Principle of Operation - Generator
Principle of Operation - Generator
A DC supply is applied to the rotor (field) winding creating a constant magnetic field.
field.
The rotor is rotated by a prime-
prime-mover at a constant speed.
speed. The rotor magnetic field
rotor. The rotating magnetic field induces a three-
therefore rotates at the speed of the rotor. three-
phase EMF at the stator (armature) windings.
windings. The frequency of the induced emf
corresponds to the rotor speed, and is therefore, constant.
constant.
f = frequency of induced emf
120 f
ns = in RPM ns = rotor speed (held constant)
p
p = is the number of poles
Ea is directly proportional to the flux and the speed, but the flux depends on the
rotor (field) current If . The relation between If and flux φ is shown by a plot
called the magnetization curve or the saturation characteristic or the open-circuit
characteristic of the machine.
Magnetization Curve
Ea ω=ω (constant)
φ sync
If
If
open-circuit characteristic (OCC)
motor
Ia jXS Ra The synchronous reactance XS is the sum of the
+ armature reaction reactance and the leakage
generator reactance.
+
Ea Vt The synchronous impedance, Zs = Ra + jXs
Ia jXS
The equivalent circuit parameters can be +
determined from following tests:
tests: +
Ea Vt
Ra : DC Test
Xs : Open-circuit and Short-circuit Tests
Vt = Ea – jXs .Ia
DC Test
A DC voltage source is connected
between two stator terminals.
The DC voltage is adjusted to
provide approximately rated stator
current.
The voltmeter and ammeter readings
are recorded.
VDC
RDC =
I DC
RDC
If the stator is Y-connected, the per phase stator resistance is R1 =
2
It should be noted that in practice, the ac resistance will be slightly higher than the dc
resistance (as a result of the skin effect at higher frequencies).
Short-circuit Test
The field current is set to zero and the stator terminals are shorted. Record the stator
current ISC as the field If current is increased. Such a plot is called the short-circuit
characteristic (SCC).
If
ISC + A
SCC ISC
VDC A
ISC2
ISC1
,
rotor
If1 If2 If
stator
The synchronous impedance Zs can be calculated by combining the OCC and SCC:
Ea
OCC ISC
Vrated Vrated
SCC Zs =
I sc ( v _ rated )
ISC(V_rated)
X s = Z s2 − Ra2
If(V_rated) If
Short-circuit Ratio
δ: power (torque)
angle
θ: power factor
angle Lagging p.f. load
Regulation Curves
Compounding Curves
Voltage Regulation
Voltage regulation is related to the change in the generator’s terminal voltage
as the load varies. Voltage regulation (VR) at a specified p.f. is calculated by:
Example:
A 3-phase, Y-connected, cylindrical-rotor synchronous generator rated at 10 kVA,
230 V has a synchronous reactance of 1.2 ohms per phase. Calculate the voltage
regulation at 0.8 leading power factor. Also, determine the power (torque) angle.