.
In the FCR regulation mode, the application of a 0-3 Vdc signal corresponds to a 0-3 Adc field current set point.
For example, the application of a 1.25 Vdc signal will result in a field current of 1.25 Adc.
15
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
: If the DC voltage is removed from the Auxiliary Input, the operating set point will no longer
be modified and the regulator will regulate to the programmed regulation set point.
Auxiliary - Meter
In this mode the auxiliary input functions as a meter with user-defined scaling. A voltage up to +/- 5 Vdc or a cur-
rent of 4 to 20 mA may be applied to terminals J1-1 (+) and J1-12 (-). The circuit imposes a 2260-ohm burden on
the DC source for voltage input. The circuit imposes a 250-ohm burden on the DC source for current input when
a jumper is applied across terminals J1-5 and J1-8. The default scaling is 5000 counts for a +5 Vdc voltage input
and 5000 counts for a 20 mA current input. The user provides further scaling through the Windows® communica-
tion software. For example, if the user provides a scale factor of 0.20 units, the metered value corresponding to a
+5 Vdc voltage input will be +100 units. The metered value corresponding to a 20 mA current input will be +100
units.
Load Sharing
The DVR®2000E+ provides a reactive droop compensation feature to assist in the sharing of reactive load during
parallel generator operation. When this feature is enabled, the DVR®2000E+ calculates the reactive portion of
the generator load using the sensed generator output voltage and current quantities and then modifies the volt-
age regulation set point accordingly. A unity power factor generator load results in almost no change in genera-
tor output voltage. A lagging power factor generator load (inductive) results in a reduction of generator output
voltage. A leading power factor generator load (capacitive) results in an increase of generator output voltage.
Droop is adjustable up to 10 percent with rated line current and 0.8 power factor. The effect of droop on the set
point is displayed in the Windows® communication software. The droop feature is enabled and disabled through
the DROOP_OFF contact input circuit (terminals J1-10 and J1-4). When single-phase current sensing is used,
the droop function responds to phase-B current. When three-phase current sensing is used, the droop function
responds to the average phase current.
16
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
DVR®2000E+ PROTECTION FEATURES
The DVR®2000E+ has the protective functions listed below:
• Field Over Excitation Shutdown
• Generator Over Voltage Shutdown
• Generator Under Voltage Shutdown
• Generator Voltage Imbalance Shutdown
• Loss of Generator Sensing Shutdown
• Field Current Limiting Shutdown
• Instantaneous Field Over Current Shutdown
• Regulator Over Temperature Shutdown
• Generator Under Frequency Alarm
• Generator Reverse Power Flow Alarm
• Loss of CAN Communication Alarm
Each fault or alarm condition is displayed through the HMI and the Windows® communication software.
17
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Generator Under Voltage Shutdown
The DVR®2000E+ has a Generator Under Voltage Shutdown threshold that is adjustable from 5% to 50%
(default of 25%) with a timer that is adjustable from 1.0 to 15.0 seconds (default of 6.0 sec). If generator voltage
drops below the under voltage threshold the timer is started. The HMI will change from a status to an alarm
status with alarm code . The Windows communication software also displays this alarm condition. If generator
®
voltage stays below the under voltage set point for the duration of the timer, the regulator will stop providing
excitation to the field and close the fault output contact. The HMI will change from a alarm status to a fault status
with fault code . The Windows® communication software also displays this fault condition. This is a latch-
ing condition that can be reset by removing power from the regulator for at least 10 seconds or by momentarily
shorting the EXCITATION_OFF circuit. When the DVR®2000E+ is powered up or the EXCITATION_OFF short is re-
moved following a Generator Under Voltage Shutdown, the fault code will flash for 15 seconds on the HMI
and the fault will be indicated in the Windows communication software on the History tab of the Faults and Alarms
®
section of the monitor screen. This protection feature is inactive when operating in the FCR Regulation Mode.
Note: In AVR1 and AVR3 regulation modes, Loss of Sensing is not enabled until a speed of 850 RPM is detected.
18
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Field Current Limiting Shutdown
The DVR®2000E+ has a Field Current Limit that is adjustable from 0.500 to 7.500 A (default of 6.5 A) with an adjust-
able time delay that has a range of 1.0 to 10.0 seconds (default of 10.0 sec). If load conditions dictate that the field
current exceed the field current limit, the timer is started and the current is limited. The HMI will change from a
status to an alarm status with alarm code . The Windows® communication software also displays this alarm
condition. If the current limiting condition continues for the duration of the timer (the default value is 10 seconds),
the regulator will stop providing excitation to the field and close the fault output contact. The HMI will change from
an alarm status to a fault status with fault code . The Windows® communication software also displays this
fault condition. This is a latching condition that can be reset by removing power from the regulator for at least 10
seconds or by momentarily shorting the EXCITATION_OFF circuit. When the DVR®2000E+ is powered up or the
EXCITATION_OFF short is removed following a Field Current Limit shutdown, the fault code will flash on
the HMI and the fault will be indicated in the Windows® communication software on the History tab of the Faults
and Alarms section of the monitor screen.
19
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Generator Under Frequency Alarm
When generator frequency drops below the selected knee frequency set point, the voltage set point is automati-
cally adjusted by the DVR®2000E+ so that generator voltage follows the selected PU (per unit) V/Hz curve. When
operating in an under frequency condition, the HMI will change from a status to an alarm status with alarm
code . The Windows communication software also displays this alarm condition. The knee frequency is ad-
®
justable from 40.0 to 70.0 Hertz (default of 59.0 Hz) and the base slope of the PU V/Hz curve may be modified by a
Slope Multiplier from 1.00 to 3.00 (default of 2.00 PU) through the Windows® communication software. If generator
frequency drops below 25 Hz, the regulator will stop providing generator excitation and AC metering.
If generator frequency drops below a detectable level and generator speed is greater than 850 RPM, a short
circuit condition is assumed and the regulator will force current up to the Field Current Limit value (see Field
Current Limiting).
Under frequency V/Hz slope is dependent upon the knee frequency and the slope multiplier. The base slope is
defined according to the following (see Figure 3-2):
• For a knee between 40.0 and 50.0 Hz, the base slope is 1/50 (0.02) Vpu/Hz,
• For a knee between 50.1 and 60.0 Hz, the base slope is 1/60 (0.0167) Vpu/Hz,
• For a knee between 60.1 and 70.0 Hz, the base slope is 1/70 (0.0143) Vpu/Hz,
where Vpu = 1.0 at regulator voltage set point. The base slope is modified by the Slope Multiplier to achieve a
desired voltage roll-off characteristic. See Figure 3-3 for examples.
20
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Figure 3-3 Examples of Under Frequency and Slope
21
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
SECTION 4 – INSTALLATION
GENERAL
Generally the DVR®2000E+ is supplied mounted to the conduit box of the generator. The purpose of this section
is to provide mounting information to customers replacing an existing regulator with the DVR®2000E+ or those
wishing the mount the regulator remotely.
If the unit is not installed immediately, store it in the original shipping package in an environment free of moisture
and dust.
MOUNTING
The DVR®2000E+ is normally located in the generator conduit box. It is designed for behind-the-panel mounting
and requires a cutout for front panel viewing and access. Mounting hardware consists of six customer-supplied,
#12 thread-forming screws that pass through mounting holes in the conduit box and thread into the plastic shell
of the DVR®2000E+. The unit must be mounted where the ambient temperature does not exceed the allowable
environmental conditions called out in Section 2, Specifications. DVR®2000E+ package dimensions are shown in
Figure 4-1. Cutout and drilling dimensions are shown in Figure 4-2.
When the DVR®2000E+ Voltage regulator is mounted on the generator at the factory a molded cover is
provided. This cover prevents exposure and unintentional contact. This cover must be installed whenever the voltage
regulator is energized.
22
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Figure 4-1. DVR®2000E+ Dimensions with and without cover
23
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Figure 4-2. Cut out and Drilling Dimensions
24
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
CONNECTIONS
DVR®2000E+ connections are dependent on the application. Incorrect wiring may damage the unit.
