Building A SCADA System
Building A SCADA System
Version 6.1
JANUARY 2020
Disclaimer of Warranties and Liability
The information contained in this publication is believed to be accurate and reliable. However, General Electric Company assumes no
responsibilities for any errors, omissions or inaccuracies. Information contained in the publication is subject to change without notice.
No part of this publication may be reproduced in any form, or stored in a database or retrieval system, or transmitted or distributed in any
form by any means, electronic, mechanical photocopying, recording or otherwise, without the prior written permission of General Electric
Company. Information contained herein is subject to change without notice.
Trademark Notices
© 2020, General Electric Company. All rights reserved.
* Indicates a trademark of General Electric Company and/or its subsidiaries.
All other product names and marks identified throughout this book are trademarks or registered trademarks of their respective companies.
They are used throughout this book in editorial fashion only. No such use, or the use of any trade name, is intended to convey endorse-
ment or affiliation.
No part of this publication may be reproduced in any form, or stored in a database or retrieval system, or transmitted or distributed in any
form by any means, electronic, mechanical photocopying, recording or otherwise, without the prior written permission of GE. Information
contained herein is subject to change without notice.
We want to hear from you. If you have any comments, questions, or suggestions about our documentation, send them to the following
email address:
[email protected]
Table of Contents
Reference Documents 1
Introduction 2
Database Manager 2
Understanding a Database 2
Understanding Chains 3
Sample Application 6
Getting Started 7
To get started: 7
Exchanging Data 8
Designing a Chain 12
To design a chain: 12
Describing the Sample Process Application 12
Block Fields 28
Scan Times 29
Phasing 33
Overphasing 35
Block Modes 35
I/O Drivers 39
Simulation Drivers 40
Example 43
Example 45
Adding Blocks 53
Duplicating Blocks 56
To configure Excel: 56
Moving Blocks 57
Modifying Blocks 58
Deleting Blocks 59
Saving a Database 59
Find Options 60
Replacing Data 61
Find Options 61
Using Go To 61
Case Sensitivity 67
Grouping Queries 68
Editing a Query 68
Managing Databases 71
Verifying Databases 71
Correcting Errors 72
To correct errors: 72
Reloading Databases 72
Exporting Databases 74
Syntax 75
Parameters 75
Error Codes 75
Importing Databases 77
Advanced Topics 78
Index 82
Building a SCADA System
Building a SCADA System is intended for process engineers responsible for designing and building a process database. This
manual shows engineers how to create, modify, and delete blocks and chains. It also teaches the skills engineers need to sort,
query, and optimize iFIX® databases.
Reference Documents
For related information about iFIX, refer to the following documents:
l Understanding iFIX
l Writing Scripts
l Creating Recipes
Introduction
iFIX® provides process information for plant managers, supervisors, and operators in the form of reports, displays, archived
data, alarms, messages, and statistical charts. The sources of this information are OPC servers or process hardware — the con-
trollers, sensors, motors, switches, and other devices — required to manufacture your product.
iFIX reads process information from these devices and saves it in one or more process databases residing on your SCADA serv-
ers. The database plays an integral part in your industrial automation strategy; it is the primary source of process data for most
iFIX applications. Whether you collect historical values or generate shift reports, iFIX enables you to create a database that sup-
ports your specific industrial control and automation needs.
Database Manager
Your main tool for creating and managing process databases is Database Manager. This program lets you open and configure
the database of any SCADA server. You can also:
Understanding a Database
Every SCADA server loads a process database at start-up. Once loaded, the database:
l Receives values from an I/O driver or OLE for Process Control (OPC) server.
l Manipulates values according to its configuration (a control strategy).
l Compares the values to alarm limits you define.
l Outputs adjusted values to the I/O driver or OPC server.
l Sends alarms to operator displays, printers, files, and network alarm destinations.
The following figure illustrates how values enter a database, travel through a sequence of blocks, and exit the database as out-
put.
I/O Data and the Database
The main components of a process database are blocks. Blocks are capable of:
l Receiving values either from another block, OPC server, or directly from an I/O driver.
l Manipulating values according to its configuration.
l Comparing incoming values against pre-defined limits.
l Scaling process values to a specified range.
l Performing calculations.
l Outputting values back to the I/O driver or OPC server.
iFIX provides different types of blocks, each capable of performing a unique function. For a brief description of each block, refer
to the section Block Types and Descriptions.
By default, when you install iFIX, it creates an empty database for your SCADA server. Using Database Manager, you can add
the blocks you require to this database.
Understanding Chains
Blocks by themselves perform specific tasks in the database. By combining two or more blocks together, you can form chains.
