Part 4 Troubleshooting
4. Troubleshooting ............................................................ 74
68 Troubleshooting
MCAC-VTSM-2013-03 R410A Full DC Inverter Mini VRF
1. PCB ports instructions
Troubleshooting 69
R410A Full DC Inverter Mini VRF M CAC-VTSM-2013-03
26CN63 Loading output terminal (Delay control of DC power) AC 220V
27CN61 Loading output terminal(crankcase heating control) AC 220V
28CN57 Loading output terminal(solenoid valve SV6 control) AC 220V
29CN20 Program terminal connected to the computer ---
LED digital
tube display
SW2: Query
button Function setting
dial switch
SW1:
Forced
cooling
UPD78F0537A
button
IRMCF341
70 Troubleshooting
MCAC-VTSM-2013-03 R410a Full DC Inverter Mini VRF
Remark:
1) Normal display: Display frequency of compressor when capacity needing.
2) Standby;
3) 7
4) SW1: Forced cooling button.
SW2: Query button.
SW3
ON Obtain network address automatically
1
OFF Obtain network address manually
ON Revocation indoor unit network address
2
OFF /
Troubleshooting 71
R410A Full DC Inverter Mini VRF M CAC-VTSM-2013-03
2.4 LED on PCB instructions
LED 1 (Red)
LED 2(Green)
LED1: Malfunction indicator lamp of inverter module. The lamp will be off if the system running is normal.
And it will be on if the inverter module is faulty and the error code will display on digital tube.
LED2: Running indicator lamp of inverter module. The lamp will be on if the system running is normal.
72 Troubleshooting
MCAC-VTSM-2013-03 R410A Full DC Inverter Mini VRF
3. Error code table
Error code Content Note
HF Not matched with M_HOME indoor unit Only display on 18kW
E0 For 12~16kW model
EEPROM malfunction
E9 For 18kW model
E2 Communication malfunction between indoor/outdoor units All the unit
E3 For 12~16kW model
Communication malfunction in outdoor PCB
H0 For 18kW model
E4 T3&T4 temperature sensor malfunction All the unit
L6 Reserved ----
Speed difference>15Hz protection between the front and the For 18kW model
L8
back clock
Speed difference>15Hz protection between the real and the For 18kW model
L9
setting speed
Troubleshooting 73
R410a Full DC Inverter Mini VRF MCAC-VTSM-2013-03
4. Troubleshooting
4.1 HF: not matched with M_Home indoor unit.(Only display on 18kW model)
LED display HF
The communication between indoor unit chip and outdoor unit chip is not matched.
YES
NO
Replace indoor unit or chip of indoor unit
Whether the chip of indoor unit is right or not.
74 Troubleshooting
MCAC-VTSM-2013-03 R410A Full DC Inverter Mini VRF
4.2 E0/E9: EEPROM malfunction (E0 display on 12~16kW model;E9 display on 18kW model)
The malfunction may be caused by two reasons:
1) The EEPROM is not inserted well;2) Outdoor main board is broken.
LED display E0 or E9
EEPROM malfunction
YES
Troubleshooting 75
R410a Full DC Inverter Mini VRF MCAC-VTSM-2013-03
4.3 E2: Communication malfunction between indoor unit chip and outdoor unit chip.
LED displays E2
Communication malfunction between indoor unit chip and outdoor unit chip.
YES
Judge 2: check whether the three-cored NO Replace shielded wire or earth the wire
shielded wire is used as the communication properly.
wire and earthed properly.
YES
NO
Judge 3: check the communication wire
Connect the wire again.
sequence is correct or not.
YES
Judge 4: Check whether there is disconnection.
Replace
NO
76 Troubleshooting
MCAC-VTSM-2013-03 R410a Full DC Inverter Mini VRF
4.4 E3/H0: Communication malfunction in outdoor PCB (E3 display on 12~16kW; H0 display on 18kW)
NO
NO
NO
Check whether the connecting wiring between the YES Insert the connecting wiring well over
IPM module positive pole and the CN12 on the power again
board is break off
NO
NO
Troubleshooting 77
R410a Full DC Inverter Mini VRF MCAC-VTSM-2013-03
4.5 E4: T3&T4 sensor malfunction
LED displays E4
YES
Judge: T3&T4 sensor malfunction
Replace T3/T4 sensor
NO
YES
Judge: whether the body is broken. Connect the wire again.
NO
NO
78 Troubleshooting
MCAC-VTSM-2013-03 R410a Full DC Inverter Mini VRF
4.6 E5: Voltage protection malfunction
LED displays E5
NO
Judge whether the input voltage is 180-260V Check the power supply.
