Harmony: HMI GTO For Vijeo Designer User Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 140

Harmony

EIO0000001133 11/2019

Harmony
HMI GTO for Vijeo Designer
User Manual
11/2019
EIO0000001133.06

www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical character-
istics of the performance of the products contained herein. This documentation is not intended as a
substitute for and is not to be used for determining suitability or reliability of these products for specific user
applications. It is the duty of any such user or integrator to perform the appropriate and complete risk
analysis, evaluation and testing of the products with respect to the relevant specific application or use
thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for
misuse of the information contained herein. If you have any suggestions for improvements or amendments
or have found errors in this publication, please notify us.
You agree not to reproduce, other than for your own personal, noncommercial use, all or part of this
document on any medium whatsoever without permission of Schneider Electric, given in writing. You also
agree not to establish any hypertext links to this document or its content. Schneider Electric does not grant
any right or license for the personal and noncommercial use of the document or its content, except for a
non-exclusive license to consult it on an "as is" basis, at your own risk. All other rights are reserved.
All pertinent state, regional, and local safety regulations must be observed when installing and using this
product. For reasons of safety and to help ensure compliance with documented system data, only the
manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must
be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in
injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2019 Schneider Electric. All rights reserved.

2 EIO0000001133 11/2019
Table of Contents

Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
HMIGTO Package Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Certifications and Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
GTO Series of Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Chapter 2 Device Connectivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
System Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Chapter 3 Parts Identification and Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Parts Identification and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Chapter 4 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.1 HMIGTO1300/1310 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Electrical Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Structural Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Display Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Memory, Clock, Touch Panel, and Function Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Interface Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Specifications of Serial Interface COM1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Specifications of Serial Interface COM2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
4.2 HMIGTO2300/2310/2315 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Electrical Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Structural Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Display Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Memory, Clock, and Touch Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Interface Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Specifications of Serial Interface COM1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Specifications of Serial Interface COM2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
4.3 HMIGTO3510/4310 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Electrical Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Structural Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Display Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Memory, Clock, Touch Panel, and Function Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Interface Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Specifications of Serial Interface COM1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Specifications of Serial Interface COM2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
4.4 HMIGTO5310/5315 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Electrical Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Structural Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Display Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Memory, Clock, and Touch Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

EIO0000001133 11/2019 3
Interface Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Specifications of Serial Interface COM1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Specifications of Serial Interface COM2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
4.5 HMIGTO6310/6315 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Structural Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Display Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Memory, Clock, and Touch Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Interface Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Specifications of Serial Interface COM1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Specifications of Serial Interface COM2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Chapter 5 Installation and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
5.1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Installation Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
5.2 Wiring Principles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Connecting the Power Cord . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Connecting the Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
5.3 SD Card Insertion/Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Inserting the SD Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Removing the SD Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
SD Card Data Backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
5.4 USB Cable Clamp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
USB Cable Clamp for USB (Type A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
USB Holder for USB (mini-B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Chapter 6 Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Regular Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Replacing the Installation Gasket. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Periodic Check Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Replacing the Primary Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139

4 EIO0000001133 11/2019
Safety Information

Important Information

NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before
trying to install, operate, service, or maintain it. The following special messages may appear throughout
this documentation or on the equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.

PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this
material.
A qualified person is one who has skills and knowledge related to the construction and operation of
electrical equipment and its installation, and has received safety training to recognize and avoid the
hazards involved.

EIO0000001133 11/2019 5
6 EIO0000001133 11/2019
About the Book

At a Glance

Document Scope
This manual describes how to use the HMIGTO panels.

Validity Note
This documentation is valid for Vijeo Designer 6.2 or higher.
The technical characteristics of the devices described in the present document also appear online. To
access the information online:

Step Action
1 Go to the Schneider Electric home page www.schneider-electric.com.
2 In the Search box type the reference of a product or the name of a product range.
 Do not include blank spaces in the reference or product range.
 To get information on grouping similar modules, use asterisks (*).

3 If you entered a reference, go to the Product Datasheets search results and click on the
reference that interests you.
If you entered the name of a product range, go to the Product Ranges search results and click
on the product range that interests you.
4 If more than one reference appears in the Products search results, click on the reference that
interests you.
5 Depending on the size of your screen, you may need to scroll down to see the datasheet.
6 To save or print a datasheet as a .pdf file, click Download XXX product datasheet.

The characteristics that are presented in the present document should be the same as those character-
istics that appear online. In line with our policy of constant improvement, we may revise content over time
to improve clarity and accuracy. If you see a difference between the document and online information, use
the online information as your reference.

Product Related Information

WARNING
UNINTENDED EQUIPMENT OPERATION
The application of this product requires expertise in the design and programming of control systems. Only
persons with such expertise should be allowed to program, install, alter, and apply this product.
Follow all local and national safety standards.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

EIO0000001133 11/2019 7
8 EIO0000001133 11/2019
Harmony
Overview
EIO0000001133 11/2019

Chapter 1
Overview

Overview

Overview
This chapter describes the HMIGTO panels and general topics such as package contents and standards.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
HMIGTO Package Contents 10
Certifications and Standards 11
GTO Series of Panels 13

EIO0000001133 11/2019 9
Overview

HMIGTO Package Contents

Overview
Verify all items listed here are present in your package:

1 HMIGTO: 1
2 Installation gasket: 1 (attached to the panel)
3 Installation fasteners: 4 per set
4 Brackets: 4
5 M4 Hex Nuts: 8
6 DC power connector: 1*1
7 USB cable clamp Type A: 1 set (1 clip and 1 tie)
8 USB cable clamp mini-B: 1 (1 USB holder)
9 HMIGTO Quick Reference Guide: 1

This product has been carefully packed with special attention to quality. However, should you find anything
damaged or missing, contact your local distributor.
*1You can use the DC power connector for HMIGTO1300/1310/2300/2310/2315/3510/4310 to supply
power to HMIGTO5310/5315/6310/6315. However the reverse is not possible. You cannot use the power
connector for HMIGTO5310/5315/6310/6315 on HMIGTO1300/1310/2300/2310/2315/3510/4310.

Revision
You can identify the product version (PV), revision level (RL), and the software version (SV) from the unit
product label:

10 EIO0000001133 11/2019
Overview

Certifications and Standards

Introduction
Schneider Electric submitted this product for independent testing and qualification by third-party listing
agencies. These agencies have certified this product as meeting the following standards.

Agency Certifications
The HMIGTO is manufactured in accordance with:
o
 Standard UL 508 and CSA C22.2 n 142 for Industrial Control Equipment
 Standard ANSI/ISA - 12.12.01 and CSA C22.2 no213 for Electrical Equipment for Use in Class I,
Division 2 Hazardous Locations

NOTE:
 For use in Pollution Degree 2 environments.
 For use on a flat surface of a Type 1, Type 4X (Indoor Use Only) or Type 13 Enclosure.
 24 Vdc input panel must be used with a Class 2 power supply.
 Suitable for use in Class I, Division 2 Groups A, B, C, and D Hazardous Locations.

 GOST certification.
Refer to product markings.
 ATEX certification by Technical Inspection Association.
Refer to product label.
 Merchant Navy rules. (Except Harmony GTOxxx5.)
Products are designed to comply with Merchant Navy rules.
Refer to the Schneider Electric Web site for Merchant Navy rules installation guidelines.
 Standard EN1672-2 (Harmony GTOxxx5).
 FDA regulation 21 CFR 177 (Harmony GTOxxx5).
Refer to the Schneider Electric web site for installation guidelines.
For detailed information, contact your local distributor or see the catalog & marking on the product.

Hazardous Substances
The HMIGTO is a device for use in factory systems. When using the HMIGTO in a system, the system
should comply with the following standards with regard to the installation environment and handling:
 WEEE, Directive 2002/96/EC
 RoHS, Directive 2011/65/EU
 RoHS China, Standard SJ/T 11363-2006

CE Markings
This product conforms to the requirements of the following Directives for applying the CE label:
 2006/95/EC Low Voltage Directive
 2004/108/EC EMC Directive

This conformity is based on compliance with EN61000-6-4, EN61000-6-2

DANGER
POTENTIAL FOR EXPLOSION
 Verify that the power, input, and output (I/O) wiring are in accordance with Class I, Division 2 wiring
methods.
 Substitution of any component may impair suitability for Class I, Division 2.
 Do not connect or disconnect equipment unless power has been switched off or the area is known to
be non-hazardous.
 Securely lock externally connected units and each interface before turning on the power supply.
 Do not use, connect, or disconnect USB cable unless area is known to be non-hazardous.
 Do not disconnect while circuit is live or unless the area is known to be free of ignitable concentrations.
 Potential electrostatic charging hazard. Wipe the front panel of the terminal with a damp cloth before
turning ON.
Failure to follow these instructions will result in death or serious injury.

EIO0000001133 11/2019 11
Overview

KC Markings

12 EIO0000001133 11/2019
Overview

GTO Series of Panels

Critical Systems, Alarms, and Handling Requirements


Critical alarm indicators and system functions require independent and redundant protection hardware
and/or mechanical interlocks.
When you cycle power, wait at least 10 seconds before restoring the power to the panel after it has been
turned off. Switching the power OFF and ON can damage the panel.
In the event the screen cannot be properly read, for example, if the backlight is not functioning, it may be
difficult or impossible to identify a function. Functions that may present a hazard if not immediately
executed, such as a fuel shut-off, must be provided independently of the panel. The machine’s control
system design must take into account the possibility of the backlight no longer functioning and the operator
being unable to control the machine or making mistakes in the control of the machine.

WARNING
LOSS OF CONTROL
 The designer of any control scheme must consider the potential failure modes of control paths and,
for certain critical control functions, provide a means to achieve a safe state during and after a path
failure. Examples of critical control functions are emergency stop and overtravel stop, power outage
and restart.
 Separate or redundant control paths must be provided for critical control functions.
 System control paths may include communication links. Consideration must be given to the
implications of unanticipated transmission delays or failures of the link.
 Observe all accident prevention regulations and local safety guidelines.
 Each implementation of this equipment must be individually and thoroughly tested for proper operation
before being placed into service.
 The machine control system design must take into account the possibility of the backlight no longer
functioning and the operator being unable to control the machine, or making errors in the control of the
machine.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

For additional information, refer to NEMA ICS 1.1 (latest edition), "Safety Guidelines for the Application,
Installation, and Maintenance of Solid State Control" and to NEMA ICS 7.1 (latest edition), "Safety
Standards for Construction and Guide for Selection, Installation and Operation of Adjustable-Speed Drive
Systems" or their equivalent governing your particular location.

WARNING
UNINTENDED EQUIPMENT OPERATION
 Do not use this equipment as the only means of control for critical system functions such as motor
start/stop or power control.
 Do not use this equipment as the only notification device for critical alarms, such as device overheating
or overcurrent.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

EIO0000001133 11/2019 13
Overview

Handling the LCD Panel


The following characteristics are specific to the LCD panel and are considered normal behavior:
 LCD screen may show unevenness in the brightness of certain images or may appear different when
seen from outside the specified viewing angle. Extended shadows, or crosstalk may also appear on the
sides of screen images.
 LCD screen pixels may contain black and white colored spots and color display may seem to have
changed.
 When the same image is displayed on the screen for a long period, an after-image may appear when
the image is changed.
NOTE: Change the screen image periodically and try not to display the same image for a long period of
time.

CAUTION
SERIOUS EYE AND SKIN INJURY
The liquid in the LCD panel contains an irritant:
 Avoid direct skin contact with the liquid.
 Wear gloves when you handle a broken or leaking unit.
 Do not use sharp objects or tools in the vicinity of the LCD touch panel.
 Handle the LCD panel carefully to prevent puncture, bursting, or cracking of the panel material.

Failure to follow these instructions can result in injury or equipment damage.

If the panel is damaged and any liquid comes in contact with your skin, immediately rinse the area with
running water for at least 15 minutes. If the liquid gets in your eyes, immediately rinse your eyes with
running water for at least 15 minutes and consult a doctor.

14 EIO0000001133 11/2019
Harmony
Connectivity
EIO0000001133 11/2019

Chapter 2
Device Connectivity

Device Connectivity

Introduction
This chapter presents the equipment you can connect to the panel.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
System Design 16
Accessories 22

EIO0000001133 11/2019 15
Connectivity

System Design

Introduction
The following diagrams represent equipment you can connect to the panel.

COM1 COM2
HMIGTO1300 RS-232C (see page 17) RS-485 (see page 19)
HMIGTO1310 RS-232C / RS-485 –
(see page 18)
HMIGTO2300 RS-232C (see page 17) RS-485 (see page 19)
HMIGTO2310
HMIGTO2315
HMIGTO3510
HMIGTO4310
HMIGTO5310
HMIGTO5315
HMIGTO6310
HMIGTO6315

CAUTION
LOSS OF COMMUNICATION
 All connections to the communication ports must not put excessive stress on the ports.
 Securely attach communication cables to the panel or cabinet.
 Use only D-Sub 9-pin cables with a locking system in good condition.
Failure to follow these instructions can result in injury or equipment damage.

16 EIO0000001133 11/2019
Connectivity

RUN Mode Peripherals - RS-232C

*1When connecting the XBTZGI232, the COM port's pin 9 setting should be VCC. You can define COM
port settings in Vijeo Designer or in the HMIGTO's offline menu.
*2
The RS-232C Isolation Unit works with only RS-422/485 (4 wire) communication.
*3 Cable-Gateway for Siemens Profibus / MPI (XBT ZG9292) is not supported by HMIGTO1310.

EIO0000001133 11/2019 17
Connectivity

RUN Mode Peripherals - RS-232C / RS-485

*1 Use the RS-485 Isolation Unit's USB port to supply power to itself. There is no need to set up a separate

power supply.
*2
In 1:n, n:1, or n:m communication, you can use the online adapter as a terminal. (Use 1 unit in either
communication setup.)
*3 The connector has a switch to control the terminal. Turn on the switch to enable communication.

18 EIO0000001133 11/2019
Connectivity

RUN Mode Peripherals - RS-485

*1 Use the RS-485 Isolation Unit's USB port to supply power to itself. There is no need to set up a separate

power supply.
*2
In 1:n, n:1, or n:m communication, you can use the online adapter as a terminal. (Use 1 unit in either
communication setup.)
*3
The connector has a switch to control the terminal. Turn on the switch to enable communication.

RUN Mode Peripherals - Ethernet Communication

EIO0000001133 11/2019 19
Connectivity

RUN Mode Peripherals - USB Type A / mini-B Interface

20 EIO0000001133 11/2019
Connectivity

Edit Mode Peripherals

EIO0000001133 11/2019 21
Connectivity

Accessories

Serial Interface Items

Product Name Product Number Description


RS-232C Cable XBTZG9731 Connects a host controller to the panel (RS-232C).
RS-422 Cable XBTZG9722 Connects a host controller to the panel (RS-422).
Mitsubishi PLC Q-Series Link XBTZG9772 Connects Mitsubishi PLC Q-Series (or other host controller) to
Cable the panel (RS-232C).
Omron PLC SYSMAC Link Cable XBTZG9740 Connects Omron PLC SYSMAC Series unit (or other host
XBTZ9743 controller) to the panel (RS-232C).
XBTZ9740
Mitsubishi PLC A-Series XBTZG9773 Connects Mitsubishi PLC A or QnA Series programming
Connection Cable console I/F to panel (simultaneous use of programming
consoles is not possible).
Mitsubishi PLC Q-Series XBTZG9774 Connects Mitsubishi PLC Q-Series programming console I/F
Connection Cable to panel (simultaneous use of programming consoles is not
possible).
Mitsubishi PLC FX-Series XBTZG9775 Connects Mitsubishi PLC FX-Series programming console I/F
Connection Cable XBTZ980 and panel (simultaneous use of programming consoles is not
possible).
Premium, Micro, Twido Cable TSXPCX1031 Connects Premium, Micro, or Twido to the panel.
Modicon, Quantum Cable 990NAA26320 Connects Modicon or Quantum to the panel.
XBTZ9710
2 Port Adapter Cable XBTZG9778 Connects Mitsubishi PLC directly to the panel (D-sub 9 pin
plug) using 2-port adapter II (RS-422).
Mitsubishi PLC A, QnA, FX Series XBTZG979 Enables simultaneous use of a panel and a Mitsubishi PLC A,
2 Port Adapter II QnA, or FX Series peripheral device.
Advantys STB Cable STBXCA4002 Connects Advantys STB to panel.
XBTZ9715
XBTZ988
Terminal Block Conversion XBTZG949 Connects output from a panel's Serial Interface (D-sub 9 pin
Adapter plug) directly with an RS-422 terminal block.
COM Port Conversion Adapter XBTZGCOM1 Connects optional RS-422 communication items to panel's
COM1 port.
DF1-full Duplex D-Sub Cable XBTZ9730 Connects DF1-full Duplex to HMIGTO.
XBTZ9733
XBTZ9734
DF1-full Duplex mini-DIN Cable XBTZ9731 Connects DF1-full Duplex to HMIGTO.
XBTZ9720
Modicon, Momentum M1 Cable XBTZ9711 Connects Modicon, Momentum M1 to HMIGTO.
PLC Twido Connection Cable XBTZ9780 / Connects PLC Twido to HMIGTO.
XBTZ9782
Derivation Box Connection Cable VW3A8306 Connects Derivation Box to HMIGTO.
Derivation Connection Cable VW3A8306TF10 Connects Derivation to HMIGTO.
Modicon M340 Connection Cable XBTZ9980 / Connects Modicon M340 to HMIGTO.
XBTZ9982
Siemens PLC Connection Cable XBTZG9721 Connects Siemens PLC to HMIGTO.
RS-232C Isolation Unit XBTZGI232 Connects a host controller to HMIGTO with isolation (RS-232C
and RS-422 are switchable).
RS-485 Isolation Unit XBTZGI485 Connects a host controller to HMIGTO with isolation.
Cable-gateway for Siemens XBTZG9292 Connects Siemens Profibus / MPI units to HMIGTO.
Profibus / MPI
RJ45 to D-Sub 25 pin Conversion XBTZG939 Connects a RJ45 cable to HMIGTO (D-sub 9 pin plug).
Cable
9-pin to 25-pin RS-232C XBTZG919 Connects a standard RS-232C cable (D-Sub 25-pin socket) to
Conversion Cable HMIGTO (D-sub 9 pin plug).
Online Adapter XBTZGCOM2 Terminal adapter for RS-485 communication.

