Calibration Procedure for Delta4310/4110
http://www.megger.com
Valley Forge Corporate Center
2621 Van Buren Ave
Norristown, PA 19403-2329 USA Page 1 of 2
1-800-723-2861 PN: 82412 Rev. 1
June 27, 2012
Product Instructions
Calibration Procedure for Delta4310/4110
(In this step, the Control Unit and the HV are inter-connected, and the HV voltage is connected to 100PF
standard)
o Turn on Control Unit
o Start MIX software, then select Maintenance tab.
o You will need to re-start MIX software if you have just used it to program firmware.
o Press CTL-ALT-SHIFT-S on keyboard to enter “MAINTENANCE (SERVICE) MODE”.
o choose Calibration tab, and in Calibration Tasks window select only D190 and D200 ( All others must be
deselected).
Note: Before commencing calibration, ensure that the Delta4000 is setup correctly as follows: Low
Voltage Red cables is and HV cable are connected from the Delta4000 units to the certified 100 pF
standard, the two Interlocks are installed, short ground wire is installed between the two unit’s wing
nut grounds, Main Test Ground cable connected between earth ground and Test ground connector on
Control Unit, Connect HV Power and HV Control cables between the two Units, and supplied USB from
PC to Control Unit.
o Click “Start Calibration” button .
o Follow instructions on the computer (Mix software).
o Select save to instrument at the end of procedure.
o End of Procedure
Use PowerDB or the Delta control software to take multiple readings in different modes of the Capacitor
Standard used to verify the unit accuracy.