Note: Be sure that the DVR®2000E+ is hard-wired to earth ground with no smaller than 12 AWG copper wire at-
tached to the ground terminal on the rear of the unit case. When the unit is configured in a system with other de-
vices, it is recommended to use a separate lead to the ground bus from each device.
DVR®2000E+ Connectors
DVR®2000E+ units have four types of interface connectors (see Section 1 – Overview, General). All connectors
are located on the rear of the unit. Wires performing common functions, such as voltage sensing leads, should be
grouped together. Figure 4-3 shows the quick disconnect terminal connections located on the rear panel of the
DVR®2000E+.
25
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Terminal Name Description
GND Protective earth ground
4 PMG – terminal 1
3 PMG – terminal 2 (Fused)
E1 Generator armature – Phase A
E2 Generator armature – Phase B
E3 Generator armature – Phase C
F- Exciter stator field (-)
F+ Exciter stator field (+)
CT1 Generator Phase B CT (X1)
CT2 Generator Phase B CT (X2)
26
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Figure 4-4. System Connectors J1 (left) and J2 (right) Terminal Position
Note: The current transformer primaries are aligned such that the H1 face is nearest to the generator for typical
donut-style current transformers.
27
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
UP and DOWN Contact Inputs
Remote set point adjustment may be accomplished by connecting a SPDT momentary contact switch to the J1
connector UP and DOWN contacts. To connect this switch, the common terminal must be connected to J1-4
(CGND). The other two switch terminals are connected to J1-2 (UP) and J1-3 (DOWN). Refer to Section 3 – Fea-
tures and Protection for a detailed description of the UP and DOWN contact function.
28
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Pin Number Function Name
1 N/C
2 Receive Data RXD
3 Transmit Data TXD
4 Data Terminal Ready DTR
5 Signal Ground GND
6 Data Set Ready DSR
7 Ready To Send RTS
8 N/C
9 N/C
Note: If serial port does not support DTR and RTS functions, then these lines must be connected to serial port
positive supply voltage of Data Terminal Equipment.
29
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
DVR®2000E+ Connections for Typical Applications
Figures 4-7 through 4-10 illustrate typical applications using the DVR®2000E+.
• Figure 4-7 shows an application where the regulator is connected for three-phase voltage sensing and
three-phase current sensing.
• Figure 4-8 shows an application where the regulator is connected for three-phase voltage sensing and
single-phase current sensing.
• Figure 4-9 shows an application where the regulator is connected for with single-phase voltage sensing
and single-phase current sensing.
• Figure 4-10 illustrates an application with a single-phase generator.
Figure 4-11 and 4-12 illustrate how the regulators can be interconnected for use in Cross-Current (Reactive
Differential) applications. When operating in Cross-Current mode, attention must be paid to the use of the burden
resistor shown in Figure 4-11 and 4-12. The burden resistor should have a value of approximately 10 times the
cross current loop resistance for proper differential operation. The value of 0.1 ohm is a suggested value. The
volt-ampere (VA) capacity of the paralleling current transformers should be considered when sizing the burden
resistor.
NOTES k :
1. Excitation enabled when switch is open and disabled when switch is closed. Switch supplied by others.
2. SPDT, spring return to center-off position type switch for remote set point adjust. Switch supplied by others.
3. Droop enabled when switch is open and disabled when switch is closed. Switch supplied by others.
4. Normally open contact closes in a fault condition.
5. Analog signal input when Auxiliary is configured for control or metering.
6. Should be shorted when Auxiliary is configured as 4-20 mA metering input.
7. Sensing potential transformer is required if generator output voltage exceeds 600 Volts.
Figure 4-7. Typical Connections with ABC Rotation, Three-Phase Voltage Sensing and
Three-Phase Current Sensing
30
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
NOTES k :
1. Excitation enabled when switch is open and disabled when switch is closed. Switch supplied by others.
2. SPDT, spring return to center-off position type switch for remote set point adjust. Switch supplied by others.
3. Droop enabled when switch is open and disabled when switch is closed. Switch supplied by others.
4. Normally open contact closes in a fault condition.
5. Analog signal input when Auxiliary is configured for control or metering.
6. Should be shorted when Auxiliary is configured as 4-20 mA metering input.
7. Sensing potential transformer is required if generator output voltage exceeds 600 Volts.
Figure 4-8. Typical Connections with ABC Rotation, Three-Phase Voltage Sensing and
Single-Phase Current Sensing
31
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
NOTES k :
1. Excitation enabled when switch is open and disabled when switch is closed. Switch supplied by others.
2. SPDT, spring return to center-off position type switch for remote set point adjust. Switch supplied by others.
3. Droop enabled when switch is open and disabled when switch is closed. Switch supplied by others.
4. Normally open contact closes in a fault condition.
5. Analog signal input when Auxiliary is configured for control or metering.
6. Should be shorted when Auxiliary is configured as 4-20 mA metering input.
7. Sensing potential transformer is required if generator output voltage exceeds 600 Volts
Figure 4-9. Typical Connections with ABC Rotation, Single-Phase Voltage Sensing and
Single-Phase Current Sensing
32
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
NOTES k :
1. Excitation enabled when switch is open and disabled when switch is closed. Switch supplied by others.
2. SPDT, spring return to center-off position type switch for remote set point adjust. Switch supplied by others.
3. Droop enabled when switch is open and disabled when switch is closed. Switch supplied by others.
4. Normally open contact closes in a fault condition.
5. Analog signal input when Auxiliary is configured for control or metering.
6. Should be shorted when Auxiliary is configured as 4-20 mA metering input.
7. Sensing potential transformer is required if generator output voltage exceeds 600 Volts.
33
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Figure 4-11. Cross-Current (Reactive Differential) Connections for Two Generators
34
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
PRELIMINARY SETUP – ON GENERATOR
: .Use caution when working around the component side of the DVR®2000E+. Voltage levels
may be present at the exposed components when the unit is energized. The protective cover must be
installed whenever the regulator is energized.
: Read and understand the operation of the individual adjustments before attempting any
initial adjustments.
The regulator may be configured on the generator using the following procedure:
1. Before starting the engine, remove the regulator’s 4.0 A fuse. This will prevent the generator’s PMG from
energizing the regulator and prevent unintended operating functions from occurring.
2. Perform all preliminary engine governor adjustments with the regulator de-energized.
3. After initial governor adjustments are complete, shut down the prime mover. Reinstall the 4.0 A fuse.
Disconnect the E3 and F+ terminal connectors from the regulator and temporarily insulate them to
prevent accidental shorting.
4. Start and run the generator at rated speed. The regulator will enter a Loss of Sensing shutdown mode,
indicated by on the display.
5. At this time, initial adjustments can be made. If adjusting via the HMI, see “MAKING SETTINGS
CHANGES” in Section 5. If adjusting via the Windows Communication Software, see Section 6.
6. After the initial adjustments are made, shut down the generator and reconnect the regulator leads
removed in Step 3. The generator may be started and final adjustments may be performed on the
regulator.
35
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
PRELIMINARY SETUP – ON BENCH
: .Use caution when working around the component side of the DVR®2000E+. Voltage levels
may be present at the exposed components when the unit is energized. The protective cover must be
installed whenever the regulator is energized.
: Read and understand the operation of the individual adjustments before attempting any
initial adjustments.
After the initial adjustments are made, disconnect the 120 Vac source and install the regulator onto the generator.
The generator may be started and final adjustments may be performed on the regulator.
36
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
SECTION 5 - HUMAN-MACHINE INTERFACE
GENERAL
The DVR®2000E+ human-machine interface (HMI) consists of a four-button keypad and four-character LED
display as illustrated in Figure 5-1. The display indicates status conditions and parameter settings. Button function
descriptions are given in Table 5-1.
Button Description
This pushbutton steps the user through a menu list of editable
SELECT
parameters. It also serves as an escape key in EDIT mode.
This pushbutton increases the setting level of the parameter
UP
being adjusted.
This pushbutton decreases the setting level of the parameter
DOWN
being adjusted.
This pushbutton stores the current value of the parameter being
ENTER
adjusted and returns the user to the main menu list.
