J03 - TRF 2 CT Test
J03 - TRF 2 CT Test
J03 - TRF 2 CT Test
50/1 A 100/1 A
SIEMENS 5P20 50-100/1 A 4MC7033 ZEK
5 VA 7.5 VA
Serial Number R Y B
2. VISUAL CHECKS:
1.Mechanical Damage : NO
2.Tight Connections : OK
3.Star Point Connected and Earth: OK
Test Points L1 L2 L3
CT Sec.Core – Earth (500 V DC) GΩ GΩ GΩ
Primary – secondary(2500 V DC) GΩ GΩ GΩ
Core (1S1-1S2)
Phases Core (1S1-1S3)
Phases A. Temp mΩ R. Temp mΩ
A. Temp mΩ R. Temp mΩ
L1
L1 CT ANALYSER
L2
TEST CT
REPORT
ANALYSER
ATTACHED
L2
L3 TEST REPORT ATTACHED
L3
5. CT POLARITY TEST BY FLICK TEST:
Phases 1S1-1S2
L1 OK
P1(+ve),P2(-ve)
L2 OK
S1(+ve),S2,(-ve)
L3 OK
Phases 1S1-1S3
L1 OK
P1(+ve),P2(-ve)
L2 OK
S1(+ve),S3(-ve)
L3 OK
6. CT SATURATION TEST:
7. RATIO TEST:
(CT ANALYSER TEST REPORTS ARE ATTACHED ALONG WITH THIS REPORT.)
9. REMARKS
50/1 A 100/1 A
SIEMENS 1FS5 50-100/1 A 4MC7033 ZEK
5 VA 7.5 VA
Serial Number R Y B
2. VISUAL CHECKS:
1.Mechanical Damage : NO
2.Tight Connections : OK
3.Star Point Connected and Earth: OK
Test Points L1 L2 L3
CT Sec.Core – Earth (500 V DC) GΩ GΩ GΩ
Primary – secondary(2500 V DC) GΩ GΩ GΩ
Core (1S1-1S2)
Phases Core (1S1-1S3)
Phases A. Temp mΩ R. Temp mΩ
A. Temp mΩ R. Temp mΩ
L1
L1 CT ANALYSER
L2
TEST CT
REPORT
ANALYSER
ATTACHED
L2
L3 TEST REPORT ATTACHED
L3
5. CT POLARITY TEST:
Phases 1S1-1S2
L1 OK
P1(+ve),P2(-ve)
L2 OK
S1(+ve),S2,(-ve)
L3 OK
Phases 1S1-1S3
L1 OK
P1(+ve),P2(-ve)
L2 OK
S1(+ve),S3(-ve)
L3 OK
6. CT SATURATION TEST:
7. RATIO TEST:
(CT ANALYSER TEST REPORTS ARE ATTACHED ALONG WITH THIS REPORT.)
L1-L2 50 A 100/1 A 50 50 0
L2-L3 50 A 100/1 A 0 50 50
L3-L1 50 A 100/1 A 50 0 50
9. REMARKS