Kline
Kline
Kline
Enclosed Starters,
Overload Relays, and Accessories
Class 8502
CONTENTS
Description Page
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Mini-contactors
Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Auxiliary Contacts and Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Dimensions and Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Overload Relays
Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Dimensions, Mounting, and Schematics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Low-consumption Mini-contactors
Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Schneider Electric Brands Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Auxiliary Contacts, Timers, and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Dimensions and Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
General Information
K-line Mini-contactors, Enclosed Starters, and Overload Relays are ideal for general-duty applications
where small size and reliability are key concerns. They feature:
• Three contactor ratings for the USA market:
— K06 rated for 3 HP motors at 480 Vac or 600 Vac.
— K09 rated for 5 HP motors at 480 Vac or 600 Vac.
— K12 rated for 7.5 HP motors at 480 Vac or 10 HP at 600 Vac.
• Space savings — the special magnet and armature structure allow for a DC coil-operated device with
the same physical size and panel footprint of the AC coil version.
• IP20-rated touch-safe terminals with both North American and International terminal markings
• Mountable on 35mm DIN rail or panel mount with screws
• Available in 3-pole contactor versions with built-in auxiliary contact for holding circuit or 4-pole
contactor versions.
• Easily-installed accessories.
— 2-pole or 4-pole instantaneous auxiliary contact blocks with screw clamp, slip-on, or spring
terminals.
— Transient voltage surge suppressors.
— Electronic 1 to 30 second on-delay timers.
• Four wiring methods to reduce installation time:
— Captive screw terminals for use with either Phillips or slotted head screwdrivers.
— Slip-on terminals for quick installation of single 1/4" or double 1/8" tabs.
— Terminal pins for soldering the contactor directly to a printed circuit board.
— Spring terminals for extreme-vibration applications.
• Control circuit flexibility
All versions of the K-line mini-contactors are available with an AC, DC, or low-consumption DC
operating coil. The low-consumption DC coil operating device can be energized by a low level DC
signal from a computer or PLC and includes built-in transient suppression and LED “On” indicator.
• Bimetallic overload relays
The K-line Class 10 bimetallic overload relays are ambient-compensated and include single-phase
sensitivity for phase unbalance and phase loss protection. Standard features include isolated N/C trip
contact and N/O alarm contact, manual or automatic reset function, tamper resistant window for full
load current settings, and Test trip button. Five pins connect to the contactor load side terminals —
three for the power circuit and two for the control circuit — which eliminate customer wiring for the 3-
wire control holding circuit.
34
© 2001 Schneider Electric All Rights Reserved 04/01
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Characteristics of Type LC•K and LP•K Contactors
Environment
Conforming to IEC 60947 V 690
E164862 E164862
LC•K06, LC•K09, LC•K12 NLDX NLDX2 LR 43364
Approvals 321104
LP•K06, LP•K09, LP•K12 (Screw (Slip-on &
Clamp) Solder Pin)
Protective treatment Conforming to IEC 60068 (DIN 50016) “TC” (Fungus-proof, tropicalization protection)
Degree of protection Conforming to VDE 0106 Protection against direct finger contact
90
90
90
°
°
18 0 °
Operating position
°
90
Without derating Without derating Derate current carrying capability by 15% when
not mounted vertically
Safe circuit separation Conforming to VDE 0106 and IEC 60536 SELV ◆, up to 400 V
Stranded cable with cable end mm2 1 x 0.34 1 x 1.5 + 1 x 2.5 1 x 1.5 + 1 x 2.5
Tightening torque Phillips no. 2 or 3/16” slotted head screwdriver 0.8 N•m (7lb.-in.)
Conforming to standards
Terminal referencing Up to 5 contacts
EN 50005 and EN 50012
35
04/01 © 2001 Schneider Electric All Rights Reserved
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Characteristics of Type LC•K and LP•K Contactors
Pole Characteristics
Conventional thermal current (Ith) For ambient temperature ≤ 50 °C (122 °F) 20 A
LC•K16 160 A
Rated breaking capacity LC•K06, LP•K06, LC•K09, LP•K09 I rms 110 A 110 A 110 A 110 A 80 A 70 A
LC•K16 – – – 110 A 80 A 70 A
0.37 0.75
LC•K06, LP•K06 Motor ratings 1.5 kW 2.2 kW 3 kW 3 kW 3 kW
kW kW
0.55
LC•K09, LP•K09 Motor ratings 1.1 kW 2.2 kW 4 kW 4 kW 4 kW 4 kW
kW
Utilization in category AC-3
Squirrel cage motors 5.5/4
LC•K12, LP•K12 Motor ratings – – 3 kW 5.5 kW (480) 4 kW 4 kW
kW
5.5/4
LC•K16 Motor ratings – – 4 kW 7.5 kW (480) 4 kW 4 kW
kW
Maximum operating rate (in operating cycles/ Op. cycles/hour 600 900 1200
hour in relation to percentage of rated power) Power 100% 75% 50%
36
© 2001 Schneider Electric All Rights Reserved 04/01
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Characteristics of Type LC•K and LP•K Contactors
Rated control circuit voltage (Vc) 12 to 690 Vac ◆ 24 to 230 Vac 12 to 250 Vdc ◆
Control voltage limits For operation ▲ 0.8 to 1.15 Vc 0.85 to 1.1 Vc 0.8 to 1.15 Vc
(≤ 50 °C [122 °F]) single voltage coil For drop-out ≥ 0.20 Vc ≥ 0.10 Vc ≥ 0.10 Vc
Inrush 30 VA 3 VA 3W
Average consumption at 20 °C (68 °F) and at Vc
Sealed 4.5 VA 3 VA 3W
Maximum operating rate In operating cycles per hour 3600 3600 3600
◆ For mains supplies with a high level of interference (voltage surge > 800 V), use a suppressor module LA4KE1FC (50 to 129 V) or
LAFKE1UG (130 to 250 V); see page 52.
▲ LC1K16: 0.85 to 1.15 Vc.
37
04/01 © 2001 Schneider Electric All Rights Reserved
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Characteristics of Type LC•K and LP•K Contactors
Auxiliary Contact Characteristics and Instantaneous Contact Blocks
On LC•K or LP•K 1
Number of contacts
On LA1K 2 or 4
1s 80 A
100 ms 110 A
Non-overlap distance Linked contacts conforming to INRS and BIA spec. 0.5 mm
Electrical durability (valid up to 3600 operating cycles Electrical durability (valid up to 1200 operating cycles
per hour) on an inductive load such as the coil of an per hour, on an inductive load such as the coil of an
electromagnet: making current (power factor 0.7) = 10 electromagnet, without economy resistor, the time
times the breaking current (power factor 0.4). constant increasing with the load.
Occasional making capacity VA 1000 2050 5000 10000 13000 9000 W 720 600 400 300 230 200
16 000
10 000 1000
Time constant
4
1 Breaking limit of contacts valid for 8000
6000 700
maximum of 50 operating cycles at 10 s 5000
1 500
in ms
4000
intervals (breaking current = making 3
3000 300
current x power factor 0.7).
2000
250 200
2 Electrical durability of contacts for:
- 1 million operating cycles (2a) 1000 4
800 200 100
- 3 million operating cycles (2b) 600 80 2a
-10 million operating cycles (2c). 500 60
400 140 50
3 Breaking limit of contacts valid for 300 40 2b
2a 100 30
maximum of 20 operating cycles at 10 s 200
intervals with current passing for 0.5 s 20
38
© 2001 Schneider Electric All Rights Reserved 04/01
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Selection of Contactors for Motor Control
General-purpose Contactors for AC Control Circuits
The table below shows general-purpose contactors. The contactors mount on 35 mm DIN rails or with
4 mm (# 6) screws. The wire termination screws are in the open, “ready-to-tighten” position.
For information on add-on auxiliary contact blocks and accessories, see page 50 to 53.