37
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
FRONT PANEL DISPLAY
The HMI display has three display modes:
1. STATUS mode – the HMI displays the non-editable operating state of the DVR®2000E+ as described in
Table 5-2. The display flashes while in STATUS mode.
2. EDIT mode - The HMI displays a multi-layer menu for reading and editing operating parameters of the
DVR®2000E+ as described in Table 5-3. The display is steady-on while in EDIT mode.
3. SLEEP mode – The HMI turns off the display after a period of button-press inactivity.
Display Description
(no display) No display is the default mode of the HMI. No display indicates that
the regulator is operating normally, but operating in a sleep mode.
This display indicates that the regulator is operating normally with
excitation enabled.
This display indicates that the regulator is operating normally and
excitation is disabled.
(where xxx in- This display indicates that the regulator is in an alarm state. During
dicates a three-digit this state, the regulator continues to provide excitation if excitation
alarm code) is enabled. (See Appendix for description of Alarm Codes)
(where xxx in- This display indicates that the regulator is in a fault state. During
dicates a three-digit this state, the regulator ceases to provide excitation.
alarm code) (See Appendix for description of Fault Codes)
38
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Parameter Parameter Value Description
Name
Frame size of generator
AVR3 – Voltage regulator with three-phase sensing
AVR1 – Voltage regulator with single-phase sensing
FCR – Field current regulator
Voltage set point (Vrms) in AVR3 and AVR1 mode
Field current set point (Adc) in FCR mode
Under frequency knee (Hz)
Voltage droop (%) at rated reactive current
Auxiliary Off – Auxiliary input is disabled
Auxiliary Control – Auxiliary input modifies regulation set point
Auxiliary Meter – Auxiliary input is used as a meter with user-
defined scale factor
Table 5-3. DVR®2000E HMI EDIT Mode Parameters
NOTE: While in STATUS mode, pressing either the UP or DOWN button places the regulator directly into EDIT
mode. This feature allows a shortcut to set point adjustment.
39
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
SECTION 6 – GRAPHICAL USER INTERFACE
The DVR®2000E+ Graphical User Interface (GUI) offers the user a means of programming the regulator and
monitoring generator performance. This Windows® based software is available as a free download from the
Marathon Electric website, www.marathonelectric.com. With this software, the user will be able to change all of
the user programmable parameters.
The GUI consists of a header, and three tabbed panels (Metering, Configuration and Identification). The
header displays regulator status and basic administration functions. The Metering tab displays metered quantities
and fault information. The Configuration tab permits regulator setting of all user programmable parameters. The
identification tab contains information specific to the regulator and allows for customer tags.
HEADER BUTTONS
Administration
This button allows the user to change serial port communication settings and modify passwords.
Login
The default user type is Customer. The type of user logged in is displayed in the header area.
Save to EEPROM
When this button is pressed, all parameter values in the regulator’s RAM (Configuration and Identification tabs)
are transferred to the regulator’s user settings in EEPROM. These user settings are loaded into RAM whenever the
regulator is powered up. Any parameters adjusted before saving are lost.
Load Config
When this button is pressed, the user will be prompted to select a previously saved .xml file. When the file is
selected, all user-adjustable settings are loaded into the volatile RAM memory of the DVR®2000E+ from the
selected .xml file. These settings can be transferred to the user settings in non-volatile EEPROM by pressing the
“Save to EEPROM” button.
Note: When a file is transferred from a computer to the regulator, the operating status will switch to “OFF” and
excitation be disabled To enable excitation, go to the Operating Modes sub panel of the Configure tab and click
the “Excitation ON” button.
40
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Save Config
When this button is pressed, the user will be prompted to select a .xml file name. When the file is selected, all user
adjustable settings presently in the volatile RAM memory are saved into the selected .xml file. These settings can
be edited and loaded to the regulator’s volatile RAM memory by pressing the “Load Config” button.
Note: .xml files are text files that can be printed for reference.
Connect
When this button is pressed, the GUI establishes communication with the regulator. Communication must be
established before data can be transferred between the regulator and the GUI. When connected, this button dis-
plays “Disconnect” to permit disconnection of communication.
On some of the parameter selection screens, you will find the following buttons:
Apply – This button sends the values in a given area presently being displayed to the regulator’s RAM. These
values can be sent to the regulator’s EEPROM by pressing the Save to EEPROM button in the header area of the
GUI.
Undo – This button displays the values in a given parameter area previous to the last change the user made.
These values can be sent to the regulators RAM by clicking on the Apply button. From there, these values can be
sent to the regulator’s EEPROM by pressing the Save to EEPROM button in the header area of the GUI.
Refresh – This button displays the values in a given parameter area that are presently in the regulators RAM.
These values can be sent to the regulator’s
Metering Tab
This panel displays Line-to-Line Voltages, Line-to-Neutral Voltages, Line Currents, Real Power, Apparent
Power and Reactive Power. When the Generator tab is active (default), the values displayed correspond to the
generator output terminals (primaries of potential and current transformers). When the Regulator tab is active, the values
displayed correspond to the regulator terminals (secondary sides of potential and current transformers). In
addition, values for Power Factor, Field Current, Field Voltage, Regulator Temperature, Speed and Auxiliary Input
Voltage are displayed.
There is also a tabbed panel for the display of faults and alarms. When the Current Faults and Alarms tab is active,
the panel displays faults and alarms that are currently active on the regulator. When the Historical tab is active, the
panel displays the faults and alarms that were present (if any) the previous time the regulator was energized.
Note: The historical fault data will clear 15 seconds after regulator power-up or until another alarm or fault
is detected.
41
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
If the regulator is in an alarm state, there will be a yellow indicator next to the corresponding condition causing the
alarm and the status indicator in the header will display a yellow “Alarm” state. If the regulator is in a fault state,
there will be a red indicator next to the corresponding condition causing the fault and the status indicator in the
header will display a red “Fault” state. If the regulator is in a run state, there will be a green indicator next to all
active alarm and fault conditions in this panel and the status indicator in the header will display a green “Run”
state. If a given alarm or fault condition is disabled (for example Generator Voltage Imbalance in AVR1 regulation
mode), that condition will display a gray indicator.
Configuration Tab
In this panel there are four tabbed sub panels: Operating Modes (default), Set Points, Protection Settings and CAN
Bus Configuration.
AVR3 Regulation Mode corresponds to Automatic Voltage Regulation for three-phase generator voltage
sensing.
AVR1 Regulating Mode corresponds to Automatic Voltage Regulation for single phase generator voltage
sensing.
FCR Regulation Mode corresponds to Field Current Regulation. In this mode the regulator will maintain a fixed
level of field current.
Three Phase Current Sensing activates metering of all three phase currents. This sensing mode should only be
selected when using three current transformers.
Single Phase Current Sensing activates metering of phase-B current. This sensing mode should only be
selected when using one current transformer in phase-B. Currents for phases A and C will not be metered.
Excitation Off deactivates excitation to the generator exciter field. The status indicator in the header will display
a gray “Off” state. This state is recommended for making adjustments to the user settings.
Excitation On activates excitation to the generator exciter field. If the regulator was previously “Off,” selecting this
state will initiate a new soft start ramp.
Generator Frame Size selects stability settings for the chosen frame size. Settings are displayed with gray num-
bers in the panel. Selecting the appropriate frame size chooses proportional, integral and derivative gain values.
These gain values are not editable. For editable custom gains, Generator Frame Size “CUST” should be selected.
Choosing “CUST” will copy the gains from the previous frame size. The grayed gains will then become active for
editing. Saving to EEPROM will store the edited gains to the user settings.
42
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Set Points Sub Panel
This panel contains editable fields for Regulator Voltage Set Point, Maximum Voltage Adjust, Field Current Set
Point, Under Frequency Knee, Under Frequency Slope, Droop, Auxiliary Input Scale Factor, PT Ratio and CT Ratio
and a radio button for configuration of the auxiliary input port. Offsets to the regulator set point are also displayed
in this panel.
Regulator Voltage Set Point is editable in AVR1 or AVR3 Regulation Modes. This value represents the desired
voltage at the regulator voltage sensing terminals, regardless of potential transformers. Offsets from the UP and
DOWN contacts, auxiliary input port, droop and/or the CAN bus are derived from this set point.