22 EIO0000001133 11/2019
Connectivity

USB Interface Items

Product Name Product Number Description


USB Transfer Cable XBTZG935 Downloads project data created with the
software via the panel's USB I/F.
USB Front Cable XBTZGUSB Extension cable attaching USB interface to
front panel.
USB-Serial (RS-232C) Conversion Cable HMIZURS Cable for converting a panel's USB
interface into a serial interface (RS-232C).
Allows connection to modems*1 or bar code
readers*1 that support RS-232C.
USB Transfer Cable (USB Type A/mini-B) BMXXCAUSBH018 Cable for transferring screen data from a PC
BMXXCAUSBH045 (USB Type A) to the panel (USB mini-B).
Remote USB port location for mini-USB HMIZSUSBB Extension cable that attaches to the USB
XBTZGUSBB (mini-B) interface on the front side of the
operation panel.
Illuminated USB Switch HMIZRA1 Unit of 5 illuminated switches with multiple
color LEDs easily connected with HMIGTO
via USB.
Biometric USB Switch for HMI XB5S5B2L2 Fingerprint recognition unit easily
connected with HMIGTO via USB.
Tower light USB Switch XVGU3SHAV Monolithic USB tower lights with multiple
XVGU3SWV color LEDs easily connected with HMIGTO
via USB.
Keyboard USB HMIZKB1 Keyboard unit easily connected with
HMIGTO via USB.

Software

Product name Description


Vijeo Designer Software you install on your computer to create project data for your HMIGTO.
(Version 6.1 or later)

SD Card Items

Product Name Product Number Description


SD Memory Card (4 GB) HMIZSD4G SD Memory Card (4 GB, CLASS4).

Option Items

Product Name Product Number Corresponding Description


panel
Screen Protection Sheet XBTZG66 HMIGTO6310/6315 Disposable, dirt-resistant sheet
for the HMIGTO screen
XBTZG65 HMIGTO5310/5315
(5 sheets/set).
XBTZG64 HMIGTO4310
XBTZG63 HMIGTO3510
XBTZG62 HMIGTO2300/2310/
2315
XBTZG60 HMIGTO1300/1310
UV Protection Sheet HMIUV6 HMIGTO6310 Sheet to protect the display and
ultraviolet light.
HMIUV5 HMIGTO5310
HMIUV4 HMIGTO4310
HMIUV3W HMIGTO3510
HMIUV2 HMIGTO2300/2310
HMIUV1 HMIGTO1300/1310

EIO0000001133 11/2019 23
Connectivity

Product Name Product Number Corresponding Description


panel
Environment Cover HMIZECOV6 HMIGTO6310 Disposable, environment cover
for the HMIGTO screen
HMIZECOV5 HMIGTO5310
(1 sheet/set).
HMIZECOV4 HMIGTO3510/4310
HMIZECOV2 HMIGTO2300/2310
HMIZECOV1 HMIGTO1300/1310

Maintenance Options

Product Name Product Number Corresponding Description


panel
Installation Fastener HMIZGFIX HMIGTO (except Used to install the HMIGTO into a
HMIGTO2315/5315/ solid panel (4 pieces/set).
6315)
Installation System HMIZGFIX2 HMIGTO2315/5315/ Used to install the HMIGTO into a
6315 solid panel.
Brackets (4 pieces/set).
M4 Hex nuts (8 pieces/set).
Installation Gasket HMIZG56 HMIGTO6310 Provides dust and moisture
resistance when HMIGTO is
HMIZG562 HMIGTO6315
installed into a solid panel
HMIZG55 HMIGTO5310 (1 piece).
HMIZG552 HMIGTO5315
HMIZG54 HMIGTO3510/4310
HMIZG52 HMIGTO2300/2310
HMIZG522 HMIGTO2315
HMIZG51 HMIGTO1300/1310
USB Clamp TypeA (1 port) HMIZGCLP1 Harmony GTO Clamp to prevent disconnection
of USB cable (USB/A, 1 port,
5 clamps/set).
USB Clamp mini-B (1 port) HMIZSCLP3 Harmony GTO Clamp to prevent disconnection
of USB cable (USB/mini-B, 1 port,
5 clamps/set).
DC Power Supply Connector HMIZGPWS HMIGTO3510/4310 Connector to connect DC power
HMIGTO2300/2310/ supply cables (5 pieces/set).
2315
HMIGTO1300/1310
DC Power Supply Connector (Right- HMIZGPWS2 HMIGTO6310/6315 Right-angle connector to connect
angle) HMIGTO5310/5315 DC power supply cables
(5 pieces/set).
Battery for Memory Backup HMIZGBAT HMIGTO (except Primary battery for memory and
HMIGTO1300/1310/ time data backup.
2300)
Panel Cutout Adapter XBTZGGCO4 HMIGTO5310 Panel cutout adapter for
mounting HMIGTO5310 in cutout
for XBTGT5230.
Insert Label HMIZLYGO3 HMIGTO3510 Label insert for HMIGTO 7-inch
Wide models.
HMIZLYGO1 HMIGTO1300/1310 Label insert for HMIGTO 3.5-inch
models.

24 EIO0000001133 11/2019
Harmony
Parts/Functions
EIO0000001133 11/2019

Chapter 3
Parts Identification and Functions

Parts Identification and Functions

Parts Identification and Functions

HMIGTO1300/1310 Parts Identification

Side HMIGTO1300/1310
Front

Rear

Bottom

Part Name Description


A Status LED *1

B Function Switches Six switches (F1 to F6). You can define operations for these
switches using Vijeo Designer.
C USB (mini-B) Interface Conforms to USB2.0 (mini-B) x 1. Communication Distance: 5 m
(16.4 ft) or less.
D USB (Type A) Interface Conforms to USB2.0 (Type A) x 1. Power supply voltage:
5 Vdc+/-5%. Output Current: 500 mA or less. Maximum
communication distance: 5 m (16.4 ft).

EIO0000001133 11/2019 25
Parts/Functions

Part Name Description


E Serial Interface (COM1) HMIGTO1300: RS-232C Serial Interface. Connector: D-Sub 9 pin
(plug) x 1.
HMIGTO1310: RS-232C/485 Serial Interface. (You can switch
the communication method via software.) Connector: Modular
jack (RJ45).
F Ethernet Interface*2 Ethernet transmission interface (10BASE-T/100BASE-TX)
Connector: Modular jack (RJ45) x 1. Ethernet Interface is not
attached to HMIGTO1300.
G Power Plug Connector -
H Serial Interface (COM2) HMIGTO1300: RS-485 Serial Interface. Connector: Modular jack
(RJ45) x 1.

*1
Status LED operations are as shown below:

Color Indicator Description


Green ON In operation
Orange Flashing Software starting up.
Red ON Power is turned ON.
- OFF Power is turned OFF.

*2
Ethernet LED operations are as shown below.

Color Indicator Description


Green (Active) Flashing Data transmission is occurring.
OFF No data transmission.
Green (Link) ON Data transmission is available in 10BASE-T/100BASE-TX.
OFF No connection or subsequent transmission failure.

HMIGTO2300/2310/2315 Parts Identification

Side HMIGTO2300 / HMIGTO2310 HMIGTO2315


Front

Right

26 EIO0000001133 11/2019
Parts/Functions

Side HMIGTO2300 / HMIGTO2310 HMIGTO2315


Rear

Bottom

Part Name Description


A Status LED *1

B Stainless Steel Bezel (grade 304) HMIGTO2315 only.


C USB (Type A) Interface Conforms to USB2.0 (Type A) x 1.
Power supply voltage: 5 Vdc+/-5%.
Output Current: 500 mA or less.
Maximum communication distance: 5 m (16.4 ft).
D Serial Interface (COM1) RS-232C Serial Interface. Connector: D-Sub 9 pin (plug) x 1.
E Serial Interface (COM2) *2 RS-485 Serial Interface. Connector: Modular jack (RJ45).
F Power Plug Connector -
G SD Card Access LED *3 This lamp lights up when SD card is inserted.
For more information, refer to SD Card Insertion/Removal
(see page 121).
NOTE: SD card access LED is not available on HMIGTO2300.
H SD Card Interface For information on how to open the cover, and insert or remove the
Cover/Replacement Battery SD card, refer to SD Card Insertion/Removal (see page 121).
Insertion Cover For information on how to open the cover and replace the battery,
refer to Replacing the Primary Battery (see page 136).
NOTE: This cover is not on HMIGTO2300.
I USB (mini-B) Interface Conforms to USB2.0 (mini-B) x 1.
Communication Distance: 5 m (16.4 ft) or less.
J Ethernet Interface*4 Ethernet transmission interface (10BASE-T/100BASE-TX)
Connector: Modular jack (RJ45) x 1.
NOTE: Ethernet Interface is not available on HMIGTO2300.

*1
Status LED operations are as shown below:

Color Indicator Description


Green ON In operation
Orange Flashing Software starting up.
Red ON Power is turned ON.
- OFF Power is turned OFF.

EIO0000001133 11/2019 27
Parts/Functions

*2
COM2 LED operations are as shown below.

Color Indicator Description


Yellow ON Communication (sending or receiving data) is occurring.
OFF No communication.

*3
SD card access LED operations are as shown below.

Color Indicator Description


Green (Active) ON The SD card is inserted.
OFF The SD card is not inserted or is not being accessed.

*4
Ethernet LED operations are as shown below.

Color Indicator Description


Green (Active) Flashing Data transmission is occurring.
OFF No data transmission.
Green (Link) ON Data transmission is available in 10BASE-T/100BASE-TX.
OFF No connection or subsequent transmission failure.

HMIGTO3510/4310 Parts Identification

Side HMIGTO3510/4310
Front

Right

28 EIO0000001133 11/2019
Parts/Functions

Side HMIGTO3510/4310
Rear

Bottom

Part Name Description


A Status LED *1

B Function Switches Height switches (F1 to F8). You can define operations for these
switches using Vijeo Designer.
C USB (Type A) Interface Conforms to USB2.0 (Type A) x 1. Power supply voltage:
5 Vdc+/-5%. Output Current: 500 mA or less. Maximum
communication distance: 5 m (16.4 ft).
D Serial Interface (COM1) RS-232C Serial Interface. Connector: D-Sub 9 pin (plug) x 1.
E Serial Interface (COM2)*2 RS-485 Serial Interface. Connector: Modular jack (RJ45) x 1.
F Power Plug Connector -
G SD Card Access LED *3 This lamp lights up when SD card is inserted.
For more information, refer to SD Card Insertion/Removal
(see page 121).
H SD Card Interface For information on how to open the cover, and insert or remove
Cover/Replacement Battery the SD card, refer to SD Card Insertion/Removal (see page 121).
Insertion Cover For information on how to open the cover and replace the
battery, refer to Replacing the Primary Battery (see page 136).
I USB (mini-B) Interface Conforms to USB2.0 (mini-B) x 1. Communication Distance: 5 m
(16.4 ft) or less.
J Ethernet Interface*4 Ethernet transmission interface (10BASE-T/100BASE-TX)
Connector: Modular jack (RJ45) x 1.

*1 Status LED operations are as shown below:

Color Indicator Description


Green ON In operation
Orange Flashing Software starting up.
Red ON Power is turned ON.
- OFF Power is turned OFF.

*2 COM2 LED operations are as shown below.

Color Indicator Description


Yellow ON Communication (sending or receiving data) is occurring.
OFF No communication.

EIO0000001133 11/2019 29
Parts/Functions

*3
SD card Access LED operations are as shown below.

Color Indicator Description


Green (Active) ON The SD card is inserted.
OFF The SD card is not inserted or is not being accessed.

*4
Ethernet LED operations are as shown below.

Color Indicator Description


Green (Active) Flashing Data transmission is occurring.
OFF No data transmission.
Green (Link) ON Data transmission is available in 10BASE-T/100BASE-TX.
OFF No connection or subsequent transmission failure.

HMIGTO5310/5315 Parts Identification

Side HMIGTO5310 HMIGTO5315


Front

Rear

Bottom

Part Name Description


A Status LED *1

B Stainless Steel Bezel (grade 304) HMIGTO5315 only.


C Power Plug Connector (DC model) -
D SD Card Access LED*2 This lamp lights up when SD card is inserted.
NOTE: Do not remove or insert the SD card when the LED lamp
is on. Doing so may damage data on the SD card.
E Ethernet Interface*3 Ethernet transmission interface (10BASE-T/100BASE-TX)
Connector: Modular jack (RJ45) x 1.
F USB (mini-B) Interface Conforms to USB2.0 (mini-B) x 1.
Communication Distance: 5 m (16.4 ft) or less.

30 EIO0000001133 11/2019
Parts/Functions

Part Name Description


G SD Card Interface For information on how to open the cover, and insert or remove the
Cover/Replacement Battery SD card, refer to SD Card Insertion/Removal (see page 121).
Insertion Cover For information on how to open the cover and replace the battery,
refer to Replacing the Primary Battery (see page 136).
H Serial Interface (COM2)*4 RS-485 Serial Interface.
Connector: Modular jack (RJ45).
I Serial Interface (COM1) RS-232C Serial Interface.
Connector: D-Sub 9 pin (plug) x 1.
J USB (Type A) Interface Conforms to USB2.0 (Type A) x 1. Power supply voltage: 5 Vdc+/-
5%. Output Current: 500 mA or less. Maximum communication
distance: 5 m (16.4 ft).

*1
Status LED operations are as shown below:

Color Indicator Description


Green ON In operation
Orange Flashing Software starting up.
Red ON Power is turned ON.
- OFF Power is turned OFF.

*2
SD card access LED operations are as shown below.

Color Indicator Description


Green (Active) ON The SD card is inserted.
OFF The SD card is not inserted or is not being accessed.

*3 Ethernet LED operations are as shown below.

Color Indicator Description


Green (Active) Flashing Data transmission is occurring.
OFF No data transmission.
Green (Link) ON Data transmission is available in 10BASE-T/100BASE-TX.
OFF No connection or subsequent transmission failure.

*4 COM2 LED operations are as shown below.

Color Indicator Description


Yellow ON Communication (sending or receiving data) is occurring.
OFF No communication.

HMIGTO6310/6315 Parts Identification

Side HMIGTO6310 HMIGTO6315


Front

EIO0000001133 11/2019 31
Parts/Functions

Side HMIGTO6310 HMIGTO6315


Rear

Bottom

Part Name Description


A Status LED *1

B Stainless Steel Bezel (grade 304) HMIGTO6315 only.


C Power Plug Connector (DC model) -
D SD Card Access LED *2 This lamp lights up when SD card is inserted.
NOTE: Do not remove or insert the SD card when the LED lamp
is on. Doing so may damage data on the SD card.
E Ethernet Interface*3 Ethernet transmission interface (10BASE-T/100BASE-TX)
Connector: Modular jack (RJ45) x 1.
F USB (mini-B) Interface Conforms to USB2.0 (mini-B) x 1.
Communication Distance: 5 m (16.4 ft) or less.
G SD Card Interface For information on how to open the cover, and insert or remove the
Cover/Replacement Battery SD card, refer to SD Card Insertion/Removal (see page 121).
Insertion Cover For information on how to open the cover and replace the battery,
refer to Replacing the Primary Battery (see page 136).
H Serial Interface (COM2)*4 RS-485 Serial Interface. Connector: Modular jack (RJ45)
I Serial Interface (COM1) RS-232C Serial Interface. Connector: D-Sub 9 pin (plug) x 1.
J USB (Type A) Interface Conforms to USB2.0 (Type A) x 1.
Power supply voltage: 5 Vdc+/-5%.
Output Current: 500 mA or less.
Maximum communication distance: 5 m (16.4 ft).

*1 Status LED operations are as shown below:

Color Indicator Description


Green ON In operation
Orange Flashing Software starting up.
Red ON Power is turned ON.
- OFF Power is turned OFF.

*2 SD card access LED operations are as shown below.

Color Indicator Description


Green (Active) ON The SD card is inserted.
OFF The SD card is not inserted or is not being accessed.

32 EIO0000001133 11/2019
Parts/Functions

*3
Ethernet LED operations are as shown below.

Color Indicator Description


Green (Active) Flashing Data transmission is occurring.
OFF No data transmission.
Green (Link) ON Data transmission is available in 10BASE-T/100BASE-TX.
OFF No connection or subsequent transmission failure.

*4
COM2 LED operations are as shown below.

Color Indicator Description


Yellow ON Communication (sending or receiving data) is occurring.
OFF No communication.

EIO0000001133 11/2019 33
Parts/Functions

34 EIO0000001133 11/2019
Harmony
Specifications
EIO0000001133 11/2019

Chapter 4
Specifications

Specifications

Overview
This chapter presents the HMIGTO specifications.

What Is in This Chapter?


This chapter contains the following sections:
Section Topic Page
4.1 HMIGTO1300/1310 36
4.2 HMIGTO2300/2310/2315 49
4.3 HMIGTO3510/4310 64
4.4 HMIGTO5310/5315 78
4.5 HMIGTO6310/6315 93

EIO0000001133 11/2019 35
Specifications

Section 4.1
HMIGTO1300/1310

HMIGTO1300/1310

What Is in This Section?