Horsepower Ratings for North American Applications Kilowatt Ratings for International Applications Auxiliary
Maximum Horsepower Rating Standard power ratings of 3-phase Contacts
Category AC-3, 50/60 Hz motors, 50/60 Hz in category AC-3 Rated
Max. Catalog
operational
1-Phase 3-Phase Inductive Type of Connection Number Weight lb. (kg)
220 V 380 V 440/500 V current,
Current ▼▲
115/ 230/ 200/ 220/ 460/ 575/ 230 V 415 V 660/690 V up to 440 V
120 V 240 V 208 V 240 V 480 V 600 V
HP HP HP HP HP HP A kW kW kW A N/O N/C
1 – LC1K0610•• 0.40 (0.180)
Screw clamp
– 1 LC1K0601•• 0.40 (0.180)
Slip-on 1 x 0.25 in., or 1 – LC1K06107•• 0.40 (0.180)
2 x 0.11 in. – 1 LC1K06017•• 0.40 (0.180)
0.5 1 1.5 1.5 3 3 6 1.5 2.2 3 6
Solder pins for 1 – LC1K06105•• 0.46 (0.210)
printed circuit board – 1 LC1K06015•• 0.46 (0.210)
1 – LC1K06103•• 0.40 (0.180)
Spring terminals
– 1 LC1K06013•• 0.40 (0.180)
1 – LC1K0910•• 0.40 (0.180)
Screw clamp
– 1 LC1K0901•• 0.40 (0.180)
Slip-on 1 x 0.25 in., 1 – LC1K09107•• 0.40 (0.180)
or 2 x 0.11 in. – 1 LC1K09017•• 0.40 (0.180)
0.5 1.5 2 3 5 5 9 2.2 4 4 9
Solder pins for 1 – LC1K09105•• 0.46 (0.210)
printed circuit board – 1 LC1K09015•• 0.46 (0.210)
1 – LC1K09103•• 0.40 (0.180)
Spring terminals
– 1 LC1K09013•• 0.40 (0.180)
1 – LC1K1210•• 0.40 (0.180)
Screw clamp
– 1 LC1K1201•• 0.40 (0.180)
Slip-on 1 x 0.25 in., 1 – LC1K12107•• 0.40 (0.180)
or 2 x 0.11 in. – 1 LC1K12017•• 0.40 (0.180)
4 (> 440)
0.5 1.5 3 3 7.5 10 12 3 5.5 12
5.5 (440) 1 – LC1K12105•• 0.46 (0.210)
Solder pins for
printed circuit board – 1 LC1K12015•• 0.46 (0.210)
1 – LC1K12103•• 0.40 (0.180)
Spring terminals
– 1 LC1K12013•• 0.40 (0.180)
1 – LC1K1610•• 0.40 (0.180)
Screw clamp
– 1 LC1K1601•• 0.40 (0.180)
Slip-on 1 x 0.25 in., 1 – LC1K16107•• 0.40 (0.180)
or 2 x 0.11 in. – 1 LC1K16017•• 0.40 (0.180)
Not for North American applications — not UL Listed or 4 (440)
3 7.5 16
CSA Certified 5.5 (440) 1 – LC1K16105•• 0.46 (0.210)
Solder pins for
printed circuit board – 1 LC1K16015•• 0.46 (0.210)
1 – LC1K16103•• 0.40 (0.180)
Spring terminals
– 1 LC1K16013•• 0.40 (0.180)
▼ Use voltage codes on page 49 “Coil Selection” to complete catalog number.
▲ For mains supplies with a high level of interference (voltage surge > 800 V), use a suppressor module LA4KE1FC (50 to 129 V) or LA4KE1UG (130 to 250 V), see page 52.
39
04/01 © 2001 Schneider Electric All Rights Reserved
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Selection of Contactors for Motor Control
Sensitive-Environment Contactors for AC Control Circuits
The tables below show the kilowatt ratings (for international applications) and horsepower ratings (for
North American applications) of contactors for use in sensitive environments. They are recommended
for use in areas sensitive to noise, high interference mains supplies, and so forth. The contactors mount
on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are in the open, “ready-to-
tighten” position, and include a coil with a built-in rectifier and suppressor.
For information on add-on auxiliary contact blocks and accessories, see page 50 to 53.
LC7K06105••
Horsepower Ratings for North American Applications Kilowatt Ratings for International Applications Auxiliary
Maximum Horsepower Rating Standard power ratings of 3-phase Contacts
Category AC-3, 50/60 Hz motors, 50/60 Hz in category AC-3 Rated
Max. Catalog
operational Weight lb.
1-Phase 3-Phase Inductive Type of connection Number
220 V 380 V 440/500 V current, (kg)
Current ▼
115/ 230/ 200/ 220/ 460/ 575/ 230 V 415 V 660/690 V 440V up to:
120 V 240 V 208 V 240 V 480 V 600 V
HP HP HP HP HP HP A kW kW kW A N/O N/C
1 – LC7K0610•• 0.50 (0.225)
Screw clamp
– 1 LC7K0601•• 0.50 (0.225)
Slip-on 1 x 0.25 in., 1 – LC7K06107•• 0.50 (0.225)
0.5 1 1.5 3 3 6 6 1.5 2.2 3 6
or 2 x 0.11 in. – 1 LC7K06017•• 0.50 (0.225)
Solder pins for 1 – LC7K06105•• 0.50 (0.225)
printed circuit board – 1 LC7K06015•• 0.50 (0.225)
1 – LC7K0910•• 0.50 (0.225)
Screw clamp
– 1 LC7K0901•• 0.50 (0.225)
Slip-on 1 x 0.25 in., 1 – LC7K09107•• 0.50 (0.225)
0.5 1.5 2 3 5 5 9 2.2 4 4 9
or 2 x 0.11 in. – 1 LC7K09017•• 0.56 (0.255)
Solder pins for 1 – LC7K09105•• 0.56 (0.255)
printed circuit board – 1 LC7K09015•• 0.50 (0.225)
1 – LC7K1210•• 0.50 (0.225)
Screw clamp
– 1 LC7K1201•• 0.50 (0.225)
4 (> 440) Slip-on 1 x 0.25 in., 1 – LC7K12107•• 0.50 (0.225)
0.5 1.5 3 3 7.5 10 12 3 5.5 12
5.5 (440) or 2 x 0.11 in. – 1 LC7K12017•• 0.50 (0.225)
Solder pins for 1 – LC7K12105•• 0.56 (0.255)
printed circuit board – 1 LC7K12015•• 0.56 (0.255)
40
© 2001 Schneider Electric All Rights Reserved 04/01
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Selection of Contactors for Motor Control
Three-Pole Contactors for DC Control Circuits
The table below shows the kilowatt ratings (for international applications) and horsepower ratings (for
North American applications) for three-pole contactors for DC control circuits. The contactors mount on
35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are in the open, “ready-to-
tighten” position.
For information on add-on auxiliary contact blocks and accessories, see page 50 to 53.
Horsepower Ratings for North American Applications Kilowatt Ratings for International
Applications Auxiliary
Contacts
Standard power ratings of Maximum Horsepower Ratings Maximum
3-phase motors 50/60 Hz Rated Catalog
1- phase 3- phase Inductive Type of Weight lb.
in category AC-3 operationa Number
50/60 HZ 50/60 HZ Current Connection (kg)
l current. ▼
in AC-3
220 V 380 V 440/500 V up to 440 V 115/ 230/ 200/
220/240 V 460/480 V 575/600 V Category
230 V 415 V 660/690 V 120 V 240 V 208 V
kW kW kW A HP HP HP HP HP HP A N/O N/C
1 – LP1K0610•• 0.50 (0.225)
Screw clamp
– 1 LP1K0601•• 0.50 (0.225)
Slip-on 1 x 0.25 in., 1 – LP1K06107•• 0.50 (0.225)
or 2 x 0.11 in. – 1 LP1K06017•• 0.50 (0.225)
1.5 2.2 3 6 0.5 1 1.5 1.5 3 3 6
Solder pins for 1 – LP1K06105•• 0.56 (0.255)
printed circuit board – 1 LP1K06015•• 0.56 (0.255)
1 – LP1K06103•• 0.50 (0.225)
Spring terminals
– 1 LP1K06013•• 0.50 (0.225)
1 – LP1K0910•• 0.50 (0.225)
Screw clamp
– 1 LP1K0901•• 0.50 (0.225)
Slip-on 1 x 0.25 in., 1 – LP1K09107•• 0.50 (0.225)
or 2 x 0.11 in. – 1 LP1K09017•• 0.50 (0.225)
2.2 4 4 9 0.5 1.5 2 3 5 5 9
Solder pins for 1 – LP1K09105•• 0.50 (0.225)
printed circuit board – 1 LP1K09015•• 0.56 (0.255)
1 – LP1K09103•• 0.50 (0.225))
Spring terminals
– 1 LP1K09013•• 0.50 (0.225)
1 – LP1K1210•• 0.50 (0.225)
Screw clamp
– 1 LP1K1201•• 0.50 (0.225)
Slip-on 1 x 0.25 in., 1 – LP1K12107•• 0.50 (0.225)
or 2 x 0.11 in. – 1 LP1K12017•• 0.50 (0.225)
4 (>440 V)
3 5.5 12 0.5 1.5 3 3 7.5 10 12
5.5 (440 V) 1 – LP1K12105•• 0.56 (0.255)
Solder pins for
printed circuit board – 1 LP1K12015•• 0.56 (0.255)
1 – LP1K12103•• 0.50 (0.225)
Spring terminals
– 1 LP1K12013•• 0.50 (0.225)
▼ Use voltage codes on page 49 “Coil Selection” to complete catalog number.
