Opto Input Mappings: Non - Latching

The document describes the mapping of digital data bus (DDB) signals for a MiCOM P143 programmable scheme logic. It maps DDB signals for opto inputs, circuit breaker status, fault records, output relays, check synchronization and voltage monitoring, protection elements including overcurrent, earth fault, power, and sensitive power, and trip signals. It contains the DDB numbers for these mappings across multiple pages of the programmable logic diagram.

Uploaded by

sani priadi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
259 views6 pages

Opto Input Mappings: Non - Latching

The document describes the mapping of digital data bus (DDB) signals for a MiCOM P143 programmable scheme logic. It maps DDB signals for opto inputs, circuit breaker status, fault records, output relays, check synchronization and voltage monitoring, protection elements including overcurrent, earth fault, power, and sensitive power, and trip signals. It contains the DDB numbers for these mappings across multiple pages of the programmable logic diagram.

Uploaded by

sani priadi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

MiCOM P143 Programmable Scheme Logic

Opto Input Mappings


L1
L1 BB1 MCB TRIP SG Select x1
DDB #032 DDB #526
L2 BB2 MCB TRIP MCB/VTS SG Select 1x
1
L2
DDB #033 DDB #231 DDB #527

L3
L3 CS DISABLE IN1>3 Timer Blk
DDB #034 DDB #210

IN1>4 Timer Blk


DDB #211

L4
L4 CS ENABLE I>3 Timer Block
DDB #035 DDB #205
I>4 Timer Block
DDB #206

L5
L5 CS OVERIDE Reset Relays/LED
DDB #036 DDB #235

L6
L6 DC MCB FAIL SR User Alarm 1 Ext. Trip 3ph
DDB #037 DDB #168 DDB #227

L7
Input L7 CB Aux 3ph(52-A)
DDB #038 Non - LED 8 DDB #228
Latching DDB #071
L8
Input L8 CB Aux 3ph(52-B)
DDB #039 DDB #229

L15
L15 EXT RESET
DDB #046
Reset Relays/LED
DDB #235
Reset Lockout
DDB #237

1 Test Mode
DDB #441
L16
L16 IN SERVICE
DDB #047

Circuit Breaker Mapping


CB Closed 3 ph CB in Service
DDB #379 DDB #454

Fault Record Trigger Mapping


R3 OC.EF TC2 R3
Fault REC TRIG
DDB #002 DDB #144

Output Relay Mappings


0
R1 OC.EF L.O R1
Straight DDB #000
I>1 Trip
DDB #243 0

IN1>1 Trip
DDB #261
1
0
R2 OC.EF TC1 R2
Straight DDB #001
0

Check Synch. and Voltage Monitor Mapping


L4
L4 CS ENABLE
DDB #035

SysChks Inactive CS1 Enabled


DDB #449 DDB #450

Check Sync 1 OK
& CS2 Enabled
DDB #451
DDB #447

Check Sync 2 OK
DDB #448
1 Check Sync Alt1
DDB #1915
Live Line
DDB #443
&
Dead Bus
DDB #446

Dead Line
&
DDB #444

1 Page : 1
Live Bus
DDB #445 &
MiCOM P143 Programmable Scheme Logic

Stg1 f+t Trp


DDB #1282
Stg1 f+df/dt Trp
DDB #1283
Stg1 df/dt+t Trp
DDB #1285
Stg1 f+Df/Dt Trp
DDB #1287

Stg2 f+t Trp


DDB #1296
Stg2 f+df/dt Trp
DDB #1297
Stg2 df/dt+t Trp
DDB #1299
Stg2 f+Df/Dt Trp
DDB #1301

Stg3 f+t Trp


DDB #1310
Stg3 f+df/dt Trp
DDB #1311
Stg3 df/dt+t Trp
DDB #1313
Stg3 f+Df/Dt Trp
DDB #1315

Stg4 f+t Trp


DDB #1324
Stg4 f+df/dt Trp
DDB #1325
Stg4 df/dt+t Trp
DDB #1327
Stg4 f+Df/Dt Trp
DDB #1329

Stg5 f+t Trp


DDB #1338

Stg5 f+df/dt Trp


DDB #1339

Stg5 df/dt+t Trp


1
DDB #1341

Stg5 f+Df/Dt Trp


DDB #1343

Stg6 f+t Trp


DDB #1352
Stg6 f+df/dt Trp
DDB #1353
Stg6 df/dt+t Trp
DDB #1355
Stg6 f+Df/Dt Trp
DDB #1357

Stg7 f+t Trp


DDB #1366
Stg7 f+df/dt Trp
DDB #1367
Stg7 df/dt+t Trp
DDB #1369
Stg7 f+Df/Dt Trp
DDB #1371

Stg8 f+t Trp


DDB #1380
Stg8 f+df/dt Trp
DDB #1381
Stg8 df/dt+t Trp
DDB #1383
Stg8 f+Df/Dt Trp
DDB #1385

