Project:: Chilled Water Pump Head Calculation

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

CHILLED WATER PUMP HEAD CALCULATION

Project: DJ-275 HARBOUR MASTERS BUILDING

Units Pipe Size No Of Total Pipe Total Pipe Length Friction Loss Friction Head
Ref. No. Fittings & Valves
(L/s) MM Fittings Length & Fittings M/M Total Losses (Kpa.)

12.3 100Ø Straight Pipes 1.00 2.00 2.00


Butterfly Valve 1.00 1.37 1.37
A toB Tee Branch 1.00 6.40 6.40
Gate Valve 1.00 1.37 1.37
Flexible Connector 1.00 1.37 1.37
12.52 0.0220 2.791

24.6 150Ø Straight Pipes 1.00 14.50 14.50


Tee Branch 2.00 9.15 18.29
B to C
Tee Straight 2.00 3.05 6.10
Elbow 90° 3.00 4.88 14.63
53.52 0.0105 5.695

12.3 100Ø Straight Pipes 1.00 5.20 5.20


Tee Straight 1.00 2.04 2.04
C to D
Butterfly Valve 1.00 1.37 1.37
Strainer 1.00 18.29 18.29
26.91 0.0220 5.998

Chiller Pressure Drop 32.000


12.3 100Ø Butterfly Valve 1.00 1.37 1.37
D to E
DRV 1.00 18.29 18.29
Motorized Valve 1.00 51.83 51.83
71.49 0.0220 15.937

12.3 100Ø Straight Pipes 1.00 2.00 2.00


Tee Branch 1.00 6.40 6.40
U to V
Gate Valve 1.00 1.37 1.37
Strainer 1.00 18.29 18.29
28.07 0.0220 6.257

Straight Pipes 1.00 6.15 6.15


24.6 150Ø Elbow 90° 2.00 4.88 9.76
T to U
Tee Straight 2.00 3.05 6.10 5.000
Tee Branch 1.00 9.15 9.15 5.000
31.15 0.0562 17.738

24.6 150Ø Straight Pipes 1.00 20.30 20.30


Elbow 90° 4.00 4.88 19.51
E to F &
Tee Straight 2.00 3.05 6.10
S to T
Tee Branch 1.00 9.15 9.15
AIR SAPERATOR 1.00 20.000
55.06 0.0105 5.857

21.68 150Ø Straight Pipes 2.00 64.56 129.12


Tee Straight 6.00 3.05 18.29
F to G &
Tee Branch 2.00 9.15 18.29
R to S
Elbow 90° 12.00 4.88 58.54
Gate Valve 2.00 2.13 4.27
228.51 0.0084 19.449

Straight Pipes 2.00 37.00 74.00


G to H &
17.12 100Ø Tee Straight 24.00 2.04 49.02
Q to R
Elbow 90° 8.00 3.05 24.39
147.41 0.0420 62.735

H to I & Straight Pipes 2.00 9.00 18.00


P to Q 10.32 100Ø Tee Straight 2.00 2.04 4.09
22.09 0.0160 3.580

1.39 40Ø Straight Pipes 2.00 23.50 47.00


I to J & O
Elbow 90° 6.00 1.22 7.32
to P
Tee Straight 4.00 0.79 3.17
57.49 0.0360 20.970

J to K & N Straight Pipes 2.00 2.15 4.30


to O 1.22 32Ø Tee Straight 4.00 0.70 2.80
7.10 0.0590 4.247

Straight Pipes 2.00 9.65 19.30


K to L & M 0.56 25Ø Elbow 90° 4.00 0.79 3.17
to N VALVE PACKAGE 2.000
FCU DROP 15.000
22.47 0.0562 12.796
Sub Total 263.050

10% Safety Factor 289.355


Calculated Pressure Head in (Kpa) 289.35
Calculated Pressure Head in (m) 28.56
Calculated Pressure Head in (Bar) 2.86

Selection of Chilled Water Pump Capacity: (12.30 LPS @ 3 Bar) - 2 Duty + 1Standby