LP1K0610•• LP1K06107••
41
04/01 © 2001 Schneider Electric All Rights Reserved
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Selection of Contactors for Resistive Loads
Three- and Four-Pole Contactors for AC Control Circuits
The tables below show general-purpose and sensitive-environment three- and four-pole contactors for
AC control circuits. (The sensitive-environment contactors are recommended for use in areas sensitive
to noise, high interference mains supplies, and so forth.) The contactors mount on 35 mm DIN rails or
with 4 mm (# 6) screws. The wire termination screws are in the open, “ready-to-tighten” position. In
addition, the sensitive-environment contactors include a coil with a built-in rectifier and suppressor.
For information on add-on auxiliary contact blocks and accessories, see page 50 to 53.
General-purpose Contactors ◆
Power Auxiliary
Non-inductive loads Poles Contacts
Category AC-1 Catalog
Maximum current at ≤ Type of Connection Number Weight lb. (kg)
50 °C (122 °F) ▼
Sensitive-environment Contactors
3 – 1 – LC7K0910•• 0.56 (0.255)
3 – – 1 LC7K0901•• 0.56 (0.255)
Screw clamp
4 – – – LC7K09004•• 0.56 (0.255)
2 2 – – LC7K09008•• 0.56 (0.255)
3 – 1 – LC7K09107•• 0.56 (0.255)
3 – – 1 LC7K09017•• 0.56 (0.255)
20 Slip-on 1 x 0.25 in. or 2 x 0.11 in.
4 – – – LC7K090047•• 0.56 (0.255)
2 2 – – LC7K090087•• 0.56 (0.255)
3 – 1 – LC7K09105•• 0.56 (0.255)
3 – – 1 LC7K09015•• 0.56 (0.255)
Solder pins for printed circuit board
4 – – – LC7K090045•• 0.56 (0.255)
2 2 – – LC7K090085•• 0.56 (0.255)
◆ For mains supplies with a high level of interference (voltage surge > 800 V), use a suppressor module LA4KE1FC (50 to 129 V) or
LC7K090047•• LAFKE1UG (130 to 250 V), see page 52.
▼ Use voltage codes on page 49 “Coil Selection” to complete catalog number.
42
© 2001 Schneider Electric All Rights Reserved 04/01
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Selection of Contactors for Resistive Loads
Three- and Four-pole Contactors for DC Control Circuits
The table below shows three- and four-pole contactors for DC control circuits. The contactors mount on
35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are in the open, “ready-to-
tighten” position.
For information on add-on auxiliary contact blocks and accessories, see page 50 to 53.
Power Auxiliary
Non-inductive loads Poles Contacts
Category AC-1 Catalog
Maximum current at Type of Connection Number Weight lb. (kg)
≤ 50 °C (122 °F) ▼
43
04/01 © 2001 Schneider Electric All Rights Reserved
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Selection of Reversing Contactors for Motor Control
Three-pole Reversing Contactors for AC Control Circuits
The table below shows three-pole reversing contactors with integrated mechanical interlock. The
contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are in the
open, “ready-to-tighten” position. Customer wiring is required to connect coil terminations to electrical
interlock; see page 56 (top row, center drawing).
For information on add-on auxiliary contact blocks and accessories, see page 50 to page 53.
Horsepower Ratings for North American Applications Kilowatt Ratings for International Applications Auxiliary
Maximum Horsepower Rating Standard power ratings of 3-phase Contacts
Category AC-3, 50/60 Hz motors, 50/60 Hz in category AC-3 Rated
Max. Catalog
Operational Weight
1-Phase 3-Phase Inductive Type of Connection Number
220 V 380 V 440/500 V Current, lb. (kg)
Current ▼■
115/ 230/ 200/ 220/ 460/ 575/ 230 V 415 V 660/690 V up to 440 V
120 V 240 V 208 V 240 V 480 V 600 V
HP HP HP HP HP HP A kW kW kW A N/O N/C
1 – LC2K0610•• 0.86 (0.390)
Screw clamp ▲
– 1 LC2K0601•• 0.86 (0.390)
Slip-on 1 x 0.25 in., or 1 – LC2K06107•• 0.81 (0.370)
2 x 0.11 in. – 1 LC2K06017•• 0.81 (0.370)
0.5 1 1.5 1.5 3 3 6 1.5 2.2 3 6
Solder pins for 1 – LC2K06105•• 0.95 (0.430)
printed circuit board – 1 LC2K06015•• 0.95 (0.430)
1 – LC2K06103•• 0.86 (0.390)
Spring terminals
– 1 LC2K06013•• 0.86 (0.390)
1 – LC2K0910•• 0.86 (0.390)
Screw clamp ▲
– 1 LC2K0901•• 0.86 (0.390)
Slip-on 1 x 0.25 in., 1 – LC2K09107•• 0.86 (0.390)
or 2 x 0.11 in. – 1 LC2K09017•• 0.86 (0.390)
0.5 1.5 2 3 5 5 9 2.2 4 4 9
Solder pins for 1 – LC2K09105•• 0.95 (0.430)
printed circuit board – 1 LC2K09015•• 0.95 (0.430)
1 – LC2K09103•• 0.86 (0.390)
Spring terminals
– 1 LC2K09013•• 0.86 (0.390)
1 – LC2K1210•• 0.86 (0.390)
Screw clamp ▲
– 1 LC2K1201•• 0.86 (0.390)
Slip-on 1 x 0.25 in., 1 – LC2K12107•• 0.86 (0.390)
or 2 x 0.11 in. – 1 LC2K12017•• 0.86 (0.390)
4 (> 440)
0.5 1.5 3 3 7.5 10 12 3 5.5 12
5.5 (440) 1 – LC2K12105•• 0.95 (0.430)
Solder pins for
printed circuit board – 1 LC2K12015•• 0.95 (0.430)
1 – LC2K12103•• 0.86 (0.390)
Spring terminals
– 1 LC2K12013•• 0.86 (0.390)
1 – LC2K1610•• 0.86 (0.390)
Screw clamp ▲
– 1 LC2K1601•• 0.86 (0.390)
Slip-on 1 x 0.25 in., 1 – LC2K16107•• 0.86 (0.390)
or 2 x 0.11 in. – 1 LC2K16017•• 0.86 (0.390)
Not for North American applications — not UL Listed or 4 (440)
3 7.5 16
CSA Certified 5.5 (440) 1 – LC2K16105•• 0.95 (0.430)
Solder pins for
printed circuit board – 1 LC2K16015•• 0.95 (0.430)
1 – LC2K16103•• 0.86 (0.390)
Spring terminals
– 1 LC2K16013•• 0.86 (0.390)
▼ Use voltage codes on page 49 “Coil Selection” to complete catalog number.
■ For mains supplies with a high level of interference (voltage surge > 800 V), use a suppressor module LA4KE1FC (50 to 129 V) or LA4KE1UG (130 to 250 V), see page 52.
▲ Pre-wired power circuit connections are standard on screw clamp versions.