If there are no PTs (potential transformers) in the system, and the regulator sensing leads are connected line-to-
line, the desired generator output voltage is the Regulator Voltage Set Point. If the regulator sensing leads are
connected midpoint-to-midpoint of a series wye configuration, the desired generator output voltage is twice the
Regulator Voltage Set Point.
If there are PTs in the sensing circuit, the desired generator output voltage is determined by the multiplication of
the PT ratio and the Regulator Voltage Set Point.
Maximum Voltage Adjust is the maximum adjustment percentage of the Regulator Voltage Set Point allowed
through use of the UP and DOWN contact inputs.
Field Current Set Point is editable in FCR Regulation Mode. This value represents the desired field current of the
regulator. The regulator will maintain this fixed level of field current regardless of changes in load.
Under Frequency Knee is the value of frequency below which the regulator operates in a Volts-per-Hertz mode.
Refer to Section 3 – Features and Protection for a detailed description of Generator Under Frequency.
Slope Multiplier is the factor applied to the base slope for voltage roll-off with respect to frequency in a Volts-
per-Hertz mode. Refer to Section 3 – Features and Protection for a detailed description of Generator Under
Frequency.
Droop is the maximum percentage of Regulator Voltage Set Point allowed for adjustment of voltage during load
sharing with another generator. Refer to Section 3 – Features and Protection for a detailed description of Load
Sharing.
Auxiliary Input Scale Factor is used when the auxiliary input port is configured as “Auxiliary – Meter.” This value
scales the auxiliary input. Refer to Section 3 – Features and Protection for a detailed description of the Auxiliary
Input function.
PT Ratio is the value of the potential transformer ratio of the system. The generator output voltages displayed in
the Generator tab of the Metering panel are equivalent to the voltages displayed in the Regulator tab times this
value. Example: A PT with a 13,200 Volt primary rating and a 230 Volt secondary rating would have a PT ratio of
57.39.
CT Ratio is the value of the current transformer ratio of the system. The generator output currents displayed in the
Generator tab of the Metering panel are equivalent to the currents displayed in the Regulator tab times this value.
Example: A CT with an 800 A primary rating and a 5 A secondary rating would have a CT ratio of 160.
43
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Auxiliary Input Type configures the auxiliary input port as a controller, a meter or off. Refer to Section 3 – Features
and Protection for a detailed description of the Auxiliary Input function.
Contact Offset displays the effect that the contact inputs have on the regulator set point value. Refer to Section
3 – Features and Protection for a detailed description of the UP and DOWN contact input functions.
Auxiliary Offset displays the effect that the auxiliary input has on the regulator set point value. Refer to Section
3 – Features and Protection for a detailed description of the Auxiliary Input function.
Droop Offset displays the effect that the regulator’s droop function has on the regulator set point value. Refer to
Section 3 – Features and Protection for a detailed description of the Load Sharing function.
CAN Offset displays the effect that the Set Point Adjust CAN message has on the regulator set point value. Refer
to Section 8 – CAN Bus Interface for a detailed description of the Set Point Adjust message.
Total Set Point displays the total reference to the controller within the regulator. This reference value is comprised
of the set point and any offsets currently active.
44
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Voltage Imbalance Timer is the amount of time the regulator operates before shutting down due to a Generator
Voltage Imbalance fault. Refer to Section 3 – Features and Protection for a detailed description of the Generator
Voltage Imbalance Shutdown protection feature.
Identification Tab
This panel contains non-editable fields for Serial Number, Software Version, Settings Version and MODBUS
Address. It also contains editable fields for Customer Tags.
Serial Number is the serial number of the regulator.
Software Version is the version of regulator firmware.
Settings Version is the version of factory default settings for the regulator.
MODBUS Address is the MODBUS address of the regulator.
Customer Tag 1 is a 15-character string that can be stored to the regulator’s non-volatile memory when the Save
to EEPROM button is pressed.
Customer Tag 2 is a 15-character string that can be stored to the regulator’s non-volatile memory when the Save
to EEPROM button is pressed.
45
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
SECTION 7 – MAINTENANCE AND TROUBLESHOOTING
PREVENTATIVE MAINTENANCE
The only preventive maintenance required on the DVR®2000E+ is to periodically check that the connections
between the DVR®2000E+ and the system are clean and tight. The only user serviceable part on this regulator is
the fuse. Marathon Electric recommends that no repair procedures, other than replacing the fuse if needed, be
attempted by anyone other than Marathon Electric personnel.
TROUBLESHOOTING
If you do not get the results that you expect from the DVR®2000E+, first check the programmable settings for
the appropriate function. Use the following troubleshooting procedures when difficulties are encountered in the
operation of your excitation system.
46
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Step 6. Verify that the DVR®2000E+ soft start settings are correct. Too long of a soft start setting may give the
appearance of no buildup.
If the soft start settings are incorrect, adjust the settings.
If the soft start settings have no effect, proceed to Step 7.
Step 7. Further system troubleshooting may be required. If it is determined that the rest of the system is not the
source of the problem, the DVR®2000E+ may need to be replaced.
47
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Step 9. Low generator output voltage may occur when the regulator input is being influenced by the UP and
DOWN contacts. Refer to Section 3 – Features and Protection for more information about the UP and
DOWN contacts.
If the low voltage condition is not caused by the UP and DOWN contacts, proceed to Step 10.
Step 10. Further system troubleshooting may be required. If it is determined that the rest of the system is not the
source of the problem, the DVR®2000E+ may need to be replaced.
48
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Step 5. Verify that the front panel display is not indicating an alarm status. If the display indicates an alarm
status, refer to Appendix A – Alarm and Fault Codes to determine what alarm condition is being
indicated. Check the generator and/or load conditions. Determine what is causing the alarm condition
and resolve the issue. Interrupt input power or shutdown the generator for a minimum of 30 seconds.
Repeat Step 6 until all alarm conditions have been resolved. When the display shows a status of RUN,
the regulator is functioning properly. If the generator voltage regulator is still poor, proceed to Step 6.
Step 6. Low generator output voltage may occur when operating in droop mode with an inductive load. Refer to
Section 3 – Features and Protection for more information about the Load Sharing function.
If the low voltage condition is not caused by the droop function, proceed to Step 7.
Step 7. Low generator output voltage may occur when the regulator input is being influenced by the auxil-
iary input. Refer to Section 3 – Features and Protection for more information about the Auxiliary Input
function.
If the low voltage condition is not caused by the auxiliary input, proceed to Step 8.
Step 8. Low generator output voltage may occur when the regulator input is being influenced by the UP and
DOWN contacts. Refer to Section 3 – Features and Protection for more information about the UP and
DOWN contacts.
If the low voltage condition is not caused by the UP and DOWN contacts, proceed to Step 9.
Step 9. Further system troubleshooting may be required. If it is determined that the rest of the system is not the
source of the problem, the DVR®2000E+ may need to be replaced.
49
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Step 5. Low generator output voltage may occur when operating in droop mode with an inductive load. Refer
to Section 3 – Features and Protection for more information about the Load Sharing function.
If the low voltage condition is not caused by the droop function, proceed to Step 6.
Step 6. Low generator output voltage may occur when the regulator input is being influenced by the auxiliary
input. Refer to Section 3 – Features and Protection for more information about the Auxiliary Input func-
tion.
If the low voltage condition is not caused by the auxiliary input, proceed to Step 7.
Step 7. .Low generator output voltage may occur when the regulator input is being influenced by the UP and
DOWN contacts. Refer to Section 3 – Features and Protection for more information about the UP and
DOWN contacts.
If the low voltage condition is not caused by the UP and DOWN contacts, proceed to Step 8.
Step 8. Further system troubleshooting may be required. If it is determined that the rest of the system is not the
source of the problem, the DVR®2000E+ may need to be replaced.
50
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Loss of Generator Sensing ( ) is displayed on the HMI
Step 1. Verify that the voltage sensing leads are properly connected.
If the sensing leads are not properly connected, correct the connections.
