DSE810 PC Software Manual PDF
DSE810 PC Software Manual PDF
Software Manual
TABLE OF CONTENTS
Section Page
1 DESCRIPTION ................................................................................................. 5
1.1 CLARIFICATION OF NOTATION USED WITHIN THIS PUBLICATION. ...........................6
1.1.1 MANUAL STRUCTURE ................................................................................................7
1.2 PC INTERFACE MODULE 810............................................................................................8
1.2.1 THE RS232 PC INTERFACE 810 KIT COMPRISES THE FOLLOWING:- ..................8
1.2.2 THE USB PC INTERFACE 810 KIT COMPRISES THE FOLLOWING:- ......................8
1.3 INSTALLATION INSTRUCTIONS .......................................................................................8
1.3.1 MINIMUM SYSTEM REQUIREMENTS.........................................................................8
1.3.2 INSTALLING „P810 FOR WINDOWS™‟ PROGRAM FROM SOFTWARE CD –
(WINDOWS 95/98/ME/2000/XP/NT4) .........................................................................................9
1.3.3 INSTALLING „P810 FOR WINDOWS™‟ PROGRAM FROM FLOPPY DISKS –
(WINDOWS 95/98/ME/2000/XP/NT4) .......................................................................................10
1.3.4 TO RUN P810 FOR WINDOWS PROGRAM .............................................................12
2 CONFIG MANAGER MENU ........................................................................... 15
2.1.1 MODULE SECURITY ..................................................................................................16
3 EDIT CONFIG MENU ..................................................................................... 19
3.1 EDIT CONFIGURATION TAB ............................................................................................19
3.1.1 EDIT MODULE ............................................................................................................19
3.1.2 EDIT MISCELLANEOUS ITEMS .................................................................................21
3.1.3 EDIT CONFIGURABLE INPUTS.................................................................................26
3.1.4 EDIT RELAY OUTPUTS .............................................................................................36
3.1.5 EDIT FRONT PANEL LED‟S .......................................................................................48
3.1.6 EDIT SYSTEM TIMERS ..............................................................................................51
3.1.7 EDIT MAINS LEVELS .................................................................................................59
3.1.8 EDIT GENERATOR LEVELS ......................................................................................64
3.1.9 EDIT GENERATOR SYNCHRONISING/ CHECK SYNC TAB ...................................72
3.1.10 55X CONTROLLER CONFIGURATION FOR LOAD SHARING ................................78
3.1.11 CONNECTIONS TO GOVERNOR CONTROLLER AND AVR. ..................................82
3.1.12 EDIT SYSTEM LEVELS ..............................................................................................83
3.1.13 EDIT ENGINE LEVELS ...............................................................................................85
3.1.14 EDIT ENGINE MAINTENANCE ALARM TAB .............................................................93
3.1.15 EDIT SCHEDULER .....................................................................................................95
3.1.16 EDIT LANGUAGES .....................................................................................................97
4 SCADA MENU ............................................................................................... 98
4.1 DIAGNOSTICS ...................................................................................................................98
4.1.1 COMMUNICATIONS STATE INDICATION ................................................................99
4.1.2 REQUESTING MODULE SETTINGS FOR SCADA DISPLAY (IF ENABLED).........100
4.1.3 MODULE SECURITY ................................................................................................100
4.2 MIMIC TAB .......................................................................................................................103
4.3 ALARM STATUS TAB .....................................................................................................104
4.4 STATUS DISPLAY TAB...................................................................................................105
4.5 BASIC INSTRUMENTATION TAB ..................................................................................106
4.6 MORE INSTRUMENTATION TAB...................................................................................107
4.7 EVENT LOG TAB .............................................................................................................108
5 SETUP MENU OPTIONS ............................................................................. 109
5.1 SETUP ..............................................................................................................................109
5.1.1 OPERATOR PASSWORD ........................................................................................112
5.1.2 TECHNICIAN PASSWORD ......................................................................................113
5.1.3 MAINTENANCE PASSWORD ..................................................................................114
5.1.4 ENGINEERING PASSWORD ...................................................................................115
6 RE-CALIBRATION MENU ........................................................................... 116
6.1 RE-CALIBRATE CONTROLLER .....................................................................................116
DSE P810 for Windows ISSUE 9 16/07/2007 AM 3
DSE P810 for Windows ™ Software Manual
1 DESCRIPTION
The DSE 810 Configuration interface allows the 55x family of modules to be connected to a PC.
Once connected the various operating parameters within the module can be viewed or edited as
required by the engineer. This software allows easy controlled access to these values and also has
diagnostic monitoring facilities.
The Configuration interface should only be used by competent, qualified personnel, as changes to
the operation of the module may have safety implications on the panel / generating set to which it is
fitted. Access to critical operational sequences and settings for use by qualified engineers, are
barred by a security code. Timers are protected by a separate code allowing operator changes to
be made.
The information contained in this manual should be read in conjunction with the information
contained in the appropriate module documentation. This manual only details which settings are
available and how they may be used. The operation of the module is detailed in its own relevant
manual.
There are two versions of the interface available, an RS232 version and a USB 1.1 version. Both
are housed in a robust plastic case. The RS232 version is terminated in a standard 25 pin D type
RS232 connector and is supplied with an adapter cable to allow connection to the 9 pin D type
RS232 connectors as required. The USB version is terminated in a USB type B socket and is
supplied with a USB connecting cable fitted with a type A plug at one end and a type B plug at the
other end. In both cases, connection to the module is via an FCC 68 „Network‟ type cable, this
allows for easy replacement in the field should the connecting lead be damaged or lost.
DEEP SEA ELECTRONICS PLC own the copyright to this manual,
which cannot be copied, reproduced or disclosed to a third party
without prior written permission.
NOTE:- This Manual does not cover Remote Communication using the P55x fitted
with either RS232 or RS485. For details of these systems please refer to the Link500Plus
Manual.
NOTE:- This Manual does not cover commissioning and/or electrical connections of
Load sharing systems. For details on this, you are referred to the DSE Guide to
Synchronising and Load Sharing.
NOTE:- As P810 for Windows™ is a 32-Bit application it will not operate on Windows
2.0, 3.0, 3.1 or 3.11.
NOTE:- Exit all other programs before installing the P810 for Windows™ software. It
is recommended that any earlier releases of the software are uninstalled prior to
installing this version.
Insert the Software CD into the CD-ROM drive on the PC. The CD should then Auto-run.
Alternatively
There will be a short delay while the CD-ROM is accessed, then the install program will run
Click on the „P810 for Windows „ button to install the software onto your PC in its own folder
(directory). It will also create „START MENU‟ items.
NOTE:- The Software CD will also allow the user to create a set of floppy disks to
enable installation on PC‟s without CD-ROM drives. Full software manuals are also
included on the Software CD in PDF format.
NOTE:- As P810 for Windows™ is a 32-Bit application it will not operate on Windows
2.0, 3.0, 3.1 or 3.11.
NOTE:- Exit all other programs before installing the P810 for Windows™ software. It
is recommended that any earlier releases of the software are uninstalled prior to
installing this version.
There will be a short delay while the floppy disk is accessed, then the disk contents will be
displayed.
Set-up will now automatically install P810 for Windows onto your PC in its own folder (directory). It
will also create „START MENU‟ items.
Press the :
Start
NOTE:- Alternatively locate the „P810 for Windows‟ Directory on your hard drive and
Click on the icon:-
The software provides four levels of password protection. The first level is the operator level, if the
operator password is entered it will only be possible to edit the Timers not the module configuration.
In addition, operator level only allows the creation of new configuration files, existing files cannot be
over-written. The second level of password protection is the technician Level, if this password is
entered all of the module functions can be configured.
The third level of password is the Maintenance level, if this password is entered SCADA information
can be viewed, Module time, hours run clocks, accumulated values can be adjusted. A software
Maintenance reset can also be performed.
The fourth level of password is the Engineer level, if this password is entered all of the module
functions can be configured, LOP and HET senders can be calibrated and the Module time, hours
run clocks, accumulated values can be adjusted. A software Maintenance reset can also be
performed. Password for all levels can also be changed with this level.
It is intended that the technician and engineering passwords be given to qualified engineers who
are responsible for initial configuration of the unit, or modification of settings at a later stage.
The operator password is intended to be given to personnel who will not need to be altering the
configuration of the module, but may need to visit a controller and modify timer settings, record
these changes in a new file and view diagnostic information from the module.
The Maintenance password is intended to be given to personnel who will be attend the generator to
perform routine maintenance only.
The final level is the Mimic level, if the password „MIMIC‟ is entered the software will display the
diagnostic mimic display. None of the module values can be altered and no software settings can
be changed. This password is intended for use in situations where the PC is being used for remote
monitoring and it is not desirable to allow access to any parameters.
Users without a password will not be able to gain access to the software at all.
Enter the correct password for the required access level then; Click „OK‟ or press the ENTER key.
NOTE:- The default Engineer password is blank and when a password is requested,
Click „OK‟ or press the ENTER button.
Modules Type:- This indicates the type of module for which the P810 for Windows software is
currently configured. This will automatically be selected to the correct module when a configuration
file is „Loaded‟ from disk or „Read‟ from the module. It can also be changed from the „Edit
Configuration‟, „Misc‟ menu.
Access Level:- This indicates the current level of access to the software. Access is gained
depending on the password typed to enter to program on start-up. It is the access level that
determines what configuration options are available.
File Loaded:- This indicates name of the configuration file currently loaded into the P810 for
windows program. If the configuration was „Read‟ from the module then „FROM MODULE‟ will be
displayed.
Load from Disk:- This is used to load an existing configuration from disk into the P810 for
windows program. The file could then be edited (if required) and then „Written‟ to the module. To
load a file, simply click this button and enter the name of the file to be loaded in the dialog box.
Then click „OK‟. The „File Loaded‟ will then be indicated.
Save to Disk:- This is used to save the current configuration file to disk. The required filename for
the configuration can be typed in the dialog box. Then click „OK‟.
Print Configuration:- This is used to produce a print-out of the current configuration. You will be
prompted to enter your name (to allow it to be easily identified). A list of all the settings will then be
produced.
Read from Controller:- This is used to „Read‟ the configuration which exists in the module. The
module must be connected to the PC via the 810 interface and have a DC supply feeding it. It is
possible to read from the module while the generating set is running. Clicking the „Read‟ button will
transfer the current configuration to the P810 for windows program to allow the setting to be
inspected or modified.
Write to Controller:- This is used to write a new configuration to the module. To write to the
module it must be connected to the PC via the 810 interface and be fed from a suitable DC supply.
Additionally the module must be in the correct operating mode in order for re-configuration to be
accepted.
Should the module not be ready to receive data i.e. generator not at rest in stop mode, the software
senses that the engine is running and a message at the bottom of the screen will be displayed.
Steps should then be taken to ensure that the engine is at rest and the module is in the „STOP‟
mode before attempting to write to the module.
Exit:- This is used to exit the P810 for windows program and return to windows. If any
configuration files are open which have not been saved, the software will query if it is OK to
continue or if they need to be saved.
CAUTION!:- Ensure that you make a note of the PIN number when you allocate it to a
module. With out the correct PIN number it will be impossible to gain configuration
access to the module. If the PIN number is lost the module will need to be returned to
DSE to be re-initialised – All module setting will however be lost in this operation.
If the password is set to something other than the default “0000” P810 will display the following
screen:-
Using the selectors the correct PIN should be selected and then the OK button selected. The PIN
entered will be compared against the module PIN and if a match is found access will be granted.
if the user tryies to send a second config the P810 software will try to use the last PIN number
entered during that session and if this fails it will try the default PIN number, if this also fails it will
then prompt the user to enter the module PIN.
The module will allow three attempts to enter the PIN number – If this is exceeded it will stop
responding to attempts for a period of 60 seconds. The following message will be displayed:-
After this period the module will start checking the PIN numbers again, a further two attempts will
be granted. If these are both incorrect the module will again stop responding for double the
previous period. This will continue to a maximum wait period between retries of 64 minutes. This
is to prevent a more determined attack on the security of the module via a remote link.