This section contains the following topics:
Topic Page
Electrical Specifications 37
Environmental Specifications 38
Structural Specifications 39
Display Specifications 40
Memory, Clock, Touch Panel, and Function Switches 41
Interface Specifications 42
Specifications of Serial Interface COM1 43
Specifications of Serial Interface COM2 45
Dimensions 46

36 EIO0000001133 11/2019
Specifications

Electrical Specifications

Rated Input Voltage 24 Vdc


Input Voltage Limits 19.2...28.8 Vdc
Voltage Drop 2 ms or less
Power Consumption 9.6 W or less
When power is not supplied to 5.2 W or less
external devices
Power Supply

Backlight OFF (Standby Mode) 4.2 W or less


Backlight Dimmed (Brightness: 20%) 4.3 W or less
In-Rush Current 30 A or less
Voltage Endurance 1,000 Vac 20 mA for 1 minute (between charging
and FG terminals)
Insulation Resistance 500 Vdc, 10 MΩ or more (between charging and
FG terminals)

EIO0000001133 11/2019 37
Specifications

Environmental Specifications

Surrounding Air 0...50 °C (32...122 °F)


Temperature
Storage Temperature -20...60 °C (-4...140 °F)
Surrounding Air and 10%...90% RH (non-condensing, wet bulb temperature 39 °C (102.2 °F) or
Storage Humidity less)
Electrical Environment Mechanical Environment Physical Environment

Dust 0.1 mg/m3 (10-7 oz/ft3) or less (non-conductive levels)


Pollution Degree For use in Pollution Degree 2 environment
Corrosive Gases Free of corrosive gases
Atmospheric Pressure 800...1,114 hPa (2,000 m [6,561 ft] or lower)
(Operating Altitude)
Vibration Resistance IEC/EN 61131-2 compliant
5...9 Hz Single amplitude 3.5 mm (0.14 in.)
9...150 Hz Fixed acceleration: 9.8 m/s2
X, Y, Z directions for 10 cycles (approx. 100 min.)
Concussion Resistance IEC/EN 61131-2 compliant
147 m/s2, X, Y, Z directions for 3 times

Noise Immunity Noise Voltage: 1,000 Vp-p


Pulse Width: 1 μs
Rise Time: 1 ns
(via noise simulator)
Electrostatic Discharge Contact Discharge Method: 6 kV (IEC/EN 61000-4-2 Level 3)
Immunity

Air Quality Requirements


Do not operate or store the panel where chemicals evaporate, or where chemicals are present in the air:
 Corrosive chemicals: Acids, alkalines, liquids containing salt.
 Flammable chemicals: Organic solvents.

CAUTION
INOPERATIVE EQUIPMENT
Do not allow water, liquids, metal, and wiring fragments to enter the panel case.
Failure to follow these instructions can result in injury or equipment damage.

38 EIO0000001133 11/2019
Specifications

Structural Specifications

Grounding Functional grounding: Grounding resistance of 100 Ω, 2 mm2


(AWG 14) or thicker wire, or your country's applicable standard. (Same
for FG and SG terminals)
Cooling Method Natural air circulation
Structure *1 IP65f NEMA #250 TYPE 4X/13 (on the front panel when properly
installed in an enclosure)
External Dimensions W 132 x H 106 x D 42 mm (W 5.2 x H 4.17 x D 1.65 in)
Panel Cut Dimensions W 118.5 x H 92.5 mm (W 4.67 x H 3.64 in)*2
Panel thickness area: 1.6...5 mm (0.06...0.2 in)*3
Weight 0.4 kg (0.9 lb) or less (main unit only)

*1 The front face of the HMIGTO, installed in a solid panel, has been tested using conditions equivalent to

the standards shown in the specification. Even though the HMIGTO's level of resistance is equivalent to
these standards, oils that should have no effect on the HMIGTO can possibly harm the panel. This can
occur in areas where either vaporized oils are present, or where low viscosity cutting oils are allowed to
adhere to the panel for long periods of time. If the panel's front face protection sheet peels off, these
conditions can lead to the ingress of oil into the panel and separate protection measures are suggested.
Also, if non-approved oils are present, they may cause deformation or corrosion of the front panel's plastic
cover. Therefore, prior to installing the panel, be sure to confirm the type of conditions that will be present
in the panel's operating environment. If the installation gasket is used for a long period of time, or if the
panel and its gasket are removed from the panel, the original level of protection cannot be kept. To
maintain the original protection level, be sure to replace the installation gasket regularly.
*2
For dimensional tolerance, everything +1/-0 mm (+0.04/-0 in), and R in angle are below R3 (R0.12 in)
*3Even if the installation wall thickness is within the recommended range for the “Panel Cut Dimensions”,
depending on wall’s material, size, and installation location of the panel and other devices, the installation
wall could warp. To prevent warping, the installation surface may need to be strengthened.
The front face of the panel, installed in a solid panel, has been tested using conditions equivalent to the
standards shown in the specification.

CAUTION
EQUIPMENT DAMAGE
Ensure that the panel is not in permanent and direct contact with oils.
Failure to follow these instructions can result in injury or equipment damage.

NOTICE
STORAGE AND OPERATION OUTSIDE OF SPECIFICATIONS
 Store this product in areas where temperatures are within the product’s specifications.
 Do not restrict or block this product’s ventilation slots.
Failure to follow these instructions can result in equipment damage.

NOTICE
GASKET AGING
 Inspect the gasket periodically as required by your operating environment to keep the initial IP level.
 Change the gasket at least once a year, or as soon as scratches or dirt become visible.
Failure to follow these instructions can result in equipment damage.

EIO0000001133 11/2019 39
Specifications

Display Specifications

HMIGTO1310 HMIGTO1300
Display Type TFT Color LCD
Display Size 3.5”
Resolution 320 x 240 pixels (QVGA)
Effective Display Area W 70.56 x H 52.92 mm (W 2.78 x H 2.08 in.)
Display Colors 65,536 colors (no blink) / 16,384 colors (blink)
Backlight White LED (not user replaceable). When replacement is required,
contact your local distributor.
Backlight Service Life 50,000 hours or more (continuous operation at 25 °C (77 °F) before
backlight brightness decreased to 50%)
Brightness Control 16 levels (Adjusted with touch panel or software
Language Fonts ASCII: (Code page 850) Alphanumeric (including European characters)
Chinese: (GB2312-80 codes) Simplified Chinese fonts
Japanese (except for XBT GT1000 series): ANK 158, Kanji: 6,962 (JIS
Standards 1 & 2) (including 607 non-kanji characters)
Korean: (KSC5601 - 1992 codes) Hangul fonts
Taiwanese: (Big 5 codes) Traditional Chinese fonts
Character Sizes 8 x 8, 8 x 16, 16 x 16 and 32 x 32 pixel fonts
Font Sizes You can expand width up to 8 times, and expand height up to 8 times.*1
Text 8 x 8 pixels 40 characters per row x 30 rows
8 x 16 pixels 40 characters per row x 15 rows
16 x 16 pixels 20 characters per row x 15 rows
32 x 32 pixels 10 characters per row x 7 rows

*1
You can set up other font sizes using the software.

40 EIO0000001133 11/2019
Specifications

Memory, Clock, Touch Panel, and Function Switches

Introduction
NOTE:
 When the message indicating that the battery level is low is displayed, supply power to the panel and
fully charge the battery. In 24 hours the battery charges to a level that allows backup operation.
Completing a full charge requires about 120 hours (five days).
 The lifetime of the rechargeable lithium battery is 10 years when the battery’s ambient temperature is
40 °C (104 °F) or less, 4.1 years when the battery’s ambient temperature is 50 °C (122 °F) or less, and
1.5 years when the battery’s ambient temperature is 60 °C (140 °F) or less.
When used for backup:
 Approximately 100 days with a fully charged battery.
 Approximately 6 days with a half-charged battery.

Memory

HMIGTO1310 HMIGTO1300
Application Memory *1 FLASH EPROM 96 MB FLASH EPROM 64 MB
Application run DRAM 128 MB 128 MB
Data Backup SRAM 512 KB (Rechargeable lithium SRAM 128 KB (Rechargeable lithium
battery for data backup) battery for data backup)

*1
Capacity available for user application.

Clock

Clock Accuracy*1 ±65 seconds/month (deviation at room temperature and power is OFF).

*1 Depending on the operating temperature and age of panel, the clock can deviate from -380 to +90
sec/month. For systems where this level of precision is insufficient, the user should monitor and make
adjustments when required.

Touch Panel

Touch Panel Type Resistive Film (analog)


Touch Panel Resolution 1,024 x 1,024
Touch Panel Service Life 1 million times or more

Function Switches
Six switches (F1 to F6).

EIO0000001133 11/2019 41
Specifications

Interface Specifications

Serial Interface COM1

HMIGTO1310 HMIGTO1300
Asynchronous RS-232C / RS-485 RS-232C
Transmission
Data Length 7 bits or 8 bits
Stop Bit 1 bit or 2 bits
Parity None, odd or even
Data Transmission 2,400...115,200 bps, 187,500 bps (MPI) 2,400...115,200 bps
Speed
Connector Modular jack (RJ45) D-Sub 9 pin (plug)

Serial Interface COM2

HMIGTO1300
Asynchronous Transmission RS-485
Data Length 7 bits or 8 bits
Stop Bit 1 bit or 2 bits
Parity None, odd or even
Data Transmission Speed 2,400...115,200 bps, 187,500 bps (MPI)
Connector Modular jack (RJ45)

USB Interface

USB (Type A) Interface USB (mini-B) Interface


Connector USB 2.0 (Type A) x 1 USB 2.0 (mini-B) x 1
Power Supply Voltage 5 Vdc ±5% -
Maximum Current 500 mA -
Supplied
Maximum Transmission 5 m (16.4 ft)
Distance

Ethernet Interface

HMIGTO1310
Ethernet (LAN) IEEE802.3i / IEEE802.3u, 10BASE-T/100BASE-TX
Connector Modular jack (RJ45) x 1

NOTE: HMIGTO1300 does not have an Ethernet interface.

42 EIO0000001133 11/2019
Specifications

Specifications of Serial Interface COM1

Introduction
NOTE: For information on how to connect controllers and other types of equipment, refer to the
corresponding device driver manual of your screen editing software.

CAUTION
LOSS OF COMMUNICATION
 All connections to the communication ports must not put excessive stress on the ports.
 Securely attach communication cables to the panel or cabinet.
 Use only D-Sub 9-pin cables with a locking system in good condition.
Failure to follow these instructions can result in injury or equipment damage.

The serial port is not isolated. The SG (signal ground) and FG (frame ground) terminals are connected
inside the panel.

DANGER
ELECTRIC SHOCK
When using the SG terminal to connect an external device to the panel:
 Verify that a short-circuit loop is not created when you set up the system.
 For HMIGTO1300, connect the #5 SG terminal to remote equipment when the host (PLC) unit is not
isolated. Connect the #5 SG terminal to a known reliable ground connection to reduce the risk of
damaging the circuit.
 For HMIGTO1310, connect the #8 SG terminal to remote equipment when the host (PLC) unit is not
isolated. Connect the #8 SG terminal to a known reliable ground connection to reduce the risk of
damaging the circuit.
Failure to follow these instructions will result in death or serious injury.

Serial Interface COM1


HMIGTO1300: D-Sub 9-pin plug connector via a RS-232C cable.

Pin Connection Pin No. RS-232C


Signal Name Direction Meaning
1 CD Input Carrier Detect
2 RD(RXD) Input Receive Data
3 SD(TXD) Output Send Data
4 ER(DTR) Output Data Terminal Ready
5 SG - Signal Ground
6 DR(DSR) Input Data Set Ready
7 RS(RTS) Output Request to Send
8 CS(CTS) Input Send possible
9 CI(RI)/VCC Input– Called Status Display
+5 V±5% Output 0.25 A
Shell FG – Frame Ground (Common
with SG)

You can switch pin #9 between RI and VCC via software.

NOTICE
EQUIPMENT DAMAGE
Use only the rated current.
Failure to follow these instructions can result in equipment damage.

EIO0000001133 11/2019 43
Specifications

Interfit bracket is #4-40 (UNC).

CAUTION
LOSS OF COMMUNICATION
 All connections to the communication ports must not put excessive stress on the ports.
 Securely attach communication cables to the panel wall or cabinet.
 Use only D-Sub 9 pin cables with a locking tab in good condition.
Failure to follow these instructions can result in injury or equipment damage.

HMIGTO1310: RJ45 connector via a RS-232C or 485 cable.

Pin Connection Pin No. RS-232C/RS-485


Signal Name Direction Meaning
1 RD(RXD) Input Receive Data (RS-232C)
2 SD(TXD) Output Send Data (RS-232C)
3 NC – –
4 D1 Input/Output Transfer Data (RS-485)
5 D0 Input/Output Transfer Data (RS-485)
6 RS(RTS) Output Request to Send
7 NC – –
8 SG – Signal Ground

CAUTION
LOSS OF COMMUNICATION
 All connections to the communication ports must not put excessive stress on the ports.
 Securely attach communication cables to the panel wall or cabinet.
 Use only RJ45 with a locking tab in good condition.
Failure to follow these instructions can result in injury or equipment damage.

44 EIO0000001133 11/2019
Specifications

Specifications of Serial Interface COM2

Introduction
NOTE: For information on how to connect controllers and other types of equipment, refer to the
corresponding device driver manual of your screen editing software.
The serial port is not isolated. The SG (signal ground) and FG (frame ground) terminals are connected
inside the panel.

DANGER
ELECTRIC SHOCK
When using the SG terminal to connect an external device to the panel:
 Verify that a short-circuit loop is not created when you set up the system.
 Connect the #8 SG terminal to remote equipment when the host (PLC) unit is not isolated. Connect
the #8 SG terminal to a known reliable ground connection to reduce the risk of damaging the circuit.
Failure to follow these instructions will result in death or serious injury.

Serial Interface COM2


HMIGTO1300: RJ45 connector via an RS-485 cable
NOTE: When setting up RS-485 communication, the cable diagram for some equipment may require
polarization on the terminal side. This terminal does not require any special setting as it handles
polarization automatically.

Pin Connection Pin No. RS-485


Signal Name Direction Meaning
1 NC – –
2 NC – –
3 NC – –
4 Line A Input/Output Transfer Data (RS-485)
5 Line B Input/Output Transfer Data (RS-485)
6 RS(RTS) Output Request to Send
7 NC – –
8 SG – Signal Ground

CAUTION
LOSS OF COMMUNICATION
 All connections to the communication ports must not put excessive stress on the ports.
 Securely attach communication cables to the panel wall or cabinet.
 Use only RJ45 with a locking tab in good condition.
Failure to follow these instructions can result in injury or equipment damage.

EIO0000001133 11/2019 45
Specifications

Dimensions

External Dimensions

1 Front
2 Right side
3 Top
4 Display area center
5 Product center

Installation with Installation Fasteners

1 Front
2 Right side
3 Top
4 Display area center
5 Product center

46 EIO0000001133 11/2019
Specifications

Dimensions with Cables: HMIGTO1300

1 Rear
2 Right side

NOTE: All the above values are designed with cable bending in mind. The dimensions given here are
representative values depending on the type of connection cable in use. Therefore, these values are
intended for reference only.

Dimensions with Cables: HMIGTO1310

1 Rear
2 Right side

NOTE: All the above values are designed with cable bending in mind. The dimensions given here are
representative values depending on the type of connection cable in use. Therefore, these values are
intended for reference only.

EIO0000001133 11/2019 47
Specifications

Panel Cut Dimensions


Create a panel cut and insert the panel into the opening from the front.

A B C R
118.5 mm (+1, -0 mm) 92.5 mm (+1, -0 mm) 1.6...5 mm 3 mm (0.12 in)
(4.67 in (+0.04, -0 in)) (3.64 in (+0.04, -0 in)) (0.06...0.2 in) maximum

NOTE: Before designing the panel cut, refer to Installation.

Installation Fastener Dimensions

48 EIO0000001133 11/2019
Specifications

Section 4.2
HMIGTO2300/2310/2315

HMIGTO2300/2310/2315

What Is in This Section?


This section contains the following topics:
Topic Page
Electrical Specifications 50
Environmental Specifications 51
Structural Specifications 52
Display Specifications 54
Memory, Clock, and Touch Panel 55
Interface Specifications 56
Specifications of Serial Interface COM1 57
Specifications of Serial Interface COM2 59
Dimensions 60

EIO0000001133 11/2019 49
Specifications

Electrical Specifications

Rated Input Voltage 24 Vdc


Input Voltage Limits 19.2...28.8 Vdc
Voltage Drop 5 ms or less
Power Consumption 10.5 W or less
When power is not supplied to 6.5 W or less
external devices
Power Supply

Backlight OFF (Standby Mode) 4.5 W or less


Backlight Dimmed (Brightness: 20%) 5 W or less
In-Rush Current 30 A or less
Voltage Endurance 1,000 Vac, 20 mA for 1 minute (between charging
and FG terminals)
Insulation Resistance 500 Vdc, 10 MΩ or more (between charging and
FG terminals)

50 EIO0000001133 11/2019
Specifications

Environmental Specifications

HMIGTO2310 / HMIGTO2315 HMIGTO2300


Surrounding Air 0...55 °C (32 °F...131 °F) 0...50 °C (32...122 °F)
Temperature
Storage Temperature -20...60 °C (-4...140 °F)
Surrounding Air and 10...90% RH (non-condensing, wet bulb temperature 39 °C (102.2 °F) or
Storage Humidity less)
Electrical Environment Mechanical Environment Physical Environment

Dust 0.1 mg/m3 (10-7 oz/ft3) or less (non-conductive levels)


Pollution Degree For use in Pollution Degree 2 environment
Corrosive Gases Free of corrosive gases
Atmospheric Pressure 800...1,114 hPa (2,000 m [6,561 ft] or lower)
(Operating Altitude)
Vibration Resistance IEC/EN 61131-2 compliant
5...9 Hz Single amplitude 3.5 mm (0.14 in.)
9...150 Hz Fixed acceleration: 9.8 m/s2
X, Y, Z directions for 10 cycles (approx. 100 min)
Concussion Resistance IEC/EN 61131-2 compliant
147 m/s2, X, Y, Z directions for 3 times

Noise Immunity Noise Voltage: 1,000 Vp-p


Pulse Width: 1 μs
Rise Time: 1 ns
Electrostatic Discharge Contact Discharge Method: 6 kV (IEC/EN 61000-4-2 Level 3)
Immunity

Air Quality Requirements


Do not operate or store the panel where chemicals evaporate, or where chemicals are present in the air:
 Corrosive chemicals: Acids, alkalines, liquids containing salt.
 Flammable chemicals: Organic solvents.