If the sensing lead connections are correct, proceed to Step 2.
Step 2. Verify that the sensing leads E1, E2 and E3 are all connected per the appropriate figure in Section 4 for
the regulator mode being used.
If E2 and E3 are not connected properly, connect them per the appropriate figure in Section 4.
If E2 and E3 are properly connected, proceed to Step 3.
Step 3. Verify that the sensing potential transformer (if used) has the correct turns ratio and is functioning
properly.
If the sensing potential transformer has the wrong turns ratio or is malfunctioning, replace it.
If the sensing potential transformer is correct and functioning properly, proceed to Step 4.
Step 4. Verify that the generator output voltage is present on all phases.
If the generator is missing a phase, refer to the generator manual for further system troubleshooting.
If generator output voltage is balanced on all phases, proceed to Step 5.
Step 5 Further system troubleshooting may be required. If it is determined that the rest of the system is not the
source of the problem, the DVR®2000E+ may need to be replaced.
51
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
No Droop
Step 1. Verify that the DVR®2000E+ DROOP_OFF contact input is open.
If the DROOP_OFF contact input is not open, it must be opened to enable the droop function.
If the DROOP_OFF contact input is open, proceed to Step 2.
Step 2. Verify that the DVR®2000E+ droop setting is not adjusted to 0% droop.
If the droop setting is adjusted to 0% droop, increase the set point above 0%.
If the droop setting is adjusted to above 0%, proceed to Step 3.
Step 3. Check for an open in the circuit connected to any CTs used for current sensing.
If there is an open circuit, repair as necessary.
If there is no open circuit, proceed to Step 4.
Step 4. Verify that all connections are correct according to Figures 4-? and 4-?.
If connections are incorrect, correct the problem.
If connections are correct, proceed to Step 5.
Step 5. Verify that the load being applied to the generator for droop testing is not purely resistive.
If only a resistive load is being applied to the generator, apply an inductive load and retest.
If the load being applied to the generator is inductive, proceed to Step 6.
Step 6. Verify that the DVR®2000E+ is compatible with the current sensing transformer (5 A secondary) being
used. For example, a current sensing transformer with a 1 ampere output rating would produce very little
droop since your DVR®2000E+ has a 5 ampere current transformer input.
If the current transformer input is incorrect, replace the current sensing transformer for compatibility.
If the current transformer input is correct, proceed to Step 7.
Step 7. Further system troubleshooting may be required. If it is determined that the rest of the system is not the
source of the problem, the DVR®2000E+ may need to be replaced.
52
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
SECTION 8 – CAN BUS INTERFACE
The DVR®2000E+ utilizes a CAN BUS interface for reporting metered quantities and providing set point control.
The protocol for the CAN is CAN 2.0B with the J1939 Superset per ISO 11898, SAE J1939-11 and SAE J1939-21.
MESSAGE FORMAT
The message format for the DVR®2000E+ is the 29-bit extended frame identifier followed by 8 bytes of data.
All messages use the Proprietary PDU2 Format in Section 5.3 of SAE J1939-21, Revision APR 2001. For the
DVR®2000E+ protocol, the 29 bit identifier is defined as follows:
• The Priority Bits field is user-settable from 0-5 for a given message group.
• The Reserved Bit (R) is set to zero (0) for all messages.
• The Data Page (DP) bit is set to zero (0) for all messages.
• The Proprietary PDU2 Format byte is 0xFF for all messages
• The PDU Specific byte is uniquely defined for each message as a group extender of the PDU2 format
• The Source Address is the user-settable regulator address for outbound messages or the address of the
control ECU communicating to the regulator for inbound messages
The message identifier field is followed by 8 bytes (64 bits) of data. No message shall require more than one pack-
et to complete the exchange of data. Multi-packet messaging is not used in the DVR®2000E+ protocol. Message
contents in the tables below defined as “0x??” indicate a variable quantity within a data byte. Fixed quantities are
identified where applicable. By default, unused data bytes are filled with the “0xFF” byte.
The source address for the DVR®2000E+ and the electronic control units (ECUs) that it responds to can be edited
in the Windows® communication software. The default DVR®2000E+ address is 0 and the range is 0-255d. The
regulator will respond to messages from up to three different ECUs with addresses also in the range 0-255d.
Outbound messages from the DVR®2000E+ are divided into 4 message groups: meter, control, generator
status and regulator status. Inbound messages are not included in these groups. Each of these groups has a
configurable message rate and data priority. Priority has a default value of 0 but can be in the range of 0-5.
Message transmission rates are editable as follows:
53
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
The DVR®2000E+ also has a timeout feature defined by the timeout message time. This feature is disabled if the
timeout time is set to 0 seconds. For any other value of timeout time, the DVR®2000E+ will enunciate a Loss of
Communication alarm (Alarm Code A006) unless any ECU delivers a VR Heartbeat message to the DVR®2000E+
within the prescribed timeout time. This alarm is latched until the regulator receives a VR Heartbeat message.
The DVR®2000E+ message set is defined in the following tables. For each message, the message ID is the
hexadecimal value of the PDU Format and PDU Specific fields combined. Since the DVR®2000E+ uses PDU2
format, the first two bytes of all of the identifiers are 0xFF. The message group field identifies which group an
outbound message belongs to for purposes of its priority and transmission rate. The source field identifies
messages coming from the DVR®2000E+ (outbound) or to the regulator from an ECU (inbound).
Data byte 0 is the first data byte after the message identifier and data byte 7 is the last data byte. For bit fields
within these data bytes, bit 7 is the most significant bit (leftmost) within a byte and bit 0 is the least significant bit
(rightmost) within a byte. Unless otherwise specified, all values are unsigned bytes. For values containing a Least
Significant Byte (LSB) and a Most Significant Byte (MSB), the result is an unsigned 16-bit word composed of the
two bytes unless otherwise stated.
54
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
OUTBOUND MESSAGES FROM DVR®2000E+
GENERATOR AVERAGE VOLTAGE AND CURRENT (GENERATOR OUTPUT) – This message contains average
generator line voltage and phase current at the generator output after possible step-up from potential and current
transformers.
Message ID (0xFF19) – Generator Average Voltage and Current (Generator Output)
Source: DVR®2000E+
Message Group: Metering
PDU Format: 255 (PDU2)
PDU Specific: 25
Byte 0 Average RMS Current (LSB) – this is the Least Significant Byte of the average
three-phase root-mean-square current. (1 bit = 1 Arms)
Byte 1 Average RMS Current (MSB) – this is the Most Significant Byte of the average
three-phase root-mean-square current (1 bit = 1 Arms)
Byte 2 Average Line-to-Line RMS Voltage (LSB) – this is the Least Significant Byte of the
average of all three line-to-line voltages. (see Voltage Units in message 0xFF1B for
scaling)
Byte 3 Average Line-to-Line RMS Voltage (MSB) – this is the Most Significant Byte of the
average of all three line-to-line voltages. (see Voltage Units in message 0xFF1B for
scaling)
Byte 4-6 PT Ratio – these three bytes comprise the potential transformer ratio as a fixed-point
number. The PT ratio is calculated as: Scalar*2^(-Exp) where Scalar is a 16-bit
word with LSB and MSB given by bytes 4 and 5 and the exponent is given by byte
6. See Message 0xFF39 For a similar representation of the CT Ratio
Byte 7 Unused
55
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
GENERATOR AVERAGE VOLTAGE AND CURRENT (REGULATOR SENSING) – This message contains average
generator line voltage and phase current sensed at the regulator after possible step-down from potential and cur-
rent transformers.
