0% found this document useful (0 votes)
89 views40 pages

06-240 07 PassMan Software Manual

Uploaded by

ususari
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
89 views40 pages

06-240 07 PassMan Software Manual

Uploaded by

ususari
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 40

MANUAL

PassMan Software Manual


v1.6.1

Doc no. 06-240 07


© TagMaster AB
PassMan Software Manual Doc no. 06-240 07

Revision Date Comment


03 2007-10-16 Updated for System Software 1.4.0
04 2008-03-28 Updated for System Software 1.5.0
05 2008-05-07 Updated for System Software 1.5.1
06 2009-04-29 Updated for System Software 1.6.0
07 2009-08-31 Updated for System Software 1.6.1

Copyright
The copyright and ownership of this document belongs to TagMaster AB. The document may be
downloaded or copied provided that all copies contain the full information from the complete document. All
other copying requires a written approval from TagMaster AB.
Disclaimer
While effort has been taken to ensure the accuracy of the information in this document TagMaster AB
assumes no responsibility for any errors or omissions, or for damages resulting from the use of the
information contained herein. The information in this document is subject to change without notice.

© TagMaster AB 2 (40)
PassMan Software Manual Doc no. 06-240 07

1 Introduction 4
2 General Information 5
2.1 Basic Tasks .................................................................................................. 6
2.2 Communication Interfaces ............................................................................ 7
2.3 ID-tag Data ................................................................................................... 8
3 Message Formats 8
3.1 Site Code...................................................................................................... 9
3.2 ID-tag Mark ................................................................................................. 10
3.3 Mag-stripe Message Format ....................................................................... 11
3.4 Wiegand Message Format .......................................................................... 12
3.5 Serial Message Format............................................................................... 13
4 Serial Communication Commands 15
4.1 Commands Sent from the Host to the Reader............................................. 15
4.2 Messages sent from the Reader to the Host ............................................... 17
5 Configuration 19
5.1 Configuration Interfaces.............................................................................. 19
5.2 System Settings.......................................................................................... 22
5.3 ID-tag Settings ............................................................................................ 30
6 Testing 37
6.1 Testing the Reading Lobe ........................................................................... 37
6.2 Trouble Shooting ........................................................................................ 37
7 Contact 38
7.1 Technical Support ....................................................................................... 38
7.2 Office .......................................................................................................... 38
8 Glossary 39
9 References 40

© TagMaster AB 3 (40)
PassMan Software Manual Doc no. 06-240 07

1 Introduction
This section introduces PassMan, which is application software for the LR-series
Reader.

The PassMan software is suited for a Reader which is being integrated with an existing
access control system or for a Reader connected to a host computer and used in an
identification system. The Reader communicates with an access control system or a
host computer via standard communication interfaces.

The Reader has two main software layers. Every Reader is installed with system
software, which constitutes the software foundation of the Reader. The Reader system
software can be compared to the operating system of a host computer.

Different Reader application software can reside on top of the system software. The
Reader application software defines the behaviour of the Reader.

Access
Control
System

Reader Host
Communication
Application Application
Interface
Software Software

Reader Host Computer


System Software Operating System

06-300 01

Figure 1 Application and system software overview


The main focus of this manual is the Reader application software. This manual is
regarded as a complement to the GEN4 Reader User’s Manual [1]. For a more
comprehensive coverage of the Reader hardware and software, see the GEN4 Reader
User’s Manual.

© TagMaster AB 4 (40)
PassMan Software Manual Doc no. 06-240 07

2 General Information
This section describes the purpose and the basic tasks of the PassMan software.

The PassMan software makes it possible to incorporate the Reader in an existing


access control system using Wiegand or Mag-stripe communication protocols. The
PassMan software also makes it possible to connect the Reader to a host computer
using the RS485 serial communication interface.

The main function of the PassMan software is to detect an ID-tag and automatically
forward ID-tag data to the access control system or to the host computer.

The Reader installed with PassMan has only limited decision-making capabilities on its
own. The Reader application software cannot store any information about read ID-tags.
Functionality is primarily placed in the access control system or the host computer.

A typical application for an LR-series Reader installed with PassMan is an extension of


an existing access control system lacking long-range reading capabilities, for instance
in an industrial area protected by a gate.

06-301 01

Figure 2 Existing access control system lacking long-range reading capabilities

© TagMaster AB 5 (40)
PassMan Software Manual Doc no. 06-240 07

06-302 01

Figure 3 A typical installation using PassMan is an extension of an existing access control


system
The ID-tag mounted in the windshield is detected when the vehicle approaches the
Reader. The ID-tag data is transmitted to the existing access control system that sends
an opening signal to the gate if the reported ID-tag is to be granted access. The
Reader is also capable of detecting moving objects without ID-tags.

2.1 Basic Tasks


Described at the most basic level, the PassMan software receives input and produces
output. The access control system or the host computer stores information and makes
necessary decisions.

Input includes events generated by readings of ID-tags and detection of moving


objects. Input can also be information received from an access control system or from
a host computer, or both.

Output includes causing the relay to be pulled, sounding the buzzer, and turning on the
externally-visible indicator. Output can also be information about events which is sent
to an access control system or to a host computer, or both.

PassMan Access

Software Control

Input System

Output

06-303 01

Figure 4 Basic tasks of the PassMan software when the Reader is connected to an access
control system
When the Reader is connected to an access control system, output includes
information about read ID-tags that is sent to the access control system over the
Wiegand/Mag-stripe interface. The Wiegand/Mag-stripe interface sends information

© TagMaster AB 6 (40)
PassMan Software Manual Doc no. 06-240 07

one-way, from the Reader to the access control system. When the Reader is
connected to an access control system, input includes signals received from the
access control system to the input connection.

PassMan Host

Software Application
Input
Software

Output

06-304 01

Figure 5 Basic tasks of the PassMan software when the Reader is connected to a host
computer
When a Reader is connected to a host computer, output includes information about
read ID-tags and motion detections that is sent to the host computer over a serial
communication interface. When a Reader is connected to a host computer, input
includes information received from the host computer over a serial communication
interface.

Output generated by the Reader is based on the configuration settings of the PassMan
software. Application settings are stored in Flash memory and are unaffected when the
Reader is reset.

2.2 Communication Interfaces


The PassMan software uses three main communication interfaces, which are an
RS485 serial interface, a Wiegand/Mag-stripe interface, and an RS232 serial interface.

Table 1 Communication interfaces overview

Communication Interface Controller Board Description


Connection
RS485 J41 Used for communication between
the Reader and a host computer or
for configuration of the Reader from
a temporarily connected PC.

PassMan supports 2-wire RS485.


RS232 J42 Used for communication between
the Reader and a host computer or
for configuration of the Reader from
a temporarily connected PC.
Wiegand/Mag-stripe J2 Used for one-way communication
from the Reader to an access
control system.

For a chart of the controller board with the external connections mentioned above, see
the LR-series Installation Manual [2].

© TagMaster AB 7 (40)
PassMan Software Manual Doc no. 06-240 07

The two protocols Wiegand and Mag-stripe share the same physical interface on the
controller board of the Reader and therefore cannot be used simultaneously.