CAUTION
INOPERATIVE EQUIPMENT
Do not allow water, liquids, metal, and wiring fragments to enter the panel case.
Failure to follow these instructions can result in injury or equipment damage.

EIO0000001133 11/2019 51
Specifications

Structural Specifications

HMIGTO2300 / HMIGTO2310 HMIGTO2315


Grounding Functional grounding: Grounding resistance of 100 Ω, 2mm2 (AWG 14) or thicker
wire, or your country's applicable standard. (Same for FG and SG terminals)
Cooling Method Natural air circulation
Structure*1 IP65f NEMA #250 TYPE 4X/13 (on the IP66k NEMA #250 TYPE 4X/13 (on the
front panel when properly installed in an front panel when properly installed in an
enclosure) enclosure)*2
External Dimensions W 169.5 x H 137 x D 59.5 mm (W 6.67 x W 213.5 x H 181 x D 59.5 mm (W 8.41 x
H 5.39 x D 2.34 in) H 7.13 x D 2.34 in)
Panel Cut Dimensions W 156 x H 123.5 mm (W 6.14 x W 195 x H 162.5 mm (W 7.68 x
H 4.86 in) *3 H 6.40 in) *3
Panel thickness area: 1.6...5 mm Panel thickness area: 1.6...5 mm
(0.06...0.2 in) *4 (0.06...0.2 in) *4
Weight 0.8 kg (1.8 lbs) or less (main unit only) 1.2 kg (2.6 lbs) or less (main unit only)

NOTE: *1 The front face of the HMIGTO, installed in a solid panel, has been tested using conditions
equivalent to the standards shown in the specification. Even though the HMIGTO's level of resistance is
equivalent to these standards, oils that should have no effect on the HMIGTO can possibly harm the panel.
This can occur in areas where either vaporized oils are present, or where low viscosity cutting oils are
allowed to adhere to the panel for long periods of time. If the panel's front face protection sheet peels off,
these conditions can lead to the ingress of oil into the panel and separate protection measures are
suggested.
Also, if non-approved oils are present, they may cause deformation or corrosion of the front panel’s plastic
cover. Therefore, prior to installing the panel, be sure to confirm the type of conditions that will be present
in the panel’s operating environment. If the installation gasket is used for a long period of time, or if the
panel and its gasket are removed from the panel, the original level of protection cannot be kept. To
maintain the original protection level, be sure to replace the installation gasket regularly.
*2 When installing the HMIGTO in a panel, you may not be able to mount the HMIGTO flush with the panel.

This occurs due to the thickness of the gasket. The difference in level between the HMIGTO and panel
depends on how much the gasket is compressed.
There is a conformal coating on circuit boards for HMIGTO2315

NOTICE
EQUIPMENT DAMAGE
For food and beverage and pharmaceutical industries, when the HMIGTO is not flush with panel, use
silicon to form a seal to prevent water, chemicals, or food from lodging into place. Otherwise, the panel
face could leak.
Failure to follow these instructions can result in equipment damage.

*3
For dimensional tolerance, everything +1/-0 mm (+0.04/-0 in) and R in angle are below R3 (R0.12 in).
*4Even if the installation wall thickness is within the recommended range for the “Panel Cut Dimensions”,
depending on wall's material, size, and installation location of the panel and other devices, the installation
wall could warp. To prevent warping, the installation surface may need to be strengthened.

CAUTION
EQUIPMENT DAMAGE
Ensure that the panel is not in permanent and direct contact with oils.
Failure to follow these instructions can result in injury or equipment damage.

52 EIO0000001133 11/2019
Specifications

NOTICE
STORAGE AND OPERATION OUTSIDE OF SPECIFICATIONS
 Store this product in areas where temperatures are within the product’s specifications.
 Do not restrict or block this product’s ventilation slots.
Failure to follow these instructions can result in equipment damage.

NOTICE
GASKET AGING
 Inspect the gasket periodically as required by your operating environment to keep the initial IP level.
 Change the gasket at least once a year, or as soon as scratches or dirt become visible.
Failure to follow these instructions can result in equipment damage.

EIO0000001133 11/2019 53
Specifications

Display Specifications

Display Type TFT Color LCD


Display Size 5.7”
Resolution (pixels) 320 x 240 pixels (QVGA)
Effective Display Area W 115.2 x H 86.4 mm (W 4.54 x H 3.40 in.)
Display Colors 65,536 colors (no blink) / 16,384 colors (blink)
Backlight White LED (not user replaceable). When replacement is required, contact your
local distributor.
Backlight Service Life 50,000 hours or more (continuous operation at 25 °C (77 °F) before backlight
decreases to 50%)
Brightness Control 16 levels (Adjusted with touch panel or software)
Language Fonts ASCII: (Code page 850) Alphanumeric (including European characters)
Chinese: (GB2312-80 codes) Simplified Chinese fonts
Japanese (except for XBT GT1000 series): ANK 158, Kanji: 6,962 (JIS
Standards 1 & 2) (including 607 non-kanji characters)
Korean: (KSC5601 - 1992 codes) Hangul fonts
Taiwanese: (Big 5 codes) Traditional Chinese fonts
Character Sizes 8 x 8, 8 x 16, 16 x 16 and 32 x 32 pixel fonts
Font Sizes You can expand the width up to 8 times, and expand the height up to 8 times.*1
Text 8 x 8 pixels 40 characters per row x 30 rows
8 x 16 pixels 40 characters per row x 15 rows
16 x 16 pixels 20 characters per row x 15 rows
32 x 32 pixels 10 characters per row x 7 rows

*1
You can set up other font sizes using the software.

54 EIO0000001133 11/2019
Specifications

Memory, Clock, and Touch Panel

Introduction
NOTE:
 When the message indicating that the battery level is low is displayed, on the HMIGTO2300, supply
power to the panel and fully charge the battery. In 24 hours the battery charges to a level that allows
backup operation. Completing a full charge requires about 120 hours (five days).
 The lithium battery's lifetime is: 10 years when the battery's ambient temperature is 40 °C (104 °F) or
less, 4.1 years when the battery's ambient temperature is 50 °C (122 °F) or less, and 1.5 years when
the battery's ambient temperature is 60 °C (140 °F) or less.
When used for backup:
 Approximately 100 days with a fully charged battery.
 Approximately 6 days with a half-charged battery.

 When the message indicating that the battery level is low is displayed on HMIGTO2310/2315, replace
the battery (see page 136).

Memory

HMIGTO2310 / HMIGTO2315 HMIGTO2300


Application Memory *1 FLASH EPROM 96 MB FLASH EPROM 64 MB

Application run DRAM 128 MB 128 MB


Data Backup SRAM 512 KB (Replaceable lithium SRAM 128 KB (Rechargeable lithium
battery for data backup) battery for data backup)

*1
Capacity available for user application.

Clock

Clock Accuracy*1 ±65 seconds/month (deviation at room temperature and power is OFF).

*1
Depending on the operating temperature and age of panel, the clock can deviate from -380 to +90
sec/month. For systems where this level of precision is insufficient, the user should monitor and make
adjustments when required.

Touch Panel

Touch Panel Type Resistive Film (analog)


Touch Panel Resolution 1,024 x 1,024
Touch Panel Service Life 1 million times or more

EIO0000001133 11/2019 55
Specifications

Interface Specifications

Serial Interface COM1

Asynchronous Transmission RS-232C


Data Length 7 or 8 bits
Stop Bit 1 or 2 bits
Parity None, odd or even
Data Transmission Speed 2,400...115,200 bps
Connector D-Sub 9-pin (plug)

Serial Interface COM2

Asynchronous Transmission RS-485


Data Length 7 bits or 8 bits
Stop Bit 1 bit or 2 bits
Parity None, odd or even
Data Transmission Speed 2,400...115,200 bps, 187,500 bps (MPI)
Connector Modular jack (RJ45)

USB Interface

USB (Type A) Interface USB (mini-B) Interface


Connector USB 2.0 (Type A) x 1 USB 2.0 (mini-B) x 1
Power Supply Voltage 5 Vdc ±5% -
Maximum Current Supplied 500 mA -
Maximum Transmission Distance 5 m (16.4 ft)

Ethernet Interface

HMIGTO2310 / HMIGTO2315
Ethernet (LAN) IEEE802.3i / IEEE802.3u, 10BASE-T/100BASE-TX
Connector Modular jack (RJ45) x 1

SD Card Interface
HMIGTO2310/HMIGTO2315: SD card slot x 1 (maximum 32 GB SD/SDHC Card)
NOTE: HMIGTO2300 does not have a SD card interface.

56 EIO0000001133 11/2019
Specifications

Specifications of Serial Interface COM1

Introduction
NOTE: For information on how to connect controllers and other types of equipment, refer to the
corresponding device driver manual of your screen editing software.

CAUTION
LOSS OF COMMUNICATION
 All connections to the communication ports must not put excessive stress on the ports.
 Securely attach communication cables to the panel or cabinet.
 Use only D-Sub 9-pin cables with a locking system in good condition.
Failure to follow these instructions can result in injury or equipment damage.

The serial port is not isolated. The SG (signal ground) and FG (frame ground) terminals are connected
inside the panel.

DANGER
ELECTRIC SHOCK
When using the SG terminal to connect an external device to the panel:
 Verify that a short-circuit loop is not created when you set up the system.
 Connect the #5 SG terminal to remote equipment when the host (PLC) unit is not isolated. Connect
the #5 SG terminal to a known reliable ground connection to reduce the risk of damaging the circuit.
Failure to follow these instructions will result in death or serious injury.

Serial Interface COM1


HMIGTO2300 / HMIGTO2310/ HMIGTO2315: D-Sub 9-pin plug connector via a RS-232C cable.

Pin Connection Pin No. RS-232C


Signal Name Direction Meaning
1 CD Input Carrier Detect
2 RD(RXD) Input Receive Data
3 SD(TXD) Output Send Data
4 ER(DTR) Output Data Terminal Ready
5 SG - Signal Ground
6 DR(DSR) Input Data Set Ready
7 RS(RTS) Output Request to Send
8 CS(CTS) Input Send possible
9 CI(RI)/VCC Input– Called Status Display
+5 V±5% Output 0.25 A*1
Shell FG – Frame Ground (Common with
SG)

NOTE: *1 You can switch pin number 9 between RI and VCC via software.

NOTICE
EQUIPMENT DAMAGE
Use only the rated current.
Failure to follow these instructions can result in equipment damage.

EIO0000001133 11/2019 57
Specifications

CAUTION
LOSS OF COMMUNICATION
 All connections to the communication ports must not put excessive stress on the ports.
 Securely attach communication cables to the panel wall or cabinet.
 Use only D-Sub 9 pin cables with a locking tab in good condition.
Failure to follow these instructions can result in injury or equipment damage.

58 EIO0000001133 11/2019
Specifications

Specifications of Serial Interface COM2

Introduction
NOTE: For information on how to connect controllers and other types of equipment, refer to the
corresponding device driver manual of your screen editing software.
The serial port is not isolated. The SG (signal ground) and FG (frame ground) terminals are connected
inside the panel.

DANGER
ELECTRIC SHOCK
When using the SG terminal to connect an external device to the panel:
 Verify that a short-circuit loop is not created when you set up the system.
 Connect the #8 SG terminal to remote equipment when the host (PLC) unit is not isolated. Connect
the #8 SG terminal to a known reliable ground connection to reduce the risk of damaging the circuit.
Failure to follow these instructions will result in death or serious injury.

Serial Interface COM2


HMIGTO2300 / HMIGTO2310 / HMIGTO2315: RJ45 connector via a RS-485 cable.
NOTE: When setting up RS-485 communication, the cable diagram for some equipment may require
polarization on the terminal side. This terminal does not require any special setting as it handles
polarization automatically.

Pin Connection Pin No. RS-485


Signal Name Direction Meaning
1 NC - -
2 NC - -
3 NC - -
4 Line A Input/Output Transfer Data (RS-485)
5 Line B Input/Output Transfer Data (RS-485)
6 RS(RTS) Output Request To Send
7 NC - -
8 SG - Signal Ground

CAUTION
LOSS OF COMMUNICATION
 All connections to the communication ports must not put excessive stress on the ports.
 Securely attach communication cables to the panel wall or cabinet.
 Use only RJ45 with a locking tab in good condition.
Failure to follow these instructions can result in injury or equipment damage.

EIO0000001133 11/2019 59
Specifications

Dimensions

External Dimensions: HMIGTO2300 / HMIGTO2310

1 Front
2 Right side
3 Top

External Dimensions: HMIGTO2315

1 Front
2 Right side
3 Top

60 EIO0000001133 11/2019
Specifications

Installation with Installation Fasteners: HMIGTO2300 / HMIGTO2310

1 Front
2 Right side
3 Top
4 Bottom

Installation with Installation Fasteners: HMIGTO2315

1 Front
2 Right side
3 Top

EIO0000001133 11/2019 61
Specifications

Dimensions with Cables: HMIGTO2300

NOTE: All the above values are designed with cable bending in mind. The dimensions given here are
representative values depending on the type of connection cable in use. Therefore, these values are
intended for reference only.

Dimensions with Cables: HMIGTO2310

NOTE: All the above values are designed with cable bending in mind. The dimensions given here are
representative values depending on the type of connection cable in use. Therefore, these values are
intended for reference only.

Dimensions with Cables: HMIGTO2315

NOTE: All the above values are designed with cable bending in mind. The dimensions given here are
representative values depending on the type of connection cable in use. Therefore, these values are
intended for reference only.

62 EIO0000001133 11/2019
Specifications

Panel Cut Dimensions


Create a panel cut and insert the panel into the opening from the front.

A B C R
HMIGTO2310 156 mm (+1/-0) mm 123.5 mm (+1, -0 mm) 1.6...5 mm 3 mm (0.12 in)
HMIGTO2300 (6.14 in (+0.04, -0 in)) (4.86 in (+0.04, -0 in)) (0.06...0.2 in) maximum
HMIGTO2315 195 mm (+1/-0) mm 162.5 mm (+1/-0) mm
(7.68 in (+0.04, -0 in)) (6.40 in (+0.04, -0 in))

NOTE: Before designing the panel cut, refer to Installation.

Installation Fastener Dimensions

EIO0000001133 11/2019 63
Specifications

Section 4.3
HMIGTO3510/4310

HMIGTO3510/4310

What Is in This Section?


This section contains the following topics:
Topic Page
Electrical Specifications 65
Environmental Specifications 66
Structural Specifications 67
Display Specifications 68
Memory, Clock, Touch Panel, and Function Switches 69
Interface Specifications 70
Specifications of Serial Interface COM1 71
Specifications of Serial Interface COM2 73
Dimensions 74

64 EIO0000001133 11/2019
Specifications

Electrical Specifications

Rated Input Voltage 24 Vdc


Input Voltage Limits 19.2...28.8 Vdc
Voltage Drop 5 ms or less
Power Consumption 12 W or less
When power is not supplied to 8 W or less
external devices
Power Supply

Backlight OFF (Standby Mode) 5 W or less


Backlight Dimmed (Brightness: 20%) 5.5 W or less
In-Rush Current 30 A or less
Voltage Endurance 1,000 Vac, 20 mA for 1 minute (between charging
and FG terminals)
Insulation Resistance 500 Vdc, 10 MΩ or more (between charging and
FG terminals)

EIO0000001133 11/2019 65
Specifications

Environmental Specifications

HMIGTO4310 HMIGTO3510
Surrounding Air 0...55 °C (32...131 °F) 0...50 °C (32...122 °F)
Temperature
Storage Temperature -20...60 °C (-4...140 °F)
Surrounding Air and 10...90% RH (non-condensing, wet bulb temperature 39 °C (102.2 °F) or
Storage Humidity less)
Electrical Environment Mechanical Environment Physical Environment

Dust 0.1 mg/m3 (10-7 oz/ft3) or less (non-conductive levels)


Pollution Degree For use in Pollution Degree 2 environment
Corrosive Gases Free of corrosive gases
Atmospheric pressure 800...1,114 hPa (2,000 m [6,561 ft] or lower)
(Operating Altitude)
Vibration Resistance IEC/EN 61131-2
5...9 Hz Single amplitude 3.5 mm (0.14 in.)
9...150 Hz Fixed acceleration: 9.8 m/s2
X, Y, Z directions for 10 cycles (approx. 100 min)
Concussion Resistance IEC/EN 61131-2 compliant
147 m/s2, X, Y, Z directions for 3 times

Noise Immunity Noise Voltage: 1,000 Vp-p


Pulse Width: 1 μs
Rise Time: 1 ns
Electrostatic Discharge Contact Discharge Method: 6 kV (IEC/EN 61000-4-2 Level 3)
Immunity

Air Quality Requirements


Do not operate or store the panel where chemicals evaporate, or where chemicals are present in the air:
 Corrosive chemicals: Acids, alkalines, liquids containing salt.
 Flammable chemicals: Organic solvents.