CAUTION!:- Ensure that you make a note of the PIN number when you allocate it to a
module. With out the correct PIN number it will be impossible to gain configuration
access to the module. If the PIN number is lost the module will need to be returned to
DSE to be re-initialised – All module settings will however be lost in this operation.
CAUTION!:- Setting a PIN number in the module will stop all access to the module via
the P810 software. Therefore, it is important to ensure that any field service personnel
who are likely to need access to the module configuration as advised of the PIN number
prior to visiting site. Without the correct PIN number, the module will not allow changes
to its configuration.
Access to the various configuration parameters depends on the password entered when the
program was started. If the Operator password was entered, then selecting the Edit Configuration
option will take the user directly to the Edit Timers page as this is the only editable section with
operator level clearance.
If the Technician or Engineering level password was entered then full access to the settings is
possible.
NOTES:- It will not be possible to send a configuration for the wrong module type to
a different module. E.g You cannot send a 550 config to a 555 module. However, it is
possible to base a new config on an existing config and change the options to suit the
new module.
MODULE DESCRIPTION
Item Function
Base Module These setting are used to select the base module on which the configuration
is based.
Module Type -
= 550 Remote Start Module
= 555/557 Automatic mains failure module
= 556 ATS / Mains controller
This setting determines whether the configuration file is for a 550, 555/557 or
a 556 module. If a 550 module is selected options for the 555/557 module will
be hidden. The software will not allow the operator to „Write‟ the wrong
configuration file to the 55x module.
Module Version-
1 = Module is a V1.xx version.
2 = Module is a V2.xx version.
3 = Module is a V3.xx version.
4 = Module is a V4.xx version.
5 = Module is a V5.xx version.
6 = Module is a V6.xx version.
7 = Module is a V7.xx version.
A number of features were added to the 55x range of module when V2.00,
V3.00, V4.00, V5.00, V6.00 & V7.00 software was released. These features
are not available on earlier modules.
NOTES:- It is possible to configure the 55x module to use either alternator frequency
or magnetic pickup speed sensing, both or none (Not 556). If both sources are used, a
shutdown will occur if either speed sensing source gives an over or under-speed
(frequency) signal.
If a magnetic pickup is not to be used it is important that is selected for „Magnetic
pickup present‟. If the module expects to receive magnetic pickup pulses and none are
apparent on starting, it assumes that the pickup is faulty and will shutdown the engine.
MISCELLANEOUS DESCRIPTION
Item Function
Configuration These four boxes are used to store details about the configuration. This
description could be used to store details such as Plant/Machine Number, Site location,
Customer, and configuration author, etc
Speed sensing This setting is used to select which method of speed sensing is used by the
options. module:-
(Not applicable to the Generator Frequency -
556.) = Speed sensing will not be derived from generator output frequency.
= Speed sensing will be derived from the generator output frequency
The number of alternator poles then needs to be set to allow the module to
determine the engine speed.
Magnetic Pick-up -
= Speed sensing will not be derived from the magnetic pickup.
= Speed sensing will be derived from the magnetic pickup
The number of flywheel teeth on the engine then needs to be set.
NOTE:- The above is only available if using MPU sensing and only
on modules.
Item Function
AC Options These settings are used to detail the type of AC system to which the module
is connected:-
AC system -
3 phase 4 wire
1 phase 2 wire
This setting is used to select the type of AC wiring system used.
Phase Rotation - (Enhanced Instrumentation Modules Only)
Phase Sequence L1 L2 L3
Phase Sequence L3 L2 L1
This setting is used to select the direction of phase rotation.
Enable Generator Phase Rotation Alarm -
= Incorrect Phase rotation will not cause an alarm.
= Phase rotation will be monitored, and if found to be incorrect an alarm will
be triggered.
Enable Mains Phase Rotation Alarm -(Enhanced AMF Modules Only)
= Incorrect Phase rotation will not cause an alarm.
= Phase rotation will be monitored, and if found to be incorrect an alarm will
be triggered.
Enable Bus Phase Rotation Alarm -(Check Sync 550 and 556 Modules
Only)
= Incorrect Phase rotation will not cause an alarm..
= Phase rotation will be monitored, and if found to be incorrect an alarm will
be triggered.
Item Function
Miscellaneous These settings are used to select a range of different functions:-
Options Enable Fast Loading feature - (Not applicable to the 556.)
= Normal Operation, the safety on timer will be observed in full. This
feature is useful if the module is to be used with some small engines where
pre-mature termination of the delay timer can lead to overspeed alarms on
start up.
= The module will terminate the safety on timer once all monitored
parameters have reached their normal settings. This feature is useful if the
module is to be used as a standby controller as it allows the generator to start
and go on load in the shortest possible time.
Item Function
Module Display These settings are used to select a range of different functions:-
Options Display indications on LCD -
= Indications will illuminate to appropriate LED only.
= Indications will illuminate the appropriate LED and/or be displayed in a list
on the „Information page‟. This list can be viewed by operating the „up‟ or
„down‟ button.
Display Load Switching state machine -
= LCD display only shows main „information‟ state machine.
= LCD display shows the main „information‟ state machine as default, but
the state of the contactors or breakers can be viewed by operating the „up‟ or
„down‟ buttons. This selects the „Load switching‟ state machine to be
displayed.
Function Description
Oil Pressure settings This section is used to configure the Oil Pressure sender input.
Input Type:-
(Not applicable to the 556.) Disabled - The Oil pressure input will not be monitored.
Digital - closed for low oil pressure - The Oil Pressure input is fed from an
engine mounted digital pressure switch. This switch returns a closed
signal during low oil pressure conditions (and engine at rest), once oil
pressure is established the switch will open.
Digital - open for low oil pressure - The Oil Pressure input is fed from an
engine mounted digital pressure switch. This switch returns an open
signal during low oil pressure conditions (and engine at rest), once oil
pressure is established the switch will close.
VDO match, 0-5bar - The Oil Pressure input is connected to a resistive
type engine mounted oil pressure transducer. The output of this
transducer matches that of a VDO type sender with an operating range
of 0-5bar.
VDO match, 0-10bar* - The Oil Pressure input is connected to a resistive
type engine mounted oil pressure transducer. The output of this
transducer matches that of a VDO type sender with an operating range
of 0-10bar.
Datcon match, 0-5bar - The Oil Pressure input is connected to a resistive
type engine mounted oil pressure transducer. The output of this
transducer matches that of a Datcon type sender with an operating
range of 0-5bar.
Datcon match, 0-10bar - The Oil Pressure input is connected to a resistive
type engine mounted oil pressure transducer. The output of this
transducer matches that of a Datcon type sender with an operating
range of 0-10bar.
Murphy, 0-7bar - The Oil Pressure input is connected to a resistive type
engine mounted oil pressure transducer. The output of this transducer
matches that of a Murphy type sender with an operating range of 0-
7bar.
Function Description
High Coolant Temperature This section is used to configure the Coolant Temperature sender
settings input.
Input Type:-
(Not applicable to the 556.) Disabled - The Coolant Temperature input will not be monitored.
Digital Switch, Normally Closed - The Coolant Temperature input is fed
from an engine mounted digital temperature switch. This switch returns
a closed signal during low temperature conditions, should the
temperature rise above the switch manufacturers trip point the switch
contacts will open.
Digital Switch, Normally Open - The Coolant Temperature input is fed from
an engine mounted digital temperature switch. This switch returns an
open signal during low temperature conditions, should the temperature
rise above the switch manufacturers trip point the switch contacts will
close.
VDO match, 120oC* - The Coolant Temperature input is connected to a
resistive type engine mounted temperature transducer. The output of
this transducer matches that of a VDO type sender with an operating
o
range of up to 120 C.
Datcon HIGH match - The Coolant Temperature input is connected to a
resistive type engine mounted temperature transducer. The output of
this transducer matches that of a Datcon HIGH type sender.
Datcon LOW match - The Coolant Temperature input is connected to a
resistive type engine mounted temperature transducer. The output of
this transducer matches that of a Datcon LOW type sender.
Murphy - The Coolant Temperature input is connected to a resistive type
engine mounted temperature transducer. The output of this transducer
matches that of a Murphy type sender.
Cummins – The Coolant Temperature input is connected to a resistive
type engine mounted temperature transducer. The output of this
transducer matches that of a Cummins type sender.
NOTE:- Each of the auxiliary inputs has the same selection choices, allowing
flexibility of selection to be made. However, only one of the fixed input functions can be
used at any one time, i.e only one input can be configured to be „remote start‟. The User
Configurable option is the exception to this rule, and allows any number of inputs to be
used as Indications (Single or Dual) , Warnings, Shutdowns or as an electrical trip Input
POLARITY
The polarity of the input switching can be configured to be either “Close to Activate”, this is a
normally open switch, and closes to negative when activated. Alternatively “Open to Activate”, this
is a Normally Closed switch to negative, and opens when activated.
ACTIVIATION DELAY
User configured inputs can be delayed using the activation delay timer. The input must be active for
the duration of the activation delay timer setting before any action is taken. This is particularly useful
for use with external float switches etc to prevent nuisance tripping.
INPUT SELECTION
Function Description
Not Used The input is not configured to perform any function.
User Configured The input is configured to perform an auxiliary function, this may
be any of the following:-
Indication (annunciation only, no alarm or shutdown)
Dual Indication (annunciation only allowing both the active and
in-active states to have different text, no alarm or shutdown)
Warning (Alarm only, no shutdown)
Shutdown (Alarm and shutdown)
Electrical Trip (Alarm/off-load generator followed by shutdown
after cooling)
Function Description
Auto start Inhibit This input is used to provide an over-ride function to prevent the
55x from starting the generator in the event of a remote
start/mains out of limits condition occurring. If this input is active
and a remote start signal/mains failure occurs the 55x will not
give a start command to the generator. If this input signal is then
removed, the 55x will operate as if a remote start/mains failure
has occurred, starting and loading the generator. This function
can be used to give an „AND‟ function so that a generator will
only be called to start if the mains fails and another condition
exists which requires the generator to run. If the „Auto start
Inhibit‟ signal become active once more it will be ignored until the
module has returned the mains supply on load and shutdown.
Auxiliary Mains Fail The 555, 557 and 556 module will monitor the incoming single or
three phase supply for Over voltage, Under Voltage, Over
Frequency or Under frequency. It may be required to monitor a
different mains supply or some aspect of the incoming mains not
monitored by the 555, 557 and 556. If the devices providing this
additional monitoring are connected to operate this input, the
555, 557 and 556 will operate as if the incoming mains supply
has fallen outside of limits, the generator will be instructed to
start and take the load. Removal of the input signal will cause
the module to act if the mains has returned to within limits.
Bus closed auxiliary This input is used to provide feedback to allow the 556 to give
556 only true indication of the contactor or circuit breaker switching status.
It should be connected to the generator bus load switching
device auxiliary contact.
Function Description
Lamp Test This input is used to provide a test facility for the front panel
indicators fitted to the 55x module. When the input is activated
all LED‟s should illuminate.
MSC Alarms inhibit This input is used to prevent MSC alarms. It is particularly useful
when a set is being removed from duty for maintenance.
Function Description
Remote Start off load If this input is active operation will be similar to the „Remote Start
on load‟ function except that the generator will not be instructed
to take the load. This function can be used where an engine only
run is required eg for exercise.
Remote Start on load If this input is active, the 55x will operate thus:- To use this
function the 55x should be placed in the AUTO mode. The
module will perform the start sequence as described earlier in
this manual.
Remote Start on load If this input is active, the load demand start up and shut down
demand scheme will be activated when two or more generators are
running in parallel.
Function Description
Speed lower On 550/555/557 systems where internal relays are used to
control the governor, this input can be used to decrease the
(Not applicable to the 556.) speed.
The first button press will cause the module to close the
generator contactor once the genset bus and Mains are
synchronised.
Once synchronised the genset bus and mains will parallel. The
second press of the button will then cause the genset bus to take
full load and open the mains contactor.