44
© 2001 Schneider Electric All Rights Reserved 04/01
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Selection of Reversing Contactors for Motor Control
Sensitive-environment Reversing Contactors for AC Control Circuits
The tables below show the kilowatt ratings (for international applications) and horsepower ratings (for
North American applications) for reversing contactors with mechanical interlock for use in sensitive
environments. They are recommended for use in areas sensitive to noise, high interference mains
supplies, and so forth. A coil with incorporated rectifier and suppressor is standard.
LC8K06105•• The contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are
in the open, “ready-to-tighten” position. Customer wiring is required to connect coil terminations to
electrical interlock; see page 56 (top row, center drawing). For information on add-on auxiliary contact
blocks and accessories, see page 50 to 53.
Horsepower Ratings for North American Applications Kilowatt Ratings for International Applications Auxiliary
Maximum Horsepower Rating Standard power ratings of 3-phase Contacts
Category AC-3, 50/60 Hz motors, 50/60 Hz in category AC-3 Rated
Max. Catalog
Operational Weight
1-Phase 3-Phase Inductive Type of Connection Number
220 V 380 V 440/500 V Current, lb. (kg)
Current ▼
115/ 230/ 200/ 220/ 460/ 575/ 230 V 415 V 660/690 V up to 440 V
120 V 240 V 208 V 240 V 480 V 600 V
HP HP HP HP HP HP A kW kW kW A N/O N/C
1 – LC8K0610•• 1.05 (0.480)
Screw clamp ▲
– 1 LC8K0601•• 1.05 (0.480)
Slip-on 1 x 0.25 in., 1 – LC8K06107•• 1.00 (0.460)
0.5 1 1.5 3 3 6 6 1.5 2.2 3 6
or 2 x 0.11 in. – 1 LC8K06017•• 1.00 (0.460)
Solder pins for printed 1 – LC8K06105•• 1.14 (0.520)
circuit board – 1 LC8K06015•• 1.14 (0.520)
1 – LC8K0910•• 1.05 (0.480)
Screw clamp ▲
– 1 LC8K0901•• 1.05 (0.480)
Slip-on 1 x 0.25 in., 1 – LC8K09107•• 1.00 (0.460)
0.5 1.5 2 3 5 5 9 2.2 4 4 9
or 2 x 0.11 in. – 1 LC8K09017•• 1.00 (0.460)
Solder pins for printed 1 – LC8K09105•• 1.14 (0.520)
circuit board – 1 LC8K09015•• 1.14 (0.520)
1 – LC8K1210•• 1.05 (0.480)
Screw clamp ▲
– 1 LC8K1201•• 1.05 (0.480)
4 (> 440) Slip-on 1 x 0.25 in., 1 – LC8K12107•• 1.00 (0.460)
0.5 1.5 3 3 7.5 10 12 3 5.5 12
5.5 (440) or 2 x 0.11 in. – 1 LC8K12017•• 1.00 (0.460)
Solder pins for printed 1 – LC8K12105•• 1.14 (0.520)
circuit board – 1 LC8K12015•• 1.14 (0.520)
▼ Use voltage codes on page 49 “Coil Selection” to complete catalog number.
▲ Pre-wired power circuit connections are standard on screw clamp versions.
45
04/01 © 2001 Schneider Electric All Rights Reserved
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Selection of Reversing Contactors for Motor Control
Three-pole Reversing Contactors for DC Control Circuits
The table below show the kilowatt ratings (for international applications) and horsepower ratings (for
North American applications) for three-pole reversing contactors with integrated mechanical interlock for
DC control circuits. The contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire
termination screws are in the open, “ready-to-tighten” position. Customer wiring is required to connect
coil terminations to electrical interlock; see page 56 (top row, center drawing).
For information on add-on auxiliary contact blocks and accessories, see page 50 to 53.
Horsepower Ratings for North American Applications Kilowatt Ratings for International Applications
Auxiliary
Standard power ratings of 3-phase motors 50/ Rated
Maximum Horsepower ratings Contacts
Maximum 60 Hz in category AC-3 Operation
Inductive al Current Catalog
1- phase 3- phase Type of Weight
Current in AC-3 up Number
50/60 HZ 50/60 HZ 220 V 380 V 440/500 V Connection lb. (kg)
in AC-3 to 400 V ▼
115/ 230/ 200/ 220/ 460/ 575/ Category 230 V 415 V 660/690 V
120 V 240 V 208 V 240 V 480 V 600 V
HP HP HP HP HP HP A kW kW kW A N/O N/C
1 – LP2K0610•• 1.05 (0.480)
Screw clamp ▲
– 1 LP2K0601•• 1.05 (0.480)
LP2K0610•• LP2K06107••
46
© 2001 Schneider Electric All Rights Reserved 04/01
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Selection of Reversing Contactors for Resistive Loads
Three- and Four-pole Reversing Contactors for AC Control Circuits
The tables below show general purpose and sensitive-environment three- and four-pole reversing
contactors for AC control circuits. The sensitive-environment contactors are recommended for use in
areas sensitive to noise, high interference mains supplies, and so forth. The contactors incorporate an
integrated mechanical interlock.
Both types of contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination
screws are in the open, “ready-to-tighten” position. In addition, the sensitive-environment contactors
include a coil with a built-in rectifier and suppressor. Customer wiring is required to connect coil
terminations to the electrical interlock; see page 56 (top row, center drawing).
For information on add-on auxiliary contact blocks and accessories, see page 50 to 53.
General-purpose Contactors ◆
Power Auxiliary
Non-inductive Poles Contacts
loads Category
AC-1 Maximum Catalog
current at ≤ 50 °C Type of Connection Number Weight lb. (kg)
(122 °F) ▼
Sensitive-Environment Contactors
3 – 1 – LC8K0910•• f 1.05 (0.480)
Screw clamp ▲ 3 – – 1 LC8K0901•• f 1.05 (0.480)
4 – – – LC8K09004•• 1.03 (0.470)
3 – – 1 LC8K09107•• 1.01 (0.460)
20 Slip-on 1 x 0.25 in. or 2 x 0.11 in. 3 – 1 – LC8K09017•• 1.01 (0.460)
4 – – – LC8K090047•• 1.01 (0.460)
3 – 1 1 LC8K09105•• 1.14 (0.520)
Solder pins for circuit board 3 – – – LC8K09015•• 1.14 (0.520)
LC8K09105•• 4 – – – LC8K090045•• 1.14 (0.520)
◆ For mains supplies with a high level of interference (voltage surge > 800 V), use a suppressor module LA4KE1FC (50 to 129 V) or
LAFKE1UG (130 to 250 V), see page 52.
▼ Use voltage codes on page 49 “Coil Selection” to complete catalog number.
▲ Pre-wired power circuit connections are standard on screw clamp versions.
■ WARNING: This reversing contactor is pre-wired for reverse motor operation as standard.
47
04/01 © 2001 Schneider Electric All Rights Reserved
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Selection of Reversing Contactors for Resistive Loads
Three- and Four-pole Reversing Contactors for DC Control Circuits
The table below shows general-purpose three- and four-pole reversing contactors for DC control
circuits. The contactors incorporate an integrated mechanical interlock.
The contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are
in the open, “ready-to-tighten” position. Customer wiring is required to connect coil terminations to the
electrical interlock; see page 56 (top row, center drawing).
For information on add-on auxiliary contact blocks and accessories, see page 50 to 53.
Power Auxiliary
Non-inductive loads Poles Contacts
Category AC-1 Catalog
Maximum current at Type of Connection Number Weight lb. (kg)
≤ 50 °C (122 °F) ▼
48
© 2001 Schneider Electric All Rights Reserved 04/01
K-line Mini-contactors, D-line Contactors, and Enclosed Starters
Coil Selection
NOTE: Voltage codes in bold face are typical control voltages..
Contactors LC1K, LC2K (0.8 to 1.15 Vc)
Volts AC 200/ 220/ 230/ 380/ 400/ 660/
12 20 24 ▲ 36 42 48 110 120 127 230 256 277 400 440 480 500 575 600
50/60 Hz 208 230 ◆ 240 ◆ 400 ◆ 415 ◆ 690 ◆
Voltage
J7 Z7 B7 C7 D7 E7 F7 G7 FC7 L7 M7 P7 U7 W7 UE7 Q7 V7 N7 R7 T7 S7 SC7 X7 Y7
Code
Up to and including 240 V, coil with integral suppression device available: add 2 to the code required. Example: J72.