YES
Replace the filter board to check whether the unit operates YES
normally. OK
NO
Troubleshooting 79
R410a Full DC Inverter Mini VRF MCAC-VTSM-2013-03
4.7 E6:DC Fan Error
The error may be caused by two reasons:
1). The wiring connection is wrong; 2). Power supply voltage is not normal.
LED displays E6
NO
Refers to the wiring nameplate to check Connect again.
whether the DC fan wiring correct or not.
YES
Adjust to the right
range. Then
NO NO check whether
Check whether PN voltage of the DC fan Insure the input power
the system is
transfer board is from 255V to 367V. supply is 380-415V,
running normally.
3N, 50Hz.
YES
YES
DC fan motor power supply is normal, Check the Replace main control
Voltage between DC fan motor s white terminal board
and black terminal is 15V at stand by state
NO
Whether the outdoor fan will work after the indoor fan
operates for 3 minutes.
NO
80 Troubleshooting
MCAC-VTSM-2013-03 R410a Full DC Inverter Mini VRF
4.8 E7/EA: Discharge Sensor Malfunction (E7 display on 12~16kW; EA display on 18kW)
T3 pipe temperature exceeds 27 degrees for more than 5 minutes under heating mode.
YES
Whether the outdoor ambient temperature is higher than Belongs to system
the unit s operating condition under heating mode. normal protection
NO
Connect the pipe again,
Check whether the refrigerant volume of the system is
YES check leakage, insure the
added according to the requirement and check if the
pressure & add the
refrigerant leaks.
refrigerant.
NO
YES
Check whether the condenser is
Rectify the pipe system.
blocked?
NO
NO
Troubleshooting 81
R410a Full DC Inverter Mini VRF MCAC-VTSM-2013-03
4.10 P1 malfunction: High pressure protection
LED displays P1
NO
YES
NO
Judge: short-circuit high pressure switch. Check the
Replace the high pressure
system can operate normally.
switch.
YES
YES
Judge 3: whether high pressure of the system is too high. Stop the system.
NO
NO
Judge 4: whether side air duct of outdoor unit meets the Rectify the air duct
standard.
YES
YES
NO
NO
82 Troubleshooting
MCAC-VTSM-2013-03 R410a Full DC Inverter Mini VRF
4.12 P2: Low pressure protection
LED displays P2
NO
Judge 1: whether wiring connection between low pressure Connect well
switch and PCB is connected well or properly.
YES
YES
Confirm: short-circuit low pressure switch and check
Replace low pressure.
whether the system can work normally.
NO
YES
Judge 3: Check whether the outdoor ambient temperature is too low. Stop the unit.
NO YES
NO
YES Remove the refrigerant pipe and then use high
Judge 7:whether the refrigerant pipe is blocked. pressure nitrogen or refrigerant to blow the pipe.
Vacuume the pipe then add the refrigerant again.
NO
Troubleshooting 83
R410a Full DC Inverter Mini VRF MCAC-VTSM-2013-03
4.13 P3: Compressor current protection
It will protect when input current is more than 15A. It will recover when input current is less than 15A.
It will recover automatically.
LED displays P3
YES
YES
Judge 2: Check whether the outdoor ambient temperature is Stop the unit.
too high.
NO YES
Judge 3: check whether the outdoor unit ventilates well. Make the outdoor unit
ventilates well.
NO
YES
`
Judge 4: whether the heat exchanger needs cleaning or not. Clean heat exchanger.
NO
YES Remove the refrigerant pipe and then use
Judge 5: if the refrigerant pipe is blocked or not? high pressure nitrogen or refrigerant to blow
the pipe. Vacuume the pipe then add the
NO refrigerant again.
84 Troubleshooting
MCAC-VTSM-2013-03 R410a Full DC Inverter Mini VRF
4.14 P4:Compressor discharged temperature protection
When the discharged temperature of the compressor is higher than 115°C, the unit will stop running.
When the discharged temperature of the compressor is lower than 90°C , the unit resumes normal
operation automatically.
LED displays P4
NO
Judge: whether the discharged temperature sensor Stop leaking and then confirm the
is damaged or not. refrigerant volume again.
NO
Judge: check whether resistance of compressor Replace compressor discharged
discharged temperature sensor is correct or not . temperature sensor.
YES
Troubleshooting 85
R410a Full DC Inverter Mini VRF MCAC-VTSM-2013-03
4.15 P5: Condenser high temperature protection
When condenser temperature is higher than 62 degrees for 3 seconds, the unit will stop operating.
When pipe temperature outside is lower than 52 degrees, the unit will resume operate.