Function Description
Transfer to generator/Open This input is used to transfer the load to the generator when
Mains running in MANUAL MODE.
(Not applicable to the 556.) If used with a Check sync/auto sync module – The first button
press will cause the module to close the generator contactor
once the genset and Bus/Mains are synchronised.
On 555 and 557 module only: Once synchronised the genset and
bus/mains will parallel. The second press of the button (or expiry
of the parallel run timer) will then cause the genset to take full
load and open the mains contactor.
Transfer to Mains/ Open This input is used to transfer the load to the mains supply when
Generator running in MANUAL MODE. (Also used to provide an „Open
Generator‟ signal in the 550 Module.)
(Not applicable to the 556.)
If used with a Check sync/auto sync module – The first button
press will cause the module to close the mains contactor once
the genset and Bus/Mains are synchronised.
On 555 and 557 module only: Once synchronised the genset and
bus/mains will parallel. The second press of the button (or expiry
of the parallel run timer) will then cause the mains to take full
load and open the generator contactor.
Transfer to Mains/ Open bus This input is used to transfer the load to the mains supply when
(556 only) running in MANUAL MODE.
The first button press will cause the module to close the mains
contactor once the genset bus and mains are synchronised.
Once synchronised the genset bus bus mains will parallel. The
second press of the button (or expiry of the parallel run timer) will
then cause the mains to take full load and open the generator
bus contactor.
Volts lower On 550/555/557 systems where internal relays are used to
control the AVR, this input can be used to decrease the volts.
(Not applicable to the 556.)
NOTE:- Each Auxiliary output has the same selection choices, allowing a
combination of different uses.
Expansion outputs are available for 55x type modules on a plug in Expansion module type
157, this provides volt free contacts. A maximum of two such expansion modules can be
used giving a total of 16 voltage free contacts. The 157 modules are fitted with switch
labelled „A‟ and „B‟. With the switch in the „A‟ position the 157 module will respond to
signals for expansion relays „A‟ 1 - 8. If the switch is placed in the „B‟ position the 157
module will respond to signals for expansion relays „B‟ 1-8. Therefore, to use all sixteen
possible relays two 157 modules need to be fitted one with the switch set to „A‟ the other
set to „B‟
If expansion outputs are required to be fitted for indication purposes only, a plug in LED
Expansion module type 548 is available. A maximum of two such expansion modules can
be used giving a total of 16 configurable LED‟s (+ Power On and Link Lost indicators).
The 548 modules are fitted with switch labelled „A‟ and „B‟. With the switch in the „A‟
position the 548 module will respond to signals for expansion relays „A‟ 1 - 8 and
illuminate the appropriate LED‟s. If the switch is placed in the „B‟ position the 548
module will respond to signals for expansion relays „B‟ 1-8. And illuminate the
appropriate LED‟s. Therefore to use all sixteen possible configurable LED‟s two 548
modules need to be fitted one with the switch set to „A‟ the other set to „B‟ If required it is
possible to use a mix of both 157 Relay modules and 548 LED modules on the same 55x
Host.
CAUTION!:- The 157 relay status is updated a minimum of twice a second. While this
makes the response of the relays fast enough for annunciation, remote monito ring and
normal system control it is not considered suitable for use in time critical applications
such as high speed breaker tripping etc. If this type of function is intended, we would
recommend using the 55x modules own internal relay outputs to control such systems.
CAUTION!:- When used in conjunction with the P122 Digital Resistance Modules, only
P157/P548 Expansion modules with Part Number 81xxxxx MUST be used. The digital
resistance requires a different set of data commands to operate and the 55x module will
change the data output by the expansion port to suit the P122 when selected. The older
P157/P548 modules (Part No. 80xxxxx) will only function if the P122 module is not
configured for use by the 555.
POLARITY
Each of the outputs can be configured as:
a) Energised
Normally open relay contact which closes on activation.
b) De-energised
Normally closed relay contact, which opens on activation.
NOTE:- If the Expansion relays are actually control sources used for a 548 module
then Energised = Lit and De-energised = Unlit.
OUTPUT SELECTION
Function Description
Output Not Used The output in not used.
Activate Synchroniser This output indicates that the generator is ready to synchronise to the
bus. The output can be used to signal an external synchroniser to
control the generator and synchronise with the bus.
Air-flap Alarm This output indicates that the air-flap is closed, to operate it requires an
input configured as „Air-flap closed‟ connected to the external air-flap
switch.
Air flap Relay The output controls the closing of the air-flaps in an Emergency Stop or
Over-speed situation.
Alarm Mute This output indicates that the module‟s internal audible alarm has been
muted. The output could be used to command a muting of some
external sounding device.
Alarm Reset This output indicates that an alarm reset is being performed. Once the
alarm reset has been completed, the output will become inactive again.
This output could be used to give a reset signal to external systems
such as annunciators or BMS systems to clear any latched alarms.
All available sets on bus This output indicates that all the available sets in the multiset load
sharing system are closed onto the generator bus. This output can be
used to close an external breaker to allow the generator bus to power
the load. „Available sets‟ are sets in auto mode with no alarms present.
So sets not in auto mode, or sets that have alarms present are not
considered to be „available sets‟.
Audible Alarm This output indicates that the internal sounder is operating. It may be
used to feed an external sounder. Operation of the Mute pushbutton
will reset this output once activated.
Auto Start Inhibit This output indicates that a digital input that has been configured as
„Auto Start Inhibit‟ is active. Refer to the „Edit Inputs‟ section of this
manual for details.
Auxiliary Mains failure This output indicates that a digital input that has been configured as
„Auxiliary Mains Failure‟ is active. Refer to the „Edit Inputs‟ section of
this manual for details.
Battery High Voltage This output indicates that a Battery High Voltage alarm has occurred.
Battery Low Voltage This output indicates that a Battery Low Voltage alarm has occurred.
Bus and mains in parallel This output indicates that the generator bus and mains supply are in
(556 only) parallel.
Bus failed to close This output indicates that the generator bus load switching device failed
(556 only) to close in the time allowed by the “bus failed to close” timer.
Bus failed to open This output indicates that the generator bus load switching device failed
(556 only) to open in the time allowed by the “bus failed to open” timer.
Bus Live This output indicates that a voltage has been detected on the bus.
Once the voltage on the bus is detected above the “Dead bus relay
setting”, it will no-longer be considered a „dead-bus‟ and the generator
will need to synchronise in order to get onto the bus.
Function Description
Bus Phase Sequence This output indicates that the module has detected a phase sequence
Wrong error on the bus.
Calling for Scheduled run This output indicates that a scheduled run has been called for. The
generator will run if the module is in the „Auto‟ mode and no shutdown
alarms are present. Refer to the Schedule section of this manual for
more details.
Charge alternator failure This output indicates that a failure of the auxiliary charging alternator on
the generator has occurred.
Check Sync. This output indicates that the generator and bus are in sync and that it
is safe to close the set onto the bus. This output provides a similar
function to that of a sync check relay.
Clock not set warning This output indicates that the internal clock used by the module event
log is not running. This should be set to the correct date and time.
Close Bus This output source is intended to be used to control the bus load
(556 only) switching device. Whenever the 55x module selects the generator bus
to be on load this control source will be active.
Close Bus Pulse This output source is intended to be used to control the bus load
(556 only) switching device. Whenever the 55x module selects the bus to be on
load, this control source will be active for the duration of the „Breaker
Close Pulse Timer‟. Once this timer has expired, the output source will
once again become in-active.
Close Generator This output source is intended to be used to control the load switching
device. Whenever the 55x module selects the generator to be on load
this control source will be active.
Close Generator Pulse This output source is intended to be used to control the load switching
device. Whenever the 55x module selects the generator to be on load,
this control source will be active for the duration of the „Breaker Close
Pulse Timer‟. Once this timer has expired, the output source will once
again become in-active.
Close Mains This output source is intended to be used to control the load switching
device. Whenever the 555 557 and 556 module selects the mains to
be on load this control source will be active.
Close Mains Pulse This output source is intended to be used to control the load switching
device. Whenever the 555 557 and 556 module selects the mains to
be on load this control source will be active for the duration of the
„Breaker Close Pulse Timer‟. Once this timer has expired the output
source will once again become in-active.
Combined under & over The output indicates that a either an under frequency or over frequency
Frequency shutdown shutdown has been activated.
Function Description
Combined under & over The output indicates that a either an under voltage or over voltage
voltage shutdown shutdown has been activated.
Duty select
Earth Fault This output indicates that the module has detected that an earth fault
(Not applicable to the 556.) exists on the generator output.
Function Description
Emergency Stop This output indicates that an Emergency stop alarm has occurred.
(Not applicable to the 556.)
Energise to stop The output controls the fuel solenoid on an ETS type generator,
energising for the time period selected in the Edit Timer Menu. The
(Not applicable to the 556.) normal fuel output (pin 4) should not be connected to the fuel solenoid,
however it can be used for controlling panel instruments and other
functions required whilst the engine is running.
Fail to start alarm The output indicates that the engine has not started after the specified
(Not applicable to the 556.) number of attempts, selected in the Edit Miscellaneous Menu.
Fail to stop alarm The output indicates that the generator has failed to stop within the time
period selected in the Edit Timer Menu. The module monitors that the
(Not applicable to the 556.) oil pressure has gone low and that the speed-sensing source detects
no movement of the generator to establish that the generator has
stopped.
Fail to Synchronise Alarm This output indicates that the generator has not synchronised to the
bus within the time allowed. This could indicate a problem with the
AVR or governor.
Fast Trip Generator This output source is intended to be used if it is required to trip a
generator excitation circuit breaker or operate some other means of
tripping alternator off load. This would then be activated under short
circuit or earth fault conditions as well as normal electrical trip events.
Fast trip generator is the only output source that should be used for this
purpose as it is a fast acting output. This output can only be reset by
removal of the fault and by then pressing the Stop Reset button or by
using an external „Alarm Reset‟ Input.
Generator & Mains in 555, 557 and 556 only:
Parallel This output indicates that the gen-set and mains are running in parallel.
This will be active whenever the two supplies are on load together.
Fuel relay energised The output mimics the operation of the fuel relay. Can be used to
(Not applicable to the 556.) control external logic circuitry.
Generator Low Frequency This output indicates that a Generator Low Frequency Shutdown has
Shutdown occurred.
(Not applicable to the 556.)
Generator at Rest This output indicates that the generator is not running.
(Not applicable to the 556.)
Generator Available This output indicates when the generator is ready to accept load, i.e.
(Not applicable to the 556.) after safety on and warm up timers have timed out. It could be used to
connect to an Automatic Transfer System or PLC to give a signal that
the set is available.
Function Description
Generator Closed Auxiliary This output indicates that a digital input that has been configured as
„Generator Closed Auxiliary‟ is active. Refer to the „Edit Inputs‟ section
of this manual for details.
Generator Close Request This output indicates that the module has synchronised and is
requesting to close onto the dead bus.
Generator Failed to Close This output source is intended to be used to indicate a failure of the
generator contactor or breaker. It can only be used if the module is
configured to use „Generator Closed Auxiliary‟ feedback.
Generator Failed to Open This output source is intended to be used to indicate a failure of the
generator contactor or breaker. It can only be used if the module is
configured to use „Generator Closed Auxiliary‟ feedback.
Generator High Frequency This output indicates that a Generator High Frequency Warning (pre-
Pre-alarm alarm) has occurred.
(Not applicable to the 556.)
Generator High Frequency This output indicates that a Generator High Frequency Shutdown has
Shutdown occurred.
(Not applicable to the 556.)
Generator High Voltage This output indicates that a Generator High Voltage Warning (pre-
Pre-alarm alarm) has occurred.
(Not applicable to the 556.)
Generator High Voltage This output indicates that a Generator High Voltage Shutdown has
Shutdown occurred.
(Not applicable to the 556.)
Generator Load Inhibit This output indicates that a digital input that has been configured as
(Not applicable to the 556.) „Generator Load Inhibit’ is active. Refer to the „Edit Inputs‟ section of
this manual for details.
