PROJECT

SPECIFICATION

TITLE: BRUNA BAUTISTA VILLE CPM

LOCATION: RIZAL SANTIAGO CITY


SPECIFICATIONS

General Conditions

All parts of the construction shall be finished with good workmanship to the
fullest talent and meaning of the plans and specifications, and to the entire satisfaction
of the Contractor and Owner.

Excavation

All excavation shall be made to grade indicated in the drawings. Where the
building site is covered with any kind of fill, the excavation for footings should be made
deeper until the stratum for safe bearing capacity of the soil reached.

Backfills

After concrete for foundations are hard enough to withstand pressure resulting
from fill, the materials removed from excavation shall be used backfill around them.

Backfills and fills shall be placed in layers not exceeding 100mm in thickness, and
layer shall be thoroughly compacted by wetting and tamping.

Proportioning Of Concrete

All concrete shall be done in accordance with the standard specifications for plan
and reinforced concrete as adopted by the Government. Cement to be use shall be
Portland cement so selected must meet the requirements of Portland cement and
approved by the designing Architect.
Forms and Concrete Works

All forms for concrete work shall be properly braced on tied together so as to
maintain the concrete position and shapes of the concrete members. Forms shall be
constructed sufficiently tight to prevent bulging and seepage of water.

Reinforcement Bars

All steel reinforcing bars to be used in this construction shall consist of round
deformed bars with lugs or projection on their sides to provide the greater bond
between the concrete and steel.

All steel reinforcing bars shall be accurately placed and secured against
displacement by trying together at each bar intersection with Gauge No. 12 GI wire.

The steel reinforcing bars indicated for footings, columns, slabs, beams and other
concrete members shall all conform to number, size and spacing as indicated in the
drawing or schedule of steel reinforcement.

No metal reinforcement shall be installed in place unless it is free form rust, scale
and other coating which will destroy or reduce the bond with concrete.

Concrete Hollow Blocks

All firewalls shall be at least 125mm thick, while concrete hollow blocks for front and
rear walls unless otherwise indicated, shall be 100mm thick..

The concrete hollow blocks walls shall be cells filled with cement mortar consisting
of 1 part Portland cement and 3 parts sand by volume. They shall be reinforced with
round deformed bars, 10mm diameter, spaced bot more than 0.80m on center, both
ways.
Floor Finishes

The materials are used as floor finished for rooms of the building shall be as follows.

Ground Floor : Plain Concrete

T&B : Unpolished Tiles 0.30 x 0.30 m

Counter Top : Unpolished Tiles 0.30 x 0.30 m

Loft

All steel reinforcing bars to be used in this construction shall consist of 2 x 3 tubular

All loft floor shall consist of ¾ flyboards

Stairs

All steel reinforcing bars to be used in this construction of the stairs shall consist of 2 x
3 c purlins and 2x2 tubular as railings

Walls

Plastered finish with paint off-white color .

Lumbers & Doors

Lumber to be used in this project will be well seasoned, thoroughly dry and free
from loose or unsound knots or other imperfections impairing their strength or
appearance.
The kind of lumber to be used for the various parts of the building shall be as
follows.

Exterior and Interior Door Jamb : Wood

Main Door & Exit Door : Flush Door

Toilet Doors : PVC Door

Roofing and Trusses

The type of roofing materials is 0.40mm color brown Rib Type The Trusses is 2x3
tubular with 2x3 GI Purlins.

Electrical Works

All electrical works and materials shall be conforming to provision of the latest
edition of Electrical code of the Philippine or National Electrical Code.

The electrical wiring shall be installed thru MOFLEX coilable PVC electrical conduit,
fillings and appurtenances the conform to ISO dimensions.

Electrical Materials to be used for the electric installation shall be as follows;

Automatic Circuit Breaker : Royu/Equivalent

Flush wall switches, CO

Other wiring device : Royu/ Equivalent


Wires/ Conductors : Phelps-Dodge Brand/ Equivalent

The spare circuit shall be approved with an empty PVC pipe, size 19 mm diameters
which should extend at least 300mm above the ceiling line.

The panel board shall be providing with a circuit directory.

Plumbing Works

All plumbing works for this project shall be done in accordance with the approved
plans and specifications.

The plumbing installation shall conform to the provision of the national Plumbing
code and the rules and regulations enforced in the locality.

The plumbing fixture and accessories to be provided and installed shall be as


follows;

Water Closet : Ordinary

Lavatory : Ordinary

Piping for drain, waste and vent shall be done using Neltex PVC. For the in
house water supply installation, Neltex PVC blue.

Fitting to be used
Floor drain : 100mm x 100mm, ordinary plate

Railings

All railings in this project shall consist of 2x2 & 2x3 tubular.

Glass Works

Analok & Awning framing with ¼ thk reflective bronze Glass in a sliding window.