CAUTION
INOPERATIVE EQUIPMENT
Do not allow water, liquids, metal, and wiring fragments to enter the panel case.
Failure to follow these instructions can result in injury or equipment damage.

66 EIO0000001133 11/2019
Specifications

Structural Specifications

Grounding Functional grounding: Grounding resistance of 100 Ω, 2 mm2


(AWG 14) or thicker wire, or your country's applicable standard. (Same
for FG and SG terminals)
Cooling Method Natural air circulation
Structure *1 IP65f NEMA #250 TYPE 4X/13 (on the front panel when properly
installed in an enclosure)
External Dimensions W 218 x H 173 x D 60 mm (W 8.58 x H 6.81 x D 2.36 in)
Panel Cut Dimensions W 204.5 x H 159.5 mm (W 8.05 x H 6.28 in)*2
Panel thickness area: 1.6...5 mm (0.06...0.2 in)*3
Weight 1.2 kg (2.6 lb) or less (main unit only)

NOTE: *1 The front face of the HMIGTO, installed in a solid panel, has been tested using conditions
equivalent to the standards shown in the specification. Even though the HMIGTO's level of resistance is
equivalent to these standards, oils that should have no effect on the HMIGTO can possibly harm the panel.
This can occur in areas where either vaporized oils are present, or where low viscosity cutting oils are
allowed to adhere to the panel for long periods of time. If the panel's front face protection sheet peels off,
these conditions can lead to the ingress of oil into the panel and separate protection measures are
suggested.
Also, if non-approved oils are present, they may cause deformation or corrosion of the front panel’s plastic
cover. Therefore, prior to installing the HMIGTO, be sure to confirm the type of conditions that will be
present in the panel’s operating environment. If the installation gasket is used for a long period of time, or
if the HMIGTO and its gasket are removed from the panel, the original level of protection cannot be kept.
To maintain the original protection level, be sure to replace the installation gasket regularly.
*2 For dimensional tolerance, everything +1/-0 mm (+0.04/-0 in) and R in angle are below R3 (R0.12 in)
*3 Even if the installation wall thickness is within the recommended range for the “Panel Cut Dimensions”,

depending on wall’s material, size, and installation location of the panel and other devices, the installation
wall could warp. To prevent warping, the installation surface may need to be strengthened.

CAUTION
EQUIPMENT DAMAGE
Ensure that the panel is not in permanent and direct contact with oils.
Failure to follow these instructions can result in injury or equipment damage.

NOTICE
STORAGE AND OPERATION OUTSIDE OF SPECIFICATIONS
 Store this product in areas where temperatures are within the product’s specifications.
 Do not restrict or block this product’s ventilation slots.
Failure to follow these instructions can result in equipment damage.

NOTICE
GASKET AGING
 Inspect the gasket periodically as required by your operating environment to keep the initial IP level.
 Change the gasket at least once a year, or as soon as scratches or dirt become visible.
Failure to follow these instructions can result in equipment damage.

EIO0000001133 11/2019 67
Specifications

Display Specifications

HMIGTO4310 HMIGTO3510
Display Type TFT Color LCD
Display Size 7.5” 7.0”
Resolution 640 x 480 pixels (VGA) 800 x 480 pixels (WVGA)
Effective Display Area W 153.7 x H 115.8 mm W 152.4 x H 91.44 mm
(W 6.05 x H 4.56 in.) (W 6.0 x H 3.6 in.)
Display Colors 65,536 colors (no blink) / 16,384 colors (blink)
Backlight White LED (not user replaceable). When replacement is required, contact your
local distributor.
Backlight Service Life 50,000 hours or more (continuous operation at 25 °C (77 °F) before backlight
brightness decreases to 50%)
Brightness Control 16 levels (Adjusted with touch panel or software)
Language Fonts ASCII: (Code page 850) Alphanumeric (including European characters)
Chinese: (GB2312-80 codes) Simplified Chinese fonts
Japanese (except for XBT GT1000 series): ANK 158, Kanji: 6,962 (JIS
Standards 1 & 2) (including 607 non-kanji characters)
Korean: (KSC5601 - 1992 codes) Hangul fonts
Taiwanese: (Big 5 codes) Traditional Chinese fonts
Character Sizes 8 x 8, 8 x 16, 16 x 16 and 32 x 32 pixel fonts
Font Sizes You can expand the width up to 8 times, and expand the height up to 8 times.*1
Text 8 x 8 pixels 80 characters per row x 60 rows 100 characters per row x 60 rows
8 x 16 pixels 80 characters per row x 30 rows 100 characters per row x 30 rows
16 x 16 pixels 40 characters per row x 30 rows 50 characters per row x 30 rows
32 x 32 pixels 20 characters per row x 15 rows 25 characters per row x 15 rows

*1
You can set up other font sizes using the software.

68 EIO0000001133 11/2019
Specifications

Memory, Clock, Touch Panel, and Function Switches

Memory

HMIGTO4310 HMIGTO3510
Application Memory *1 FLASH EPROM 96 MB FLASH EPROM 96 MB
Application run DRAM 128 MB 128 MB
Data Backup SRAM 512 KB (Replaceable lithium SRAM 128 KB (Replaceable lithium
battery for data backup) battery for data backup)

*1 Capacity available for user application.


NOTE: When the message indicating that the battery level is low is displayed, replace the battery
(see page 136).

Clock

Clock Accuracy*1 ±65 seconds/month (deviation at room temperature and power is OFF).

*1 Depending on the operating temperature and age of panel, the clock can deviate from -380 to +90
sec/month. For systems where this level of precision is insufficient, the user should monitor and make
adjustments when required.

Touch Panel

Touch Panel Type Resistive Film (analog)


Touch Panel Resolution 1,024 x 1,024
Touch Panel Service Life 1 million times or more

Function Switches
HMIGTO3510: Eight switches (F1 to F8).

EIO0000001133 11/2019 69
Specifications

Interface Specifications

Serial Interface COM1

Asynchronous Transmission RS-232C


Data Length 7 bits or 8 bits
Stop Bit 1 bit or 2 bits
Parity None, odd or even
Data Transmission Speed 2,400...115,200 bps
Connector D-Sub 9-pin (plug)

Serial Interface COM2

Asynchronous Transmission RS-485


Data Length 7 bits or 8 bits
Stop Bit 1 bit or 2 bits
Parity None, odd or even
Data Transmission Speed 2,400...115,200 bps, 187,500 bps (MPI)
Connector Modular jack (RJ45)

USB Interface

USB (Type A) Interface USB (mini-B) Interface


Connector USB 2.0 (Type A) x 1 USB 2.0 (mini-B) x 1
Power Supply Voltage 5 Vdc ±5% -
Maximum Current Supplied 500 mA -
Maximum Transmission Distance 5 m (16.4 ft)

Ethernet Interface

Ethernet (LAN) IEEE802.3i / IEEE802.3u, 10BASE-T/100BASE-TX


Connector Modular jack (RJ45) x 1

SD Card Interface
SD card slot x 1 (maximum 32 GB SD/SDHC card)

70 EIO0000001133 11/2019
Specifications

Specifications of Serial Interface COM1

Introduction
NOTE: For information on how to connect controllers and other types of equipment, refer to the
corresponding device driver manual of your screen editing software.

CAUTION
LOSS OF COMMUNICATION
 All connections to the communication ports must not put excessive stress on the ports.
 Securely attach communication cables to the panel or cabinet.
 Use only D-Sub 9-pin cables with a locking system in good condition.
Failure to follow these instructions can result in injury or equipment damage.

The serial port is not isolated. The SG (signal ground) and FG (frame ground) terminals are connected
inside the panel.

DANGER
ELECTRIC SHOCK
When using the SG terminal to connect an external device to the panel:
 Verify that a short-circuit loop is not created when you set up the system.
 Connect the #5 SG terminal to remote equipment when the host (PLC) unit is not isolated. Connect
the #5 SG terminal to a known reliable ground connection to reduce the risk of damaging the circuit.
Failure to follow these instructions will result in death or serious injury.

Serial Interface COM1


HMIGTO3510 / HMIGTO4310: D-Sub 9-pin plug connector via a RS-232C cable.

Pin Connection Pin No. RS-232C


Signal Name Direction Meaning
1 CD Input Carrier Detect
2 RD(RXD) Input Receive Data
3 SD(TXD) Output Send Data
4 ER(DTR) Output Data Terminal Ready
5 SG - Signal Ground
6 DR(DSR) Input Data Set Ready
7 RS(RTS) Output Request to Send
8 CS(CTS) Input Send possible
9 CI(RI)/VCC Input– Called Status Display
+5 V±5% Output 0.25 A*1
Shell FG – Frame Ground (Common with
SG)

NOTE: *1 You can switch pin number 9 between RI and VCC via software.

NOTICE
EQUIPMENT DAMAGE
Use only the rated current.
Failure to follow these instructions can result in equipment damage.

EIO0000001133 11/2019 71
Specifications

CAUTION
LOSS OF COMMUNICATION
 All connections to the communication ports must not put excessive stress on the ports.
 Securely attach communication cables to the panel wall or cabinet.
 Use only D-Sub 9 pin cables with a locking tab in good condition.
Failure to follow these instructions can result in injury or equipment damage.

72 EIO0000001133 11/2019
Specifications

Specifications of Serial Interface COM2

Introduction
NOTE: For information on how to connect controllers and other types of equipment, refer to the
corresponding device driver manual of your screen editing software.
The serial port is not isolated. The SG (signal ground) and FG (frame ground) terminals are connected
inside the panel.

DANGER
ELECTRIC SHOCK
When using the SG terminal to connect an external device to the panel:
 Verify that a short-circuit loop is not created when you set up the system.
 Connect the #8 SG terminal to remote equipment when the host (PLC) unit is not isolated. Connect
the #8 SG terminal to a known reliable ground connection to reduce the risk of damaging the circuit.
Failure to follow these instructions will result in death or serious injury.

Serial Interface COM2


HMIGTO3510 / HMIGTO4310: RJ45 connector via an RS-485 cable.
NOTE: When setting up RS-485 communication, the cable diagram for some equipment may require
polarization on the terminal side. This terminal does not require any special setting as it handles
polarization automatically.

Pin Connection Pin No. RS-485


Signal Name Direction Meaning
1 NC - -
2 NC - -
3 NC - -
4 Line A Input/Output Transfer Data (RS-485)
5 Line B Input/Output Transfer Data (RS-485)
6 RS(RTS) Output Request To Send
7 NC - -
8 SG - Signal Ground

CAUTION
LOSS OF COMMUNICATION
 All connections to the communication ports must not put excessive stress on the ports.
 Securely attach communication cables to the panel wall or cabinet.
 Use only RJ45 with a locking tab in good condition.
Failure to follow these instructions can result in injury or equipment damage.

EIO0000001133 11/2019 73
Specifications

Dimensions

External Dimensions: HMIGTO3510

1 Front
2 Right side
3 Top

External Dimensions: HMIGTO4310

1 Front
2 Right side
3 Top

74 EIO0000001133 11/2019
Specifications

Installation with Installation Fasteners: HMIGTO3510

1 Front
2 Right side
3 Top

Installation with Installation Fasteners: HMIGTO4310

1 Front
2 Right side
3 Top

EIO0000001133 11/2019 75
Specifications

Dimensions with Cables: HMIGTO3510

NOTE: All the above values are designed with cable bending in mind. The dimensions given here are
representative values depending on the type of connection cable in use. Therefore, these values are
intended for reference only.

Dimensions with Cables: HMIGTO4310

NOTE: All the above values are designed with cable bending in mind. The dimensions given here are
representative values depending on the type of connection cable in use. Therefore, these values are
intended for reference only.

Panel Cut Dimensions


Create a panel cut and insert the panel into the opening from the front.

A B C R
204.5 mm (+1, -0 mm) 159.5 mm (+1, -0 mm) 1.6...5 mm 3 mm (0.12 in)
(8.05 in (+0.04, -0 in)) (6.28 in (+0.04, -0 in)) (0.06...0.2 in) maximum

NOTE: Before designing the panel cut, refer to Installation.

76 EIO0000001133 11/2019
Specifications

Installation Fastener Dimensions

EIO0000001133 11/2019 77
Specifications

Section 4.4
HMIGTO5310/5315

HMIGTO5310/5315

What Is in This Section?


This section contains the following topics:
Topic Page
Electrical Specifications 79
Environmental Specifications 80
Structural Specifications 81
Display Specifications 83
Memory, Clock, and Touch Panel 84
Interface Specifications 85
Specifications of Serial Interface COM1 86
Specifications of Serial Interface COM2 88
Dimensions 89

78 EIO0000001133 11/2019
Specifications

Electrical Specifications

Rated Input Voltage 24 Vdc


Input Voltage Limits 19.2...28.8 Vdc
Voltage Drop 10 ms or less
Power Consumption 17 W or less
When power is not supplied to 12 W or less
external devices
Power Supply

Backlight OFF (Standby Mode) 7 W or less


Backlight Dimmed (Brightness: 20%) 8 W or less
In-Rush Current 30 A or less
Voltage Endurance 1500 Vac, 20 mA for 1 min. (between charging
and FG terminals)
Insulation Resistance 500 Vdc, 10 MΩ or more (between charging and
FG terminals)

EIO0000001133 11/2019 79
Specifications

Environmental Specifications

Surrounding Air Temperature 0...55 °C (32...131 °F)


Storage Temperature -20...60 °C (-4...140 °F)
Surrounding Air and Storage 10...90% RH (non-condensing, wet bulb temperature 39 °C
Humidity (102.2 °F) or less)
Electrical Environment Mechanical Environment Physical Environment

Dust 0.1 mg/m3 (10-7 oz/ft3) or less (non-conductive levels)


Pollution Degree For use in Pollution Degree 2 environment
Corrosive Gases Free of corrosive gases
Atmospheric Pressure 800...1,114 hPa (2,000 m [6,561 ft] or lower)
(Operating Altitude)
Vibration Resistance IEC/EN 61131-2 compliant
5...9 Hz Single amplitude 3.5 mm (0.14 in.)
9...150 Hz Fixed acceleration: 9.8 m/s2
X, Y, Z directions for 10 cycles (approx. 100 min.)
Concussion Resistance IEC/EN 61131-2 compliant
147 m/s2, X, Y, Z directions for 3 times

Noise Immunity Noise Voltage: 1,000 Vp-p


Pulse Width: 1 μs
Rise Time: 1 ns
Electrostatic Discharge Contact Discharge Method: 6 kV (IEC/EN 61000-4-2 Level 3)
Immunity

Air Quality Requirements


Do not operate or store the panel where chemicals evaporate, or where chemicals are present in the air:
 Corrosive chemicals: Acids, alkalines, liquids containing salt.
 Flammable chemicals: Organic solvents.

CAUTION
INOPERATIVE EQUIPMENT
Do not allow water, liquids, metal, and wiring fragments to enter the panel case.
Failure to follow these instructions can result in injury or equipment damage.

80 EIO0000001133 11/2019
Specifications

Structural Specifications

HMIGTO5310 HMIGTO5315
Grounding Functional grounding: Grounding resistance of 100 Ω, 2 mm2
(AWG 14) or thicker wire, or your country's applicable standard. (Same
for FG and SG terminals)
Cooling Method Natural air circulation
Structure*1 IP65f NEMA #250 TYPE 4X/13 (on IP66k NEMA #250 TYPE 4X/13
the front panel when properly (on the front panel when properly
installed in an enclosure) installed in an enclosure)*2
External Dimensions W 272.5 x H 214.5 x D 57 mm W 316.5 x H 258.5 x D 57 mm
(W 10.73 x H 8.44 x D 2.24 in) (W 12.44 x H 10.18 x D 2.24 in)
Panel Cut Dimensions W 259 x H 201 mm (W 10.2 x W 298 x H 240 mm (W 11.73 x
H 7.91 in)*3 H 9.45 in)*3
Panel thickness area: 1.6...5 mm Panel thickness area: 1.6...5 mm
(0.06...0.2 in)*4 (0.06...0.2 in)*4
Weight 2.0 kg (4.4 lb) or less (main unit 2.5 kg (5.5 lb) or less (main unit
only) only)

NOTE: *1 The front face of the HMIGTO, installed in a solid panel, has been tested using conditions
equivalent to the standards shown in the specification. Even though the HMIGTO's level of resistance is
equivalent to these standards, oils that should have no effect on the HMIGTO can possibly harm the panel.
This can occur in areas where either vaporized oils are present, or where low viscosity cutting oils are
allowed to adhere to the panel for long periods of time. If the panel's front face protection sheet peels off,
these conditions can lead to the ingress of oil into the panel and separate protection measures are
suggested.
Also, if non-approved oils are present, they may cause deformation or corrosion of the front panel's plastic
cover. Therefore, prior to installing the HMIGTO, be sure to confirm the type of conditions that will be
present in the panel' operating environment. If the installation gasket is used for a long period of time, or if
the HMIGTO and its gasket are removed from the panel, the original level of protection cannot be kept. To
maintain the original protection level, be sure to replace the installation gasket regularly.
*2 When installing the HMIGTO in a panel, you may not be able to mount the HMIGTO flush with the panel.

This occurs due to the thickness of the gasket. The difference in level between the HMIGTO and panel
depends on how much the gasket is compressed.
There is a conformal coating on circuit boards for HMIGTO5315.

NOTICE
EQUIPMENT DAMAGE
For food and beverage and pharmaceutical industries, when the HMIGTO is not flush with panel, use
silicon to form a seal to prevent water, chemicals, or food from lodging into place. Otherwise, the panel
face could leak.
Failure to follow these instructions can result in equipment damage.