Generator Low Frequency This output indicates that a Generator Low Frequency Warning (pre-
Pre-alarm alarm) has occurred.
(Not applicable to the 556.)
Generator Low Frequency This output indicates that a Generator Low Frequency Shutdown has
Shutdown occurred.
(Not applicable to the 556.)
Generator Low Voltage This output indicates that a Generator Low Voltage Warning (pre-
Pre-alarm alarm) has occurred.
(Not applicable to the 556.)
Generator Low Voltage This output indicates that a Generator Low Voltage Shutdown has
Shutdown occurred.
(Not applicable to the 556.)
Generator Phase This output indicates that the module has detected a phase sequence
Sequence Wrong error from the generator output.
Generator Reverse Power This output indicates that a Generator Reverse Power alarm has
(Not applicable to the 556.) occurred.
Generator Stopping This output source indicates that the engine has been instructed to stop
(Not applicable to the 556.) but has not yet come to rest. Once the engine comes to a standstill
this output will become in-active.
Function Description
Lamp test This output indicates that the module is performing a lamp test. Once
the lamp test is completed, the output will become inactive again. The
output can be used to feed a lamp test on external modules or panel
lamps.
Loss of Magnetic pick-up This output indicates that the magnetic pick up signal is not sufficient to
speed signal be used by the module for speed monitoring. The alarm can only
operate if the speed signal fails to appear during cranking. It is
(Not applicable to the 556.) disabled if „multiple attempts to engage‟ is selected. If the MPU fails
during engine running this would result in an underspeed alarm.
Louvre control The output controls the opening of the louvres on engine starting and
(Not applicable to the 556.) closure when engine has stopped.
MSC failure Indicates a complete failure of the multiset communications data link.
MSC ID Error Indicates that two or more modules share the same ID number. They
must all be unique.
MSC Data error Indicates a data transfer error on the multiset communications link data
MSC too few sets Indicates that the number of sets on the multiset communications data
link is lower than that specified in the module‟s configuration.
Magnetic Pick-up open This output indicates that the module has detected an open circuit
circuit failure in the Magnetic Pickup transducer circuit.
(Not applicable to the 556.)
Maintenance Due Alarm This output indicates that the generator is now due for maintenance
either because it has used all the available running hours or the
periodic maintenance time has expired. To clear the output a
maintenance reset must be performed. (refer to the Maintenance
(Not applicable to the 556.) alarm section of this manual).
Minimum sets not reached This output indicates that the minimum number of sets has not been
(556 only) reached prior to closing the generator bus load switching device as
dictated by the “minimum number of sets” setting on the „System‟ tab.
Mains Closed Auxiliary This output indicates that a digital input that has been configured as
„Mains Closed Auxiliary’ is active. Refer to the „Edit Inputs‟ section of
this manual for details.
Mains Failed to Close This output source is intended to be used to indicate a failure of the
mains contactor or breaker. It can only be used if the module is
configured to use „Mains Closed Auxiliary‟ feedback.
Function Description
Mains Failed to Open This output source is intended to be used to indicate a failure of the
mains contactor or breaker. It can only be used if the module is
configured to use „Mains Closed Auxiliary‟ feedback.
Mains Failure This output indicates that the module has sensed that a failure of the
incoming AC mains supply. This output will become active whenever
the mains voltage or frequency goes out of limits, or if the auxiliary
mains failure input active (if used) and the mains transient timer has
expired.
Mains High frequency This output indicates that the module has sensed that the incoming AC
mains supply has exceeded the frequency limit setting.
Mains High voltage This output indicates that the module has sensed that the incoming AC
mains supply voltage has exceeded the voltage limit setting.
Mains Load Inhibit This output indicates that a digital input that has been configured as
„Mains Load Inhibit’ is active. Refer to the „Edit Inputs‟ section of this
manual for details.
Mains Low frequency This output indicates that the module has sensed that the incoming AC
mains supply has fallen below the frequency setting.
Mains Low voltage This output indicates that the module has sensed that the incoming AC
mains supply voltage has fallen below the voltage limit setting.
Mains Phase Sequence This output indicates that the module has detected a phase sequence
Wrong error on the incoming AC mains supply.
Modem Power Fault (RS232 Communication option only.) This output indicates that the
module has detected an overload of the internal Power supply feeding
the modem. This could indicate a faulty modem or a modem
unsuitable for connection to the P55x Module‟s power supply.
Mute / Lamp test button This output indicates that the alarm mute / Lamp test pushbutton is
pressed being operated. Once the button is released the output will become
inactive.
No loading command This output indicates that the module is not calling of the generator (or
mains [555 and 557 Modules only]) contactor or breaker to be closed.
Should the module close the generator (or mains) contactor this output
will become inactive.
Oil pressure low Pre-alarm This output indicates that a low oil pressure warning (pre-alarm) has
(Not applicable to the 556.) occurred.
Oil pressure low shutdown This output indicates that a low oil pressure shutdown has occurred.
(Not applicable to the 556.)
Oil Press sender Open This output indicates that the module has detected an open circuit
circuit failure in the Oil Pressure transducer circuit.
(Not applicable to the 556.)
Open bus This output source is intended to be used to control the bus load
(556 only) switching device. Whenever the 556 module selects the bus to be on
load this control source will be active.
Open bus Pulse This output source is intended to be used to control the bus load
(556 only) switching device. Whenever the 556 module selects the bus to be on
load, this control source will be active for the duration of the „Breaker
open Pulse Timer‟.
Open Generator This output source is intended to be used to control the load switching
(Not applicable to the 556.) device. Whenever the 55x module selects the mains to be on load this
control source will be active.
Function Description
Open Generator Pulse This output source is intended to be used to control the load switching
(Not applicable to the 556.) device. Whenever the 55x module selects the mains to be on load, this
control source will be active for the duration of the „Breaker open Pulse
Timer‟.
Open Mains This output source is intended to be used to control the load switching
device. Whenever the 555,556 or 557 module selects the generator to
be on load this control source will be active.
Open Mains Pulse This output source is intended to be used to control the load switching
device. Whenever the 555,556 or 557 module selects the generator to
be on load this control source will be active for the duration of the
„Breaker open Pulse Timer‟. Once this timer has expired the output
source will once again become in-active and the 555,556 or 557 will
issue commands to load the generator.
Over current Pre-alarm This output indicates that the over-current warning (pre-alarm) level
(Not applicable to the 556.) has been reached.
Over current trip This output indicates that the over-current trip level been reached.
(Not applicable to the 556.)
Overspeed Pre-alarm This output indicates that an overspeed warning (pre-alarm) has
(Not applicable to the 556.) occurred.
Overspeed Shutdown This output indicates that an overspeed shutdown has occurred.
(Not applicable to the 556.)
Panel locked This output indicates that the module „Panel Lock‟ is active. If the Panel
lock input is active, the module will not respond to operation of the
Mode select or start buttons. This allows the module to be placed into
a specific mode (such as Auto) and then secured. The operation of the
module is not affected and the operator will still be able to view the
various instrumentation pages etc. (Front panel configuration access is
barred while system lock is active).
Panel lock by digital input This output indicates that a digital input that has been configured as
„Panel Lock‟ is active. If the Panel lock input is active, the module will
not respond to operation of the Mode select or start buttons. This
allows the module to be placed into a specific mode (such as Auto) and
then secured. The operation of the module is not affected and the
operator will still be able to view the various instrumentation pages etc.
(Front panel configuration access is barred while system lock is active).
Refer to the „Edit Inputs‟ section of this manual for details.
Panel lock by telemetry This output indicates that remote „Panel Lock‟ via telemetry is active. If
the Panel lock is active, the module will not respond to operation of the
Mode select or start buttons. This allows the module to be controller
remotely without local interference The operation of the module is not
affected and the local operator will still be able to view the various
instrumentation pages etc. (Front panel configuration access is barred
while system lock is active). Refer to the Link500plus manual for
details.
Pre-heat (during preheat The output controls the pre-heater. Pre-heat output is available for the
timer) duration of the pre-heat timer, which terminates prior to cranking.
(Not applicable to the 556.)
Pre-heat (until end of The output controls the pre-heater. As „Pre-heat (during preheat timer)‟
crank) mode but pre-heat is also available during cranking.
(Not applicable to the 556.)
Pre-heat (until end of The output controls the pre-heater. As „Pre-heat (until safety on)‟ but
warming timer) pre-heat continues to be available until the warm-up timer has elapsed.
(Not applicable to the 556.)
Function Description
Pre-heat (until safety on) The output controls the pre-heater. As „Pre-heat (until end of cranking)‟
(Not applicable to the 556.) but pre-heat is also available while waiting for the delayed alarms to
become active.
Remote start off load This output indicates that a digital input that has been configured as
„Remote Start off load‟ is active. This output could be used to pass the
remote start signal on to elsewhere in the control system.
Remote start on load This output indicates that a digital input that has been configured as
„Remote Start on load‟ is active. This output could be used to pass the
remote start signal on to elsewhere in the control system.
Reset to Governor/AVR This output is intended to be used in conjunction with an electronic or
Datum motorised potentiometer, which has a „centre pot‟ type input. This
output is activated whenever the module needs to reset the
potentiometer to its centre position.
(Not applicable to the 556.)
Return delay in progress This output source will be active to indicate that the return timer is
running.
Short Circuit Generator This output indicates that the module has detected a short circuit on the
(Not applicable to the 556.) generator output.
Simulate Mains available This output indicates that a digital input that has been configured as
„Simulate mains available’ is active.
Function Description
Sufficient sets available This output indicates that there are sufficient sets available on the bus.
(556 only)
System healthy This output indicates that the module is in Auto mode and there are no
alarms present.
System in Test Mode This output indicates that the module is in the test mode.
System in Auto Mode The output indicates that the module is in the Auto mode.
System in Manual Mode This output indicates that the module is in the manual mode.
System in Stop Mode The output indicates that the module is in the Stop mode.
Telemetry data Active This output indicates that the remote telemetry link is active. This
(LED) output is intended to be fed to an LED to indicate data activity. It is not
suitable for use by the output relays. Refer to the „Link500plus„
manual.
Telemetry Active (Relay) This output indicates that the remote telemetry link is active. This
output may be used by either an LED or a Relay. It will be active
whenever the remote telemetry link is active. Refer to the „Link500plus‟
manual.
Underspeed Warning This output indicates that an underspeed warning (pre-alarm) has
(Not applicable to the 556.) occurred.
Underspeed Shutdown This output indicates that an underspeed shutdown has occurred.
(Not applicable to the 556.)
Voltage Lower Relay Auto-sync and load share units only:-
This output will be used to give a Voltage lower signal to the external
governor or electronic pot.
(Not applicable to the 556.)
Speed Raise Relay Auto-sync and load share units only:-
This output will be used to give a voltage raise signal to the external
governor or electronic pot.
(Not applicable to the 556.)
Waiting for generator This output indicates that the engine has been instructed to start but
has not yet become available. Once the generator becomes available
(Not applicable to the 556.) this output will become in-active. (Available = Generator Frequency
and Voltage levels are above the „Loading‟ levels set in the
configuration.)
Waiting for manual restore The 55x has detected that the remote start signal is inactive or the
mains supply has returned to within limits and is now available to take
the load. However, it is receiving a „Manual Restore‟ signal. Until this
is removed it will continue to run on the generator.
NOTES
1:- Each LED has the same selection of choices as stated in the edit outputs section of
this manual. The exception to this is the „Alarm‟ LED, this LED‟s function is fixed and
cannot be re-configured.
2:- Each LED can be configured to any function, allowing for flexible configuration.
3:- If expansion outputs are required to be fitted for indication purposes only, a plug in
LED Expansion module type 548 is available. A maximum of two such expansion modules
can be used giving a total of 16 configurable LED‟s (+ Power On and Link Lost
indicators). The 548 modules are fitted with switch labelled „A‟ and „B‟. With the switch
in the „A‟ position the 548 module will respond to signals for expansion relays 1 - 8 and
illuminate the appropriate LED‟s. If the switch is placed in the „B‟ position the 548
module will respond to signals for expansion relays 9-16, and illuminate the appropriate
LED‟s. Therefore to use all sixteen possible configurable LED‟s two 548 modules need to
be fitted one with the switch set to „A‟ the other set to „B‟.