Message ID (0xFF39) – Generator Average Voltage and Current (Regulator Output)
Source: DVR®2000E+
Message Group: Metering
PDU Format: 255 (PDU2)
PDU Specific: 57
Byte 0 Average RMS Current (LSB) – this is the Least Significant Byte of the average
three-phase root-mean-square current. (1 bit = 0.001 Arms)
Byte 1 Average RMS Current (MSB) – this is the Most Significant Byte of the average three-
phase root-mean-square current. (1 bit = 0.001 Arms)
Byte 2 Average Line-to-Line RMS Voltage (LSB) – this is the Least Significant Byte of the
average of all three line-to-line voltages. (1 bit = 0.1 Vrms)
Byte 3 Average Line-to-Line RMS Voltage (MSB) – this is the Most Significant Byte of the
average of all three line-to-line voltages. (1 bit = 0.1 Vrms)
Byte 4-6 CT Ratio – these three bytes comprise the current transformer ratio as a fixed-point
number. The CT ratio is calculated as: Scalar*2^(-Exp) where Scalar is a 16-bit
word with LSB and MSB given by bytes 4 and 5 and the exponent is given by byte
6. See Message 0xFF19 For a similar representation of the PT Ratio
Byte 7 Unused
56
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
GENERATOR PHASE PHASE CURRENT (GENERATOR OUTPUT) – This message contains the root-mean-square
phase currents for each individual phase at the output of the generator after step-up from a current transformer.
Byte 0 Average Phase-A AC RMS Current (LSB) – this is the Least Significant Byte of the
average phase-A root-mean-square current. (1 bit = 1 Arms)
Byte 1 Average Phase-A AC RMS Current (MSB) – this is the Most Significant Byte of the
average phase-A root-mean-square current. (1 bit = 1 Arms)
Byte 2 Average Phase-B AC RMS Current (LSB) – this is the Least Significant Byte of the
average phase-B root-mean-square current. (1 bit = 1 Arms)
Byte 3 Average Phase-B AC RMS Current (MSB) – this is the Most Significant Byte of the
average phase-B root-mean-square current. (1 bit = 1 Arms)
Byte 4 Average Phase-C AC RMS Current (LSB) – this is the Least Significant Byte of the
average phase-C root-mean-square current. (1 bit = 1 Arms)
Byte 5 Average Phase-C AC RMS Current (MSB) – this is the Most Significant Byte of the
average phase-C root-mean-square current. (1 bit = 1 Arms)
Byte 6-7 Unused
57
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
GENERATOR PHASE CURRENT (REGULATOR SENSING) – This message contains the root-mean-square phase
currents for each individual phase at the regulator sensing terminals with a 5 Amp secondary on the current
transformer.
Byte 0 Average Phase-A AC RMS Current (LSB) – this is the Least Significant Byte of the
average phase-A root-mean-square current. (1 bit = 0.001 Arms)
Byte 1 Average Phase-A AC RMS Current (MSB) – this is the Most Significant Byte of the
average phase-A root-mean-square current. (1 bit = 0.001 Arms)
Byte 2 Average Phase-B AC RMS Current (LSB) – this is the Least Significant Byte of the
average phase-B root-mean-square current. (1 bit = 0.001 Arms)
Byte 3 Average Phase-B AC RMS Current (MSB) – this is the Most Significant Byte of the
average phase-B root-mean-square current. (1 bit = 0.001 Arms)
Byte 4 Average Phase-C AC RMS Current (LSB) – this is the Least Significant Byte of the
average phase-C root-mean-square current. (1 bit = 0.001 Arms)
Byte 5 Average Phase-C AC RMS Current (MSB) – this is the Most Significant Byte of the
average phase-C root-mean-square current. (1 bit = 0.001 Arms)
Byte 6-7 Unused
58
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
GENERATOR LINE-TO-LINE VOLTAGES (GENERATOR OUTPUT) – This message contains the root-mean-square
line-to-line voltages for each individual phase at the output of the generator after possible step-up from a potential
transformer.
Byte 0 Average Line-to-Line AC RMS Voltage Vab (LSB) – this is the Least Significant Byte
of the average line-to-line AC root-mean-square voltage, Vba.
Byte 1 Average Line-to-Line AC RMS Voltage Vab (MSB) – this is the Most Significant Byte
of the average line-to-line AC root-mean-square voltage, Vba.
Byte 2 Average Line-to-Line AC RMS Voltage Vbc (LSB) – this is the Least Significant Byte
of the average line-to-line AC root-mean-square voltage, Vac.
Byte 3 Average Line-to-Line AC RMS Voltage Vbc (MSB) – this is the Most Significant Byte
of the average line-to-line AC root-mean-square voltage, Vac.
Byte 4 Average Line-to-Line AC RMS Voltage Vca (LSB) – this is the Least Significant Byte
of the average line-to-line AC root-mean-square voltage, Vbc.
Byte 5 Average Line-to-Line AC RMS Voltage Vca (MSB) – this is the Most Significant Byte
of the average line-to-line AC root-mean-square voltage, Vbc.
Byte 6 Voltage Units – an enumerated quantity used to define the scaling for output volt-
ages as follows:
0x00 – scaling for all voltages are 1 bit = 0.1 Vrms
0x01 – scaling for all voltages are 1 bit = 0.1 kVrms
Note: this scaling also applies to output voltages in messages 0xFF19
Byte 7 Unused
59
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
GENERATOR LINE-TO-LINE VOLTAGES (REGULATOR SENSING) – This message contains the root-mean-square
line-to-line voltages for each individual phase at the sensing inputs of the regulator after possible step-down from
a potential transformer.
Byte 0 Average Line-to-Line AC RMS Voltage Vab (LSB) – this is the Least Significant Byte
of the average line-to-line AC root-mean-square voltage, Vba. (1 bit = 0.1 Vrms)
Byte 1 Average Line-to-Line AC RMS Voltage Vab (MSB) – this is the Most Significant Byte
of the average line-to-line AC root-mean-square voltage, Vba. (1 bit = 0.1 Vrms)
Byte 2 Average Line-to-Line AC RMS Voltage Vbc (LSB) – this is the Least Significant Byte
of the average line-to-line AC root-mean-square voltage, Vac. (1 bit = 0.1 Vrms)
Byte 3 Average Line-to-Line AC RMS Voltage Vbc (MSB) – this is the Most Significant Byte
of the average line-to-line AC root-mean-square voltage, Vac. (1 bit = 0.1 Vrms)
Byte 4 Average Line-to-Line AC RMS Voltage Vca (LSB) – this is the Least Significant Byte
of the average line-to-line AC root-mean-square voltage, Vbc. (1 bit = 0.1 Vrms)
Byte 5 Average Line-to-Line AC RMS Voltage Vca (MSB) – this is the Most Significant Byte
of the average line-to-line AC root-mean-square voltage, Vbc. (1 bit = 0.1 Vrms)
Byte 6-7 Unused
60
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
GENERATOR LINE-TO-NEUTRAL VOLTAGES (GENERATOR OUTPUT) – This message contains the root-mean-
square line-to-neutral voltages for each individual phase at the generator output after possible step-up from a
potential transformer.
Byte 0 Average Line-to-Neutral AC RMS Voltage Va (LSB) – this is the Least Significant
Byte of the average line-to-neutral root-mean-square voltage, Va.
Byte 1 Average Line-to-Neutral AC RMS Voltage Va (MSB) – this is the Most Significant
Byte of the average line-to-neutral root-mean-square voltage, Va.
Byte 2 Average Line-to-Neutral AC RMS Voltage Vb (LSB) – this is the Least Significant
Byte of the average line-to-neutral root-mean-square voltage, Vb.
Byte 3 Average Line-to-Neutral AC RMS Voltage Vb (MSB) – this is the Most Significant
Byte of the average line-to-neutral root-mean-square voltage, Vb.
Byte 4 Average Line-to-Neutral AC RMS Voltage Vc (LSB) – this is the Least Significant
Byte of the average line-to-neutral root-mean-square voltage, Vc.
Byte 5 Average Line-to-Neutral AC RMS Voltage Vc (MSB) – this is the Most Significant
Byte of the average line-to-neutral root-mean-square voltage, Vc.
Byte 6 Voltage Units – an enumerated quantity used to define the scaling for output volt-
ages as follows:
0x00 – scaling for all voltages are 1 bit = 0.1 Vrms
0x01 – scaling for all voltages are 1 bit = 0.1 kVrms
Byte 7 Unused
61
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
GENERATOR LINE-TO-NEUTRAL VOLTAGES (REGULATOR SENSING) – This message contains the root-mean-
square line-to-neutral voltages for each individual phase at the generator output after possible step-up from a
potential transformer.
