Flowcon SM 15-40Mm: Dynamic Self Balancing Control Valve
Flowcon SM 15-40Mm: Dynamic Self Balancing Control Valve
Flowcon SM 15-40Mm: Dynamic Self Balancing Control Valve
SPECIFICATIONS
Pressure rating: 2500 kPa / 360 psi
Temperature rating, media: -20°C to +120°C / -4°F to +248°F
Temperature rating, ambient: -10°C to +50°C / +14°F to +122°F
Material:
- Diaphragm: Hydrogenated acrylonitrile-butadiene-rubber
- Body: Forged brass ASTM CuZn40Pb2
- Union end connections: Brass alloy ISO or NPT
- O-rings: EPDM
- Internal metal components: Stainless steel
Body tappings : 1/4” NPT
Maximum close off pressure: 600 kPa / 87 psi
Maximum operational ΔP: 320 kPaD / 46 psid
Flow rate range: 0.176-2.34 l/sec / 2.78-37.1 GPM
H1 H3
H2 H2
C L C C L C
1.5
Flow (l/sec)
SM.1.1
0.5
0
0 2 4 6 8 10 12
Voltage (volt) (at max setting)
Note 3: Above curves show the control curve of the valves in maximum allowed pre-setting
condition and may vary if lower pre-settings are selected. The valves will always have 1.000
positions between the pre-set flow value and 0V if control range is selected to 0-10V.
H=15mm=1/2” K=15mm
E=15mm=1/2”
15-25mm, 1/2”-1” I=20mm=3/4” L=18mm
F=20mm=3/4” J=25mm=1” M=22mm
Example: SM.2.1.B.1.Q.Q.I=SM 25-40mm body with p/t plugs, standard brush basic actuator and 40mm ISO female threaded end connections.
ACTUATOR SPECIFICATIONS4
Note 5: Above values are related to maximum flow rate setting of the
valve and thereby defining the flow through the valve at maximum
control signal, normally 10V. Values above do not relate to control
signals below 10V. All above valves will have 1.000 positions
between the pre-set flow value and 0V if control range is selected
to 0-10V.
The SM Series are self balancing dynamic flow control valves that are pressure independent, two-way, modulating
to accept digital or analog input signals. The valves accept 2-10V DC, 4-20mA or digital 3-point floating input signals.
Each valve has an adjustable maximum flow rate setting to enable flow limitation and balancing to the coils or zones
that the valves are controlling.
GENERAL SPECIFICATIONS
1. PRESSURE INDEPENDENT DYNAMIC CONTROL VALVES - FLOWCON SM
1.1. Contractor shall install pressure independent dynamic control valves where indicated in drawings.
1.2. Valve shall be an electronic, dynamic, modulating, 2-way pressure independent control device.
1.3. Pressure independent dynamic control valve shall accurately control flow, independent of system
pres sure fluctuation.
1.4. Maximum flow setting shall be adjustable to 51 different settings within the range of the valve size.
2.a. VALVE ACTUATOR / FLOWCON SM.0.0.0.1
2.a.1. Valve actuator housing shall be rated to IP42.
2.a.2. Actuator shall be driven by a 24V AC or 30V DC motor, and shall accept 2-10V DC, 4-20mA or 3-point
floating electric signal and shall include resistor to facilitate any of these signals.
2.a.3. Actuator shall be capable of providing 4-20mA or 2-10V DC feedback signal to the control system.
2.a.4. External LED read-out of current valve position and maximum valve position setting shall be available.
OR...
2.b. VALVE ACTUATOR / FLOWCON SM.0.0.0.3, SM.0.0.0.4, SM.0.0.0.5 and SM.0.0.0.6
2.b.1. Valve and actuator coupling shall have snap couplings for fast mounting and demounting.
2.b.2. Actuator housing shall be rated to IP54 including up-side-down mounting.
2.b.3. Actuator shall be driven by a 24V AC/DC motor and shall accept 0-10V DC, 2-10V DC, 0-20mA,
4-20mA, 2-position or 3-point floating electric input signal.
2.b.4. Actuator shall be capable of providing same as input, 4-20mA, 0-10V DC or 2-10V DC feedback
signal to the control system.
2.b.5. Automatic calibration of valve position shall be standard.
2.b.6. Actuator shall include display and buttons for external programming of all settings.
2.b.7. External display of current valve flow, maximum valve flow, input signal, feedback signal and
operational direction shall be standard.
2.b.8. Optional fail safe system to power valve to either open (max. setting) or closed position from any
position in case of power failure shall be available.
2.b.9. Optional BACnet connection for remote setting and control of actuator shall be available.
3. VALVE HOUSING
3.1. Valve housing shall consist of forged brass ASTM CuZn40Pb2, rated at no less than 2500 kPa static
pressure and +120°C.
3.2. Valve housing shall be permanently marked to show direction of flow.
3.3. Valve housing shall be double union end constructed with a range of pipe connections available for
the appropriate pipe size.
3.4. Optional dual pressure/temperature test plugs for verifying accuracy of flow performance shall be
available for all valve sizes.
4. FLOW REGULATOR / AUTOMATIC BALANCING UNIT
4.1. Flow regulation unit shall be manufactured of stainless steel and hydrogenated acrylonitrile-
butadiene-rubber and shall be capable of controlling flow within ±5% rated flow rate or ±2% of maxi-
mum flow rate.
4.2. Flow regulation unit shall be accessible for change-out maintenance.
RETURN RETURN
COIL
COIL
SUPPLY
SUPPLY
UPDATES