CAUTION!:- When used in conjunction with the P122 Digital Resistance Modules, only
P157/P548 Expansion modules with Part Number 81xxxxx MUST be used. The digital
resistance requires a different set of data commands to operate and the 55x module will
change the data output by the expansion port to suit the P122 when selected. The older
P157/P548 modules (Part No. 80xxxxx) will only function if the P122 module is not
configured for use by the 555 or 557.
POLARITY
Each of the LED‟s can be configured as:
a)Lit - Normally extinguished LED, which illuminates on activation.
b)Un-lit - Normally illuminated LED which extinguishes on activation.
CONTROL SOURCE
Refer to Output Selection shown in Edit Outputs section of this manual.
LED IDENTIFICATION
LED1
Deep Sea Electronics plc
Model 550 LED2
LED3
LED4
i
O I AUTO
The above diagram indicates which LED number in the configuration corresponds to which LED on
the front label.
LED EXPANSION
548 LED Expansion Modules
+Ve
Up to 50m
-Ve
Up to 100m
810
NOTES:-
Timers can be adjusted by clicking on either the up or Down arrow or by clicking on the
bar and dragging the bar to the correct time.
As the timers can be accurately set to exact times, it is possible to initially configure the
module with the timers reduced to allow rapid testing of the finished generating set.
Once the set is ready for a final witness test, it is just a simple matter of entering the
specified timer settings and writing them to the module.
TIMER DESCRIPTIONS
Start Timers Function
Mains Transient Delay (Only available on 555, 557and 556 module)
This timer dictates how long a mains anomaly must be present before the
module will respond to it. This can be used to prevent nuisance tripping
when switching loads etc.
Start delay This timer dictates how long the module will wait after it has received a
remote start signal (or mains failure signal – 555, 557 and 556) before it
will attempt to start. This prevents un-necessary starting on a fluctuating
mains supply, etc.
Pre-heat This timer dictates the duration that the pre-heat output will be active
(Not applicable to the before an attempt is made to start the engine. Once this timer has expired
556.) cranking will commence.
NOTE:- If the generator does not start on the first attempt Pre-
heat is enabled prior to the second crank attempt.
Sensor fail delay (Only available if using Magnetic pick-up without multiple engage attempts)
This is only used if magnetic pick speed sensing is selected. Once
(Not applicable to the cranking has commenced the module must receive a speed signal within
556.) this time. If no signal is present the generator will be shutdown and a Loss
of Speed Sensing alarm given.
Engage Attempt time (Only available if using Magnetic pick-up and multiple engage attempts)
This timer dictates the duration that the module will attempt to engage the
(Not applicable to the starter motor during each engage attempt. If the Magnetic Pick-up is not
556.) detecting movement of the flywheel when this timer expires the engage
attempt will terminate. Once all engage attempts have been made the
module will generate a „Fail to engage‟ alarm.
Engage Rest Time (Only available if using Magnetic pick-up and multiple engage attempts)
(Not applicable to the This timer dictates the duration that the module will wait between attempts
556.) to engage to starter.
Cranking time This is the maximum amount of time that the module will energise the
(Not applicable to the starter motor for during starting attempts once the starter has engaged.
556.)
Crank rest time This is the amount of time the module will wait for between start attempts.
(Not applicable to the This is to allow the starter motor to cool and the starter batteries to
556.) recover.
Manual Crank Limit (Only available if using ‘Start Button must be held down to crank’)
(Not applicable to the This is a protective time limit on the duration that the module is allowed to
556.) manually crank for. It is used to prevent the operator from holding the
„Start‟ button depressed for an unacceptable length of time. Once the
crank limit timer has expired the crank relay will be de-energised.
Smoke limiting This is the amount of time that the smoke limiting output will remain active
(Not applicable to the for once the engine has started. While the smoke limiting output is active
556.) the engine will be held at a reduced speed to minimise smoke emissions
on start-up. (Only if fitted with an appropriate Electronic Fuel Control
module). Once the timer has expired the engine will be allowed to
accelerate up to it‟s normal operating speed.
Smoke limiting off This is the amount of time that the „delayed alarms‟ protection is held
inactive for following termination of the Smoke Limit mode. This is to allow
(Not applicable to the the engine to accelerate to it‟s normal running speed without triggering an
556.) underspeed alarm, etc. The Low Oil Pressure Alarm is not delayed by this
timer.
Safety on delay This timer dictates how long the module will ignore the Low oil pressure,
High Engine Temperature, Underspeed, Undervolts and any other inputs
(Not applicable to the configured as active from safety on. It allows the values such as oil
556.) pressure to rise to their operating values on starting without triggering an
alarm. Once the timer has expired all alarm conditions are monitored
again.
If configured to use „fast loading‟, should all the monitored conditions, such
as oil pressure, come to the expected state prior to the end of the safety
on timer, the timer will be terminated prematurely ensuring maximum
protection as soon as possible.
TIMER DESCRIPTIONS
ETS Solenoid hold time This timer is used if the unit is configured to operate an Energise to stop
engine. It dictates the duration that the ETS output will remain active after
(Not applicable to the the module has detected the engine has come to rest. If the ETS output is
556.) not configured, this timer will still operate, preventing an immediate restart.
Fail to stop delay time Once the module has given a shutdown signal to the engine it expects the
engine to come to rest. It monitors the Oil pressure and speed sensing
(Not applicable to the sources and if they still indicate engine movement when this timer expires
556.) a „Fail to stop‟ alarm signal is generated.
TIMER DESCRIPTIONS
Other/Timers Function
Battery Low Volts Delay This timer dictates how long the module will wait before it will give a low
DC plant voltage alarm in the event of the plant voltage falling below low
voltage trip level. This can be used to prevent nuisance alarms when
using poorly regulated power supplies and battery chargers, and during
engine cranking.
Battery High Volts Delay This timer dictates how long the module will wait before it will give a high
DC plant voltage alarm in the event of the high voltage trip level being
exceeded. This can be used to prevent nuisance alarms when using
poorly regulated power supplies and battery chargers.
LCD Auto-scroll Timer This timer is used to control how long each message or instrument is
displayed on the LCD display when automatically scrolling. If the timer is
set to 1 second for example, then each instrument would be displayed for
1 second before changing to display the next.
LCD Page Timer This timer is used to control how long the module will remain on any page
other than the „Information Page‟. If for example the module was left on
the „Generator Instruments page‟ after this timer has expired it will
automatically return to the „Information Page‟.
Reverse Power Alarm Enhanced, synchronising, and load control Modules Only.
Timer This timer dictates how long the module will wait before it will give a
Reverse Power alarm in the event of the reverse power trip level being
(Not applicable to the exceeded. This can be used to prevent nuisance alarms when, for
556.) example, synchronising with other supplies may normally lead to short
periods of reverse power.
Export power limit This timer dictates how long the module will wait before it will give an
556 Only alarm when the mains is in reverse power (export)
Gen Transient Delay This timer dictates how long a generator anomaly must be present before
the module will respond to it. This can be used to prevent nuisance
tripping when switching loads by delaying the under/over
(Not applicable to the frequency/voltage/speed alarms.
556.)
NOTES
1:- Mains sensing is only available on the 555, 557 and 556 module
LEVELS DESCRIPTION
Level Function
Mains Under voltage These settings are used to configure the mains under voltage alarm:-
Under Voltage Trip -
This is the minimum voltage that the 555, 557 and 556 will consider the
incoming AC mains supply to be within limits. Should the input fall below
this value the module will indicate a mains failure and function accordingly.
Under Voltage Return -
This is the voltage above the under voltage trip that the incoming mains
supply must return to before the 555, 557 and 556 module will consider
that the supply is back with in limits. (i.e. With a UV trip of 184.0V and a
UV return of 207.0V, the mains voltage must return to 207.0V following an
under voltage event to be considered within limits.)
Mains Over voltage These settings are used to configure the mains Over voltage alarm:-
Over Voltage Trip -
This is the maximum voltage that the 555, 557 and 556 will consider the
incoming AC mains supply to be within limits. Should this value be
exceeded the module will indicate a mains failure and function accordingly.
Over Voltage Return -
This is the voltage that the incoming mains supply must return to before
the 555, 557 and 556 module will consider that the supply is back with in
limits. (i.e. With a OV trip of 276.0V and a OV return of 253.0V, the mains
voltage must return to 253.0V following an over voltage event to be
considered within limits.)
Mains Under Frequency These settings are used to configure the mains under frequency alarm:-
Under Frequency Trip -
This is the minimum frequency that the 555, 557 and 556 will consider the
incoming AC mains supply to be within limits. Should the input fall below
this value the module will indicate a mains failure and function
accordingly..
Under Voltage Return -
This is the frequency above the under frequency trip that the incoming
mains supply must return to before the 555, 557 and 556 module will
consider that the supply is back with in limits. (i.e. With a UF trip of 45.0Hz
and a UF return of 48.0Hz, the mains frequency must return to 48.0Hz
following an under frequency event to be considered within limits.)
Mains Over Frequency These settings are used to configure the mains Over frequency alarm:-
Over Frequency Trip -
This is the maximum frequency that the 555, 557 and 556 will consider the
incoming AC mains supply to be within limits. Should this value be
exceeded the module will indicate a mains failure and function accordingly.
Over Voltage Return -
This is the frequency below the over frequency trip that the incoming
mains supply must return to before the 555, 557 and 556 module will
consider that the supply is back with in limits. (i.e. With a OF trip of
55.0Hz and a OF return of 52.0Hz, the mains frequency must return to
52.0Hz following an over frequency event to be considered within limits.)
LEVELS DESCRIPTION
Level Function
CT Primary (L1,2,3) This setting is used to set the primary current rating of the three phase
monitoring CT‟s. The secondary of the CT‟s should be rated at 5 amps.
The CT primaries available are stored by the P810 for windows program in
the form of a table. This table can be modified by the user, to limit or
expand the range of CT ratios available. This could be used to ensure that
standard stock CT‟s are always used regardless of the rating of the mains.
Mains Full Load Rating This setting is used to set the actual full load rating of the mains supply.
This setting is used for power control, whilst running in parallel with the
mains (utility) and soft transfer of load from bus to mains, and mains to
bus.
The range of this setting is 0 – 5,000 kW.
Mains Full kVAr Rating The kVAr rating of the mains supply. If the kVAr rating was 75% of the kW
rating the power factor would be 0.8
Export Power Limit This setting is used to prevent reverse power of the mains. If mains
Alarm reverse power exceeds this setting for the amount of time set by the
Export power limit timer a reverse power trip will occur.
Actions
Warning (Alarm only, No shutdown)
Electrical Trip (Alarm/off-load the bus followed by shutdown after cooling)
CT TABLE
CT TABLE DESCRIPTION
The CT table is used to store a list of different primary rated CT‟s. This list would normally
correspond to commercially available CT ratings, but may be modified by the user to increase or
decrease the range of CT ratings.
This allows the list to be tailored to match a standard range of CT‟s held in stock by the user,
ensuring that the switch gear is built from standard stock regardless of the actual ratings.
LEVELS DESCRIPTION
The voltage must return to below the „Over volts return‟ setting before the
55x module will consider that the supply is back with in limits. (i.e. With a
OV trip of 276.0V and a OV return of 253.0V, the mains voltage must
return to 253.0V following an over voltage event to be considered within
limits.)
Shutdown -
This is the setting at which a Generator Over Volts will give a shutdown
alarm in the event of the generator output rising above the displayed „over
volts trip‟ value. The „over volts trip‟ value can be adjusted to suit user
requirements.
LEVELS DESCRIPTION
The frequency must return to below the „Over frequency return‟ setting
before the 55x module will consider that the supply is back with in limits.