LED displays P5
YES
NO
NO
Check whether the resistance of condenser
Replace the temperature sensor
temperature sensor is correct.
YES
NO
YES
Clean heat exchanger Judge 2: whether heat exchanger needs cleaning.
NO
Remove the refrigerant pipe and then YES
use high pressure nitrogen or Judge 3: if refrigerant pipe is blocked or not?
refrigerant to blow the pipe.
Vacuumed the pipe then add the NO
refrigerant again.
Replace outdoor PCB.
86 Troubleshooting
MCAC-VTSM-2013-03 R410a Full DC Inverter Mini VRF
4.16 P6: IPM Module protection
The following explanation is for 12~16kw.
LED displays P6
YES NO
YES Connect firmly
again and
Check if wiring connection NO check whether Check whether power Connect firmly again
it is connected NO
between main PCB and IPM wiring is connected and check whether it is
correctly. connected right.
module is fasten or not. correctly and firmly.
NO NO
YES YES
Troubleshooting 87
R410a Full DC Inverter Mini VRF MCAC-VTSM-2013-03
The following explanation is for 18kW
88 Troubleshooting
MCAC-VTSM-2013-03 R410a Full DC Inverter Mini VRF
1.1 DC generatrix detection
Troubleshooting 89
R410a Full DC Inverter Mini VRF MCAC-VTSM-2013-03
2.1 The voltage between N and P should be 1.41times to local power supply.
2.2 The voltage between 1 and 2 should range from 510V to 580V
2.3 The resistance between 1,2,3,4,5 should be infinite. If any of them is about 0, which means the
module has already been broken down, we need to replace the module.
3 Compressor's characteristics
3.1 Measure the resistance among the compressor's U,V,W respectively. The resistance should range
from 0.9 to 5 Ohms and be the same.
3.2 Measure the resistance between the compressor's U,V,W and GND respectively. The resistance
should be more or less mega-Ohms.
90 Troubleshooting
MCAC-VTSM-2013-03 R410a Full DC Inverter Mini VRF
3.3 Measure the current of the compressor's U,V,W terminal respectively, which should be more or less
the same, by e.g. current flow table clamp.They should be 4A at the frequency of 35 Hertz.
In normal situation:
LED 1: Flash in 1Hz (slowly flash) when standby
LED 1: On when running
LED 2: Off
Phenomenon A
LED 2 red ON
LED 1 green Flashes 8 times and stops for 1S, then repeat.
Error: Inverter module failure
Phenomenon B
LED 2 red ON
LED 1 green Flashes 9 times and stops for 1S, then repeat.
Troubleshooting 91
R410a Full DC Inverter Mini VRF MCAC-VTSM-2013-03
Error: Low voltage protection
Here are 3 circumstances:
a) The voltage between the two electrolytic capacitors is less than 450V. The AC contactor should be picked
up. If not, there's something wrong with the main control board or the PTC resistors, which need to be
replace correspondingly.
b) Somewhere is loose in the circuit.
c) The voltage between P and N of CN12 on the main control board should range from 450V to 570V. If the
voltage between N terminal and middle terminal of CN12 is 15V while error displays, it means that the main
control board fails. Please replace the main control board.
Phenomenon C
LED 2 Red ON
LED1 Green Flashes 10 times and stops for 1S, then repeat.
Error: High voltage protection
Here are 2 circumstances:
1. Three-phase power supply 's voltage is more than 440V
2. Main control board fails. Please replace it.
92 Troubleshooting
MCAC-VTSM-2013-03 R410a Full DC Inverter Mini VRF
4.17 PE/P7 malfunction: Evaporator T2 high temperature protection
(PE display on 12~16kW, P7 display on 18kW)
When the middle average temperature of the evaporator is higher than 63 degrees for 50 seconds, the
unit will stop operating. When pipe temperature is lower than 50 degrees, the unit will resume running.
YES
Check whether average temperature of evaporator is
higher than 63 degrees for 50 seconds or not.
NO
YES
NO
YES
Clean heat exchanger Judge 2: whether the heat exchanger needs cleaning.
NO
Remove the refrigerant pipe and then YES
use high pressure nitrogen or refrigerant Judge 3: whether the refrigerant pipe is blocked.
to blow the pipe. Vacuums the pipe then
add the refrigerant again. NO
Troubleshooting 93
R410a Full DC Inverter Mini VRF MCAC-VTSM-2013-03
4.18 P8: Typhoon protection
LED displays P8
Typhoon protection
NO
NO
Check whether the fan motor is normal. Replace fan motor.
YES
94 Troubleshooting