If the Reader is connected to a host computer, host application software is needed for
establishing a communication link between the Reader and the host.

2.3 ID-tag Data


There are two types of ID-tags used in a TagMaster identification system, called
ScriptTags and MarkTags. ScriptTags can both be read from and written to, while
MarkTags only can be read.

Every ID-tag has a unique and permanent identification number called ID-tag mark.
The data stored in a MarkTag includes the ID-tag mark. The data stored in a ScriptTag
includes the ID-tag mark and a writable data field called ID-tag user data.

Table 2 ID-tags overview

ID-tag Type ID-tag Data


MarkTag Readable ID-tag mark
ScriptTag Readable ID-tag mark and readable and writable ID-tag user data

The term ID-tag data is used to describe the collective data stored in an ID-tag (the ID-
tag mark or the ID-tag user data, or both). For MarkTags, ID-tag data also include an
optional site code stored in the Reader.

The ID-tag data is sent to the access control system or the host computer in different
formats, which correspond to the available communication interfaces as shown in the
table below.

Table 3 ID-tag data format overview

Data Format Descriptor ID-tag Data format


WI Wiegand data
MC Mag-stripe data
OL Special type data (previous Mag-stripe format)
FU Serial data full size (574 bits)
QU Serial data quarter size (154 bits)
MI Serial data mini size (14 bits)

3 Message Formats
This section describes the different formats used in the messages sent from the
Reader to an access control system and to a host computer.

Messages transmitted from the Reader consist of separate fields and differ in format,
depending on the communication interface and type of ID-tag.

Settings regarding the different communication interfaces, ID-tag marks and ID-tag
user data can be combined in a variety of ways.

© TagMaster AB 8 (40)
PassMan Software Manual Doc no. 06-240 07

All configuration settings are listed and explained briefly in section 5 Configuration.
However, some settings and terminology regarding the message formats require
clarification and will be described in more detail in the subsections below.

3.1 Site Code


Information about the site code applies to the PassMan settings described in the
following sections:

• 5.3.2 ID-tag Mark and Site Code Send To


• 5.3.5 Serial Data: Site Code Field Length
• 5.3.6 Serial Data: Site Code Value
• 5.3.10 Mag-stripe: Site Code Field Length
• 5.3.11 Mag-stripe: Site Code Value
• 5.3.16 Wiegand: Site Code Field Length
• 5.3.17 Wiegand: Site Code Value

A Site code is used in some access control systems for separating different sites or
facilities. The site code is an arbitrary number that is set in the Reader application
software. The site code is optional and sent together with the ID-tag mark to an access
control system or to a host computer.

The field that the site code occupies in a sent message is of fixed length. The field
length is configured in the Reader application software and is set so that it is large
enough to hold the actual site code.

If the field length is larger than the space occupied by the site code, the site code will
be preceded by zeros. If the field length is smaller than the space occupied by the site
code, the site code will be truncated and the most significant digits will be omitted.

Note that the field size sets an upper limit for the value of the site code. To omit the site
code from the message, set the field length to 0.

© TagMaster AB 9 (40)
PassMan Software Manual Doc no. 06-240 07

Site code size and field length are expressed as number of digits when using Mag-
stripe and serial data formats, as exemplified in the table below.

Table 4 Site code example using Mag-stripe and serial data formats.

Site Code value Site Code Size Site Code Site Code as Sent by
Field length PassMan
3381 4 digits 4 digits 3381
(3381)
6 digits 003381

Site code size and field length are expressed as number of bits when using Wiegand
data format, as exemplified in the table below.

Table 5 Site code example using Wiegand data format

Site Code value Site Code Size Site Code Site Code as Sent by
Field Length PassMan
3381 12 bits 12 bits 110100110101
(110100110101)
14 bits 00110100110101

3.2 ID-tag Mark


The ID-tag mark is applicable to the PassMan settings described in the following
sections:

• 5.3.2 ID-tag Mark and Site Code Send To


• 5.3.3 Serial Data: ID-tag Mark Field Length
• 5.3.4 Serial Data: ID-tag Mark Used Number of
• 5.3.9 Mag-stripe: ID-tag Mark Used Number of
• 5.3.10 Mag-stripe: Site Code Field Length
• 5.3.14 Wiegand: ID-tag Mark Field Length
• 5.3.15 Wiegand: ID-tag Mark Used Number of Bits

The ID-tag mark is the unique identification number stored in every ID-tag, typically
consisting of eight digits. The ID-tag mark is transmitted to the Reader when the ID-tag
is read. The ID-tag mark is formatted by the PassMan software before being forwarded
to the access control system or the host computer.

The field that the ID-tag mark occupies in a sent message is of fixed length. The whole
ID-tag mark stored in the ID-tag is not necessarily used in the message sent to the host
computer or the access control system. The field length is configured in the Reader
application software and is set so that it is large enough to hold the desired size of the
ID-tag mark. The size of the ID-tag mark forwarded from the Reader is configured in
the Reader application software and can be smaller than the original ID-tag mark.

If the field length is larger than the space occupied by the ID-tag mark, the ID-tag mark
will be preceded by zeros. If the field length is smaller than the space occupied by the
ID-tag mark, the ID-tag mark will be truncated and the most significant digits will be
omitted.

© TagMaster AB 10 (40)
PassMan Software Manual Doc no. 06-240 07

The field length is expressed as number of digits when using Mag-stripe and serial data
formats, as exemplified in the table below.

Table 6 ID-tag mark example using Mag-stripe and serial data formats

Original ID-tag Mark Used Field ID-tag Mark as Sent by the


Expressed with Digits Number Length Reader
of Digits
12343985 8 digits 8 digits 12343985
5 digits 5 digits 43985
5 digits 7 digits 0043985

The field length is expressed as number of bits when using the Wiegand data format,
as exemplified in the table below.

Table 7 ID-tag mark example using Wiegand data format

Original ID-tag Mark Used Field ID-tag Mark as Sent by the


Expressed with Bits Number Length Reader
of Bits
101111000101101010110001 24 bits 24 bits 101111000101101010110001
16 bits 16 bits 0101101010110001
16 bits 20 bits 00000101101010110001

Note that the ID-tag mark represented by bits will result in entirely different decimal
values depending on the used number of bits. For instance, the bit sequence
101111000101101010110001 has the decimal value 12343985 and the truncated bit
sequence 0101101010110001 has the decimal value 23217.

3.3 Mag-stripe Message Format


The PassMan system supports the following Mag-stripe formats:

• Read-only MarkTag: 5-26 digits. Site code in Reader.


• Read-write ScriptTag: 2-18 digits. Site code in tag.

The Mag-stripe message format is applicable to the PassMan settings described in the
following sections:

• 5.3.12 Mag-stripe: Leading Zero Bits


• 5.3.13 Mag-stripe: Trailing Zero Bits

The messages sent over the Mag-stripe interface is enclosed by leading and trailing
zero bits, which are used by the access control system for synchronisation. The
number of leading zero bits and the number of trailing zero bits are configured in the
Reader application software.

The Mag-stripe protocol format organises the data in groups of five bits called
sentinels, four data bits and one parity bit. A sentinel is transmitted with the least
significant bit first and the parity bit last.