(i.e. With a OF trip of 55.0Hz and a OF return of 52.0Hz, the mains
frequency must return to 52.0Hz following an over frequency event to be
considered within limits.)
Shutdown -
= Generator Over Frequency will NOT give a Shutdown alarm
= Generator Over Frequency WILL give a shutdown alarm in the event
of the generator output rising above the displayed „over frequency trip‟
value. The „over frequency trip‟ value can be adjusted to suit user
requirements.
LEVELS DESCRIPTION
CT TABLE
CT TABLE DESCRIPTION
The CT table is used to store a list of different primary rated CT‟s. This list would normally
correspond to commercially available CT ratings, but may be modified by the user to increase or
decrease the range of CT ratings.
This allows the list to be tailored to match a standard range of CT‟s held in stock by the user,
ensuring that the Generating set is built from standard stock regardless of the actual rating (see
note for generator full load rating)
NOTE:- Adjustments to the Generator Current Transformer settings may cause some
of the Current/Power alarms to flash red. This is to draw attention to the fact that
adjusting one or more of the Generator Current transformer settings has affected the
actual trip level of that particular alarm. Please ensure that the actual trip values are
correct before sending the configuration to the module.
Generator Function
Current/Power
Alarms
Delay Over current This setting is used to configure the generator over current alarm:-
= Generator over current will NOT give an electrical trip alarm.
(Not applicable to the = Generator over current WILL give an electrical trip alarm in the event
556.) of the load current exceeding the displayed „over current trip‟ values. The
„over current trip‟ values can be adjusted to suit user requirements as
detailed below.
The following configurable settings are provided:
Delayed over current setting (IT/I) (range 0.80 to 1.20 in steps of 0.01) (default 1.00)
Time multiplier (t) (range 1 to 36 in steps of 1) (default 36)
Where: IT is the delayed over-current trip point
I is the Generator full load current rating
This curve matches the thermal damage curve of a typical brush-less alternator but it can be modified if
necessary by changing the configurable settings.
Actions
Warning (Alarm only, No shutdown)
Shutdown (Alarm and shutdown)
Electrical Trip (Alarm/off-load generator followed by shutdown after
cooling)
Short Circuit This settings is used to configure the generator short circuit alarm:-
= Generator short circuit will NOT give an electrical trip alarm.
(Not applicable to the = Generator short circuit WILL give an electrical trip alarm in the event
556.) of the load current exceeding the displayed „short circuit trip‟ values. The
„short circuit trip‟ values can be adjusted to suit user requirements as
detailed below.
The following configurable settings are provided:
Short circuit current setting (IT/I) (range 1.0 to 3.0 in steps of 0.1) (default 3.0)
Short circuit tripping curve (1 to 8200 in steps of 1) (default 33)
Where: IT is the short circuit current trip point
I is the Generator full load current rating
Actions
Warning (Alarm only, No shutdown)
Shutdown (Alarm and shutdown)
Electrical Trip (Alarm/off-load generator followed by shutdown after
cooling)
Reverse Power This setting is used to configure the generator reverse power alarm:-
= Generator reverse power will NOT give an electrical trip alarm.
(Not applicable to the = Generator reverse power WILL give an electrical trip alarm in the
556.) event of the reverse power exceeding the displayed „reverse power trip‟
values. The „reverse power trip‟ values can be adjusted to suit user
requirements.
Actions
Warning (Alarm only, No shutdown)
Shutdown (Alarm and shutdown)
Electrical Trip (Alarm/off-load generator followed by shutdown after
cooling)
Generator Function
Current/Power
Alarms
Earth Fault This setting is used to configure the generator earth fault alarm:-
= Generator Earth Fault will NOT give an electrical trip alarm.
(Not applicable to the = Generator Earth Fault WILL give an electrical trip alarm in the event of
556.) the load current exceeding the displayed „earth fault trip‟ values. The
„earth fault trip‟ values can be adjusted to suit user requirements.
The following configurable settings are provided:
Earth fault current setting (IT/I) (range 0.01 to 1.00 in steps of 0.01) (default 0.10)
Earth fault tripping curve (1 to 8200 in steps of 1) (default 1000)
Where: IT is the earth fault current trip point
I is the Generator full load current rating
The earth fault current setting assumes that the CT ratio for earth current is the same as that for the main line
current and for the normal arrangement of one neutral CT and a CT for each line this will be the case. But if a
dedicated CT is used for earth current detection then this may have a different ratio to those used for the main
lines. This is a means of increasing the sensitivity of the earth fault protection since the earth fault current setting
will be multiplied by the ratio of the two CT primary currents.
As an example let us assume that:
(1) The earth CT has a ratio of 100/5. This would have to be a dedicated CT either on the cable that
connects the neutral conductor to the station earth (unrestricted protection) or it could be a core-
balance CT fitted over the neutral and line conductors (restricted protection)
(2) The main line CT(s) have a ratio of 1000/5.
(3) The above earth fault current setting is 0.01 pu
(4) The generator full load rating is 900 amps
Then if all the CT ratios had been the same the earth fault current trip-point would have been 900 x 0.01 = 9.0
amps. But in the case of this example it would be 900 x 0.01 x 100 / 1000 = 0.9 amps.
Actions
Warning (Alarm only, No shutdown)
Shutdown (Alarm and shutdown)
Electrical Trip (Alarm/off-load generator followed by shutdown after
cooling)
(Not applicable to the 556.) NOTE:- It will be necessary to configure two of the
module relays to provide the required „Voltage raise‟ and
„Voltage Lower‟ signals.
The 55x controller must be correctly configured before load sharing can take place. This
configuration is performed using the DSE P810 for Windows software, in conjunction
with the P810 interface.
MULTI-SET SETTINGS
(Only available on load sharing versions of the 550 controller and the 556, where multiple
generators controlled by 550 modules are providing either prime power or AMF when incorporating
the 556).
The multi-set settings page is used to configure the automatic starting and stopping of generators
based upon load level demands.
Running on load demand Description
This system is enabled by activating digital inputs on the
controllers that have been configured to Remote Start on
load demand. Every controller in the multiset system must
have a digital input configured and connected in this way.
This enables generating set(s) to be taken out of service for
maintenance, while still allowing the remainder of the
system to operate.
Upon activation of the Remote Start on load demand input,
all the sets in the system will start up. The first one to
become available will close onto the dead bus,
communicating with the other sets to instruct them to
synchronise onto the now live bus, before closing the load
switch in parallel with it.
If too much generating set capacity is available to supply
the current load, the sets that are not required will begin
their stop delay timers, after which they will drop off the bus
and stop.
Too few modules action : the action that will be taken if the
number of modules communication on the MSC link is less
than the “minimum modules on Multiset comms link” setting.
None : Too few modules on the MSC link will not generate an
alarm condition.
Warning: An alarm condition will be given, but the sets will still
be able to run and take load.
Electrical trip: An alarm condition will be given, the set will be
removed from the bus and shutdown after the cooling timer.
Minimum modules on Multiset comms link : The minimum
number of modules allowed on the MSC link before an alarm
is generated. The type of alarm can be configured using “Too
few modules action” detailed above.
Multiset comms alarms disabled action : The action that will
be taken if the Multiset comms alarms are disabled via
configurable input or external communications control.
None : Disabling the MSC link alarms will not generate an
alarm condition.
Indication : Disabling the MSC link alarms will generate an
„indication‟, but no alarm condition is generated.
Warning: An alarm condition will be given to remind the
user/operator that the MSC alarms have been disabled.
Load level for more sets to run: The load level at which the
550 controller decides that additional generating set capacity is
required to supply power to the load.
Once this load level is exceeded, the next highest priority set in
the sequence (determined using the Genset Run Priority) will
begin it‟s start delay timer. Once this has expired, the set will
run up, synchronise and take load. Should the set fail to
(Not applicable to the 556.) become available, it will communicate this using the MultiSet
Communications Link which will signal the next generating set
in the sequence to take its place.
The starting sequence will be terminated should the load level
drop below the Load level for more sets to run while the start
delay timer is in progress. This allows for short term increases
in load.
LOAD CONTROL
„Soft transfers‟ of this type have many benefits, the most obvious of which are:
When the generator is removed from the bus, other sets in the system are not suddenly loaded
with the load share that was being supplied by the generator being removed. Instead, the load
is slowly ramped, allowing time for the remaining sets to take up their share of the load.
Opening of the load switch occurs at a much lower load level, helping to reduce arcing of the
contacts.
Options :
Disabled: No load sharing will take place.
Load Share (550 only) : The load will be shared between all
the sets in the system.
(Not applicable to the 556.) KW fixed export : The generator will export a fixed amount of
active (kW) power.
Generator full load rating: The full load rating (in kW) of the
set.
Options :
Disabled: No reactive power (VAr/pf) sharing will take place.
VAr Share: Reactive power (VAr) will be shared between all
the sets in the system.
(Not applicable to the 556.) VAr fixed export: The generator will produce a fixed amount
of reactive power (VAr) for use when in parallel with the mains
supply .
Generator full VAr rating: The full load rating (in VAr) of the
set. This setting is used in conjunction with the full load rating
(VAr) of the other sets in the system to determine the load
share that this set will take (550 only).
NOTE:- The set will initially take load at the level set
by load ramp minimum and will then increase it‟s load
share at this rate until either
All the sets have an equal share of the load (550
module only)
or
The generated power is equal to the setting for „load
parallel power‟
System Function
Minimum number of The action that will be taken, if the minimum number of sets available on
sets the common bus, prior to the bus closing is not reached before the delay
time has expired.
Only applicable to the None: No action will be taken.
556. Warning: An alarm condition will be given, but the sets will still be able to
run and take load.
Electrical trip: An alarm condition will be given, the sets will be removed
from the bus and shutdown after the cooling timer.
System Function
Insufficient capacity The action that will be taken, if the generating system is not large enough
to ramp the mains to the desired level. The action is delayed by the delay
Only applicable to the time.
556. None: No action will be taken.
Warning: An alarm condition will be given, but the sets will remain on
load.
Plant Battery Undervolts Plant Battery Undervolts -
= Low Plant voltage trip will NOT give a warning alarm
Only applicable to the = Low Plant voltage WILL give a warning alarm in the event of the
556. generator plant battery voltage falling below the displayed „low voltage
alarm’ value. The „low voltage alarm’ value can be adjusted to suit user
requirements.
Should the input fall below this value the module will initiate the low voltage
delay timer, if the voltage remains low and the timer expires, a low voltage
warning will be given.
The voltage must return to above the „low voltage return‟ setting before the
55x module will consider that it is back with in limits.
(i.e. With a LV trip of 10.0V and a LV return of 12.0V, the plant voltage
must return to 12.0V following a low voltage event to be considered within
limits.)
Plant Battery Overvolts Plant Battery Overvolts -
= High Plant voltage trip will NOT give a warning alarm
Only applicable to the = High Plant voltage WILL give a warning alarm in the event of the
556. generator plant battery voltage rising above the displayed „High voltage
alarm’ value. The „high voltage alarm’ value can be adjusted to suit user
requirements.
Should the input rise above this value the module will initiate the high
voltage delay timer, if the voltage remains high and the timer expires, a
high voltage warning will be given.
The voltage must return to below the „high voltage return‟ setting before
the 55x module will consider that it is back with in limits.
(i.e. With a HV trip of 27.0V and a HV return of 25.0V, the plant voltage
must return to 25.0V following a high voltage event to be considered within
limits.)
This menu allows the engine configurable trip values to be edited to the users required levels. The
following menu is displayed:
NOTES
1:- The 55x module has five possible sources of crank disconnect, namely magnetic
pickup, alternator frequency, or voltage, engine oil pressure or engine charge alternator
voltage. Any of these sources may be used individually, but it is also possible to use
multiple sources or even all five. If this is the case the source which reaches it‟s crank
disconnect level first will cause the starter motor to disengage regardless of t he state of
the remaining monitored sources. This feature allows for a much faster crank
disconnect response leading to less wear on the engine and starter components, and
provides added safety in case one source is lost, by a broken fan belt or tripped f uses for
example.