▲ When connecting an electronic sensor or timer in series with the coil of the control relay, select a 20 V coil (AC control circuit voltage code Z7,
DC control circuit voltage code ZD) so as to compensate for the incurred voltage drop.
◆ 0.85 to 1.1 Vc.
DC Coils
LC1D09 . . .D38 Coils with integral suppression device fitted as standard
5V 12 V 20 V 24 V 36 V 48 V 60 V 72 V 96 V 110 V 125 V 220 V 250 V 440 V – – – – – – –
U 0.7 . . . 1.25 Uc – JD – BD CD ED ND SD – FD GD MD UD RD – – – – – – –
LC1D09 . . . D38 LOW CONSUMPTION Coils with integral suppression device fitted as standard
U 0.7 . . . 1.25 Uc AL JL ZL BL CD EL – SL DL FL – ML UL – – – – – – – –
LC1D40 . . . D95
U 0.85 . . . 1.1 Uc (standard) – JD – BD CD ED ND SD – FD GD MD UD RD – – – – – – –
U 0.75 . . . 1.2 Uc (wide range) – JW – BW CW EW – SW – FW – MW – – – – – – – – –
LC1D115 & D150 Coils with integral suppression device fitted as standard
U 0.75 . . . 1.2 Uc – – – BD – ED ND SD – FD GD MD UD RD – – – – – – –
49
12/01
12/01 © 2001 Schneider Electric All Rights Reserved
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Selection of Auxiliary Contacts and Timers
XX
LC1/LC7/LP1K
LA1KN● ● ●
LA1KN● ●M
LC1/LC7/LP1K
LA1KN● ●
LA1KT2●
LC1/LC7/LP1K
LA1 KN● ●P
50
© 2001 Schneider Electric All Rights Reserved 04/01
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Selection of Auxiliary Contacts and Timers
Instantaneous Auxiliary Contact Blocks for Type LC•K and LP•K Contactors
Recommended for standard applications. Clip-on front mounting, 1 block per contactor
Auxiliary
Contacts
N/O N/C
2 – LA1KN20 0.10 (0.045)
– 2 LA1KN02 0.10 (0.045)
1 1 LA1KN11 0.10 (0.045)
LC1, LC2
LC7, LC8 4 – LA1KN40 0.10 (0.045)
Screw Clamp
LP1, LP2 3 1 LA1KN31 0.10 (0.045)
3- or 4-pole
2 2 LA1KN22 0.10 (0.045)
1 3 LA1KN13 0.10 (0.045)
– 4 LA1KN04 0.10 (0.045)
2 – LA1KN207 0.10 (0.045)
– 2 LA1KN027 0.10 (0.045)
1 1 LA1KN117 0.10 (0.045)
LC1, LC2
LC7, LC8 4 – LA1KN407 0.10 (0.045)
Slip-on 1 x 0.25 in. or 2 x 0.11 in.
LP1, LP2 3 1 LA1KN317 0.10 (0.045)
3- or 4-pole
2 2 LA1KN227 0.10 (0.045)
1 3 LA1KN137 0.10 (0.045)
– 4 LA1KN047 0.10 (0.045)
2 – LA1KN203 0.10 (0.045)
– 2 LA1KN023 0.10 (0.045)
1 1 LA1KN113 0.10 (0.045)
LC1, LC2 4 – LA1KN403 0.10 (0.045)
Spring Terminals LP1, LP2
3- or 4-pole 3 1 LA1KN313 0.10 (0.045)
2 2 LA1KN223 0.10 (0.045)
1 3 LA1KN133 0.10 (0.045)
– 4 LA1KN043 0.10 (0.045)
With terminal referencing conforming to standard EN 50012. Clip-on front mounting, 1 block per contactor
– 2 LA1KN02M 0.10 (0.045)
LC1, LC2 1 1 LA1KN11M 0.10 (0.045)
LC7, LC8
3 1 LA1KN31M 0.10 (0.045)
LP1, LP2
Screw clamp with terminal referencing conforming to 3-pole + N/O 2 2 LA1KN22M 0.10 (0.045)
standard EN 50012 1 3 LA1KN13M 0.10 (0.045)
LC1, LC2 1 1 LA1KN11P 0.10 (0.045)
LC7, LC8
LP1, LP2 2 2 LA1KN22P 0.10 (0.045)
4-pole
Electronic Time-Delay Auxiliary Contact Blocks for Type LC•K and LP•K Contactors
– Relay output, with common point changeover contact, AC or DC 240 Vac, 2 A maximum.
– Control voltage: 0.85 to 1.1 Vc.
– Maximum switching capacity: 250 VA or 150 W.
– Operating temperature: -10 to + 60 °C (14 to 140 °F).
– Reset time: 1.5 s during the time delay period, 0.5 s after the time delay period.
Clip-on front mounting, 1 block per contactor
Auxiliary
Contacts
Voltage Timing
Type Range Catalog Number Weight lb. (kg)
s
V SPDT
AC or DC 24 to 48 On-delay 1 to 30 1 LA2KT2E 0.09 (0.040)
AC 110 to 240 On-delay 1 to 30 1 LA2KT2U 0.09 (0.040)
51
04/01 © 2001 Schneider Electric All Rights Reserved
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Selection of Accessories
Coil Suppressor Modules With an LED Indicator for Type LC•K and LP•K Contactors
Mounting and connection Type For voltages: Sold in lots of Catalog Number Weight lb. (kg)
AC and DC
5 LA4KE1B 0.02 (0.010)
12 to 24 V
AC and DC
5 LA4KE1E 0.02 (0.010)
32 to 48 V
Varistor ■
AC and DC
5 LA4KE1FC 0.02 (0.010)
50 to 129 V
Clip-on mounting on the front of
AC and DC
LC1 and LP1 contactors. 5 LA4KE1UG 0.02 (0.010)
201 to 250 V
No tools required.
DC
5 LA4KC1B 0.02 (0.010)
Diode + 12 to 24 V
Zener diode ◆ DC
5 LA4KC1E 0.02 (0.010)
32 to 48 V
LA4K•• AC
RC ▲ 5 LA4KA1U 0.02 (0.010)
220 to 250 V
■ Protection by limitation of the transient voltage up to 2 Vc maximum. Maximum reduction of transient voltage peaks.
Slight time delay on drop-out (1.1 to 1.5 times the normal time).
◆ No overvoltage or oscillation frequency. Polarized component. Slight time delay on drop-out (1.1 to 1.5 times the normal time).
▲ Protection by limitation of the transient voltage up to 3 Vc maximum and limitation of the oscillation frequency.
Slight time delay on drop-out (1.2 to 2 times the normal time).
Marker holder Clip-on Onto front of contactor 100 LA9D90 0.002 (0.001)
Strips of 10 identical
25 AB1R• ▲ 0.004 (0.002)
4 maximum numbers 0 to 9
Clip-in markers
per contactor Strips of 10 identical
25 AB1G• ▲ 0.004 (0.002)
capital letters A to Z
35mm " DIN rail (7.5mm deep x 2m long) 10 AM1DP200 2.88 (1.310)
35mm " DIN rail (15mm deep x 2m long) 10 AM1ED200 1.44 (0.650)
■ Order 1 mounting plate for a contactor and 2 mounting plates for a reversing contactor.
▲ Complete the catalog number by replacing the • with the required character.