*3
For dimensional tolerance, everything +1/-0 mm (+0.04/-0 in), and R in angle are below R3 (R0.12 in)
*4Even if the installation wall thickness is within the recommended range for the “Panel Cut Dimensions”,
depending on wall’s material, size, and installation location of the panel and other devices, the installation
wall could warp. To prevent warping, the installation surface may need to be strengthened.

CAUTION
EQUIPMENT DAMAGE
Ensure that the panel is not in permanent and direct contact with oils.
Failure to follow these instructions can result in injury or equipment damage.

EIO0000001133 11/2019 81
Specifications

NOTICE
STORAGE AND OPERATION OUTSIDE OF SPECIFICATIONS
 Store this product in areas where temperatures are within the product’s specifications.
 Do not restrict or block this product’s ventilation slots.
Failure to follow these instructions can result in equipment damage.

NOTICE
GASKET AGING
 Inspect the gasket periodically as required by your operating environment to keep the initial IP level.
 Change the gasket at least once a year, or as soon as scratches or dirt become visible.
Failure to follow these instructions can result in equipment damage.

82 EIO0000001133 11/2019
Specifications

Display Specifications

Display Type TFT Color LCD


Display Size 10.4”
Resolution 640 x 480 pixels (VGA)
Effective Display Area W 211.2 x H 158.4 mm (8.31 x 6.24 in.)
Display Colors 65,536 colors (no blink) / 16,384 colors (blink)
Backlight White LED (not user replaceable). When replacement is required, contract your
local distributor.
Backlight Service Life 50,000 hours or more (continuous operation at 25 °C (77 °F) before backlight
brightness dimmed to 50%)
Brightness Control 16 levels (Adjusted with the touch panel or software)
Language Fonts ASCII: (Code page 850) Alphanumeric (including European characters)
Chinese: (GB2312-80 codes) Simplified Chinese fonts
Japanese: ANK 158, Kanji: 6,962 (JIS Standards 1 & 2) (including 607 non-
kanji characters)
Korean: (KSC5601 - 1992 codes) Hangul fonts
Taiwanese: (Big 5 codes) Traditional Chinese fonts
Character Sizes 8 x 8, 8 x 16, 16 x 16 and 32 x 32 pixel fonts
Font Sizes You can expand the width up to 8 times, and expand the height up to 8 times.*1
Text 8 x 8 pixels 80 characters per row x 60 rows
8 x 16 pixels 80 characters per row x 30 rows
16 x 16 pixels 40 characters per row x 30 rows
32 x 32 pixels 20 characters per row x 15 rows

*1
You can set up other font sizes using the software.

EIO0000001133 11/2019 83
Specifications

Memory, Clock, and Touch Panel

Memory

Application Memory *1 FLASH EPROM 96 MB


Data Backup SRAM 512 KB (Replaceable lithium battery for data backup)

*1 Capacity available for user application.


NOTE: When the message indicating that the battery level is low is displayed, replace the battery
(see page 136).

Clock

Clock Accuracy*1 ±65 seconds/month (deviation at room temperature and power is OFF).

*1 Depending on the operating temperature and age of panel, the clock can deviate from -380 to +90
sec/month. For systems where this level of precision is insufficient, the user should monitor and make
adjustments when required.

Touch Panel

Touch Panel Type Resistive Film (analog)


Touch Panel Resolution 1,024 x 1,024
Service Life 1 million times or more

84 EIO0000001133 11/2019
Specifications

Interface Specifications

Serial Interface COM1

Asynchronous Transmission RS-232C


Data Length 7 bits or 8 bits
Stop Bit 1 bit or 2 bits
Parity None, odd or even
Data Transmission Speed 2,400...115,200 bps
Connector D-Sub 9-pin (plug)

Serial Interface COM2

Asynchronous Transmission RS-485


Data Length 7 bits or 8 bits
Stop Bit 1 bit or 2 bits
Parity None, odd or even
Data Transmission Speed 2,400...115,200 bps, 187,500 bps (MPI)
Connector Modular jack (RJ45)

USB Interface

USB (Type A) Interface USB (mini-B) Interface


Connector USB 2.0 (Type A) x 1 USB 2.0 (mini-B) x 1
Power Supply Voltage 5 Vdc ±5% -
Maximum Current Supplied 500 mA -
Maximum Transmission Distance 5 m (16.4 ft)

Ethernet Interface

Ethernet (LAN) IEEE802.3i / IEEE802.3u, 10BASE-T/100BASE-TX


Connector Modular jack (RJ45) x 1

SD Card Interface
SD card slot x 1 (maximum 32 GB SD/SDHC card)

EIO0000001133 11/2019 85
Specifications

Specifications of Serial Interface COM1

Introduction
NOTE: For information on how to connect controllers and other types of equipment, refer to the
corresponding device driver manual of your screen editing software.

CAUTION
LOSS OF COMMUNICATION
 All connections to the communication ports must not put excessive stress on the ports.
 Securely attach communication cables to the panel or cabinet.
 Use only D-Sub 9-pin cables with a locking system in good condition.
Failure to follow these instructions can result in injury or equipment damage.

The serial port is not isolated. The SG (signal ground) and FG (frame ground) terminals are connected
inside the panel.

DANGER
ELECTRIC SHOCK
When using the SG terminal to connect an external device to the panel:
 Verify that a short-circuit loop is not created when you set up the system.
 Connect the #5 SG terminal to remote equipment when the host (PLC) unit is not isolated. Connect
the #5 SG terminal to a known reliable ground connection to reduce the risk of damaging the circuit.
Failure to follow these instructions will result in death or serious injury.

Serial Interface COM1


HMIGTO5310 / HMIGTO5315: D-Sub 9-pin plug connector via a RS-232C cable.

Pin Connection Pin No. RS-232C


Signal Name Direction Meaning
1 CD Input Carrier Detect
2 RD(RXD) Input Receive Data
3 SD(TXD) Output Send Data
4 ER(DTR) Output Data Terminal Ready
5 SG - Signal Ground
6 DR(DSR) Input Data Set Ready
7 RS(RTS) Output Request to Send
8 CS(CTS) Input Send possible
9 CI(RI)/VCC Input– Called Status Display
+5 V±5% Output 0.25 A*1
Shell FG – Frame Ground (Common with
SG)

NOTE: *1 You can switch pin number 9 between RI and VCC via software.

NOTICE
EQUIPMENT DAMAGE
Use only the rated current.
Failure to follow these instructions can result in equipment damage.

86 EIO0000001133 11/2019
Specifications

CAUTION
LOSS OF COMMUNICATION
 All connections to the communication ports must not put excessive stress on the ports.
 Securely attach communication cables to the panel wall or cabinet.
 Use only D-Sub 9 pin cables with a locking tab in good condition.
Failure to follow these instructions can result in injury or equipment damage.

EIO0000001133 11/2019 87
Specifications

Specifications of Serial Interface COM2

Introduction
NOTE: For information on how to connect controllers and other types of equipment, refer to the
corresponding device driver manual of your screen editing software.
The serial port is not isolated. The SG (signal ground) and FG (frame ground) terminals are connected
inside the panel.

DANGER
ELECTRIC SHOCK
When using the SG terminal to connect an external device to the panel:
 Verify that a short-circuit loop is not created when you set up the system.
 Connect the #8 SG terminal to remote equipment when the host (PLC) unit is not isolated. Connect
the #8 SG terminal to a known reliable ground connection to reduce the risk of damaging the circuit.
Failure to follow these instructions will result in death or serious injury.

Serial Interface COM2


HMIGTO5310 / HMIGTO5315: RJ45 connector via an RS-485 cable.
NOTE: When setting up RS-485 communication, the cable diagram for some equipment may require
polarization on the terminal side. This terminal does not require any special setting as it handles
polarization automatically.

Pin Connection Pin No. RS-485


Signal Name Direction Meaning
1 NC - -
2 NC - -
3 NC - -
4 Line A Input/Output Transfer Data (RS-485)
5 Line B Input/Output Transfer Data (RS-485)
6 RS(RTS) Output Request To Send
7 NC - -
8 SG - Signal Ground

CAUTION
LOSS OF COMMUNICATION
 All connections to the communication ports must not put excessive stress on the ports.
 Securely attach communication cables to the panel wall or cabinet.
 Use only RJ45 with a locking tab in good condition.
Failure to follow these instructions can result in injury or equipment damage.

88 EIO0000001133 11/2019
Specifications

Dimensions

External Dimensions: HMIGTO5310

1 Front
2 Right side
3 Top

External Dimensions: HMIGTO5315

1 Front
2 Right side
3 Top

EIO0000001133 11/2019 89
Specifications

Installation with Installation Fasteners: HMIGTO5310

1 Front
2 Right side
3 Top

Installation with Installation Fasteners: HMIGTO5315

1 Front
2 Right side
3 Top

90 EIO0000001133 11/2019
Specifications

Dimensions with Cables: HMIGTO5310

NOTE: All the above values are designed with cable bending in mind. The dimensions given here are
representative values depending on the type of connection cable in use. Therefore, these values are
intended for reference only.

Dimensions with Cables: HMIGTO5315

NOTE: All the above values are designed with cable bending in mind. The dimensions given here are
representative values depending on the type of connection cable in use. Therefore, these values are
intended for reference only.

Panel Cut Dimensions


Create a panel cut and insert the panel into the opening from the front.

A B C R
HMIGTO5310 259 mm (+1, -0 mm) 201 mm (+1, -0 mm) 1.6...5 mm 3 mm (0.12 in)
(10.2 in (+0.04, -0 in)) (7.91 in (+0.04, -0 in)) (0.06...0.2 in) maximum
HMIGTO5315 298 mm (+1, -0 mm) 240 mm (+1, -0 mm)
(11.73 in (+0.04, -0 in)) (9.45 in (+0.04, -0 in))

NOTE: Before designing the panel cut, refer to Installation.

EIO0000001133 11/2019 91
Specifications

Installation Fastener Dimensions

92 EIO0000001133 11/2019
Specifications

Section 4.5
HMIGTO6310/6315

HMIGTO6310/6315

What Is in This Section?


This section contains the following topics:
Topic Page
Electrical Specifications 94
Environmental Specifications 95
Structural Specifications 96
Display Specifications 98
Memory, Clock, and Touch Panel 99
Interface Specifications 100
Specifications of Serial Interface COM1 101
Specifications of Serial Interface COM2 103
Dimensions 104

EIO0000001133 11/2019 93
Specifications

Electrical Specifications

Rated Input Voltage 24 Vdc


Input Voltage Limits 19.2...28.8 Vdc
Voltage Drop 10 ms or less
Power Consumption 17 W or less
When power is not supplied to 12 W or less
external devices
Power Supply

Backlight OFF (Standby Mode) 7 W or less


Backlight Dimmed (Brightness: 20%) 8 W or less
In-Rush Current 30 A or less
Voltage Endurance 1,500 Vac, 20 mA for 1 minute (between
charging and FG terminals)
Insulation Resistance 500 Vdc, 10 MΩ or more (between charging and
FG terminals)

94 EIO0000001133 11/2019
Specifications

Environmental Specifications

Surrounding Air 0...55 °C (32...131 °F)


Temperature
Storage Temperature -20...60 °C (-4...140 °F)
Surrounding Air and 10...90% RH (non-condensing, wet bulb temperature 39 °C (102.2 °F) or
Storage Humidity less)
Electrical Environment Mechanical Environment Physical Environment

Dust 0.1 mg/m3 (10-7 oz/ft3) or less (non-conductive levels)


Pollution Degree For use in Pollution Degree 2 environment
Corrosive Gases Free of corrosive gases
Atmospheric Pressure 800...1,114 hPa (2,000 m [6,561 ft] or lower)
(Operating Altitude)
Vibration Resistance IEC/EN 61131-2 compliant
5...9 Hz Single amplitude 3.5 mm (0.14 in.)
9...150 Hz Fixed acceleration: 9.8 m/s2
X, Y, Z directions for 10 cycles (approx.100 minute)
Concussion Resistance IEC/EN 61131-2 compliant
147 m/s2, X, Y, Z directions for 3 times

Noise Immunity Noise Voltage: 1,000 Vp-p


Pulse Width: 1 μs
Rise Time: 1 ns
Electrostatic Discharge Contact Discharge Method: 6 kV (IEC/EN 61000-4-2 Level 3)
Immunity

Air Quality Requirements


Do not operate or store the panel where chemicals evaporate, or where chemicals are present in the air:
 Corrosive chemicals: Acids, alkalines, liquids containing salt.
 Flammable chemicals: Organic solvents.

CAUTION
INOPERATIVE EQUIPMENT
Do not allow water, liquids, metal, and wiring fragments to enter the panel case.
Failure to follow these instructions can result in injury or equipment damage.

EIO0000001133 11/2019 95
Specifications

Structural Specifications

HMIGTO6310 HMIGTO6315
Grounding Functional grounding: Grounding resistance of 100 Ω, 2 mm2 (AWG 14) or thicker
wire, or your country's applicable standard. (Same for FG and SG terminals)
Cooling Method Natural air circulation
Structure*1 IP65f NEMA #250 TYPE 4X/13 (on the IP66k NEMA #250 TYPE 4X/13 (on the
front panel when properly installed in an front panel when properly installed in an
enclosure) enclosure)*2
External Dimensions W 315 x H 241 x D 56 mm W 359 x H 285 x D 56 mm
(W 12.4 x H 9.49 x D 2.2 in) (W 14.13 x H 11.22 x D 2.2 in)
Panel Cut Dimensions W 301.5 x H 227.5 mm W 340.5 x H 266.5 mm
(W 11.87 x H 8.96 in)*3 (W 13.41 x H 10.49 in)*3
Panel thickness area: 1.6...5 mm Panel thickness area: 1.6...5 mm
(0.06...0.2 in)*4 (0.06...0.2 in)*4
Weight 2.5 kg (5.5 lb) or less (main unit only) 3 kg (6.6 lb) or less (main unit only)

NOTE: *1 The front face of the HMIGTO, installed in a solid panel, has been tested using conditions
equivalent to the standards shown in the specification. Even though the HMIGTO's level of resistance is
equivalent to these standards, oils that should have no effect on the HMIGTO can possibly harm the panel.
This can occur in areas where either vaporized oils are present, or where low viscosity cutting oils are
allowed to adhere to the panel for long periods of time. If the panel's front face protection sheet peels off,
these conditions can lead to the ingress of oil into the panel and separate protection measures are
suggested.
Also, if non-approved oils are present, they may cause deformation or corrosion of the front panel's plastic
cover. Therefore, prior to installing the HMIGTO, be sure to confirm the type of conditions that will be
present in the panel's operating environment. If the installation gasket is used for a long period of time, or
if the HMIGTO and its gasket are removed from the panel, the original level of protection cannot be kept.
To maintain the original protection level, be sure to replace the installation gasket regularly.
*2 When installing the HMIGTO in a panel, you may not be able to mount the HMIGTO flush with the panel.

This occurs due to the thickness of the gasket. The difference in level between the HMIGTO and panel
depends on how much the gasket is compressed.
There is a conformal coating on circuit boards for HMIGTO6315.

NOTICE
EQUIPMENT DAMAGE
For food and beverage and pharmaceutical industries, when the HMIGTO is not flush with panel, use
silicon to form a seal to prevent water, chemicals, or food from lodging into place. Otherwise, the panel
face could leak.
Failure to follow these instructions can result in equipment damage.

*3
For dimensional tolerance, everything +1/-0 mm (+0.04/-0 in), and R in angle are below R3 (R0.12 in)
*4Even if the installation wall thickness is within the recommended range for the “Panel Cut Dimensions”,
depending on wall’s material, size, and installation location of the panel and other devices, the installation
wall could warp. To prevent warping, the installation surface may need to be strengthened.

CAUTION
EQUIPMENT DAMAGE
Ensure that the panel is not in permanent and direct contact with oils.
Failure to follow these instructions can result in injury or equipment damage.

96 EIO0000001133 11/2019
Specifications

NOTICE
STORAGE AND OPERATION OUTSIDE OF SPECIFICATIONS
 Store this product in areas where temperatures are within the product’s specifications.
 Do not restrict or block this product’s ventilation slots.
Failure to follow these instructions can result in equipment damage.

NOTICE
GASKET AGING
 Inspect the gasket periodically as required by your operating environment to keep the initial IP level.
 Change the gasket at least once a year, or as soon as scratches or dirt become visible.
Failure to follow these instructions can result in equipment damage.

EIO0000001133 11/2019 97
Specifications

Display Specifications

Display Type TFT Color LCD


Display Size 12.1”
Resolution 800 x 600 pixels (SVGA)
Effective Display Area W 246.0 x H 184.5 mm (W 9.69 x H 7.26 in.)
Display Colors 65,536 colors (no blink) / 16,384 colors (blink)
Backlight White LED (not user replaceable). When replacement is required, contact your
local distributor.
Backlight Service Life 50,000 hours (continuous operation at 25 °C (77 °F) before backlight brightness
decreases to 50%)
Brightness Control 16 levels (Adjusted with touch panel or software)
Language Fonts ASCII: (Code page 850) Alphanumeric (including European characters)
Chinese: (GB2312-80 codes) Simplified Chinese fonts
Japanese: ANK 158, Kanji: 6,962 (JIS Standards 1 & 2) (including 607 non-kanji
characters)
Korean: (KSC5601 - 1992 codes) Hangul fonts
Taiwanese: (Big 5 codes) Traditional Chinese fonts
Character Sizes 8 x 8, 8 x 16, 16 x 16 and 32 x 32 pixel fonts
Text 8 x 8 pixels 100 characters per row x 75 rows
8 x 16 pixels 100 characters per row x 37 rows
16 x 16 pixels 50 characters per row x 37 rows
32 x 32 pixels 25 characters per row x 18 rows

*1 You can set up other font sizes using the software.

