1756-td006 - ControlLogix Chassis Specifications Technical Data

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

Technical Data

1756 ControlLogix Chassis Specifications

Standard Catalog Numbers - Series B


1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

ControlLogix-XT Catalog Numbers


1756-A4LXT, 1756-A5XT, 1756-A7LXT
Topic Page
1756 Standard Chassis 3
1756 ControlLogix-XT Chassis 5
1756 Chassis Accessories 6
Spacing Requirements 7
Standard Mounting Dimensions 8

The ControlLogix system is a modular system that requires a 1756 I/O chassis.
All of the chassis are designed for horizontal-only, back-panel mounting. Place
any module into any slot. The backplane provides a high-speed
communication path between modules.

AutoCAD product drawings are available at


http://www.rockwellautomation.com/en/e-tools/drawings.html.
1756 ControlLogix Chassis Specifications

Important User Information


Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines
for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell
Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences
between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the
wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that
each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

ATTENTION
Identifies information about practices or circumstances that can lead to personal injury or death, property damage,
or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence

SHOCK HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may
be present.

BURN HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach
dangerous temperatures.

Rockwell Automation, Rockwell Software, Allen-Bradley, Tech-Connect, ControlLogix, ControlLogix-XT, RSLogix 5000, RSLinx, and Logix5000 are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

2 Publication 1756-TD006B-EN-E - June 2010


1756 ControlLogix Chassis Specifications

1756 Standard Chassis The chassis backplane provides a high-speed communication path between
modules and distributes power to each of the modules within the chassis.

Technical Specifications - 1756 Standard Chassis


Attribute 1756-A4 1756-A7 1756-A10 1756-A13 1756-A17
Backplane current, chassis/slot max @ 1.5 A/1.5 A
1.2V DC
Backplane current, chassis/slot max @ 4 A/4 A
3.3V DC
Backplane current, chassis/slot max @ 15 A/6 A
5.1V DC
Backplane current, chassis/slot max @ 2.8 A/2.8 A
24V DC
Slots 4 7 10 13 17
Mounting method Horizontal only

Dimensions (WxHxD), approx.(1) 263 x 169 x 145 mm 368 x 169 x 145 mm 483 x 169 x 145 mm 588 x 169 x 145 mm 738 x 169 x 145 mm
(10.35 x 6.65 x 5.71 in.) (14.49 x 6.65 x 5.71 in.) (19.0 x 6.65 x 5.71 in.) (23.15 x 6.65 x 5.71 in.) (29.06 x 6.65 x 5.71 in.)
Cabinet size (WxHxD), min 507 x 507 x 203 mm 507 x 609 x 203 mm 762x 507 x 203 mm 762 x 609 x 203 mm 914 x 762 x 203 mm
(20 x 20 x 8 in.) (20 x 24 x 8 in.) (30 x 20 x 8 in.) (30 x 24 x 8 in.) (36 x 30 x 8 in.)
Weight, approx. 0.75 kg (1.7 lb) 1.10 kg (2.4 lb) 1.45 kg (3.2 lb) 1.90 kg (4.2 lb) 2.20 kg (4.8 lb)
Location Panel
North American temperature code T5
IEC temperature code T6
Enclosure type rating None (open-style)
(1)
Dimensions include mounting tabs and power supply. Depth with extended terminal housing (catalog number 1756-TBE) is 160 mm (6.3 in.).

Environmental Specifications - 1756 Standard Chassis


Attribute 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17
Temperature, operating 0…60 °C (32…140 °F)
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
Temperature, surrounding air 60 °C (140 °F)
Temperature, storage -40…85 °C (-40…185 °F)
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
Relative humidity 5…95% noncondensing
IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat)
Vibration 5 g @ 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating)
Shock, operating 30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating 50 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions CISPR 11: Group 1, Class A
ESD immunity 6 kV contact discharges
IEC 61000-4-2 8 kV air discharges

Publication 1756-TD006B-EN-E - June 2010 3


1756 ControlLogix Chassis Specifications

Environmental Specifications - 1756 Standard Chassis


Attribute 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17
Radiated RF immunity 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz
IEC 61000-4-3 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
EFT/B immunity ±4 kV at 5 kHz on signal ports
IEC 61000-4-4
Conducted RF immunity 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
IEC 61000-4-6

Certifications - 1756 Standard Chassis

Certification(1) 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

UL UL Listed Industrial Control Equipment.


CSA CSA Certified Process Control Equipment.

CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations.
CE European Union 89/336/EEC EMC Directive, compliant with:
• EN 50082-2; Industrial Immunity
• EN 61326; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Ex European Union 94/9/EC ATEX Directive, compliant with:
EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
TÜV TÜV Certified for Functional Safety: up to and including SIL 2

(1)
When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

4 Publication 1756-TD006B-EN-E - June 2010


1756 ControlLogix Chassis Specifications

1756 ControlLogix-XT The ControlLogix-XT chassis support extreme temperature environments.


The chassis are conformally coated for increased survivability in ISA G3
Chassis environments.

Technical Specifications - 1756 ControlLogix-XT Chassis


Attribute 1756-A4LXT 1756-A5XT 1756-A7LXT
Backplane current, chassis/slot max @ 1.2V DC 1.5 A/1.5 A
Backplane current, chassis/slot max @ 3.3V DC 4 A/4 A
Backplane current, chassis/slot max @ 5.1V DC 10 A/6 A
Backplane current, chassis/slot max @ 24V DC 2 A/2 A
Slots 4 5 7
Mounting method Horizontal only

Dimensions (WxHxD), approx. (1) 158 x 267 x 145 mm 158 x 483 x 145 mm 158 x 368 x 145 mm
(6.22 x 10.5 x 5.71 in.) (6.22 x 19 x 5.71 in.) (6.22 x 14.49 x 5.71 in.)
Cabinet size (WxHxD), min 507 x 507 x 203 mm (20 x 20 x 8 in.) 507 x 507 x 203 mm (20 x 20 x 8 in.) 507 x 609 x 203 mm (20 x 24 x 8 in.)
Weight, approx. 0.75 kg (1.7 lb) 1.45 kg (3.2 lb) 1.1 kg (2.4 lb)
Location Panel
North American temperature code T5
IEC temperature code T5
Enclosure type rating None (open-style)
(1)
Dimensions include mounting tabs and power supply. Depth with extended terminal housing (catalog number 1756-TBE) is 160 mm (6.3 in.).

Environmental Specifications - 1756 ControlLogix-XT Chassis


Attribute 1756-A4LXT 1756-A5XT 1756-A7LXT
Temperature, operating -25…60 °C (-13…140 °F) -25…70 °C (-13…158 °F) -25…60 °C (-13…140 °F)
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
Temperature, storage -40…85 °C (-40…185 °F)
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
Relative humidity 5…95% noncondensing
IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat)
Vibration 2 g @ 10…500 Hz
IEC 60068-2-6 (Test Fc, Operating)
Shock, operating 30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating 50 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions CISPR 11: Group 1, Class A
ESD immunity 6 kV contact discharges
IEC 61000-4-2 8 kV air discharges
Radiated RF immunity 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz
IEC 61000-4-3 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz

Publication 1756-TD006B-EN-E - June 2010 5


1756 ControlLogix Chassis Specifications

Certifications - ControlLogix-XT Chassis

Certification(1) 1756-A4LXT, 1756-A5XT, 1756-A7LXT

c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.
CE European Union 2004/108/EC EMC Directive, compliant with:
• EN 61000-6-4; Industrial Emissions
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
Ex European Union 94/9/EC ATEX Directive, compliant with:
• EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
• EN 60079-0; General Requirements II 3 G Ex nA IIC T5 X
C-Tick Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

(1)
When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1756 Chassis Accessories Use a slot filler module to fill empty slots.

Cat. No. Description


1756-N2 Slot filler module for empty slots in standard
ControlLogix chassis
1756-N2XT Slot filler module for empty slots in ControlLogix-XT
chassis

6 Publication 1756-TD006B-EN-E - June 2010


1756 ControlLogix Chassis Specifications

Spacing Requirements When you mount a chassis with a standard power supply in an enclosure, meet
these spacing requirements.
Enclosure

15.3 (6.0)

10.2 10.2
(4.00) (4.00)
15.3…20 (6.0…8.0)

5.1(2.0)
Wireway
5.1(2.0)

7.7…10.2
(3.0…4.0)
15.3 (6.0)

Dimensions are in cm (in.).

If you use a 1756-PSCA2 chassis adapter with a redundant power supply,


follow the same spacing requirements as for a standard power supply. You
need the clearance on the left of the chassis for cable access.
Enclosure

1756-PA75R or 1756-PA75R or
1756-PB75R 1756-PB75R

15.3...20
(6.0...8.0)

ControlLogix with
1756-PSCA2

> 10.2 > 10.2


> 15.3
(4.0) (4.0)
(6.0)

Dimensions are in cm (in.).

Publication 1756-TD006B-EN-E - June 2010 7


1756 ControlLogix Chassis Specifications

Standard Mounting Right-side View of Standard Chassis


Dimensions
16.9
(6.65)

1756-TBE
Extended Housing

14.5
(5.8)

16.0
(6.3)
Dimensions are in cm (in.).