LA9E01
52
© 2001 Schneider Electric All Rights Reserved 04/01
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Dimensions and Mounting of Type LC•K and LP•K Contactors
XXX
Contactors
LC1K, LC7K, LP1K
On panel On mounting rail AM1DP200 or AM1DE200 1.4 in. (35 mm) DIN rail
2.28
58
2.28
1.97
50
58
2.24 1.78
57 45
1.22 2.24 = =
=
1.38
31 57 35
1.78
45
DZ5 ME5
5
1.97
50
4.72
120
4.33
110
0.83 = =
0.20
2.24 1.38
5
57 21 35
1.78
45
0.34 == = A1
8.65
2.28
1.97
2.09
58
50
53
LA2 KT
2.28
1.06
58
27
1.34 1.50
34 38 1.34 2.24
34 57
Suppressor modules
LA4K• On contactor
2.26
0.99
58
25
0.87 0.24
22 6 0.87 2.24 Dimensions Inches
22 57 mm
53
04/01 © 2001 Schneider Electric All Rights Reserved
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Dimensions and Mounting of Type LC•K and LP•K Reversing Contactors
2.28
58
2.28
1.97
58
50
2.24 3.54
57 90
1.22 2.24 = 3.15 =
=
31 57 80
3.54
90
On one asymmetrical rail DZ5MB with 2 clip-on mounting plates LA9D973 or on 2 mounting plates DX1AP25.
2 x LA9D973 2 x DX1AP25
0.20
1.78
5
45
DZ5 ME5
1.97
50
4.33
110
4.72
120
2.24 0.83 = 1.38 =
0.20
5
57 21 35
3.54
90
2.24 1.06 3.54
On printed circuit board for reversing contactors or 2 contactors mounted side by side 57 27 90
0.34 == = = == 0.34
8.65 8.65
A1 A1
1.97
2.09
2.28
50
53
58
A2 A2
LA2 KT
2.28
1.06
58
27
1.34 1.50
34 38 1.34 2.24
34 57
Suppressor modules
LA4K• On reversing contactors
2.28
0.99
58
25
0.87 0.24
22 6 0.87 2.24 Dimensions inches
22 57 mm
54
© 2001 Schneider Electric All Rights Reserved 04/01
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Schematics
Type LC•K and LP•K Contactors and Accessories
3-pole contactors Integrated-coil suppression device
LC1K, LC7K, LP1K LC7K
3-pole + N/O 3-pole + N/C
A1
3/L2
5/L3
1/L1
13/NO
3/L2
5/L3
1/L1
21/NC
A1
A1
A2
14
A2
22
T3/6
T1/2
T2/4
T3/6
T1/2
T2/4
A2
4-pole contactors Integrated-coil suppression device
LC1K, LC7K, LP1K LC7K
A1
4-pole 2-pole N/O + 2-pole N/C
3/L2
5/L3
7/L4
1/L1
R1
R3
1
3
A1
A1
A2
A2
T3/6
T4/8
T1/2
T2/4
4
R2
R4
2
A2
Instantaneous auxiliary contacts LA1K
For contactors LC•K and LP•K
2 N/O 2 N/C 1 N/O + 1 N/C
LA1KN20 LA1KN02 LA1KN11
LA1KN207 LA1KN027 LA1KN117
53/NO
61/NC
53/NO
63/NO
51/NC
61/NC
62
54
54
64
52
62
63/NO
73/NO
83/NO
51/NC
61/NC
71/NC
81/NC
53/NO
53/NO
73/NO
83/NO
61/NC
71/NC
81/NC
61/NC
53/NO
83/NO
61/NC
71/NC
52
62
72
82
54
62
72
82
54
62
74
84
54
62
72
84
54
64
74
84
31/NC
43/NO
53/NO
53/NO
21/NC
31/NC
21/NC
31/NC
41/NC
33/NO
21/NC
33/NO
43/NO
53/NO
21/NC
22
32
22
32
44
54
22
32
42
54
22
34
22
34
44
54
21/NC
13/NO
43/NO
21/NC
31/NC
22
14
14
22
32
44
16
18
15
A2
DC AC/ DC
+ −
55
04/01 © 2001 Schneider Electric All Rights Reserved
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Schematics
Type LC•K and LP•K Reversing Contactors and Accessories
3-pole reversing contactors Dashed lines indicate suggested Integrated-coil suppression device
LC2K, LC8K, LP2K customer wiring to electrically LC8K
With screw clamp terminals interlock coils
3 P + N/O 3 P + N/C
A1
5/L3
3/L2
3/L2
5/L3
1/L1
1/L1
13/NO
13/NO
5/L3
3/L2
3/L2
5/L3
1/L1
1/L1
A1
A1
21/NC
21/NC
A1
A1
A2
A2
A2
14
14
T3/6
T3/6
T1/2
T2/4
T1/2
T2/4
A2
A2
22
22
T3/6
T3/6
T1/2
T2/4
T1/2
T2/4
With Slip-on connectors or solder pins (printed circuit board) With Slip-on connectors or solder pins (printed circuit board)
3 P+ N/O 3 P + N/C
5/L3
3/L2
3/L2
5/L3
1/L1
1/L1
5/L3
3/L2
3/L2
5/L3
1/L1
1/L1
21/NC
21/NC
13/NO
13/NO
A1
A1
A1
A1
A2
A2
22
22
A2
A2
14
14
T3/6
T3/6
T1/2
T2/4
T1/2
T2/4
T3/6
T3/6
T1/2
T2/4
T1/2
T2/4
A1
1/L1
1/L2
1/L3
1N
2/L1
2/L2
2/L3
2N
7
3
7
1
1
A1
A1
A2
A2
5
7
3
5
1
1
A1
A1
8
2
4
A2
A2
6
8
2
A2
L1
L2
L3
63/NO
51/NC
61/NC
53/NO
13/NO
61/NC
21/NC
52
62
54
64
62
54
14
22
73/NO
83/NO
61/NC
53/NO
61/NC
71/NC
81/NC
53/NO
83/NO
51/NC
61/NC
71/NC
81/NC
53/NO
63/NO
73/NO
83/NO
61/NC
71/NC
54
62
74
84
54
62
72
82
52
62
72
82
54
62
72
84
54
64
74
84
For auxiliary contacts with terminal referencing conforming to standard EN 50012 see page 51.
Electronic time delay contact blocks Suppressor modules
LA2KT LA4KC LA4KE
For contactors LC•K and LP•K
1 C/O
A1
16
18
15
A2
DC AC/ DC
+ −
56
© 2001 Schneider Electric All Rights Reserved 04/01
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Characteristics of Type LR•K Overload Relays
Environment
Meets the essential
Conforming to standards requirements of the IEC 60947, NF C 63-650, VDE 0660, BS 4941, UL 508, CSA 22.2 No. 14
LV & EMC directives
Protective treatment Conforming to IEC 60068 (DIN 50016) “TC” (Fungus-proof, tropicalization protection)
Degree of protection Conforming to VDE 0106 Protection against direct finger contact
Storage -40° to +70° C (-40 to +158° F)
Ambient air temperature
For normal operation (IEC 60947) -20 to +55° C (-4 to +131° F) without derating
around the device
Operating limit -30 to +60° C (-22 to +140° F) with derating ■
Maximum operating altitude Without derating 2000 m (6562 ft.)
Vertical axis Horizontal axis
90°
Operating positions
57
04/01 © 2001 Schneider Electric All Rights Reserved
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Characteristics of Type LR•K Overload Relays
Up to 400
Frequency limits of the operational current Hz
Operating Characteristics
Sensitivity to phase failure Conforming to IEC 60947 Yes
Selected by means of a lockable and sealable switch
Manual or automatic
Reset on the front of the relay
Tripping curves
20 min 20 min
10 min 10 min
6 min 6 min
4 min 4 min
2 min 2 min
1 min 1 min
40 s 40 s
20 s 20 s
10 s 10 s
6s 6s
4s 4s
1
2s 2s 2
1s 1s
1 1.2 1.5 2 3 4 5 6 8 10 15 1 1.2 1.5 2 3 4 5 6 8 10 15
Balanced 3-phase operation, from cold state. Balanced operation with 2-phases only, from cold state.
1 = Setting: at lower end of scale.
2 = Setting: at upper end of scale.
58
© 2001 Schneider Electric All Rights Reserved 04/01
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Selection of Type LR•K Overload Relays
These overload relays are designed for the protection of motors. They are ambient-compensated and
phase-failure sensitive. They may be reset either manually or automatically.
For direct mounting, the relays are placed under the contactors with screw clamp terminals only
(pre-wired terminals; see page 60). For separate mounting, use terminal block LA7K0064 (see below).