98 EIO0000001133 11/2019
Specifications

Memory, Clock, and Touch Panel

Memory

Application Memory*1 FLASH EPROM96 MB


Application run DRAM 128 MB
Data Backup SRAM 512 KB (Replaceable lithium battery for
backup memory)

*1 Capacity available for user application.


NOTE: When the message indicating that the battery level is low is displayed, replace the battery
(see page 136).

Clock

Clock Accuracy*1 ±65 seconds/month (deviation at room temperature


and power is OFF).

*1 Depending on the operating temperature and age of the panel, the clock can deviate from -380 to +90
sec/month. For systems where this level of precision is insufficient, the user should monitor and make
adjustments when required.

Touch Panel

Touch Panel Type Resistive Film (analog)


Touch Panel Resolution 1,024 x 1,024
Touch Panel Service Life 1 million times or more

EIO0000001133 11/2019 99
Specifications

Interface Specifications

Serial Interface COM1

Asynchronous Transmission RS-232C


Data Length 7 bits or 8 bits
Stop Bit 1 bit or 2 bits
Parity None, odd or even
Data Transmission Speed 2,400...115,200 bps
Connector D-Sub 9-pin (plug)

Serial Interface COM2

Asynchronous Transmission RS-485


Data Length 7 bits or 8 bits
Stop Bit 1 bit or 2 bits
Parity None, odd or even
Data Transmission Speed 2,400...115,200 bps, 187,500 bps (MPI)
Connector Modular jack (RJ45)

USB Interface

USB (Type A) Interface USB (mini-B) Interface


Connector USB 2.0 (Type A) x 1 USB 2.0 (mini-B) x 1
Power Supply Voltage 5 Vdc ±5% -
Maximum Current Supplied 500 mA -
Maximum Transmission Distance 5 m (16.4 ft)

Ethernet Interface

Ethernet (LAN) IEEE802.3i / IEEE802.3u, 10BASE-T/100BASE-TX


Connector Modular jack (RJ45) x 1

SD Card Interface
SD card slot x 1 (maximum 32 GB SD/SDHC card)

100 EIO0000001133 11/2019


Specifications

Specifications of Serial Interface COM1

Introduction
NOTE: For information on how to connect controllers and other types of equipment, refer to the
corresponding device driver manual of your screen editing software.

CAUTION
LOSS OF COMMUNICATION
 All connections to the communication ports must not put excessive stress on the ports.
 Securely attach communication cables to the panel or cabinet.
 Use only D-Sub 9-pin cables with a locking system in good condition.
Failure to follow these instructions can result in injury or equipment damage.

The serial port is not isolated. The SG (signal ground) and FG (frame ground) terminals are connected
inside the panel.

DANGER
ELECTRIC SHOCK
When using the SG terminal to connect an external device to the panel:
 Verify that a short-circuit loop is not created when you set up the system.
 Connect the #5 SG terminal to remote equipment when the host (PLC) unit is not isolated. Connect
the #5 SG terminal to a known reliable ground connection to reduce the risk of damaging the circuit.
Failure to follow these instructions will result in death or serious injury.

Serial Interface COM1


HMIGTO6310 / HMIGTO6315: D-Sub 9-pin plug connector via a RS-232C cable.

Pin Connection Pin No. RS-232C


Signal Name Direction Meaning
1 CD Input Carrier Detect
2 RD(RXD) Input Receive Data
3 SD(TXD) Output Send Data
4 ER(DTR) Output Data Terminal Ready
5 SG - Signal Ground
6 DR(DSR) Input Data Set Ready
7 RS(RTS) Output Request to Send
8 CS(CTS) Input Send possible
9 CI(RI)/VCC Input– Called Status Display
+5 V±5% Output 0.25 A*1
Shell FG – Frame Ground (Common with
SG)

NOTE: *1 You can switch pin number 9 between RI and VCC via software.

NOTICE
EQUIPMENT DAMAGE
Use only the rated current.
Failure to follow these instructions can result in equipment damage.

EIO0000001133 11/2019 101


Specifications

CAUTION
LOSS OF COMMUNICATION
 All connections to the communication ports must not put excessive stress on the ports.
 Securely attach communication cables to the panel wall or cabinet.
 Use only D-Sub 9 pin cables with a locking tab in good condition.
Failure to follow these instructions can result in injury or equipment damage.

102 EIO0000001133 11/2019


Specifications

Specifications of Serial Interface COM2

Introduction
NOTE: For information on how to connect controllers and other types of equipment, refer to the
corresponding device driver manual of your screen editing software.
The serial port is not isolated. The SG (signal ground) and FG (frame ground) terminals are connected
inside the panel.

DANGER
ELECTRIC SHOCK
When using the SG terminal to connect an external device to the panel:
 Verify that a short-circuit loop is not created when you set up the system.
 Connect the #8 SG terminal to remote equipment when the host (PLC) unit is not isolated. Connect
the #8 SG terminal to a known reliable ground connection to reduce the risk of damaging the circuit.
Failure to follow these instructions will result in death or serious injury.

Serial Interface COM2


HMIGTO6310 / HMIGTO6315: RJ45 connector via a RS-485 cable.
NOTE: When setting up RS-485 communication, the cable diagram for some equipment may require
polarization on the terminal side. This terminal does not require any special setting as it handles
polarization automatically.

Pin Connection Pin No. RS-485


Signal Name Direction Meaning
1 NC - -
2 NC - -
3 NC - -
4 Line A Input/Output Transfer Data (RS-485)
5 Line B Input/Output Transfer Data (RS-485)
6 RS(RTS) Output Request To Send
7 NC - -
8 SG - Signal Ground

CAUTION
LOSS OF COMMUNICATION
 All connections to the communication ports must not put excessive stress on the ports.
 Securely attach communication cables to the panel wall or cabinet.
 Use only RJ45 with a locking tab in good condition.
Failure to follow these instructions can result in injury or equipment damage.

EIO0000001133 11/2019 103


Specifications

Dimensions

External Dimensions: HMIGTO6310

1 Front
2 Right side
3 Top

External Dimensions: HMIGTO6315

1 Front
2 Right side
3 Top

104 EIO0000001133 11/2019


Specifications

Installation with Installation Fasteners: HMIGTO6310

1 Front
2 Right side
3 Top

Installation with Installation Fasteners: HMIGTO6315

1 Front
2 Right side
3 Top

EIO0000001133 11/2019 105


Specifications

Dimensions with Cables: HMIGTO6310

NOTE: All the above values are designed with cable bending in mind. The dimensions given here are
representative values depending on the type of connection cable in use. Therefore, these values are
intended for reference only.

Dimensions with Cables: HMIGTO6315

NOTE: All the above values are designed with cable bending in mind. The dimensions given here are
representative values depending on the type of connection cable in use. Therefore, these values are
intended for reference only.

Panel Cut Dimensions


Create a panel cut and insert the panel into the opening from the front.

A B C R
HMIGTO6310 301.5 mm (+1, -0 mm) 227.5 mm (+1, -0 mm) 1.6...5 mm 3 mm (0.12 in)
(11.87 in (+0.04, -0 in)) (8.96 in (+0.04, -0 in)) (0.06...0.2 in) maximum
HMIGTO6315 340.5 mm (+1, -0 mm) 266.5 mm (+1, -0 mm)
(13.41 in (+0.04, -0 in)) (10.49 in (+0.04, -0 in))

NOTE: Before designing the panel cut, refer to Installation.

106 EIO0000001133 11/2019


Specifications

Installation Fastener Dimensions

EIO0000001133 11/2019 107


Specifications

108 EIO0000001133 11/2019


Harmony
Installation and Wiring
EIO0000001133 11/2019

Chapter 5
Installation and Wiring

Installation and Wiring

What Is in This Chapter?


This chapter contains the following sections:
Section Topic Page
5.1 Installation 110
5.2 Wiring Principles 115
5.3 SD Card Insertion/Removal 121
5.4 USB Cable Clamp 126

EIO0000001133 11/2019 109


Installation and Wiring

Section 5.1
Installation

Installation

Installation Procedures

Introduction
The installation fasteners are required when installing the panel.
Mount the panel in an enclosure that provides a clean, dry, robust, and controlled environment:
 HMIGTO (except HMIGTO2315 / HMIGTO5315 / HMIGTO6315): IP65, Type 1, Type 4X [Indoor Use
Only] or Type 13 enclosure.
 HMIGTO2315 / HMIGTO5315 / HMIGTO6315: IP66k, Type 1, Type 4X [Indoor Use Only] or Type 13
enclosure.

Installation Requirements

Check that the installation wall or cabinet’s surface is flat, in good condition and has no jagged edges. Metal
reinforcing strips may be attached to the inside of the wall, near the panel-cut, to increase its rigidity.
Decide on the thickness of the enclosure wall, based on the level of strength required: 1.6...5 mm
(0.06...0.2 in.).
Be sure that the surrounding air temperature and the ambient humidity are within their designated ranges.
Surrounding air temperature: 0...50 °C (32...122 °F) or 0...55 °C (32...131 °F) (see the Environment
Specifications for your HMIGTO); ambient humidity: 10...90% RH; wet bulb temperature: maximum 39 °C
[102 °F]. When installing the panel in a cabinet or enclosure, the surrounding air temperature is the cabinet's
or enclosure's internal temperature.

Be sure that heat from surrounding equipment does not cause the panel to exceed its standard operating
temperature.
When mounting the panel vertically, ensure that the right side of the unit faces up. In other words, the power
connector should be at the top.

1 Power connector

110 EIO0000001133 11/2019


Installation and Wiring

When installing the panel in a slanted position, the panel face should not incline more than 30°.

When installing the panel in a slanted position with an incline more than 30°, the ambient temperature must
not exceed 40 °C (104 °F). You may need to use forced air cooling (fan, A/C) to ensure that the ambient
operating temperature is 40 °C or less (104 °F or less).
For easier maintenance, operation and improved ventilation, install the panel at least 100 mm (3.94 in.) away
from adjacent structures and other equipment as shown in the following illustration:

The holes on the rear of the panel (except HMIGTO1300/1310) do not correspond to VESA 75 mm standards.
Do not attach the panel to a commercial-type VESA arm.

Panel Mounting Procedure: : (Except HMIGTO2315/HMIGTO5315/HMIGTO6315)

NOTICE
PANEL UNSTEADY WHEN UNSECURED
Keep HMIGTO stabilized in the panel-cut while you are installing or removing the screw fasteners.
Failure to follow these instructions can result in equipment damage.

Step Action
1 Place the panel on a clean and level surface with the display facing downward.
2 Check that the panel's gasket is seated securely into the gasket's groove, which runs around the
perimeter of the panel frame.
3 Cut a hole in the installation panel as defined by the HMIGTO's panel cutout dimensions.
HMIGTO1300/HMIGTO1310 (see page 48)
HMIGTO2300/HMIGTO2310 (see page 63)
HMIGTO3510/HMIGTO4310 (see page 76)
HMIGTO5310 (see page 91)
HMIGTO6310 (see page 106)
4 Insert the HMIGTO into the panel-cut.

EIO0000001133 11/2019 111


Installation and Wiring

Step Action
5 Insert the installation fasteners into the HMIGTO's insertion slots on the top and bottom sides
(left and right sides for the HMIGTO1300/1310). Slide the fasteners to the back. If the fasteners
are not correctly attached, the HMIGTO may shift or fall out.

HMIGTO2310

HMIGTO1310

6 Insert each of the fasteners shown below. Make sure that you pull the fastener back until it is
flush with the rear of the attachment hole insert.

7 Use a Phillips screwdriver to tighten each fastener screw and secure the panel in place. The
necessary torque is 0.5 Nm (4.4 lb•in).

NOTICE
BROKEN ENCLOSURE
 Do not exert more than 0.5 Nm (4.4 lb•in) of torque when tightening the fastener’s screws.
 Use on flat surface of a Type 1, Type 4X (Indoor Use Only) or Type 13 Enclosure.
Failure to follow these instructions can result in equipment damage.

112 EIO0000001133 11/2019


Installation and Wiring

Removal Procedure: (Except HMIGTO2315/HMIGTO5315/HMIGTO6315)

Step Action
1 Loosen the installation fasteners (4) from the HMIGTO.
2 Remove the HMIGTO slowly from the panel while pressing the projections on the top of the
HMIGTO.

1 Projections

NOTE:
 You could damage the HMIGTO if you try to remove it without holding down the projections.
 Watch your fingers so they do not get caught when holding down the projections.

CAUTION
RISK OF INJURY
Do not drop the HMIGTO when you remove it from the panel.
 Hold the HMIGTO in place after removing the fasteners.
 Use both hands.
Failure to follow these instructions can result in injury or equipment damage.

HMIGTO2315/HMIGTO5315/HMIGTO6315 Panel Mounting Procedure

CAUTION
RISK OF INJURY
Do not drop the HMIGTO when you install or remove it from the panel.
 Hold the HMIGTO in place after removing the M4 Hex nuts and brackets.
 Use both hands.
Failure to follow these instructions can result in injury or equipment damage.

NOTICE
PANEL UNSTEADY WHEN UNSECURED
Keep panel stabilized in the panel-cut while you are installing or removing the M4 Hex nuts and brackets.
Failure to follow these instructions can result in equipment damage.

Step Action
1 Place the panel on a clean and level surface with the display facing downward.
2 Confirm that the panel's gasket is seated properly on the rear of the panel.
3 Cut a hole in the panel as defined by the HMIGTO panel cutout dimensions.
HMIGTO2315 (see page 63)
HMIGTO5315 (see page 91)
HMIGTO6315 (see page 106)

EIO0000001133 11/2019 113


Installation and Wiring

Step Action
4 Insert the HMIGTO into the panel-cut.

1 Gasket
2 Panel
3 Brackets
4 M4 hex nut
5 Read step 5.
6 Read step 6.
5 Tighten the four corners of the rear of the panel with the M4 Hex nuts, in the order shown in the
example in Step 4.
Use an M4 box-type screwdriver to tighten each M4 Hex nut and secure the panel in place. The
necessary torque is 0.5 Nm (4.4 lb•in). If the M4 Hex nuts are not correctly attached, the panel
may shift or fall out.
6 Attach the bracket onto the screws in the middle between the M4 Hex nuts in the order shown
in the example in Step 4.
Use an M4 box-type screwdriver to tighten each M4 Hex nut and secure the panel in place. The
necessary torque is 0.5 Nm (4.4 lb•in). If the M4 Hex nuts are not correctly attached, the panel
may shift or fall out.
7 Tighten all the M4 Hex nuts again. The necessary torque is 0.5 Nm (4.4 lb•in).
NOTE: Do not loosen the installation fasteners, marked with red squares below.

1 Panel

NOTICE
BROKEN ENCLOSURE
 Do not exert more than 0.5 Nm (4.4 lb•in) of torque when tightening the M4 Hex nuts.
 Use on flat surface of a Type 1, Type 4X (Indoor Use Only) or Type 13 Enclosure.
Failure to follow these instructions can result in equipment damage.

114 EIO0000001133 11/2019


Installation and Wiring

Section 5.2
Wiring Principles

Wiring Principles

Overview
This section presents the HMIGTO wiring principles.

What Is in This Section?


This section contains the following topics:
Topic Page
Connecting the Power Cord 116
Connecting the Power Supply 118
Grounding 120

EIO0000001133 11/2019 115


Installation and Wiring

Connecting the Power Cord

WARNING
EXCESSIVE ELECTROMAGNETIC INTERFERENCE
 When the functional ground (FG) terminal is connected, be sure the wire is grounded. Not grounding
the HMIGTO can result in excessive Electromagnetic Interference (EMI). Grounding is required to
meet EMC level immunity.
 Remove power before wiring the HMIGTO’s power terminals.
 The DC model uses only 24 Vdc power. Using any other level of power can damage both the power
supply and the HMIGTO.
 Since the HMIGTO is not equipped with a power switch, be sure to connect a power switch to the
power supply.
 Be sure to ground the HMIGTO's FG terminal.
 Replace and secure all elements of the system before applying power to the HMIGTO.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

NOTE: The shield ground (SG) and FG terminals are connected internally in the panel.

DC Power Cord Preparation


 Make sure that the ground wire is either the same or heavier gauge than the power wires.
 Do not use aluminum wires in the power supply's power cord.
 If the ends of the individual wires are not twisted correctly, the wires may create a short circuit.
 Wherever possible, use wires that are 0.75 to 2.5 mm2 (AWG 18 - 13) for the power cord, and twist the
wire ends before attaching the terminals.
 The conductor type is solid or stranded wire.
 Field wiring terminal marking for wire type (75 °C [167 °F] copper conductors only).

DC Power Supply Connector (Plug) Specifications: Spring Clamp Terminal Blocks


HMIGTO1300/1310 / HMIGTO2300/2310/2315 / HMIGTO3510/4310

HMIGTO5310/5315 / HMIGTO6310/6315

Connection Wire
+ 24 Vdc
- 0 Vdc
FG Grounded terminal connected to the panel chassis.

116 EIO0000001133 11/2019


Installation and Wiring

How to Connect the DC Power Cord

Step Action
1 Confirm that the power cord is not connected to the power supply.
2 Check the rated voltage and remove the “DC24V” sticker on the DC power supply connector.
3 Remove 10 mm (0.39 in) of the vinyl membrane off the ends of the power cord wires.
4 If using stranded wire, twist the ends. Tinning the ends with solder reduces risk of fraying and
ensures good electrical transfer.
5 Push the Opening button with a small and flat screwdriver to open the desired pin hole.
6 Insert each pin terminal into its corresponding hole. Release the Opening button to clamp the
pin in place.