1756-A4 Chassis with Power Supply


7.0
1.1 (2.76) 0.55
(0.433) (0.217)

16.9
15.8 cm (6.65)
(6.22 in.) 14.5
(5.71)

0.55 4.5
0.78
(0.217) (1.77)
26.3 (0.31)
(10.35)

18.54
(7.30)
Dimension with 1756-PSCA2

Dimensions are in cm (in.).

1756-A7 Chassis with Power Supply


1.1 cm 17.5 cm 0.55 cm
(0.433 in.) (6.89 in.) (0.217 in.)

16.9 cm
15.8 cm (6.65 in.)
(6.22 in.) 14.5 cm
(5.71 in.)

0.55 cm 4.7 cm
(1.85 in.) 0.78 cm
(0.217 in.) 36.8 cm (0.31 in.)
(14.48 in.)

29.04 cm
(11.44 in.)
Dimension with 1756-PSCA2
Dimensions are in cm (in.).

8 Publication 1756-TD006B-EN-E - June 2010


1756 ControlLogix Chassis Specifications

1756-A10 Chassis with Power Supply


0.55
(0.217)
1.1 14.0 14.0 5.71
(0.433) (5.51) (5.51) (2.25)

16.9
15.8 (6.65)
(6.22) 14.5
(5.71)

0.55
0.78
(0.217)
48.8 (0.31)
(19.02)
40.54
(15.96) Dimension with 1756-PSCA2
Dimensions are in cm (in.).

1756-A13 Chassis with Power Supply


0.55
(0.217) 14.0 10.5 14.0
1.1 5.71
(5.51) (4.13) (5.51)
(0.433) (2.25)

16.9
15.8 (6.65)
(6.22) 14.5
(5.71)

0.55
(0.217) 0.78
58.8
(23.15) (0.31)
51.04 Dimension with 1756-PSCA2
(20.10)

Dimensions are in cm (in.).

1756-A17 Chassis with Power Supply


0.55
(0.217) 14.0 13.3 14.0 13.3
1.1 (5.51) (5.24) (5.51) (5.24) 4.7
(0.433) (1.85)

16.9
15.8 (6.65)
(6.22) 14.5
(5.71)

0.78
73.8 (0.31)
(29.06)
66.04 Dimension with 1756-PSCA2
(26.0)

Dimensions are in cm (in.).

Publication 1756-TD006B-EN-E - June 2010 9


1756 ControlLogix Chassis Specifications

ControlLogix-XT Mounting Right-side View of ControlLogix-XT Chassis


Dimensions

16.9
(6.65)

14.5
(5.71)
Dimensions are in cm (in.).

1756-A4LXT Chassis with Power Supply


6.99
(2.75)

16.9
(6.65)
13.97 15.24
(5.5) (6)

25.4
(10)
Dimensions are in cm (in.).

10 Publication 1756-TD006B-EN-E - June 2010


1756 ControlLogix Chassis Specifications

1756-A5XT Chassis with Power Supply


5.71
(2.25)
14.0 14.0
(5.51) (5.51)

16.9
15.8 (6.65)
(6.22)
14.5
(5.71)

48.3
(19.0)
Dimensions are in cm (in.).

1756-A7LXT Chassis with Power Supply


4.71
(1.85)
17.5
(6.89)

16.9
(6.65)
15.8
(6.22)
14.5
(5.71)

36.8
(14.49)
Dimensions are in cm (in.).

ControlLogix-XT Mounting Tab Dimensions


Top Mounting Tab Bottom Mounting Tab
0.55
(0.217)
1.1
(0.433)

Publication 1756-TD006B-EN-E - June 2010 11


Rockwell Automation Support

Rockwell Automation provides technical information on the Web to assist you in using its products. At
http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and
application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the
best use of these tools.

For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect
support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit
http://www.rockwellautomation.com/support/.

Installation Assistance

If you experience an anomaly within the first 24 hours of installation, review the information that is contained in this manual.
You can contact Customer Support for initial help in getting your product up and running.

United States or Canada 1.440.646.3434


Outside United States or Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html,
Canada or contact your local Rockwell Automation representative.

New Product Satisfaction Return

Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing
facility. However, if your product is not functioning and needs to be returned, follow these procedures.

United States Contact your distributor. You must provide a Customer Support case number (call the phone number
above to obtain one) to your distributor to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.

Documentation Feedback

Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.

Publication 1756-TD006B-EN-E - June 2010


Supersedes 1756-TD006A-EN-E - May 2009 Copyright © 2010 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

You might also like