LEVELS DESCRIPTION
LEVELS DESCRIPTION
The speed must return to above the „Underspeed return‟ setting before the
55x module will consider it back within limits.
The speed must return to below the „Over speed return‟ setting before the
55x module will consider that it is back with in limits.
Shutdown -
This is the setting at which a Generator Over speed will give a shutdown
alarm in the event of the generator speed rising above the displayed „over
speed trip‟ value. The „over speed trip‟ value can be adjusted to suit user
requirements.
Overshoot Over-speed Overshoot during Overshoot timer-
This value is used to prevent nuisance tripping on generators where a slow
(Not applicable to the response governor allows the engine to overspeed slightly during start-up.
556.) This setting allows the normal overspeed shutdown level to be exceeded
by a percentage (up to a maximum of 10%) for the duration of the
overspeed overshoot timer. Should the engine speed exceed this
temporarily elevated level it will be shutdown. Once the overspeed
overshoot timer has expired the overspeed shutdown value is restored to
the normal level.
LEVELS DESCRIPTION
The voltage must return to above the „low voltage return‟ setting before the
55x module will consider that it is back with in limits.
(i.e. With a LV trip of 10.0V and a LV return of 12.0V, the plant voltage
must return to 12.0V following a low voltage event to be considered within
limits.)
The voltage must return to below the „high voltage return‟ setting before
the 55x module will consider that it is back with in limits.
(i.e. With a HV trip of 27.0V and a HV return of 25.0V, the plant voltage
must return to 25.0V following a high voltage event to be considered within
limits.)
Charge Alternator Charge Alternator Failure -
Failure = Charge alternator low voltage will NOT give a warning alarm
= Charge alternator low voltage WILL give a warning alarm in the event
(Not applicable to the of the charge alternator voltage falling below the displayed „Charge fail
556.) alarm’ value. The „Charge Fail alarm’ value can be adjusted to suit user
requirements.
As the input is a true analogue value total failure of the charge alternator is
not the only failure that the module will provide protection for. Faults which
cause the output voltage to fall, such as worn brushes etc., will cause the
alarm to operate.
The voltage must return to above the „Charge Fail return‟ setting before
the 55x module will consider that it is back with in limits.
NOTE:- If this input is not used ensure that this setting is set to
to prevent the possibility of a spurious Charge Fail Alarm
occurring.
SETTINGS DESCRIPTION
Maintenance Function
Alarm Settings
Enable Maintenance Enable Maintenance Alarm -
Alarm = The module will not monitor the engine maintenance intervals.
= The module will monitor the engine maintenance intervals and issue
an alarm once maintenance become due.
(Not applicable to the
556.)
Force engine shutdown Force engine shutdown when maintenance is due -
when maintenance is = In the event of a Maintenance alarm being activated, the module will
due only issue a warning alarm. The engine will be allowed to continue running.
The alarm will remain present until the maintenance reset is operated..
= In the event of the Maintenance alarm being activated, the module will
issue an alarm and will SHUTDOWN the engine. Further operation of the
engine will not be possible until the maintenance reset is operated.
(Not applicable to the
556.) CAUTION!:- This option will prevent any operation of the
engine once triggered, it is recommended that the function is used
in conjunction with the external maintenance reset to prevent loss
of gen-set availability.
Maintenance Function
Alarm Settings
Running Hours Interval Running Hours Interval-
This setting is used to select the amount of running hours between
maintenance alarms. This should be in accordance with the engine
manufacturer‟s recommendations. Once the number of hours running
before maintenance has reached zero, a maintenance due alarm will be
(Not applicable to the issued. This will remain present until a maintenance reset command is
556.) sent to the module (either from the P810 software or from a digital input),
the running hours interval counter will then be reset to the value selected.
Maintenance Date Maintenance Date Interval -
Interval = The module will only monitor engine running hours between
maintenance intervals. This is the normal mode of operation for engines
which will accumulated a large number of running hour in the maintenance
period. E.g. Prime Power applications.
= The module will monitor both the engine running hour and calendar
(Not applicable to the months between maintenance intervals. Whichever expires first will
556.) trigger a maintenance alarm. This mode is used for engines which may
not accumulate many running hours in the maintenance period. E.g
Standby power applications
When enabled the module will monitor the passage of calendar months in
addition to the engine running hours. Whichever setting expires first will
trigger a maintenance due alarm, ensuring that the engine still receives
regular attention.
CAUTION!:- The Maintenance alarm can only be reset either via the P810 software
„Re-Calibrate‟ tab or from a digital input configured as „Maintenance Reset‟. Ensure that
suitable arrangements are made to ensure that at least one of these methods is made
available to reset the maintenance alarm on site.
When the „Maintenance Reset‟ is performed the maintenance interval values will be re -
loaded into the module and will start to countdown again.
E.g. If the maintenance interval is set to 250 hours when the reset is issued then 250
hours running will be re-loaded into the maintenance interval timer.
NOTES
1:- The 55x Module will only respond to scheduled run events if in the „auto‟ mode. The
engine will only be started if there are no shutdown alarms present.
2:- Should the module not be able to run when a scheduled event is called the event will
not be cancelled but will remain active for the duration configured. Therefore should the
module be restored to a condition where it can run, it will act in accordance with the
scheduled run settings.
3:- If the „Auto restore inhibit‟ input is active and an on-load scheduled run is requested
the generator will start and take load. However at the end of the scheduled run the
generator will remain running on-load until the „Auto restore inhibit‟ input is de-activated.
4:- It is recommended that an LED is configured to indicate „Calling for Scheduled Run‟ to
avoid operator confusion as to why the gen-set my be running for no apparent reason.
SETTINGS DESCRIPTION
CAUTION!:- Should the generator take load during a scheduled run, either because
the run was configured to be „on load‟, or a remote start/mains failure occurred during
the run; if the „Auto restore inhibit‟ input is active the gen-set will not stop at the end of
the scheduled run, until the „Auto restore inhibit‟ input becomes in-active.
To add a new scheduled run event simply; Select the day of the Week the run is required (i.e
Tuesday), select the time of day the run is to start (i.e 13:00) and select the duration of the run (i.e.
1 hour) and Click „Add‟.
NOTE:- Should a conflict arise between existing scheduled runs and the additional
one, the software will reject the new run and highlight the conflicting event in RED.
Please check the conflict and correct and re-try.
This menu is used to configure which languages are available in the module. Each
module is capable of displaying one of eight different stored languages. Four languages
are factory set in the module; English, French, German and Spanish. A further four
languages can be selected during configuration. Language selection can then be made from the
front panel keys of the module - refer to the appropriate 55x manual for further details.
NOTES
1:- It is only possible to send languages to the module which exist on the PC that is
sending the configuration. It is not possible to read the language files from a module,
only the information regarding which languages are actually set. Therefore care must be
exercised when „cloning‟ modules which have been configured on different PC‟s. Always
ensure that the PC has the correct languages files available.
2:- When configuring a module and selecting extra languages, the configuration Write
time will be increased for each additional language requested by the module. The
module will request the language files for the new configuration first and then will
request the new configuration .
3:- When configuring an module which already has all four user configurable languages
set, if a different language is selected from those already in the module, all language files
will be removed and the new selection written to the module.
4:- It is not actually possible to remove any languages once written to the module.
However languages can be over-written with new ones.
5:- If the language required is not on the list please contact Deep Sea Electronics PLC
regarding possible translation and software update to include it.
4 SCADA MENU
4.1 DIAGNOSTICS
A particularly useful feature of the module is its ability to provide real-time diagnostic information to
the PC. This can be used to give on-screen details of the operation of the module and generating
set performance.
The first display is Mimic Display, This provides at-a-glance monitoring of the system, all non-
essential information is hidden. Clear graphical displays allow easy control and performance
monitoring. Should an alarm occur this is clearly displayed by an „Alarm‟ legend. This page
provides the normal operator control interface for remote operation (if enabled)
The second display is the Alarm Display this allows the user to see details on any alarm conditions
which are currently active. The module internal firmware revision details are also given; this is to aid
DEEP SEA ELECTRONICS technical staff in the event of a query.
The third display is the Status Display this allows the user to see at a glance the values of all
measured inputs and the status of any of the digital inputs. State of the output relays and LED‟s
are also displayed. As the displays are real-time the opening and closing of the inputs and outputs
can be viewed this can assist in system performance monitoring and fault finding.
The Forth display is the Instruments Display this allows the user to see at a glance most of the
measured values to allow monitoring of the generator performance.
The fifth display is the More Instruments Display this allows the user to see further measured
values.
The final tab allows the operator to interrogate the Event log stored in the module,
allowing recent shutdown events to be viewed.
NOTE:- The display screen are updated by information sent from the module, if the
communications link to the module is lost the information displayed could be incorrect
and is therefore „greyed out‟. A small icon in the bottom right of each display indicates
that the link to the module is healthy.
Comms:- A small icon in the bottom right of the screen indicates that the link to the module is
healthy.
Security:- A small icon indicates the security state of the link to the module.
No valid PIN has been entered for the currently connected module.
Read only access – Operator can view module parameters but
can not change operating mode or reset alarms,etc.
Valid PIN entered, full read/write access – Operator can view
module parameters and control the module, resetting alarms etc.
Instrumentation:- A small icon at the bottom of the screen indicates the instrumentation level of
the module connected.
Module Type:- A small icon in the bottom left of the screen indicates the type of module and any
options fitted.
Once connected, the software will ask the module to send details of its internal configuration. This
is then used by the SCADA display to provide more detailed information about the operation of the
module and the remote site. While this information is being received the following screen will be
displayed:-
NOTE:- The additional information is used to identify the function of inputs, outputs
and LED‟s etc. If this extra detail is not required then the cancel button can be pressed
to stop the transfer. This facility can be disabled in „Setup this software‟ if it is not
required.
CAUTION!:- Ensure that you make a note of the PIN number when you allocate it to a
module. With out the correct PIN number it will be impossible to gain configuration
access to the module. If the PIN number is lost the module will need to be returned to
DSE to be re-initialised – All module setting will however be lost in this operation.
If the password is set to something other than the default “0000” P810 will display the following
screen:-
Using the selectors the correct PIN should be selected and then the OK button selected. The PIN
entered will be compared against the module PIN and if a match is found access will be granted.
This access will remain active for as long as the connection is maintained by the P810 software. If
the user selects to close the communication link the module will be instructed to secure itself again,
and if the link is re-established the password will be requested again before control of the module is
possible. Should the link to the PC be broken due to a comms error the module will wait a short
period of time and if the comms link is not re-established it will secure itself again and request a
correct PIN.
When the link is re-established the P810 software will try to use the last PIN number entered during
that session and if this fails it will try the default PIN number, if this also fails it will then prompt the
user to enter the module PIN.
The module will allow three attempts to enter the PIN number – If this is exceeded it will stop
responding to attempts for a period of 60 seconds. The following message will be displayed:-
After this period the module will start checking the PIN numbers again an further two attempts will
be granted. If these are both incorrect the module will again stop responding for double the
previous period. This will continue to a maximum wait period between retries of 64 minutes. This
is to prevent a more determined attack on the security of the module via a remote link.
CAUTION!:- Ensure that you make a note of the PIN number when you allocate it to a
module. With out the correct PIN number it will be impossible to gain configuration
access to the module. If the PIN number is lost the module will need to be returned to
DSE to be re-initialised – All module setting will however be lost in this operation.
CAUTION!:- Setting a PIN number in the module will stop all access to the module via
the P810 software in addition to the RS232 and RS485 ports. Therefore it is important to
ensure that any field service personnel who are likely to need access to the module
configuration as advised of the PIN number prior to visiting site. Without the correct PIN
number the module will not allow changes to its configuration.
NOTE:- Using the Mouse to „click‟ on the buttons will allow the module to be operated
from the PC screen. This function can be used to provide remote control of the 55x
module via the 810 interface. The 810 interface cable can be extended up to 100 meters
(from the module to the 810).
The remote control facility can be disabled from the „Set-up‟ tab if remote monitoring
only is required.