7 After inserting all three pins, insert the power plug into the power connector on the panel.

NOTE:
 Do not solder the wire directly to the power receptacle pin.
 To prevent the possibility of a terminal short, use a pin terminal that has an insulating sleeve.
 You can use the DC power connector for HMIGTO1300/1310 / HMIGTO2300/2310/2315 /
HMIGTO3510/4310 to supply power to HMIGTO5310/5315 / HMIGTO6310/6315. However the reverse
is not possible. You cannot use the power connector for HMIGTO5310/5315 / HMIGTO6310/6315 on
HMIGTO1300/1310 / HMIGTO2300/2310/2315 / HMIGTO3510/4310.

EIO0000001133 11/2019 117


Installation and Wiring

Connecting the Power Supply

Precautions
 You must use a 24 Vdc input unit with a Class 2 power supply.
 To increase the electromagnetic noise resistance, make sure that you twist the ends of the power cord
wires before connecting them to the power plug.
 The panel's power supply cord should not be bundled with or kept close to main circuit lines (high
voltage, high current), or input/output signal lines.
 Connect a lightning surge absorber to handle power surges.
 To reduce electromagnetic noise, make the power cord as short as possible.

WARNING
SHORT CIRCUIT, FIRE, OR UNINTENDED EQUIPMENT OPERATION
Avoid excessive force on the power cable to prevent accidental disconnection
 Securely attach power cables to the HMIGTO or cabinet.
 Use the designated torque to tighten the unit terminal block screws.
 Install and fasten the HMIGTO on installation panel or cabinet prior to connecting power supply and
communication lines.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

Power Supply Connections


When supplying power to the panel, separate the input/output and power lines, as shown.

NOTE:
The following shows a lightning surge absorber connection:

 Ground the surge absorber (E1) separately from the panel (E2).
 Select a surge absorber that has a maximum circuit voltage greater than that of the peak voltage of the
power supply.
If the supplied voltage exceeds the panel range, connect a constant voltage transformer.

1 Constant voltage transformer


2 Twisted-pair cord
3 panel

118 EIO0000001133 11/2019


Installation and Wiring

Select a power supply low in noise for between the line and ground. If there is an excess amount of noise,
connect an insulating transformer.

1 Insulating transformer
2 Twisted-pair cord
3 panel

NOTE: Use constant voltage and insulating transformers with capacities exceeding the Power
Consumption value.

EIO0000001133 11/2019 119


Installation and Wiring

Grounding

Exclusive Grounding
When supplying power to the panel, separate the input/output and power lines as shown below.
Connect the frame ground (FG) terminal on the power plug to an exclusive ground.

Precautions
Electromagnetic Interference (EMI) can be created if the devices are improperly grounded. EMI can cause
loss of communication. Do not use common grounding, except for the authorized configuration described
below. If exclusive grounding is not possible, use a common grounding point.
Correct grounding

Incorrect grounding

 Check that the grounding resistance is 100 Ω or less.*1


 The FG wire should have a cross sectional area greater than 2 mm2 (AWG 14) (1). Create the
connection point as close to the panel as possible, and make the wire as short as possible. When using
a long grounding wire, replace the thin wire with a thicker wire, and place it in a duct.
 FG and SG terminals are internally connected in the panel. When connecting an external device to the
panel using the SG terminal, check that you do not create a short-circuit loop when you set up the
system.
*1
Observe local codes and standards. Ensure that the ground connection has a resistance of 100 Ω and
that the ground wire has a cross-section of at least 2 mm2 or AWG 14.

120 EIO0000001133 11/2019


Installation and Wiring

Section 5.3
SD Card Insertion/Removal

SD Card Insertion/Removal

What Is in This Section?


This section contains the following topics:
Topic Page
Introduction 122
Inserting the SD Card 123
Removing the SD Card 124
SD Card Data Backup 125

EIO0000001133 11/2019 121


Installation and Wiring

Introduction

NOTICE
LOSS OF DATA
When using the HMIGTO and a SD Card, observe the following to avoid losing valuable data:
 Since accidental data loss can occur at any time, back up HMIGTO screen and SD Card data
regularly. Once HMIGTO data is lost, it cannot be recovered.
 While a SD Card is accessed, do not turn OFF or reset the HMIGTO, and do not insert or remove the
SD Card. Doing so could damage the SD Card, or corrupt its data.
 Before using the SD Card, familiarize yourself with the SD Card's front and rear face orientation, as
well as the position of the SD Card connectors. If the SD Card is not positioned correctly when inserted
into the HMIGTO, the card's internal data and HMIGTO could become damaged.
Failure to follow these instructions can result in equipment damage.

NOTICE
LOSS OF DATA
When handling the SD Card, follow the instructions below to prevent internal data on the SD Card from
being destroyed or a SD Card malfunction from occurring:
 Avoid storing the SD Card where there is static electricity or electromagnetic waves.
 Avoid storing the SD Card in direct sunlight, near a heater, or other locations where high temperatures
can occur.
 Do not bend the SD Card.
 Do not drop or strike the SD Card against another object.
 Keep the SD Card dry.
 Do not touch the SD Card connectors.
 Do not disassemble or modify the SD Card.
 Use only SD Cards formatted using FAT or FAT32. The HMIGTO does not recognize NTFS formatted
SD Cards. Format the SD Card on your computer using FAT or FAT32.
Failure to follow these instructions can result in equipment damage.

122 EIO0000001133 11/2019


Installation and Wiring

Inserting the SD Card

NOTE: As shown in the image below (example on the left-hand side), you can set the Write-Control Tab
to prevent write operations to the SD Card. Push the tab up, as shown in the example on the right-hand
side, to release the lock and enable writing to the SD Card. Before using a commercial-type SD Card, read
the manufacturer's instructions.

Step Action
1 Pull on the tab and open the SD Card cover.

1 Tab
2 Insert the SD Card into the SD Card interface, and push until you hear it “click”.

3 Close the SD Card cover.

EIO0000001133 11/2019 123


Installation and Wiring

Removing the SD Card

Step Action
1 Make sure the SD Card Access LED is off.

1 SD Card Access LED


2 Push down the tab on the SD Card cover, then pull open the cover.

1 Tab
3 Push the SD Card once to release, and pull out the card. After removing the
card, close the cover.
NOTE: After using the SD Card, store the SD Card in its case or other safe
location.

124 EIO0000001133 11/2019


Installation and Wiring

SD Card Data Backup

To make your backups, you can either insert the SD Card directly into the SD Card interface on your
computer, or use a commercially available SD Card reader.

EIO0000001133 11/2019 125


Installation and Wiring

Section 5.4
USB Cable Clamp

USB Cable Clamp

Overview
This section presents the USB cable clamp.

What Is in This Section?


This section contains the following topics:
Topic Page
USB Cable Clamp for USB (Type A) 127
USB Holder for USB (mini-B) 129

126 EIO0000001133 11/2019


Installation and Wiring

USB Cable Clamp for USB (Type A)

Introduction
When using a USB device, attaching a USB cable clamp to the USB interface to prevent the USB cable
from being disconnected.

DANGER
POTENTIAL FOR EXPLOSION
 Verify the power, input, and output (I/O) wiring are in accordance with Class I, Division 2 wiring
methods.
 Substitution of any components may impair suitability for Class I, Division 2.
 Confirm that the USB cable has been fixed with the USB cable clamp before using the USB interface.
 Remove power before attaching or detaching any connectors to or from the unit.
Failure to follow these instructions will result in death or serious injury.

Attaching the USB Cable Clamp


NOTE: Watch your fingers. The edge of the clip is sharp.

Step Action
1
Mount the clip to the USB mark connector shell so that it overlaps. The
clip matches the 27...43.5 mm (1.06...1.71 in) length of the USB connector.

2 Align the clip and the USB cable connector shell. Adjust the position of the
holes where the clip is attached. To ensure stability, select the clip-hole
position that is closest to the base of the connector shell.

EIO0000001133 11/2019 127


Installation and Wiring

Step Action
3 As shown, pass the tie through the clip hole. Next, turn the tie and pass it
through the head so that the USB cable can pass through the center of the tie
loop. The clip is now attached to the USB cable.

NOTE:
 Check the direction of the head beforehand. Make sure that the USB cable
is through the center of the tie loop and that the tie can pass through the
head.
 You can substitute the tie provided with commercially available ties with a
width of 4.8 mm (0.19 in) and thickness of 1.3 mm (0.05 in).
4 While pressing the grip on the clip, insert the cable from step 3 all the way into
the USB host interface. Make sure that the clip tab is secured to the USB cable
attached to the HMIGTO.

Removing the USB Cable


Remove the USB cable while pushing the grip section of the clip.

128 EIO0000001133 11/2019


Installation and Wiring

USB Holder for USB (mini-B)

Introduction
When using a USB device, you can attach a USB holder to the USB (mini-B) interface to prevent the USB
cable from being disconnected.

DANGER
POTENTIAL FOR EXPLOSION
 Verify the power, input, and output (I/O) wiring are in accordance with Class I, Division 2 wiring
methods.
 Substitution of any components may impair suitability for Class I, Division 2.
 Confirm that the USB cable has been fixed with the USB cable clamp before using the USB interface.
 Remove power before attaching or detaching any connectors to or from the unit.
Failure to follow these instructions will result in death or serious injury.

Attaching the USB Holder

Step Action
1 Insert the USB cable into the USB (mini-B) interface.

1 USB cable
2 Attach the USB holder to fix the USB cable in place. Insert the USB holder into the USB (mini-B)
interface.

1 USB holder
2 USB cable

Removing the USB Holder


Remove the USB holder by pressing the tabs from the sides.

EIO0000001133 11/2019 129


Installation and Wiring

130 EIO0000001133 11/2019


Harmony
Maintenance
EIO0000001133 11/2019

Chapter 6
Maintenance

Maintenance

Overview
This chapter explains how to maintain your panel.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Regular Cleaning 132
Replacing the Installation Gasket 133
Periodic Check Points 135
Replacing the Primary Battery 136

EIO0000001133 11/2019 131


Maintenance

Regular Cleaning

Cleaning the display

NOTICE
EQUIPMENT DAMAGE
 Power off the panel before cleaning it.
 Do not use hard or pointed objects to operate the touch panel as you may damage the panel surface.
 Do not use paint thinner, organic solvents, or a strong acid compound to clean the unit.
Failure to follow these instructions can result in equipment damage.

When the surface or the frame of the display gets dirty, soak a soft cloth in water with a neutral detergent,
wring the cloth tightly and wipe the display.

132 EIO0000001133 11/2019


Maintenance

Replacing the Installation Gasket

Overview
The installation gasket provides protection against dust and moisture.

NOTICE
GASKET AGING
 Inspect the gasket periodically as required by your operating environment to keep the initial IP level.
 Change the gasket at least once a year, or as soon as scratches or dirt become visible.
Failure to follow these instructions can result in equipment damage.

Installing the Installation Gasket


NOTE: For instructions on how to install the installation gasket when using
HMIGTO2315/HMIGTO5315/HMIGTO6315, see HMIGTO2315/HMIGTO5315/HMIGTO6315 Panel
Mounting Procedure (see page 113).

Stage Description
1 Place the panel on a flat, level surface, with the display face pointing down.
2 Remove the gasket from the panel.
3 Attach the new gasket to the panel. Position the gasket in the installation groove
so that the gasket seam is at the bottom of the panel. First, insert the gasket into
the 4 corners, in the order shown in the image below. Then, insert the rest of the
gasket into the installation groove.
NOTE:
 The center of the panel bezel's installation groove is ribbed. Make sure you
insert the gasket all the way in without catching the ribbed sections.
 When using a tool to insert the gasket, make sure the tool does not catch the
rubber gasket and cause a tear.

4 The upper surface of the gasket should protrude approximately 2.0 mm (0.06 in.)
from the groove. Check the gasket is inserted correctly before installing the
HMIGTO into a panel.

EIO0000001133 11/2019 133


Maintenance

The gasket must be inserted correctly into the groove for IP65f moisture resistance for the panel (IP66k
moisture resistance for HMIGTO2315/HMIGTO5315/HMIGTO6315.

CAUTION
EQUIPMENT DAMAGE
 Since the gasket is flexible but not elastic, be careful not to stretch it unnecessarily.
 Make sure the gasket seam is not inserted into any of the panel corners.
 Insert the gasket in the installation groove
Failure to follow these instructions can result in injury or equipment damage.

134 EIO0000001133 11/2019


Maintenance

Periodic Check Points

Operation Environment
 Is the operating temperature within the allowable range? Refer to Environmental Specifications
(see page 38), (see page 51), (see page 66), (see page 80), (see page 95).
 Is the operating humidity within the specified range? (10%RH to 90%RH, dry bulb temperature of 39 °C
[102.2 °F] or less)
 Is the operating atmosphere free of corrosive gasses?
When the HMIGTO is inside a panel, the ambient environment refers to the interior of the panel.

Electrical Specifications
Is the input voltage appropriate?
 100 Vac to 240 Vac 50/60 Hz
 19.2 Vdc to 28.8 Vdc

Related Items
 Are all power cords and cables connected properly? Are there any loose cables?
 Are all mounting brackets holding the unit securely?
 Are there scratches or traces of dirt on the installation gasket?

EIO0000001133 11/2019 135


Maintenance

Replacing the Primary Battery

Introduction
The replacement battery HMIZGBAT (sold separately) for the primary battery in the HMIGTO is available
from Schneider Electric.
NOTE: The HMIGTO1300/1310 and HMIGTO2300 are not equipped with a primary battery.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
 Follow the procedures step by step to replace the battery correctly and safely.
 Before replacing the battery, turn OFF the HMIGTO's power.
Failure to follow these instructions will result in death or serious injury.

DANGER
EXPLOSION, FIRE, OR CHEMICAL HAZARD
 Use only the replacement battery HMIZGBAT manufactured by Schneider Electric.
 Do not cause a short circuit.
 Recycle or properly dispose of used batteries.
Failure to follow these instructions will result in death or serious injury.

NOTICE
LOSS OF DATA
The primary battery is non-rechargeable, and is used for data backup of memory and the internal clock.
If the primary battery is depleted, the backup data is lost. One month before the primary battery is
completely depleted, a message will appear to indicate it is time to replace the primary battery.
 Replace the battery within one month after the message appears. Otherwise, backup data may be lost.
 Complete replacing the battery within ten minutes of shutting down the HMIGTO.
 The primary battery replacement time (within a month after the message appears) is only a guideline.
When backup SRAM data and clock data is lost after the message appears, Schneider Electric does
not perform data recovery/retrieval. Schneider Electric does not accept any responsibility for the loss
of data.
 Replace the primary battery regularly every five years after you purchase the HMIGTO.

Failure to follow these instructions can result in equipment damage.

Step Action
1 Disconnect the power supply from the HMIGTO.
2 Touch the housing or ground connection (not the power supply) to discharge any electrostatic
charge from your body.
3 Open the SD card Interface Cover by pressing its tab. Next, open the Replacement battery
Insertion Cover by pressing its tab.

1 SD card Interface Cover / Tab


2 Replacement battery Insertion Cover / Tab

136 EIO0000001133 11/2019


Maintenance

Step Action
4 Remove the primary battery and connector.

1 Connector
2 Primary battery
5 Attach the new primary battery and connector.

6 First close the replacement battery cover; then close the SD card interface cover.
NOTE: Make sure that the cables are inserted completely inside the enclosure. Otherwise, you
can damage the cables when you close the cover.
7 Reconnect the power supply to the HMIGTO.

EIO0000001133 11/2019 137


Maintenance

138 EIO0000001133 11/2019


Harmony
Index
EIO0000001133 11/2019

Index

A M
Accessories, 22 maintenance, 131
check points, 135
Maintenance
B Cleaning, 132
battery, 136 maintenance accessories, 24
memory, 41, 55, 69, 84, 99

C
caution N
loss of data, 122 notice
equipment damage, 134 loss of data, 122
injury, 113, 113 panel unsteady when unsecured, 111
loss of communication, 44, 44, 45, 58, 59, 72, 73, loss of data, 136
87, 88, 102, 103 overtorque, 112, 114
CE marking, 11 panel unsteady when unsecured, 113
Certifications and Standards, 11
cleaning, 132
clock, 41, 55, 69, 84, 99 O
COM1, 17, 18, 19 optional accessories, 23
connecting the power cord, 116
connecting the power supply, 118
P
parts identification and functions, 25
D power plug, 116
danger
arc flash, 136
chemical hazard, 136 R
electric shock, 43, 45, 57, 59, 71, 73, 86, 88, 101, replacing the battery, 136
103, 136 RS-232C, 17, 18
explosion, 127, 129, 136, 136 RS-422/RS-485, 18
fire, 136 RS-485, 19
dimensions, 46, 60, 74, 89, 104

S
E SD Card, 121
Ethernet, 19 backup, 125
insertion, 123
SD Card accessories, 23
F serial interface accessories, 22
function keys, 41 specifications
COM, 43, 57, 59, 73, 86, 88, 101, 103
COM1, 42, 56, 57, 70, 71, 85, 86, 100, 101
G COM2, 42, 45, 56, 59, 70, 73, 85, 88, 100, 103
gasket, 134 display, 40, 54, 68, 83, 98
grounding, 120 electrical, 37, 50, 65, 79, 94
environmental, 38, 51, 66, 80, 95
Ethernet, 100
I interfaces, 42, 56, 70, 85, 100
installation SD Card, 56, 70, 100
procedures, 110 structural, 39, 52, 67, 81, 96
installation gasket, 133 USB, 42, 42, 56, 56, 70, 70, 85, 85, 85, 100

K T
KC marking, 12 touch panel, 41, 55, 69, 84, 99

EIO0000001133 11/2019 139


Index

U
USB
cable clamp for USB Type A, 127
holder mini-B, 129
USB interface accessories, 23
USB mini-B, 20
USB Type A, 20

W
warning
electromagnetic interference, 116
fire, 118
short circuit, 118
unintended equipment operation, 7, 118

140 EIO0000001133 11/2019

You might also like