Byte 0 Average Line-to-Neutral AC RMS Voltage Va (LSB) – this is the Least Significant
Byte of the average line-to-neutral root-mean-square voltage, Va. (1 bit = 0.1 Vrms)
Byte 1 Average Line-to-Neutral AC RMS Voltage Va (MSB) – this is the Most Significant
Byte of the average line-to-neutral root-mean-square voltage, Va. (1 bit = 0.1 Vrms)
Byte 2 Average Line-to-Neutral AC RMS Voltage Vb (LSB) – this is the Least Significant
Byte of the average line-to-neutral root-mean-square voltage, Vb. (1 bit = 0.1 Vrms)
Byte 3 Average Line-to-Neutral AC RMS Voltage Vb (MSB) – this is the Most Significant
Byte of the average line-to-neutral root-mean-square voltage, Vb. (1 bit = 0.1 Vrms)
Byte 4 Average Line-to-Neutral AC RMS Voltage Vc (LSB) – this is the Least Significant
Byte of the average line-to-neutral root-mean-square voltage, Vc. (1 bit = 0.1 Vrms)
Byte 5 Average Line-to-Neutral AC RMS Voltage Vc (MSB) – this is the Most Significant
Byte of the average line-to-neutral root-mean-square voltage, Vc. (1 bit = 0.1 Vrms)
Byte 6-7 Unused
62
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
AUXILIARY INPUT METERING - This message displays the mode and metered value of the auxiliary input.
Byte 0 Auxiliary Input Mode – displays the mode selected for the auxiliary input channel
(enumerated)
0x00 Auxiliary Off (default)
0x01 Auxiliary Control
0x02 Auxiliary Meter
Byte 1-2 Scaled Meter Value – displays the metered value of the analog input channel.
If Auxiliary Input Mode is Auxiliary Off or Auxiliary Control, this value corresponds to
a value representing a voltage with 1 bit = 0.001 Volts, signed 16 bit
If Auxiliary Input Mode is Auxiliary Meter, this value represents a scaled, metered
quantity with scale factor given by bytes 3-5.
Byte 3-5 Scale Factor – these three bytes comprise the metering scale factor as a fixed-point
number. The scale factor is calculated as: Scalar*2^(-Exp) where Scalar is a 16-bit
word with LSB and MSB given by bytes 3 and 4 and the exponent is given by byte
5. This scale factor is multiplied by the quantity 0.001 V/bit to obtain the scaled
value represented in bytes 1-2.
63
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
GENERATOR POWER AND POWER FACTOR (GENERATOR OUTPUT) – This message contains the generator
power factor, average total real power, total reactive power and average apparent power as seen at the output of
the generator, possibly stepped up by potential and current transformers.
Byte 0 Generator Power Factor (LSB) – this is the Least Significant Byte of the generator
power factor. (1 bit = 0.001 pu)
Byte 1 Generator Power Factor (MSB) – this is the Most Significant Byte of the generator
power factor. (1 bit = 0.001 pu)
Byte 2 Generator Real 3-phase Power (LSB) – this is the Least Significant Byte of the
generator real power. (1 bit = 0.1kW)
Byte 3 Generator Real 3-phase Power (MSB) – this is the Most Significant Byte of the
generator real power. (1 bit = 0.1kW)
Byte 4 Generator Apparent 3-phase Power (LSB) – this is the Least Significant Byte of the
generator total real power. (1 bit = 0.1kVA)
Byte 5 Generator Apparent 3-phase Power (MSB) – this is the Most Significant Byte of the
generator total real power. (1 bit = 0.1kVA)
Byte 6 Generator Reactive 3-phase Power (LSB) – this is the Least Significant Byte of the
generator total real power. (1 bit = 0.1kVAR)
Byte 7 Generator Reactive 3-phase Power (MSB) – this is the Most Significant Byte of the
generator total real power. (1 bit = 0.1kVAR)
64
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
GENERATOR POWER AND POWER FACTOR (REGULATOR SENSING) – This message contains the generator
power factor, average total real power, total reactive power and average apparent power as seen at the regulator
sensing terminals, possibly stepped down by potential and current transformers.
Byte 0 Generator Power Factor Sense – this is the direction of the generator power factor
as given by the following enumeration:
00 – Lagging Power Factor
01 – Leading Power Factor
Byte 1 Unused
Byte 2 Generator Real 3-phase Power (LSB) – this is the Least Significant Byte of the
generator real power. (1 bit = 1 W)
Byte 3 Generator Real 3-phase Power (MSB) – this is the Most Significant Byte of the
generator real power. (1 bit = 1 W)
Byte 4 Generator Apparent 3-phase Power (LSB) – this is the Least Significant Byte of the
generator total real power. (1 bit = 1 VA)
Byte 5 Generator Apparent 3-phase Power (MSB) – this is the Most Significant Byte of the
generator total real power. (1 bit = 1 VA)
Byte 6 Generator Reactive 3-phase Power (LSB) – this is the Least Significant Byte of the
generator total real power. (1 bit = 1 VAR)
Byte 7 Generator Reactive 3-phase Power (MSB) – this is the Most Significant Byte of the
generator total real power. (1 bit = 1 VAR)
65
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
FIELD CURRENT AND ENGINE SPEED - This message to reports average DC field current, average DC field volt-
age, engine speed and regulator temperature.
Source: DVR®2000E+
Message Group: Control
PDU Format: 255 (PDU2)
PDU Specific: 42
Byte 0 Field Current (LSB) – this is the Least Significant Byte of the regulator field current.
(1 bit = 0.001 Adc)
Byte 1 Field Current (MSB) – this is the Most Significant Byte of the regulator field current.
(1 bit = 0.001 Adc)
Byte 2 Engine Speed (LSB) – this is the Least Significant Byte of the generator engine
speed. (1 bit = 1 rpm)
Byte 3 Engine Speed (MSB) – this is the Most Significant Byte of the generator engine
speed. (1 bit = 1 rpm)
Byte 4 Field Voltage (LSB) – this is the Least Significant Byte of the regulator field voltage.
(1 bit = 0.1 Vdc)
Byte 5 Field Voltage (MSB) – this is the Most Significant of the regulator field voltage. (1 bit
= 0.1 Vdc)
Byte 6 Regulator Temperature (LSB) – this is the Least Significant Byte of the regulator tem-
perature in degrees C. (1 bit = 1 deg C, signed)
Byte 7 Regulator Temperature (MSB) – this is the Most Significant Byte of the regulator tem-
perature in degrees C. (1 bit = 1 deg C, signed)
66
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
VR STATUS - This message indicates the regulator software revision level and regulation status of the VR
Source: DVR®2000E+
Message Group: Regulator Status
PDU Format: 255 (PDU2)
PDU Specific: 90
Byte 0 YEAR (LSB) - The last two digits of the year of the software version date. e.g. for
‘2006’, YEAR (MSB) = 0x06 = 6d 32d
Byte 1 YEAR (MSB) - The first two digits of the year of the software version date. e.g. for
‘2006’, YEAR (LSB) = 0x20 = 32d
Byte 2 MONTH - The month of the software version date. e.g. for ‘12’, MONTH = 0x12 =
18d
Byte 3 DAY - The day of the software version date. e.g. for ‘31’, DAY = 0x31 = 49d
Byte 4 Primary Revision – the primary revision number of the regulator firmware. For Revi-
sion 12.34.56, this byte is 12d.
Byte 5 Secondary Revision – the secondary revision number of the regulator firmware. For
Revision 12.34.56, this byte is 34d.
Byte 6 Tertiary Revision – the tertiary revision number of the regulator firmware. For Revi-
sion 12.34.56, this byte is 56d.