Stg9 f+t Trp


DDB #1394
Stg9 f+df/dt Trp
DDB #1395
Stg9 df/dt+t Trp
DDB #1397
Stg9 f+Df/Dt Trp
DDB #1399 Page : 2
MiCOM P143 Programmable Scheme Logic

dv/dt1 Trip
DDB #556

dv/dt2 Trip
DDB #560

Power>1 3Ph Trip


DDB #738

Power>1 A Trip
DDB #739
Power>1 B Trip
DDB #740
Power>1 C Trip
DDB #741

Power>2 3Ph Trip


DDB #742

Power>2 A Trip
DDB #743
Power>2 B Trip
DDB #744
Power>2 C Trip
DDB #745

Power<1 3Ph Trip


DDB #746
1
Power<1 A Trip
DDB #747
Power<1 B Trip
DDB #748

Power<1 C Trip
DDB #749

Power<2 3Ph Trip


DDB #750

Power<2 A Trip
DDB #751

Power<2 B Trip
DDB #752

Power<2 C Trip
DDB #753

SensP1 Trip A
DDB #760

SensP2 Trip A
DDB #761

Page : 3
I>1 Trip
DDB #243 Output Relay Mappings
I>2 Trip
DDB #247
I>3 Trip
DDB #251
I>4 Trip
DDB #255 Note: DDB SignalsTrip Command In
I2>1 Trip and Trip Command Out are joined
DDB #513
together in the fixed scheme logic
I2>2 Trip
DDB #514
I2>3 Trip
DDB #515
I2>4 Trip
DDB #516

Broken Line Trip


DDB #260

Thermal Trip
DDB #276
IN1>1 Trip
DDB #261

IN1>2 Trip
DDB #262

IN1>3 Trip
DDB #263
IN1>4 Trip
DDB #264
IN2>1 Trip
DDB #265

IN2>2 Trip
DDB #266

IN2>3 Trip
DDB #267

IN2>4 Trip
DDB #268

ISEF>1 Trip
DDB #269

ISEF>2 Trip
DDB #270

ISEF>3 Trip
DDB #271

ISEF>4 Trip
DDB #272

IREF> Trip
1 Trip Command In
DDB #536
DDB #273

V<1 Trip
DDB #278

V<2 Trip
DDB #282

V>1 Trip
DDB #286

V>2 Trip
DDB #290

V2> Trip
DDB #277

VN>1 Trip
DDB #274
VN>2 Trip
DDB #275
F<1 Trip
DDB #424

F<2 Trip
DDB #425

F<3 Trip
DDB #426
F<4 Trip
DDB #427
F>1 Trip
DDB #428

F>2 Trip
DDB #429
YN> Trip
DDB #436
GN> Trip
DDB #437
BN> Trip
DDB #438
AR Trip Test
DDB #372

I>5 Trip
DDB #570

I>6 Trip
DDB #574 Page : 4
Trip Output Mapping
0
R3 OC.EF TC2
Trip Command Out Straight DDB #002
R3
DDB #537
0
SG-opto Invalid
DDB #145

F out of Range
DDB #147

VT Fail Alarm
DDB #148
CT Fail Alarm
DDB #149
CB Fail Alarm
DDB #150

I^ Maint Alarm 0
DDB #151 R4 OC.EF DFR R4
Straight DDB #003
CB Ops Maint
DDB #153 0

CB Op Time Maint 1
DDB #155
Fault Freq Lock
DDB #157

CB Status Alarm
DDB #158

Man CB Trip Fail


DDB #159
CB Cls Fail
DDB #160

Man CB Unhealthy
DDB #161

Field volts fail


DDB #410

AR Lockout
DDB #163

UV Block
DDB #167

0
Trip Command Out
DDB #537
1 Straight
R6 OC.EF SCADA
DDB #005
R6

I>1 Trip 0
DDB #243
1 Straight
Output R5
DDB #004
R5

IN1>1 Trip
DDB #261 0

I>1 Trip 0
DDB #243
1 Straight
Output R12
DDB #011
R12

IN1>1 Trip
DDB #261 0

Check Sync 1 OK
DDB #447 0
Check Sync 2 OK
1 Straight
R7 CS OK
DDB #006
R7

DDB #448
0
L4
L4 CS ENABLE
DDB #035

1
CS1 Slipfreq>
DDB #471

CS1 Slipfreq<
DDB #472 0
Output R11
CS Vline>
DDB #491 1 Straight
0
DDB #010
R11

CS Vline<
DDB #489
CS Vbus>
DDB #492
CS Vbus<
DDB #490

CS1 Ang Not OK +


DDB #497

CS1 Ang Not OK -


DDB #498
Close in Prog 0
DDB #357
& Pick-Up
Output R10
DDB #009
R10

L4 CS ENABLE
L4
DDB #035 0

Page : 5
LED Mappings

I>1 Trip
DDB #243
1 Latching LED 1
DDB #064

IN1>1 Trip
DDB #261
1 Latching LED 2
DDB #065

Check Sync 1 OK
DDB #447
1 Non -
Latching
LED 3
DDB #066

I>1 Start A
DDB #296
1 Non -
Latching
LED 4
DDB #067

I>1 Start B
DDB #297 1 Non -
Latching
LED 5
DDB #068

I>1 Start C
DDB #298 1 Non -
Latching
LED 6
DDB #069

IN1>1 Start
DDB #315 1 Non -
Latching
LED 7
DDB #070

Page : 6