© TagMaster AB 11 (40)
PassMan Software Manual Doc no. 06-240 07

Each sentinel represents a digit of the ID-tag data or a control character, which can
have values in the range 0Hex–FHex.

Sentinels with special meaning in the Mag-stripe message format are:


• BHex represents start
• DHex represents field separator
• FHex represents stop

If PassMan is configured to send the optional site code and ID-tag mark to the access
control system, then the message is structured as shown in the figure below.

Leading zero bits Optional site code ID-tag mark Trailing zero bits

Figure 6 Mag-stripe message format sending site code and ID-tag mark
The ID-tag user data consists of two fields when using the Mag-stripe data format, an
optional constant field and a number field. If PassMan is configured to send ID-tag user
data to the access control system, then the message is structured as shown in the
figure below.

Leading zero bits Optional constant field Number field Trailing zero bits

Figure 7 Mag-stripe message format sending ID-tag user data

3.4 Wiegand Message Format


The PassMan system supports the following Wiegand formats:

• Read-only MarkTag: 18-50 bits. Site code in Reader.


• Read-write ScriptTag: 26-50 bits. Site code in tag.

The Wiegand message format is applicable to the PassMan settings described in the
following sections:

• 5.3.18 Wiegand: First Parity Bit Type


• 5.3.19 Wiegand: Last Parity Bit Type
• 5.3.20 Wiegand: First Parity Bit Range
• 5.3.21 Wiegand: Last Parity Bit Range

The ID-tag data is enclosed by a first and a last parity bit when using the Wiegand data
format. The two parity bits are calculated over two separate bit ranges of the message,
which are defined when configuring the PassMan software.

The first parity bit is calculated over a range from the second bit to a defined position in
the message. The last parity bit is calculated over a range from a defined position in
the message to the second-last bit of the message.

Note that the total length of the message is the sum of the ID-tag mark field length and
the site code field length plus two bits (the first and the last parity bits).

If PassMan is configured to send the optional site code and ID-tag mark to the access
control system, then the message is structured as shown in the figure below.

© TagMaster AB 12 (40)
PassMan Software Manual Doc no. 06-240 07

First parity bit Optional site code ID-tag mark Last parity bit

Figure 8 Wiegand message format sending site code and ID-tag mark

The ID-tag user data consists of three number fields when using Wiegand data format.
The first and last parity bits can be omitted when sending the ID-tag user data.

If PassMan is configured to send ID-tag user data to the access control system, then
the message is structured as shown in the figure below.

First parity bit First number Second number Third number Last parity bit

Figure 9 Wiegand message format sending ID-tag user data

3.5 Serial Message Format


The serial message format is applicable to the PassMan settings described in the
following sections:

• 5.2.13 Serial Interface Message Terminator


• 5.2.14 Serial Interface Message Frame
• 5.3.1 ID-tag User Data Send To
• 5.3.7 Serial Data: ID-tag User Data Format

The message sent over the RS485 serial communication interface consists in its most
rudimentary form of the site code and ID-tag mark or data format descriptor and ID-tag
user data.

If PassMan is configured to send the site code and ID-tag mark to the host computer,
then the message is structured as shown in the figure below.

Optional site code ID-tag mark

Figure 10 Serial message format sending site code and ID-tag mark

A data format descriptor is included when sending the ID-tag user data over RS485
interface. The data format descriptor is two ASCII characters that indicate the format of
the ID-tag user data. (See Table 3 in section 2.3 ID-tag Data for a complete listing of
the available data formats.)

If PassMan is configured to send ID-tag user data to the host computer, then the
message is structured as shown in the figure below.

Data format descriptor ID-tag user data

Figure 11 Serial message format sending ID-tag user data

3.5.1 Optional Message Frame


An optional message frame containing the ASCII characters Start of Text (STX), ASCII
character End of Text (ETX), and a checksum can be used to enclose the basic
message as shown in Figure 12 and Figure 13.

© TagMaster AB 13 (40)
PassMan Software Manual Doc no. 06-240 07

To ensure integrity of the sent data a checksum is calculated and included in the
message frame before the ETX control character. The checksum is an XOR-calculation
of all bytes from STX to the last byte in the ID-tag data. A hexadecimal value 00–FF is
used to represent the checksum, which is sent as two ASCII characters over the
RS485 interface. The first character in the checksum is referred to as CS1 and the
second character in the checksum is referred to as CS2.

STX Optional site code ID-tag mark CS1 CS2 ETX

Figure 12 Serial message format sending site code and ID-tag mark with the message frame
highlighted in grey

STX Data format descriptor ID-tag user data CS1 CS2 ETX

Figure 13 Serial message format sending ID-tag user data with the message frame highlighted
in grey

3.5.2 Optional Message Terminator


An optional message terminator containing the ASCII character Carriage Return (CR)
followed by the ASCII character Line Feed (LF) can be put at the end of the message.
The message terminator or the message frame, or both, can be used.

STX Site code ID-tag mark CS1 CS2 ETX Message terminator

Figure 14 Serial message format sending site code and ID-tag data mark with message frame
and message terminator highlighted in grey

STX Format descriptor ID-tag user data CS1 CS2 ETX Message terminator

Figure 15 Serial message format sending site code and ID-tag data mark with message frame
and message terminator highlighted in grey

3.5.3 ID-tag User Data in Bytes or Nibbles


The ID-tag user data can include bytes that do not generate printable characters when
displayed in a terminal emulator connected to the RS485 interface.

It is possible to inspect the ID-tag user data by transmitting the information as 4-bit
nibbles converted to ASCII instead of standard 8-bit ASCII.

The bit sequence 00001000 (decimal value 8), for instance, represents the ASCII
character backspace, which will corrupt the output in the terminal emulator if sent as 8-
bit ASCII. The same bit sequence represented by two 4-bit nibbles generates the bit
sequences 0000 (decimal value 0) and 1000 (decimal value 8), which will be converted
and sent as the ASCII characters “0” followed by “8”.

© TagMaster AB 14 (40)
PassMan Software Manual Doc no. 06-240 07

4 Serial Communication Commands


This section describes general commands, which are used for communication between
a host computer and a Reader over the serial communication interface.

In addition to the transmitted ID-tag data, a host computer can communicate with a
Reader installed with PassMan software by sending and receiving commands over the
RS485 interface.

The message terminator is enabled or disabled as described in section 5.2.13. The


message frame described in section 5.2.14 is always present in the serial
communication commands, regardless of the current configuration settings.

The sections below describe the commands, their structure, and the responses to the
commands.

The convention used to specify the syntax of the commands and the responses are as
follows:

• Printable characters are written as they appear in the messages.


• Non-printable characters and user-defined values are written with a short
description enclosed by angle brackets.
• Optional characters and optional parts of a message are enclosed in square
brackets.

4.1 Commands Sent from the Host to the Reader


Commands can be sent from the host to the Reader. The Reader responds with a
control character depending on weather or not the command sent from the host is
accepted.

An Acknowledgement (ACK) ASCII character is returned if the reader accepts the sent
command, and an Negative Acknowledgement (NAK) ASCII character is returned if the
reader does not accept the sent command.