The front face of the overload relay provides:
• Selection of reset mode: Manual (marked H) or Automatic (marked A).
• A red pushbutton for the Trip Test function.
• A blue pushbutton for Stop and manual reset.
• A yellow trip flag to indicate that the overload relay tripped.
Accessory
Description Type of Connection Catalog Number Weight lb. (kg)
Terminal block for separate clip-on mounting
Screw clamp LA7K0064 0.22 (0.100)
of the overload relay on 35 mm " DIN rail
LA7K0064
59
04/01 © 2001 Schneider Electric All Rights Reserved
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Dimensions, Mounting, and Schematics for Type LR•K Overload Relays
Protection components
LR2K Separate mounting with terminal block LA7K0064 on 1.4 in. (35 mm) DIN rail
Direct mounting beneath the contactor (AM1DP200 or AM1DE200)
0.31 = 1.38 =
8 35
1.50
38
0.16
3.15
1.97
80
4mm
50
(#6) screws
4.57
116
=
2.95 1.77
2.28
75 45
58
c
AM1- c
2.56 1.77
65 45 DP200 3.09 in. / 78.5mm
DE200 3.38 in. / 86mm
A1
A
13
13
1
5
H
– KM1
14
1
95
95
97
95
2
14
A2
Internal
O
96
98
Links
96
2
96
A2
– KM1
A1
97 95 98 96
Reset/stop
6
2
LR2K Overload Relays feature built-in wiring to save time and materials
when all five links of the overload relay are connected to a K-line
contactor with an integrated N/O (normally-open) auxiliary contact.
Terminal 96 of the N/C (normally-closed) overload relay contact (95-96)
will be internally linked in series with terminal A2 of the contactor
operating coil. Terminal 95 of the N/C overload relay contact (95-96) will
be internally linked in series with terminal 14 of N/O coil holding contact
(13-14) of the contactor. These internal links help to eliminate additional
wiring when using a conventional 3-wire control circuit similar to the
diagram shown.
L1 L2
Start
Stop
95 96 A2 A1
13 14 Internal
Links
60
© 2001 Schneider Electric All Rights Reserved 04/01
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Characteristics of Type LP•K Low-consumption Contactors
Environment
Conforming to IEC 60947 V 690
Conforming to VDE 0110 gr C V 750
Rated insulation voltage (Vi)
Conforming to BS 5424, NF C 20-040 V 690
Conforming to CSA 22.2 No. 14, UL 508 V 600
Rated impulse withstand
kV 8
voltage (Vimp)
Meets the essential
IEC 60947, NF C 63-110, VDE 0660, BS 5424, UL 508, CSA 22.2 No.
Conforming to standards requirements of the LV &
14
EMC directives
E164862 E164862
NLDX LR43364 NLDX2
Approvals LP•K06, LP•K09, LP•K12
(screw clamp) 3211 04 (Slip-on &
solder pin)
Protective treatment Conforming to IEC 60068 (DIN 50016) “TC” (Fungus-proof, Tropicalization protection)
Degree of protection Conforming to VDE 0106 Protection against direct finger contact
°
90
90
90
°
°
18 0 °
Operating positions
°
90
Derate current carrying capability by 15%
Without derating Without derating when not mounted vertically
Conforming to UL 94 Self-extinguishing materials V1
Flame resistance
Conforming to NF F 16-101 and 16-102 Conforming to requirement 2
61
04/01 © 2001 Schneider Electric All Rights Reserved
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Characteristics of Type LP•K Low-consumption Contactors
Pole Characteristics
Conventional rated thermal current For ambient temperature
A 20
(Ith) ≤ 50 °C (122°F)
Rated operational frequency Hz 50/60
Frequency limits of the operational
Hz Up to 400
current
Rated operational voltage (Ve) V 690
I rms conforming to NF C 63-110
A
and IEC 60947
Rated making capacity
LP•K06, LP•K09 110
LP•K12 144
Conforming to NF C 63-110 and 220/ 380/ 660/
V 415 440 500
IEC 60947 230 400 690
Rated breaking capacity
LP•K06, LP•K09 110 110 110 110 80 70
I rms A
LP•K12 – – – 120 80 70
Open mounted, for a time “t” from
1s 5s 10 s 30 s 1 min 3 min ≥15 min
cold state (θ ≤ 50 °C [122 °F])
Permissible short time rating
LP•K06, LP•K09 90 85 80 60 45 40 20
A
LP•K12 115 105 100 75 55 50 25
By circuit breaker Select in accordance with NEC and local codes
Short-circuit protection
By fuses Max 400% of motor FLA
Average impedance per pole At Ith and 50 Hz mΩ 3
Maximum rated
operational current for a A 20
temperature ≤ 50 °C (122 °F)
On-load factor 90% 60% 30%
Rated operational current limits 300 op. cycles/hour 13 15 18
in relation to on-load factor and A
operating frequency 120 op. cycles/hour 15 18 19
Utilization in category AC-1
resistive circuits, heating, lighting 30 op. cycles/hour 19 20 20
(Ve ≤ 440 V)
Apply the following coefficients to the current values given above.
These take into account the often unbalanced current distribution
between poles
Increase in operational current
by paralleling poles 2 poles in parallel: K = 1.60
3 poles in parallel: K = 2.25
4 poles in parallel: K = 2.80
62
© 2001 Schneider Electric All Rights Reserved 04/01
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Characteristics of Type LP•K Low-consumption Contactors
63
04/01 © 2001 Schneider Electric All Rights Reserved
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Characteristics of Type LP•K Low-consumption Contactors
16 000
1000
Time constant
10 000 4
8000
1 Breaking limit of contacts valid for 6000
700
maximum of 50 operating cycles at 10 5000
1 500
in ms
4000
s intervals (breaking current = making 3
3000 300
current x power factor 0.7).
2000 200
250
2 Electrical durability of contacts for:
- 1 million operating cycles (2a) 1000 4
200 100
800
- 3 million operating cycles (2b) 600 80 2a
-10 million operating cycles (2c). 500 60
400 140 50
40 2b
3 Breaking limit of contacts valid for 300
100 30
2a
maximum of 20 operating cycles at 10 200
20
s intervals with current passing for 0.5
s per operating cycle. 100
2b
2c
80 2c 50 10
60
4 Thermal limit. 8
40 6
24 48 110 220 380 500 20
120 440 690 V 12 24 48 110 220 440 600 V
64
© 2001 Schneider Electric All Rights Reserved 04/01
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Selection of Low-consumption Contactors for Motor Control
The table below shows three-pole contactors with low-consumption coils for DC control circuits. They
are compatible with programmable controller outputs, and incorporate an LED indicator. For wide-range
coils (0.7 to 1.3 Vc), a suppressor is fitted as standard (consumption is 1.8 W).
The contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are
in the open, “ready-to-tighten” position.
For information on add-on auxiliary contact blocks and accessories, see page 69.
Coil Selection
Volts DC 12 24 48 72
Code JW3 BW3 EW3 SW3
LP4K06105•••
65
04/01 © 2001 Schneider Electric All Rights Reserved
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Selection of Low-consumption Reversing Contactors for Motor Control
The table below shows three-pole reversing contactors with low-consumption coils for DC control
circuits. They are compatible with programmable controller outputs, and incorporate an LED indicator
and mechanical interlock. For wide-range coils (0.7 to 1.3 Vc), a suppressor is fitted as standard
(consumption is 1.8 W).
The contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are
in the open, “ready-to-tighten” position. Customer wiring is required to connect coil terminations to the
electrical interlock; see page 72 for more information.
For information on add-on auxiliary contact blocks and accessories, see page 69.
Coil Selection
Volts DC 12 24 48 72
Code JW3 BW3 EW3 SW3
LP5K06105•••
66
© 2001 Schneider Electric All Rights Reserved 04/01
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Selection of Low-consumption Contactors for Resistive Loads
Three- and Four-pole Contactors with Low-consumption Coils for DC Control Circuits
The table below shows three- and four-pole contactors with low-consumption coils for DC control
circuits. They are compatible with programmable controller outputs, and incorporate an LED indicator.
For wide-range coils (0.7 to 1.3 Vc), a suppressor is fitted as standard (consumption is 1.8 W).
The contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are
in the open, “ready-to-tighten” position. For information on add-on auxiliary contact blocks and
accessories, see page 69.
Coil Selection
Volts DC 12 24 48 72
Code JW3 BW3 EW3 SW3
67
04/01 © 2001 Schneider Electric All Rights Reserved
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Selection of Low-consumption Contactors for Resistive Loads
Three- and Four-pole Reversing Contactors with Low-consumption Coils for DC Control Circuits
The table below shows three- and four-pole contactors with low-consumption coils for DC control
circuits. They are compatible with programmable controller outputs, and incorporate an LED indicator
and mechanical interlock. For wide-range coils (0.7 to 1.3 Vc), a suppressor is fitted as standard
(consumption is 1.8 W).
LP5K0910••• The contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are
in the open, “ready-to-tighten” position. Customer wiring is required to connect coil terminations to the
electrical interlock; see page 72 for more information.
For information on add-on auxiliary contact blocks and accessories, see page 69.
Coil Selection
Volts DC 12 24 48 72
Code JW3 BW3 EW3 SW3
68
© 2001 Schneider Electric All Rights Reserved 04/01
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Selection of Auxiliary Contacts and Accessories for Low-consumption Contactors
Instantaneous Auxiliary Contact Blocks (clip-on front mounting, 1 block per contactor)
Auxiliary Contacts
N/O N/C
2 – LA1KN20 0.10 (0.045)
Screw clamp 3- or 4-pole – 2 LA1KN02 0.10 (0.045)
1 1 LA1KN11 0.10 (0.045)
LP1KN•• 2 – LA1KN207 0.10 (0.045)
Slip-on 1 x 0.25 in. or 2 x 0.11 in. 3- or 4-pole – 2 LA1KN027 0.10 (0.045)
1 1 LA1KN117 0.10 (0.045)
2 – LA1KN203 0.10 (0.045)
Spring terminals 3- or 4-pole – 2 LA1KN023 0.10 (0.045)
1 1 LA1KN113 0.10 (0.045)
With terminal referencing conforming to EN 50012
– 2 LA1KN02M 0.10 (0.045)
3-pole, 6 and 9 A
Screw clamp 1 1 LA1KN11M 0.10 (0.045)
4-pole, 9 A 1 1 LA1KN11P 0.10 (0.045)
LA1KT2• V s SPDT
AC or DC 24 to 48 On-delay 1 to 30 1 LA2KT2E 0.09 (0.040)
AC 110 to 240 On-delay 1 to 30 1 LA2KT2U 0.09 (0.040)
Strips of 10 identical
25 AB1R• ▲ 0.004 (0.002)
numbers 0 to 9
Clip-in markers 4 maximum per contactor
Strips of 10 identical
25 AB1G• ▲ 0.004 (0.002)
capital letters A to Z
35mm " DIN rail (7.5 mm deep x 2 m long) 10 AM1DP200 2.88 (1.310)
35mm " DIN rail (15 mm deep x 2 m long) 10 AM1ED200 1.44 (0.650)
▲ Complete the catalog number by replacing the • with the required character.
DX1AP25
Cabling Accessories
Description Application Sold in lots of Unit Catalog No. Weight lb. (kg)
With screw clamp
For 2-poles 4 LA9E01 0.02 (0.010)
terminals
Paralleling links
With screw clamp
For 4-poles 2 LA9E02 0.03 (0.015)
terminals
For 3-pole reversing
For contactors with screw
Set of 6 power connections contactors for motor 100 LA9K0969 0.02 (0.010)
clamp terminals
control
For 4-pole changeover For contactors with screw
Set of 4 power connections 100 LA9K0970 0.02 (0.010)
contactor pairs clamp terminals
LA9E01
69
04/01 © 2001 Schneider Electric All Rights Reserved
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Dimensions and Mounting of Low-consumption Contactors
XXXXX
Contactors
LP4K
On panel On mounting rail AM1DP200 or AM1DE200 1.4 in. (35 mm) DIN rail
2.28
58
2.28
1.97
50
58
2.24 1.78
57 45
1.22 2.24 = =
=
1.38
31 57 35
1.78
45
DZ5 ME5
5
1.97
50
4.72
120
4.33
110
0.83 = =
0.20
2.24 1.38
5
57 21 35
1.78
45
0.34 == = A1
8.65
2.28
1.97
2.09
58
50
53
LA2 KT
2.28
1.06
58
27
1.34 1.50
34 38 2.24
Dimensions inches
1.34 mm
34 57
70
© 2001 Schneider Electric All Rights Reserved 04/01
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Dimensions and Mounting of Low-consumption Reversing Contactors
2.28
58
2.28
1.97
58
50
2.24 3.54
57 90
1.22 2.24 = 3.15 =
=
31 57 80
3.54
90
On one asymmetrical rail DZ5MB with 2 clip-on mounting plates LA9D973 or on 2 mounting plates DX1AP25.
2 x LA9D973 2 x DX1AP25
0.20
1.78
5
45
1.97 DZ5 ME5
50
4.33
110
4.72
120
2.24 0.83 = 1.38 =
0.20
5
57 21 35
3.54
90
2.24 1.06 3.54
On printed circuit board for reversing contactors or 2 contactors mounted side by side 57 27 90
0.34 == = = == 0.34
8.65 8.65
A1 A1
1.97
2.09
2.28
50
53
58
A2 A2
LA2 KT
2.28
1.06
58
27
1.34 1.50
34 38 1.34 2.24 Dimensions inches
34 57 mm
71
04/01 © 2001 Schneider Electric All Rights Reserved
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Type LP•K Schematics
5/L3
1/L1
13/NO
3/L2
5/L3
1/L1
+A1
21/NC
A1
A1
A2
14
A2
22
T3/6
T1/2
T2/4
T3/6
T1/2
T2/4
-A2
3-pole reversing contactors Dashed lines indicate suggested customer wiring to Integrated-coil suppression device
LP5K electrically interlock coils LC5K
With screw clamp terminals
3-pole + N/O 3-pole + N/C
+A1
5/L3
3/L2
3/L2
5/L3
1/L1
1/L1
13/NO
13/NO
5/L3
3/L2
3/L2
5/L3
1/L1
1/L1
A1
A1
21/NC
21/NC
A1
A1
A2
A2
14
14
T3/6
T3/6
T1/2
T2/4
T1/2
T2/4
A2
A2
22
22
T3/6
T3/6
T1/2
T2/4
T1/2
T2/4
-A2
With Slip-on connectors or solder pins for printed circuit boards
3-pole + N/O 3-pole + N/O
5/L3
3/L2
3/L2
5/L3
1/L1
1/L1
5/L3
3/L2
3/L2
5/L3
1/L1
1/L1
13/NO
21/NC
13/NO
21/NC
A1
A1
A1
A1
A2
A2
A2
A2
22
22
14
14
T3/6
T3/6
T1/2
T2/4
T1/2
T2/4
T3/6
T3/6
T1/2
T2/4
T1/2
T2/4
63/NO
51/NC
61/NC
53/NO
61/NC
33/NO
21/NC
21/NC
31/NC
52
62
54
64
62
54
22
22
34
32
16
18
15
A2
72
© 2001 Schneider Electric All Rights Reserved 04/01
K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories
Type LP•K Schematics
+A1
3/L2
5/L3
7/L4
1/L1
R1
R3
1
3
A1
A1
A2
A2
T3/6
T4/8
T1/2
T2/4
4
R2
R4
2
-A2
4-pole reversing contactors Integrated-coil suppression device
LP5K LP5K
With screw clamp terminals With slip-on terminals or solder pins for printed circuits boards
+A1
5
7
3
7
1
1
1/L1
1/L2
1/L3
1N
2/L1
2/L2
2/L3
2N
A1
A1
A2
A2
5
7
3
5
1
1
A1
A1
8
2
4
A2
A2
6
8
2
-A2
L1
L2
L3
63/NO
51/NC
61/NC
53/NO
61/NC
13/NO
21/NC
52
62
54
64
62
54
14
22
16
18
15
A2
73
04/01 © 2001 Schneider Electric All Rights Reserved
74
© 2001 Schneider Electric All Rights Reserved 04/01