Modules also have load transfer pushbutton control available on the mimic display.
This facility can be disabled from the „Set-up‟ tab if remote monitoring only is required.
CAUTION!:- If the module has a PIN security number set, then it will not be possible
to send remote control commands to the module, unless the correct Security Access is
given.
PRINT LOG
This button will generate a print-out of the displayed event log.
NOTE:- The event log display is only updated when the „Read Event Log‟ button is
operated. Any subsequent events stored in the module will not appear on the PC unless
an update is requested. To prevent possible user confusion the event log display is
cleared whenever a different Tab in P810 is selected, or if the link to the module is lo st.
It is not possible to „Clear‟ the module event log.
The Event log can only be viewed on V2.00 or later version modules.
Normally COM2 is the spare port with COM1 being used by a mouse. This
can vary from PC to PC, so it is recommended that you check your
configuration by referring to the documentation supplied with your PC or by
contacting your PC support personnel. Should you still experience
problems contact DEEP SEA ELECTRONICS for assistance.
When using the USB version of P810 interface, the USB driver will create
a „virtual COM port‟ (i.e. COM6). This must be selected in the set up tab
for the USB P810 to operate. The „virtual COM port‟ may only be visible
when the USB P810 is connected to the PC.
Local (PC) display These options are used to set up certain display features affecting the way
settings P810 displays information to the user.
Display 3ph 4wire voltage settings as ph-ph-
= On Edit Generator voltage tab the voltage settings are all referred to
as Phase to Neutral values.
= On the Edit Generator voltage tab the voltage settings are all referred
to as Phase to Phase.
Display Oil pressure in KPa-
= On the SCADA instrument page the Oil pressure will be displayed as
PSI and BAR.
= On the SCADA instrument page the Oil pressure will be displayed as
Kpa.
Connection Options Use modules setting for SCADA display -
= Basic generic SCADA display is used.
= When connection is made the module will transmit its current settings
for use by the SCADA display. The SCADA display can then correctly
identify the functions of user configured inputs and outputs, etc.
The operator level password can only be changed if the Engineering level password is known; this
is to prevent unauthorised password changes being made.
NOTE:- The passwords are only to give access to the software for configuring the
module, not for access to the module itself.
Type in the NEW password, this password is limited to 20 characters maximum, any combination of
numbers and letters can be used. The software IS case sensitive.
The passwords will be verified and if they do not match the screen will display:
The technician level password can only be changed if the Engineering level password is known, this
is to prevent unauthorised password changes being made.
NOTE:- The passwords are only to give access to the software for configuring the
module, not for access to the module itself.
Type in the NEW password, this password is limited to 20 characters maximum, any combination of
numbers and letters can be used. The software IS case sensitive.
The passwords will be verified and if they do not match the screen will display:
The Maintenance level password can only be changed if the Engineering level password is known,
this is to prevent unauthorised password changes being made.
NOTE:- The passwords are only to give access to the software for configuring the
module, not for access to the module itself.
Type in the NEW password, this password is limited to 20 characters maximum, any combination of
numbers and letters can be used. The software IS case sensitive.
The passwords will be verified and if they do not match the screen will display:
If the software is accessed using the engineering password, all values are available for modification
including the complete module configuration and sender calibration, internal clock and hours run
counter.
NOTE:- The passwords are only to give access to the software for configuring the
module, not for access to the module itself. The default passwords are blank and when a
password is requested press the button.
When the option is selected the following will be displayed:
Type in the NEW password, this password is limited to 20 characters maximum, any combination of
numbers and letters can be used. The software IS case sensitive.
The passwords will be verified and if they do not match the screen will display:
NOTE:- A fifth password level exists for use where the module is being used to
provide a remote monitoring display on a PC. If the password „MIMIC‟ is entered on
start-up the software will enter the diagnostic Mimic display. No changes to any of the
module settings or software configuration can be made without the correct operator or
engineering password being entered. Refer to the „Diagnostics‟ section of this manual.
6 RE-CALIBRATION MENU
6.1 RE-CALIBRATE CONTROLLER
This menu is used for three purposes, the first is configure the module to read the Oil pressure and
coolant temperature senders correctly. The second function to allow the engineer to set the
module‟s internal clock, hours run counter, KW Hour meter, etc, etc. The Third is to allow the
operator to perform a software maintenance reset in the event of the module maintenance alarm
being active.
NOTE:- The re-calibration display screens are updated by information sent from the
module, if the link to the module is lost the information displayed could be incorrect and
is therefore „greyed out‟. A small icon in the bottom right of each diagnostic display
indicates that the link to the module is healthy.
This option will allow the engineer to re-calibrate the modules‟ internal clock
This option will allow the engineer to re-calibrate the modules‟ hours run and number of starts
counter.
ENGINE RUNTIME
(Not applicable to the 556.)
It is possible to set the module engine hours run counter to the required value, for instance if the
control system is to be used with an existing generating set, the hours run reading can be
transferred to the new control system, thereby maintaining the history of the generating set.
Alternatively, the hours run counter on a new generator could be reset to zero following testing.
To set the hours run simply set the accumulated time in the tool provided and press the „SET‟
button. The hours run value entered will be sent to the module. The „Current module reading‟
display will change to reflect this.
NUMBER OF STARTS
(Not applicable to the 556.)
It is possible to set the module number of starts counter to the required value, for instance if the
control system is to be used with an existing generating set, the starts reading can be transferred to
the new control system, thereby maintaining the history of the generating set. Alternatively, the
starts counter on a new generator could be reset to zero following testing.
6.1.3 TRANSDUCERS
This option will allow the engineer to re-calibrate the module transducers such that it will read
correctly the oil pressure and coolant temperature values. This action may be necessary as the
senders used for sensing the pressure and temperature are electro/mechanical devices and as
such suffer from a degree of inaccuracy. The ability to re-calibrate the senders is akin to turning
the adjustment screw on a conventional engine gauge.
CAUTION!:- To re-calibrate the senders a known good, accurate sensing device must be
used and the module reading adjusted to match.
OIL PRESSURE
(Not applicable to the 556.)
The reading shown below the adjustable slider is the current module reading. Read the actual Oil
pressure off the accurate sensing device and then by moving the slider up or down adjust the value
displayed to match that of the accurate sensing device. Once matched release the slider, the new
value will be stored in the module.
COOLANT TEMPERATURE
(Not applicable to the 556.)
The reading shown below the adjustable slider is the current module reading. Read the actual
coolant temperature off the accurate sensing device and then by moving the slider up or down
adjust the value displayed to match that of the accurate sensing device. Once matched release the
slider, the new value will be stored in the module.
If at any time you wish to return the settings to standard and remove the re-calibration applied to the
senders simply press the „Restore default calibration‟ button. This could be used for example if the
sender calibration appeared inaccurate and was modified, then a panel wiring fault was traced as
being the cause of the inaccuracy.
6.1.4 ACCUMULATED
This option will allow the engineer to calibrate the modules‟ accumulated memory
Pos KWh
It is possible to set the module‟s KWh counter to the required value, for instance if the control
system is to be used with an existing generating set, the hours run reading can be transferred to the
new control system, thereby maintaining the history of the generating set. Alternatively, the KWh
counter on a generator could be reset to zero following return from rental.
To set the KWh simply set the accumulated value in the tool provided and press the „SET‟ button.
The hours run value entered will be sent to the module. The „Current module reading‟ display will
change to reflect this.
Neg KWh
It is possible to set the module‟s KWh counter to the required value, for instance if the control
system is to be used with an existing generating set, the hours run reading can be transferred to the
new control system, thereby maintaining the history of the generating set. Alternatively, the KWh
counter on a generator could be reset to zero following return from rental.
To set the KWh simply set the accumulated value in the tool provided and press the „SET‟ button.
The hours run value entered will be sent to the module. The „Current module reading‟ display will
change to reflect this.
KVAh
It is possible to set the module‟s KVAh counter to the required value, for instance if the control
system is to be used with an existing generating set, the hours run reading can be transferred to the
new control system, thereby maintaining the history of the generating set. Alternatively, the KVAh
counter on a generator could be reset to zero following return from rental.
To set the KVAh simply set the accumulated value in the tool provided and press the „SET‟ button.
The hours run value entered will be sent to the module. The „Current module reading‟ display will
change to reflect this.
KVArh
It is possible to set the module KVArh counter to the required value, for instance if the control
system is to be used with and existing generating set, the hours run reading can be transferred to
the new control system, thereby maintaining the history of the generating set. Alternatively, the
KVArh counter on a generator could be reset to zero following return from rental.
To set the KVArh simply set the accumulated value in the tool provided and press the „SET‟ button.
The hours run value entered will be sent to the module. The „Current module reading‟ display will
change to reflect this.
Clear All
If at any time you wish to zero all the settings simply press the „Clear All‟ button.
RESET
It is possible to reset the maintenance due alarm back to the pre-configured interval.
When operated the „Reset‟ button will restore the Running Hours until Maintenance due
and the date of the next maintenance to the intervals stored in the module configuration.
If the maintenance alarm is active it can only be reset after the „Reset‟ has been sent.
NOTE:- The maintenance reset function does not allow the operator to change the
maintenance interval, ONLY reinstate the allowed maintenance intervals from values
stored in the module configuration.
The method of setting up the 55x synchroniser depends upon the interface method between the
55x controller and the AVR/Governor.
If your interface method uses the internal 55x raise/lower relays or the P122 digital resistance
module, then you will use the „pulse‟ scheme.
If your interface method uses the P120 / P121 analogue interface module, then you will use the
„analogue‟ scheme.
Synchronising tab if the P120 and P121 will be used for governor and AVR control
Synchronising tab if internal relays will be used for governor and AVR control
NOTE: - Start with gain and stability at the minimum settings. Increase gain until the
engine speed becomes unstable, then half the gain setting.
Now increase the stability setting until the engine speed again becomes unstable, then
lower a little.
You may need to perform the synchronising process a number of times to see the effect
of your changes. You can also „knock‟ the governor actuator, or change the „slip
frequency‟ setting to disturb the engine speed and force the controller into making
further changes.
NOTE: - Start with gain and stability at the minimum settings. Increase gain until the
generator voltage becomes unstable, then half the gain setting.
Now increase the stability setting until the voltage again becomes unstable, then lower a
little.
You may need to perform the voltage-matching process a number of times to see the
effect of your changes.
NOTE: - Start with gain and stability at the minimum settings. Increase gain until the
engine speed becomes unstable, then half the gain setting.
Now increase the stability setting until the engine speed again becomes unstable, then
lower a little.
You may need to change load levels a number of times to see the effect of your changes.
You can change the „load parallel power‟ setting (555 and 557 only) to disturb the load -
share process and „force‟ the controller into making further changes.
Load parallel power: The amount of power that the set will
produce when used in „Load level control‟, whilst running in
parallel with the mains (utility).
Bus Control: (556 Only). The amount of power that the sets
will produce when in parallel with the mains. This figure is a
percentage of each generators capacity, that is connected to
the bus. Therefore the actual kW will vary depending on how
many sets are on the bus. The load demand start up and shut
down scheme is disabled whilst running in parallel with the
mains (utility). E.g. on a multi set system where each
generator is rated at 500 k/W and the bus power was set to
50%, each set running would produce 250 kW of power.
E.g. If the mains load level was set to 250 kW the generators
would supply the difference between this figure and total
connected load. If the load was lower than this figure then the
generators would stay in parallel but supplying zero kW
KVAr control: The amount of reactive power that the set will
produce when used in „load level control‟ mode, when Reactive
Load Control Mode is set to Load Level Control
Pf control: The power factor that the set will maintain when
used in „load level control‟ mode, when Reactive Load Control
Mode is set to Load Level Control)
7 APPENDIX
7.1 OUTPUT EXPANSION
There are several methods of output expansion available for the 55x range of modules:-
Refer to technical data sheet on the 157 relay module for further details.
Refer to technical data sheet on the 548 LED module for further details.
It is possible to use a mix of 157 and 548 modules to give both relay and LED expansion if required.