4.1.1 Repeat Last ID-tag Command


This command will cause the Reader to repeat the last ID-tag related message.

To distinguish a repeated message from an original ID-tag related message, the


repeated message is preceded by the ASCII character Data Link Escape (DLE). The
Reader sends a Cancel (CAN) ASCII character if there is no message to repeat.

Table 8 Repeat last ID-tag command

Description Syntax
Command structure <STX>RL1C<ETX>[<CR><LF>]
Normal response <DLE>[ID-tag data>] or
<DLE><STX>[<ID-tag data>]<Checksum><ETX>[<CR><LF>]
No message to <STX><CAN>1A<ETX>[<CR><LF>]
repeat response

© TagMaster AB 15 (40)
PassMan Software Manual Doc no. 06-240 07

NAK response <STX><NAK>17<ETX>[<CR><LF>]

4.1.2 Activate Function Set 1 Command


This command will result in the same function as when the Reader input 1 is activated
according to the setting described in section 5.2.18 Function on Input 1.

Table 9 Active function set 1 command

Description Syntax
Command structure <STX>B171<ETX>[<CR><LF>]
ACK response <STX><ACK>04<ETX>[<CR><LF>]
NAK response <STX><NAK>17<ETX>[<CR><LF>]

4.1.3 Close Function Set 1 Command


This command will result in the same function as when the Reader input 1 is made
passive.

Table 10 Close function set 1 command

Description Syntax
Command structure <STX>E176<ETX>[<CR><LF>]
ACK response <STX><ACK>04<ETX>[<CR><LF>]
NAK response <STX><NAK>17<ETX>[<CR><LF>]

4.1.4 Activate Function Set 2 Command


This command will result in the same function as when the Reader input 2 is activated
according to the setting described in section 5.2.19 Function on Input 2.

Table 11 Active function set 2 command

Description Syntax
Command structure <STX>B272<ETX>[<CR><LF>]
ACK response <STX><ACK>04<ETX>[<CR><LF>]
NAK response <STX><NAK>17<ETX>[<CR><LF>]

4.1.5 Close Function Set 2 Command


This command will result in the same function as when the Reader input 2 is made
passive.

Table 12 Close function set 2 command

Description Syntax
Command structure <STX>E275<ETX>[<CR><LF>]
ACK response <STX><ACK>04<ETX>[<CR><LF>]
NAK response <STX><NAK>17<ETX>[<CR><LF>]

© TagMaster AB 16 (40)
PassMan Software Manual Doc no. 06-240 07

4.1.6 Motion Detection Start Command


This command activates the motion detection function in the Reader.

Table 13 Motion detection start command

Description Syntax
Command structure <STX>MA0E<ETX>[<CR><LF>]
ACK response <STX><ACK>04<ETX>[<CR><LF>]
NAK response <STX><NAK>17<ETX>[<CR><LF>]

4.1.7 Motion Detection Stop Command


This command deactivates the motion detection function in the Reader.

Table 14 Motion detection stop command

Description Syntax
Command structure <STX>MS1C<ETX>[<CR><LF>]
ACK response <STX><ACK>04<ETX>[<CR><LF>]
NAK response <STX><NAK>17<ETX>[<CR><LF>]

4.2 Messages sent from the Reader to the Host


Messages are sent from the Reader to the Host when events occur.

4.2.1 Motion Detection Message


A motion detection message is sent to the host computer when the Reader detects a
moving object and the motion detection is activated.

Table 15 Motion detection message

Description Syntax
Message <STX>MO00<ETX>[<CR>LF>]
structure

4.2.2 Loop Trigger Input Is Activated Message


This message is sent to the host computer when the isolated input 3 is activated and
the loop trigger is enabled according to section 5.2.20 Loop Trigger Duration on Input
3.

Table 16 Loop Trigger Input Is Activated Message

Description Syntax
Message <STX>LA0F<ETX>[<CR><LF>]
structure

4.2.3 Loop Trigger Input Becomes Inactive Message


This message is sent to the host computer when input 3 becomes inactive and the loop
trigger is enabled according to section 5.2.20 Loop Trigger Duration on Input 3.

© TagMaster AB 17 (40)
PassMan Software Manual Doc no. 06-240 07

Table 17 Loop trigger input becomes inactive message

Description Syntax
Message <STX>LP1E<ETX>[<CR><LF>]
structure

© TagMaster AB 18 (40)
PassMan Software Manual Doc no. 06-240 07

5 Configuration
This section describes the available configuration settings in the PassMan software
and how to change them.

The configuration settings are divided into two general groups. The “System Settings”
group covers reading performance, operating logic, and communication interfaces. The
“ID-tag Settings” group covers how the Reader formats information transmitted from
the ID-tags before it is forwarded to an access control system or a host computer.

The Reader can be configured using a temporarily connected PC via the web interface
or the terminal interface. For backwards compatibility it is also possible to configure the
Reader via the RS232 interface.

5.1 Configuration Interfaces


5.1.1 Web/Terminal Interfaces
Connect to the web interface or terminal interface as described in “GEN4 Reader
User’s Manual”. PassMan settings are available under
Settings…/Applications…/PassMan.

Figure 16 Web interface with PassMan settings

© TagMaster AB 19 (40)
PassMan Software Manual Doc no. 06-240 07

Figure 17 Terminal interface with PassMan settings

5.1.2 PassMan’s Terminal Interface


For backwards compatibility reasons the PassMan application is provided with a
custom text-based interface for configuration. This interface can be used in parallel to
the web interface and the terminal interface.

Perform the configuration as follows:


1. Connect the RS232 interface of the Reader to the serial port of the PC with a
RS232 cable.
2. Configure the terminal emulator so that the communication settings are as
follows:
a. 9600 baud
b. 8 data bits
c. No parity
d. 1 stop bit
e. No flow control
3. Open a connection from the terminal emulator to the Reader. The main menu
will be displayed.

PassMan v1.6.0
A. System settings menu
B. ID-tag settings menu

Your choice (A or B): A

4. Type “A” to display the system settings menu.

© TagMaster AB 20 (40)
PassMan Software Manual Doc no. 06-240 07

PassMan v1.6.0 - System settings menu:


A. Serial interface (RS485)
B. Operating mode (On)
C. Function on ID-tag read (Yellow indicator)
D. ID-tag read timeout type (Once)
E. ID-tag read timeout (2)
F. ID-tag minimum message interval (0)
G. Frequency channel (0)
H. Reading range (4)
I. ID-tag data speed (High)
J. Serial interface bit rate (9600)
K. Serial interface stop bits (1)
L. Serial interface parity bit (No)
M. Serial interface message terminator (CRLF)
N. Serial interface message frame (None)
O. Motion detection (Off)
P. Motion detection sensitivity (1)
Q. Motion detection output (To relay)
R. Function on input 1 (Red indicator)
S. Function on input 2 (Green indicator)
T. Loop trigger duration (0)

Your choice (A-T):

5. Each setting in the system settings menu is represented by a character and a


short description. The current value is displayed at the end of the row enclosed
in parentheses. Type a character to configure the corresponding setting. A
submenu will be displayed.