Byte 7 Unused; except for diagnostic and testing modes
67
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
VR OPERATING STATUS - This message indicates the current operating status of the regulator. See Section 3 of
the IOM for more details on the settings of the DVR®2000E+
Byte 0 Excitation Mode – this byte indicates the state of the excitation mode:
0x00 – Exciter Off
0x01 – Exciter On
Byte 1 Frame Size – the Least Significant Byte of the frame size used for the controller
Byte 2 Frame Size – the Most Significant Byte of the frame size used for the controller
Byte 3 Input Source – the input source used for providing power to the regulator:
0x00 – Unused
0x01 – Permanent Magnet Generator
Byte 4 Current Sense Phases – the number of current phases sensed directly through cur-
rent transformers:
0x00 – Three-phase current sensing
0x01 – Single phase current sensing
Byte 5 VR Status – the current operating status of the regulator:
0x00 – Run (regulator operating normally)
0x01 – Off (regulator excitation is off)
0x02 – Alarm (regulator is in alarm state)
0x03 – Fault (regulator is in fault state)
Byte 6 Regulation Mode – the current regulation mode of the regulator:
0x00 – AVR3 (Automatic Voltage Regulation using three phases)
0x01 – FCR (Field Current Regulation)
0x02 – AVR1 (Automatic Voltage Regulation using single phase)
Byte 7 Device Mode – the current device mode for the regulator
0x00 – diagnostics and testing
0x01 – DEVICE_ON (excitation is enabled and regulator is operating normally)
0x02 – diagnostics and testing
0x03 – diagnostics and testing
0x04 – diagnostics and testing
0x05 – diagnostics and testing
0x06 – diagnostics and testing
0x07 – DEVICE_HIST (regulator is displaying historical fault data)
0x0E – diagnostics and testing
68
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
VR ALARMS/FAULTS - This message displays the current status of alarms and faults. For the bit fields associated
with these alarms and faults, the following enumerations define the status of an individual alarm/fault indicator: 00b
= OK, 01b = Alarm active, 10b = Fault active, 11b = Disabled
Byte 0 Alarms and Faults – contains the current state of the following alarm/fault indicators.
Bits 7, 6 - Generator Imbalance
Bits 5, 4 - Generator Under Frequency
Bits 3, 2 - Generator Reverse Power Flow
Bits 1, 0 - Generator Over Voltage
Byte 1 Alarms and Faults – contains the current state of the following alarm/fault indicators.
Bits 7, 6 - Generator Under Voltage
Bits 5, 4 - Generator Loss of Sensing
Bits 3, 2 - Generator Field Current Limiting
Bits 1, 0 - Generator Instantaneous Field Over Current
Byte 2 Alarms and Faults – contains the current state of the following alarm/fault indicators.
Bits 7, 6 - Generator Field Over Excitation
Bits 5, 4 - Generator Regulator Over Temperature
Bits 3, 2 - Generator Loss of CAN Communication
Bits 1, 0 - Unused
Byte 3 Unused
Byte 4 Alarms and Faults – contains the historic value of the following alarm/fault indicators.
Bits 7, 6 - Generator Imbalance
Bits 5, 4 - Generator Under Frequency
Bits 3, 2 - Generator Reverse Power Flow
Bits 1, 0 - Generator Over Voltage
Byte 5 Alarms and Faults – contains the historic value of the following alarm/fault indicators.
Bits 7, 6 - Generator Under Voltage
Bits 5, 4 - Generator Loss of Sensing
Bits 3, 2 - Generator Field Current Limiting
Bits 1, 0 - Generator Instantaneous Field Over Current
Byte 6 Alarms and Faults – contains the historic value of the following alarm/fault indicators.
Bits 7, 6 - Generator Field Over Excitation
Bits 5, 4 - Generator Regulator Over Temperature
Bits 3, 2 - Generator Loss of CAN Communication
Bits 1, 0 - Unused
Byte 7 Unused
69
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
INBOUND MESSAGES FROM ECU1 or ECU2 or ECU3
RESET VR - This message from an ECU resets the regulator. The regulator responds by clearing any faults and
executing its soft start ramp to a stable regulation point.
70
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
VR HEARTBEAT – If the message timeout timer is enabled with a non-zero value, the regulator assumes a heart-
beat message will be sent periodically from an ECU. If this message is not received within the timeout time
specified, the Loss of CAN Communication Alarm will be in an alarm state. The regulator will continue to regulate
normally and broadcast metering messages but may not respond to CAN messages.
71
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
SET POINT ADJUST - this message can be used to adjust the set point of the regulator in its various regulation
modes.
Byte 0 Unused
Byte 1 Unused
Byte 2 Field Current Set Point (LSB) – If Regulation Mode is Field Current Regulation, this
value represents the Least Significant Byte of the field current set point from 0.000-
3.000 A. (1 bit = 1mA)
Byte 3 Field Current Set Point (LSB) – If Regulation Mode is Field Current Regulation, this
value represents the Most Significant Byte of the field current set point from 0.000-
3.000 A. (1 bit = 1mA)
Byte 4 Regulator Voltage Set Point (LSB) – If Regulation Mode is Automatic Voltage Regula-
tion (3 or 1), this value represents the Least Significant Byte of the regulator voltage
set point from 100.0-600.0 V. (1 bit = 0.1 V)
Byte 5 Regulator Voltage Set Point (MSB) – If Regulation Mode is Automatic Voltage Regu-
lation (3 or 1), this value represents the Most Significant Byte of the regulator volt-
age set point from 100.0-600.0 V. (1 bit = 0.1 V)
Byte 6 Voltage Adjust (LSB) – If Regulation Mode is Automatic Voltage Regulation (3 or 1),
this value represents the Least Significant Byte of a voltage adjustment as a signed
quantity (1 bit = 0.1 V). If this voltage adjustment exceeds a threshold (+/-30% of
the voltage regulation set point), it will be saturated.
Byte 7 Voltage Adjust (MSB) – If Regulation Mode is Automatic Voltage Regulation (3 or 1),
this value represents the Most Significant Byte of a voltage adjustment as a signed
quantity (1 bit = 0.1 V). If this voltage adjustment exceeds a threshold (+/-30% of
the voltage regulation set point), it will be saturated.
72
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
EXCITATION ENABLE/DISABLE - this message can be used to disable/enable excitation.
73
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
APPENDIX A
ALARM CODES
During an alarm condition, the HMI will display the code of the corresponding alarm condition. The table below
can be used to determine what condition is causing the alarm.
Alarm Codes
Generator Voltage Imbalance
Generator Under Frequency
Generator Reverse Power Flow
Generator Under Voltage
Field Current Limiting
Field Over Excitation
Regulator Over Temperature
Regulator Over Communication
FAULT CODES
During a fault condition, the HMI will display the code of the corresponding fault condition. The table below can
be used to determine what condition is causing the fault.
Fault Codes
Generator Voltage Imbalance
Generator Over Voltage
Generator Under Voltage
Generator Loss of Sensing
Field Current Limiting
Instantaneous Field Over Current
Field Over Excitation
Regulator Over Temperature
Regulator Over Communication
74
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
APPENDIX B
The following table should be used when making connections via quick disconnect terminals to the regulator.
75
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
Terminal Name Description
GND Protective earth ground
4 PMG – terminal 1
3 PMG – terminal 2 (Fused)
E1 Generator armature – Phase A
E2 Generator armature – Phase B
E3 Generator armature – Phase C
F- Exciter stator field (-)
F+ Exciter stator field (+)
CT1 Generator Phase B CT (X1)
CT2 Generator Phase B CT (X2)
Table B-1. Quick Disconnect Terminals
The following table should be used when making current transformer connections to the regulator.
76
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
The following table should be used when making system connections to the regulator.
The following table should be used when making MODBUS communication connections to the regulator.
The following table should be used when making CAN communication connections to the regulator.
77
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
APPENDIX C
QUICK START PROGRAMMING GUIDE
As the DVR®2000E+ is designed to work on many Marathon Electric generators in many different applications,
it is necessary to program the regulator prior to putting it in service. Please observe the following procedure to
program the regulator through the Human-Machine Interface or HMI:
78
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specifications and this manual without notice.
Revised 07/2011
RBC Manufacturing Corporation
100 East Randolph Street (54401)
P.O. Box 8003 • Wausau, WI 54402-8003
Ph: (715) 675-3311 • Fax: (715) 675-8026
Printed in U.S.A.
GPN046
7038J Rev1 - SK/BH - 2K - 07/11 - FS A Regal Beloit Company