Tip: In case of a type error, press backspace or enter to return to the main
menu.

6. Depending on the setting, the options in the submenus are set in two different
ways:
a. Options of character type are set by typing a character as seen in the
example below:

Possible values for ID-tag data speed:


A. High
B. Low
Your choice: B

b. Options of numeric types are set by typing a numeric value followed by


enter as seen in the example below:

Possible values for Frequency channel: 0=FHSS, 5 - 97


Your choice: 75

© TagMaster AB 21 (40)
PassMan Software Manual Doc no. 06-240 07

7. Return to the main menu by pressing enter.

PassMan v1.6.0
A. System settings menu
B. ID-tag settings menu

Your choice (A or B): B

8. Type “B” to display the ID-tag settings menu.

PassMan v1.6.0 - Tag settings menu:


A. ID-tag user data send to (Disable)
B. ID-tag mark and site code send to (Wiegand and serial interfaces)
C. Serial data: ID-tag mark field length (8)
D. Serial data: ID-tag mark number of digits (8)
E. Serial data: Site code field length (0)
F. Serial data: Site code value (0)
G. Serial data: ID-tag user data format (As 8-bit ASCII bytes)
H. Mag-stripe: ID-tag mark field length (9)
I. Mag-stripe: ID-tag mark number of digits (9)
J. Mag-stripe: Site code field length (6)
K. Mag-stripe: Site code value (0)
L. Mag-stripe: Leading zero bits (25)
M. Mag-stripe: Trailing zero bits (25)
N. Wiegand: ID-tag mark field length (24)
O. Wiegand: ID-tag mark used number of bits (24)
P. Wiegand: Site code field length (0)
Q. Wiegand: Site code value (0)
R. Wiegand: First parity bit type (Even)
S. Wiegand: Last parity bit type (Odd)
T. Wiegand: First parity bit range (13)
U. Wiegand: Last parity bit range (14)

Your choice (A-U):

9. Type a character to change the options for the corresponding setting in the
same manner as in the system settings menu described above.
10. A setting is automatically sent to the Reader when an option is configured. A
short beep indicates that a valid setting has been saved.

5.2 System Settings


The subsections below describe the different settings that can be configured in the
system settings group. The default value for each setting is written within parentheses.

For a chart of the controller board with input and output connections mentioned below,
see the LR-series Installation Manual [2].

5.2.1 Serial Interface


PassMan uses either RS485 (default) or RS232 as serial interface to a host computer.
The other interface is used for the text-based configuration interface that is described in
section 5.1.2.

Table 18 Serial interface setting

Setting Option Description


A. Serial A. RS232 RS232 is used as serial interface to
Interface (RS485) host computer. RS485 is used as

© TagMaster AB 22 (40)
PassMan Software Manual Doc no. 06-240 07

configuration interface.
B. RS485 RS485 is used as serial interface to
host computer. RS232 is used as
configuration interface.

5.2.2 Operating Mode


The PassMan software has two operating modes. Beside normal operation, there is an
operating mode used for testing purposes.

Table 19 Operating mode setting

Setting Option Description


B. Operating mode A. On The Reader is ready to read ID-tags
(On) and to automatically send ID-tag data
over the communication interfaces.
B. Read test The Reader beeps and the externally-
visible indicator flashes every time an
ID-tag is read. This mode is used for
testing the reading capabilities.

5.2.3 Function on ID-tag Read


The Reader can perform different functions when an ID-tag is read.

Table 20 Function on ID-tag read setting

Setting Option Description


C. Function on A. Buzzer The buzzer beeps when an ID-tag is
ID-tag read read.
(Yellow
B. Yellow The externally-visible indicator flashes
indicator)
indicator yellow when an ID-tag is read.
C. Relay The relay is pulled when an ID-tag is
read.
D. Yellow The externally-visible indicator flashes
indicator & yellow and the relay is pulled when an
relay ID-tag is read.
E. Buzzer & The buzzer beeps and the relay is
relay pulled when an ID-tag is read.
F. Buzzer & The buzzer beeps and the externally-
yellow visible indicator flashes yellow when an
indicator ID-tag is read.
G. Buzzer, The buzzer beeps, the externally-visible
yellow indicator flashes yellow, and the relay is
indicator, & pulled when an ID-tag is read.
relay
H. None The Reader does nothing when an ID-
tag is read.

© TagMaster AB 23 (40)
PassMan Software Manual Doc no. 06-240 07

5.2.4 ID-tag Read Timeout Type


A read timeout type is set in order not to flood the access control system or host
computer with reported ID-tag readings. The reporting of ID-tags is also affected by the
time interval set according to section 5.2.5 ID-tag Read Timeout.

Table 21 ID-tag read timeout type setting

Setting Option Description


D. ID-tag read A. Once The Reader automatically sends the ID-
timeout type tag data once over the communication
(Once) interfaces.
B. Periodic The Reader automatically sends the ID-
tag data periodically over the
communication interfaces.

5.2.5 ID-tag Read Timeout


If the Reader is set to forward ID-tag data once, the timeout specifies for how long the
ID-tag has to be withdrawn from the reading lobe to achieve an additional report. If the
Reader is set to forward ID-tag data periodically, the timeout specifies the time
between recurring reports.

Table 22 ID-tag read timeout setting

Setting Option Description


E. ID-tag read 1–10 Timeout time in 1–10 seconds is used.
timeout (2)

5.2.6 ID-tag Minimum Message Interval


If multiple ID-tags are read simultaneously the ID-tag message rate may be too high for
some host systems. This parameter sets the minimum time between the start of two
adjacent ID-tag messages sent by the PassMan software. The parameter is valid for all
interfaces.

Table 23 ID-tag minimum message interval setting

Setting Option Description


F. ID-tag minimum 0-5000 Minimum time in milliseconds between
message interval the start of two adjacent ID-tag
(0) messages send by PassMan.

5.2.7 Frequency Channel


Set Readers in close proximity to each other to different frequency channels to reduce
the risk of interference, or use Frequency-Hopping Spread Spectrum (FHSS).

Frequency hopping in PassMan is limited to sub-bands G-L (2.4320GHz -2.4618GHz).

Table 24 Frequency channel setting

Setting Option Description


G. Frequency 0 FHSS is used.

© TagMaster AB 24 (40)
PassMan Software Manual Doc no. 06-240 07

channel (0) 5–97 Frequency channel 5–97 is used.

5.2.8 Reading Range


The reading range can be controlled to avoid unwanted readings of remote ID-tags.

Table 25 Reading range setting

Setting Option Description


H. Reading range 1 The reading range is set to
(4) approximately 25% of the maximum
reading range (equivalent to F1).
2 The reading range is set to
approximately 50% of the maximum
reading range (equivalent to F33).
3 The reading range is set to
approximately 75% of the maximum
reading range (equivalent to F66).
4 The reading range is set to maximum
(equivalent to F100).
F1-F100 Fine tuning of reading range (F1 = min,
F100 = max).

5.2.9 ID-tag Data Speed


ID-tags send information to the Reader in high or low data speed. Set the Reader to
the data speed supported by the ID-tag.

Note: Never mix ID-tag data speeds by using high for the Reader and low for the ID-
tag or vice versa; in such cases the ID-tag will not be read.

Table 26 Reading ID-tag data speed setting

Setting Option Description


I. ID-tag data A. High High data speed
speed (High)
B. Low Low data speed

5.2.10 Serial Interface Bit Rate


The RS485 serial interface supports several bit rates.

Table 27 RS485 Interface bit rate setting

Setting Option Description


J. Serial A. 1200 1200 bps
interface bit
B. 2400 2400 bps
rate (9600)
C. 4800 4800 bps
D. 9600 9600 bps
E. 19200 19200 bps

© TagMaster AB 25 (40)
PassMan Software Manual Doc no. 06-240 07

F. 38400 38400 bps

5.2.11 Serial Interface Stop Bits


The number of stop bits can be either one or two.

Table 28 RS485 interface stop bits setting

Setting Option Description


K. Serial 1 One stop bit
interface stop
2 Two stop bits
bits (1)

5.2.12 Serial Interface Parity Bit


A parity bit is used as a simple error detecting code in the serial communication.

Table 29 RS485 interface parity setting

Setting Option Description


L. Serial A. No No parity bit is used.
interface parity
B. Odd The parity bit is set to 1 if the number of
bit (No)
ones in a given set of bits is even
(making the number of ones odd).
C. Even The parity bit is set to 1 if the number of
ones in a given set of bits is odd
(making the number of ones even).

5.2.13 Serial Interface Message Terminator


Messages sent over the RS485 interface can, as an option be terminated with the
ASCII character Carriage Return (CR) followed by the ASCII character Line Feed (LF).

Table 30 RS485 interface message terminator setting

Setting Option Description


M. Serial A. CRLF Messages from the Reader to the host
interface are terminated with CR followed by LF.
terminator (CRLF)
B. None Message terminator is disabled.

5.2.14 Serial Interface Message Frame


ID-tag data sent over the RS485 interface can, as an option be enclosed by a message
frame consisting of the ASCII character Start of Text (STX) and a checksums
consisting of two characters (CS1 and CS2) followed by the ASCII character End of
Text (ETX).

Table 31 RS485 interface message frame

Setting Option Description


N. Serial A. STX ... Message frame consisting of STX,
interface message CS1 CS2 ETX CS1, and CS2 followed by ETX is used.
frame (None)
B. None Message frame is not used.

© TagMaster AB 26 (40)
PassMan Software Manual Doc no. 06-240 07

5.2.15 Motion Detection


The Reader makes use of the Doppler effect to discover moving objects.

If motion detection is enabled, the sensitivity level is set according to the section 5.2.16
and an output can be activated according to the setting described in section 5.2.17.

Table 32 Motion detection setting

Setting Option Description


O. Motion A. On Motion detection is enabled.
detection (Off)
B. Off Motion detection is disabled.

5.2.16 Motion Detection Sensitivity


The sensitivity level of the motion detection is valid when motion detection functionality
is enabled.

Table 33 Motion detection sensitivity setting

Setting Option Description


P. Motion 1–5 Sensitivity level 1–5.
detection
sensitivity (1)

5.2.17 Motion Detection Output


Several outputs can be activated if the Reader detects a moving object. Motion
detection output is only valid when motion detection functionality is enabled according
to section 5.2.15.

Table 34 Motion detection output setting

Setting Option Description


Q. Motion A. To relay The relay is pulled.
detection output
B. To The isolated output 1 is activated.
(To relay)
output 1
C. To The isolated output 2 is activated.
output 2
D. No output No output is generated.
connection

© TagMaster AB 27 (40)
PassMan Software Manual Doc no. 06-240 07

5.2.18 Function on Input 1


The Reader can generate different outputs when the isolated input 1 is activated.

Table 35 Function on Input 1 setting

Setting Option Description


R. Function on A. Buzzer The buzzer beeps.
input 1 (Red
B. Green The externally-visible indicator is green.
indicator)
indicator
C. Red The externally-visible indicator is red.
indicator
D. Relay The relay is pulled.
E. Green The externally-visible indicator is green
indicator & and the relay is pulled.
relay
F. Red The externally-visible indicator is red
indicator & and the relay is pulled.
relay
G. Buzzer & The buzzer beeps and the relay is
relay pulled.
H. Buzzer & The buzzer beeps and the externally-
green visible indicator is green.
indicator
I. Buzzer & The buzzer beeps and the externally-
red indicator visible indicator shows red.
J. Buzzer, The buzzer beeps, the externally-visible
green indicator is green, and the relay is
indicator, & pulled.
relay
K. Buzzer, The buzzer beeps, the externally-visible
red indicator is red, and the relay is pulled.
indicator, &
relay
L. None No output is generated.

© TagMaster AB 28 (40)
PassMan Software Manual Doc no. 06-240 07

5.2.19 Function on Input 2


The Reader can generate different outputs when the isolated input 2 is activated.

Table 36 Function on input 2 setting

Setting Option Description


S. Function on A. Buzzer The buzzer beeps.
input 2 (Green
B. Green The externally-visible indicator is green.
indicator)
indicator
C. Red The externally-visible indicator is red.
indicator
D. Output 1 The isolated output 1 is activated.
E. Green The externally-visible indicator is green
indicator & and isolated output 1 is activated.
output 1
F. Red The externally-visible indicator is red
indicator & and isolated output 1 is activated.
output 1
G. Buzzer & The buzzer beeps and the isolated
output 1 output 1 is activated.
H. Buzzer & The buzzer beeps and the externally-
green visible indicator is green.
indicator
I. Buzzer & The buzzer beeps and the externally-
red indicator visible indicator is red.
J. Buzzer, The buzzer beeps, the externally-visible
green indicator is green, and the relay is
indicator, & pulled.
relay
K. Buzzer, The buzzer beeps, the externally-visible
red indicator is red, and the relay is pulled.
indicator, &
relay
L. None No output is generated.

© TagMaster AB 29 (40)
PassMan Software Manual Doc no. 06-240 07

5.2.20 Loop Trigger Duration on Input 3


In situations when the reading function should be active only if a vehicle is
approaching, a loop trigger is used. A loop detector can be connected to the isolated
input 3 and used to trigger the reading of ID-tags.

Table 37 Loop trigger duration on input 3 setting

Setting Option Description


T. Loop trigger 0 Isolated input 3 is disabled.
duration on input
1–30 When the loop detector triggers the
3 (0)
Reader on input 3, the externally-visible
indicator shows a yellow light and the
reading of ID-tags is activated for 1–30
seconds. The reading of ID-tags
becomes inactive when the time has
elapsed or an ID-tag has been read.
99 Input controlled. When the loop
detector triggers the Reader on input 3,
the externally-visible indicator shows a
yellow light and the reading of ID-tags
is activated. The reading of ID-tags
becomes inactive when input 3 is
deactivated or an ID-tag has been read.

5.3 ID-tag Settings


The subsections below describe the separate settings that can be configured in the ID-
tag settings menu. The corresponding tables include the options as they are displayed
in the terminal emulation software.

5.3.1 ID-tag User Data Send To


Different formats of ID-tag user data can be sent to separate communication interfaces.

Table 38 ID-tag user data send to setting

Setting Option Description


A. ID-tag user A. All data All ID-tag user data is sent to the
data send to to serial RS485 interface. Wiegand, Mag-stripe,
(Disable) interface and and previous Mag-stripe format data is
WI/MC/OL data sent to the Wiegand/Mag-stripe
to interface.
Wiegand/Mag-
stripe
interface
B. All data All ID-tag user data is sent to the
to serial RS485 interface.
interface
C. FU/QU/MI Full size, quarter size and mini size
data to serial data is sent to the RS485
serial interface. Wiegand, Mag-stripe, and

© TagMaster AB 30 (40)
PassMan Software Manual Doc no. 06-240 07

interface and previous Mag-stripe format data is sent


WI/MC/OL data to the Wiegand/Mag-stripe interface.
to
Wiegand/Mag-
stripe
interface
D. FU/QU/MI Full size, quarter size and mini size
data to serial data is sent to the RS485
serial interface.
interface
E. WI/MC/OL Wiegand, Mag-stripe, and previous
data to Mag-stripe format data is sent to RS485
serial interface and the Wiegand/Mag-stripe
interface and interface.
to
Wiegand/Mag-
stripe
interface
F. WI/MC/OL Wiegand, Mag-stripe, and previous
data to Mag-stripe format data is sent to the
Wiegand/Mag- Wiegand/Mag-stripe interface.
stripe
interface
G. WI/MC/OL Wiegand, Mag-stripe, and previous
data to Mag-stripe format data is sent to the
serial RS485 interface.
interface
H. Disable ID-tag user data is not sent.

5.3.2 ID-tag Mark and Site Code Send To


The ID-tag data can be sent using separate communication interfaces and data
formats.

Table 39 ID-tag mark and site code send to setting

Setting Option Description


B. ID-tag mark A. Mag-stripe ID-tag data is sent to the Wiegand/Mag-
and site code and serial stripe interface and RS485 interface as
send to (Wiegand interface Mag-stripe data.
and serial
B. Wiegand ID-tag data is sent to the Wiegand/Mag-
interfaces)
and serial stripe interface and RS485 interface as
interface Wiegand data.
C. Mag-stripe ID-tag data is sent to the Wiegand/Mag-
interface stripe interface as Mag-stripe data.
D Wiegand ID-tag data is sent to the Wiegand/Mag-
interface stripe interface as Wiegand data.
E Serial ID-tag data is sent to RS485 interface.
interface

© TagMaster AB 31 (40)
PassMan Software Manual Doc no. 06-240 07

F Disable ID-tag data is not sent.

5.3.3 Serial Data: ID-tag Mark Field Length


The ID-tag mark field length is expressed as number of digits when using serial data.
Configure the used number of digits of the ID-tag mark according to section 5.3.4, so
that the field length is large enough to hold the number of used digits.

Table 40 ID-tag mark and site code as serial data: ID-tag mark field setting

Setting Option Description


C. Serial data: 5–20 The ID-tag mark field length is 5–20
ID-tag mark field digits.
length (8)

5.3.4 Serial Data: ID-tag Mark Used Number of Digits


The used number of digits from the original ID-tag mark is set.

Table 41 Serial data: ID-tag mark used number of digits setting

Setting Option Description


D. Serial data: 5–20 The ID-tag mark occupies 5–20 digits.
ID-tag mark used
number of digits
(8)

5.3.5 Serial Data: Site Code Field Length


The site code field length is expressed as number of digits when using serial data. Set
the site code value according to section 5.3.6, so that the field length is large enough to
hold the site code value.

Set the site code field length to zero to omit the site code from the sent message.

Table 42 Serial data: site code field length setting

Setting Option Description


E. Serial data: 0–6 The site code field length is 0–6 digits.
Site code field
length (0)

5.3.6 Serial Data: Site Code Value


The site code value is expressed in digits when using serial data.

Table 43 Serial data: site code value setting

Setting Option Description


F. Serial data: 0–65535 The site code value is 0–65535.
Site code value
(0)

© TagMaster AB 32 (40)
PassMan Software Manual Doc no. 06-240 07

5.3.7 Serial Data: ID-tag User Data Format


The ID-tag user data in ScriptTags is normally sent as 8-bit ASCII. The ID-tag user
data can also be sent in groups of four bits with their hexadecimal value converted to 8-
bit ASCII. The latter is used for debugging.

Table 44 Serial data: ID-tag user data format

Setting Option Description


G. Serial data: A. As 8-bit The ID-tag user data is sent as 8-bit
ID-tag user data ASCII bytes ASCII over the RS485 interface.
format (As 8-bit
B. AS 4-bit The ID-tag used data is sent over the
ASCII bytes)
ASCII nibbles RS485 interface in groups of four bits
and converted to 8-bit ASCII.

5.3.8 Mag-stripe: ID-tag Mark Field Length


The ID-tag mark field length is expressed as number of digits when using Mag-stripe
data. Configure the used number of digits of the ID-tag mark according to section 5.3.9,
so that the field length is large enough to hold the used number of digits.

Table 45 Mag-stripe: ID-tag mark field length setting

Setting Option Description


H. Mag-stripe: 5–20 The ID-tag mark field length is 5–20
ID-tag mark field digits.
length (9)

5.3.9 Mag-stripe: ID-tag Mark Used Number of Digits


The used number of digits from the original ID-tag mark is expressed as number of
digits when using Mag-stripe data.

Table 46 Mag-stripe: ID-tag mark used number of digits setting

Setting Option Description


I. Mag-stripe: 5–20 The ID-tag mark occupies 5–20 digits.
ID-tag mark used
number of digits
(9)

5.3.10 Mag-stripe: Site Code Field Length


The site code field length is expressed as number of digits when using Mag-stripe data.
Set the site code value according to section 5.3.11, so that the field length is large
enough to hold the site code value.

Set the site code field length to zero to omit the site code from the sent message.

Table 47 Mag-stripe data: Site code field length setting

Setting Option Description


J. Mag-stripe: 0–6 The site code field length is 0–6 digits.
Site code length
(6)

© TagMaster AB 33 (40)
PassMan Software Manual Doc no. 06-240 07

5.3.11 Mag-stripe: Site Code Value


The site code value is expressed in digits when using serial data.

Table 48 Mag-stripe: Site code value setting

Setting Option Description


K. Mag-stripe: 0–65535 The site code value is 0–65535.
Site code value
(0)

5.3.12 Mag-stripe: Leading Zero Bits


Leading zero bits precede the ID-tag mark and the site code when using Mag-stripe
data format.

Table 49 Mag-stripe: Leading zero bits setting

Setting Option Description


L. Mag-stripe: 0–100 0–100 zero bits precede the ID-tag
Leading zero bits data.
(25)

5.3.13 Mag-stripe: Trailing Zero Bits


Trailing zero bits follow the ID-tag mark and the site code when using Mag-stripe data
format.

Table 50 Mag-stripe: Trailing zero bits setting

Setting Option Description


M. Mag-stripe: 0–100 0–100 zero bits follow the ID-tag data.
Trailing zero
bits (25)

5.3.14 Wiegand: ID-tag Mark Field Length


The ID-tag mark field length is expressed as number of bits when using Wiegand data.
Configure the used number of bits of the ID-tag mark according to section 5.3.15, so
that the field length is large enough to hold the used number of bits.

Table 51 Wiegand: ID-tag mark field length setting

Setting Option Description


N. Wiegand: ID- 16–32 The ID-tag mark field length is 16–32
tag mark field bits.
length (24)

5.3.15 Wiegand: ID-tag Mark Used Number of Bits


The used number of bits from the original ID-tag mark is set.

Table 52 ID-tag mark and site code as Wiegand data: ID-tag mark used number of bits setting

Setting Option Description


O. Wiegand: ID- 16–32 The ID-tag mark occupies 16–32 bits.

© TagMaster AB 34 (40)
PassMan Software Manual Doc no. 06-240 07

tag mark used


number of bits
(24)

5.3.16 Wiegand: Site Code Field Length


The site code field length is expressed as number of bits when using Wiegand data.
Set the site code value according to section 5.3.17, so that the field length is large
enough to hold the site code value.

Set the site code field length to zero to omit the site code from the sent message.

Table 53 Wiegand: Site code field length setting

Setting Option Description


P. Wiegand: Site 0–16 The site code field length is 0–16 bits.
code field length
(0)

5.3.17 Wiegand: Site Code Value


The site code value is entered as digits when using Wiegand data, but the site code is
treated as a binary value when defining the field length according to section 5.3.16.

Table 54 Wiegand: Site code value setting

Setting Option Description


Q. Wiegand: Site 0–65535 The site code value is 0–65535.
code value (0)

5.3.18 Wiegand: First Parity Bit Type


The first parity bit precedes the ID-tag mark and the site code when using Wiegand
data format. The first parity bit is calculated from the second bit of the message to the
position defined according to section 5.3.20.

Table 55 Wiegand: First parity bit type setting

Setting Option Description


R. Wiegand: First A. Odd Odd parity is calculated on the first
parity bit type parity bit range.
(Even)
B. Even Even parity is calculated on the first
parity bit range.
C. Bit=1 First parity bit is set to one.
D. Bit=0 First parity bit is set to zero.

5.3.19 Wiegand: Last Parity Bit Type


The last parity bit follows the ID-tag mark and the site code when using Wiegand data
format. The last parity bit is calculated from the position defined according to 5.3.21 to
the second last bit of the message.

Table 56 Wiegand: Last parity bit type setting

© TagMaster AB 35 (40)
PassMan Software Manual Doc no. 06-240 07

Setting Option Description


S. Wiegand: Last A. Odd Odd parity is calculated on the last
parity bit type parity bit range.
(Odd)
B. Even Even parity is calculated on the last
parity bit range.
C. Bit=1 Last parity bit is set to one.
D. Bit=0 Last parity bit is set to zero.

5.3.20 Wiegand: First Parity Bit Range


The position of the bit that delimits the first parity bit range is set.

Table 57 ID-tag mark and site code as Wiegand data: First parity bit range setting

Setting Option Description


T. Wiegand: First 2–49 The bit range for the first parity bit is 2–
parity bit range 49.
(13)

5.3.21 Wiegand: Last Parity Bit Range


The position of the bit that delimits the last parity bit range is set.

Table 58 Wiegand: last parity bit range setting

Setting Option Description


U. Wiegand: Last 2–49 The bit range for the last parity bit is 2–
parity bit range 49.
(14)

© TagMaster AB 36 (40)
PassMan Software Manual Doc no. 06-240 07

6 Testing
This section describes how to carry out performance tests using the Reader application
software.

After completing the configuration as described in the previous sections, carry out a
basic reading test.

The guidelines in section 6.2 Trouble Shooting may be valuable if an error occurs.

6.1 Testing the Reading Lobe


The testing of the reading lobe is as follows:

1. Switch on power to the Reader. The externally-visible indicator will flash green
to show that the Reader has been initiated.
2. Set the Reader to operating mode “Read test”.
3. Place an ID-tag in front of the Reader having the ID-tag on the object where it
normally will be mounted. Perform repeated readings while simultaneously
moving the ID-tag along the expected movement path and check that the ID-tag
can be read in all expected positions. Each reported reading will be indicated by
a beep and a flash by the externally-visible indicator.

6.2 Trouble Shooting


The following tables describe the most frequently-encountered problems during tests of
the reading lobe and the serial communication interface.

Table 59 Common problems when testing the reading lobe

Problem Solution
The externally-visible indicator is Check the Reader installation according
constantly off. to the LR-series Installation Manual [2].
The Reader does not beep when an ID- If several Readers are used in close
tag is presented during read test mode. proximity to each other, set them to
different frequency channels.
Verify that the tag speed setting of the
Reader corresponds to the tag speed of
the ID-tag.

© TagMaster AB 37 (40)
PassMan Software Manual Doc no. 06-240 07

7 Contact
For any further inquiries, please contact TagMaster AB.

7.1 Technical Support


Phone: + 46 8 632 19 50
Fax: +46 8 750 53 62
E-mail: [email protected]

7.2 Office
TagMaster AB
Kronborgsgränd 1
S-164 87 KISTA, Sweden

Phone: +46 8 632 19 50


Fax: +46 8 750 53 62
E-mail: [email protected]
Web: www.tagmaster.com

© TagMaster AB 38 (40)
PassMan Software Manual Doc no. 06-240 07

8 Glossary
The following abbreviations and acronyms are used in this manual:

access control system Technical system restricting entrance to a property, a


building, or a room to authorized persons.
external application See host application software.
software
host The external intelligence, for instance workstation or
server, which acts as master of a Reader or a set of
Readers.
host application software The application software installed in the host used for
communicating with the Reader.
ID-tag ID-carrier in the TagMaster system, which is readable
and writable via microwaves.
ID-tag data The collective stored information in an ID-tag
including the optional site code stored in the Reader.
ID-tag mark The unique and permanent identification number
found in every ID-tag.
ID-tag user data Programmable data field in ScriptTags carrying user
data.
Mag-stripe Mag-stripe is a technology used in card readers and
sensors, particularly for access control applications.

MarkTag Type of ID-tag which hold an identification number


called ID-tag mark.
Reader TagMaster LR-series ID-tag reader.
Reader application The application software installed in the Reader,
software defining the behaviour of the Reader.
reading lobe The space in front of the Reader in which ID-tags are
being read.
ScriptTag Type of ID-tag which hold an identification number
called ID-tag mark and programmable data called ID-
tag user data.
site code A number used in some access control systems for
separating different sites or facilities.
system software The fundamental software and operating system
installed in the Reader.
terminal emulation A serial computer interface for text entry and display.
software
terminal emulator See terminal emulation software.
Wiegand Wiegand is a technology used in card readers and
sensors, particularly for access control applications.

© TagMaster AB 39 (40)
PassMan Software Manual Doc no. 06-240 07

9 References
[1] GEN4 Reader User's Manual
Doc no. 06-118
[2] LR-series Installation Manual
Doc no. 06-136

© TagMaster AB 40 (40)

You might also like