Each chain performs the tasks of its component blocks by passing data from one block to the next. When properly configured,
chains can generate alarms, acquire data, and verify, automate, and maintain a process. In automating large processes
involving a number of I/O devices, a database can contain many chains, each designed to automate and maintain a specific
function or process step.
Each chain can contain up to 30 blocks, with each block configured to perform a specific processing function. Note that some
blocks are designed to work in chains while others are designed to operate on their own. Specific types of blocks, their func-
tions, and their relationship to one another are summarized in the section Block Types and Descriptions.
Familiarize yourself with the available blocks. Having a good understanding of the blocks and their capabilities allows you to
quickly design optimum strategies for your application.
In order for your blocks and chains to function, the Scan, Alarm, and Control program (SAC) processes them at the time interval
you define. SAC processes your blocks and chains by:
l Scanning individual blocks in the chain, reading new I/O values and returning values to the process hardware.
l Alarming on incoming values if they exceed pre-defined limits you specify.
l Controlling the automation process by assuring that each block verifies or manipulates incoming values according to its
configuration and sends values on to the next block in the chain.
The following figure shows SAC reading process values, sending these values through database chains, and returning the out-
put values.
Once you create a process database, your SCADA server can monitor process conditions and report alarms. Alarms occur
when an incoming value exceeds a pre-defined limit. Using the iFIX WorkSpace, you can draw and animate any object by rotat-
ing, coloring, or scaling it when an alarm occurs. These visual cues help operators respond to alarms in a timely fashion. For
more information on reporting alarms, refer to the Implementing Alarms and Messages manual.
For information on trending data, creating scripts and schedules, and archiving data, refer to the following topics:
SCADA servers can also trend and display real-time and historical values. Process trends enable you to record and analyze pro-
cess-critical values and allow you to:
For more information on collecting historical values, refer to the Trending Historical Data manual. For more information on trend-
ing real-time data for operators, refer to the Creating Pictures manual.
Using Visual Basic for Applications (VBA) or the Scheduler, you can adjust database values, place blocks on scan or off scan,
change a block's mode, or launch a script based on a value change or an alarm. For example, using a time-based schedule, you
could set the values of a dozen blocks prior to the manufacture of your product or you could automatically ramp a value based on
an event (such as a valve closing). Likewise, you could write a script to monitor the value of a block and, when an alarm occurs,
open a diagnostic picture. For more information on using these features, refer to the Writing Scripts and Mastering iFIX manuals.
In addition to using scripts and schedules to write values to the process database, you can use a relational database. Writing val-
ues from a relational database is similar to writing values with a script. In both cases, values are written at a pre-defined time or
when an event occurs (such as a contact opening). However, unlike scripts and schedules, writing data from a relational data-
base requires that you configure the SQL Trigger and SQL Data blocks in the process database.
These blocks also let you archive data to a relational database. Once the relational database receives and stores the process
data, you can query it to retrieve and analyze any information. For more information on setting up and using a relational data-
base, refer to your ODBC manuals and the Using SQL. For more information on process database blocks, refer to the iFIX Data-
base Reference.
IMPORTANT: If you are working in a secure environment and using the Electronic Signature option, you must be aware of the impact
of unsigned writes to the process database. Unsigned writes can originate from scripts, schedules, and writes from a relational data-
base. Refer to the Implications of Database Writes With Electronic Signature section of the Using Electronic Signatures manual for
detailed information.
Sample Application
To help you understand how to create process databases for yourself, this manual uses a sample application for manufacturing
fertilizer and monitoring chemical consumption and equipment usage. The blocks and chains that comprise the application were
developed by the Enviro company which collects sludge generated by municipal sewage plants and converts it into different
grades of agricultural fertilizer in briquette form. The Enviro company's manufacturing process encompasses:
l Continuous control
l Batch control
l Discrete parts
Getting Started
You can begin creating process databases by verifying that your SCADA servers are set up and functioning. Once you set up
these computers, follow the steps.
To get started:
1. Install iFIX on each SCADA server.
2. Configure each server with the System Configuration Utility (SCU). Refer to the Setting up the Environment manual to
learn how to enable SCADA support.
3. Set up the alarm area database for each server. This database contains the alarm areas you can assign to the blocks on
the SCADA server. If you want to share an alarm area database across multiple servers, change the Alarm Area path in
the SCU to reference a file server before you create your process databases.
You can start Database Manager by clicking the Database Manager button on the Application toolbar (Classic view) or by select-
ing Database Manager, in the Process Database group, on the Applications tab (Ribbon view). As the program starts up, it
prompts you to select the SCADA server you want to connect to and establishes a connection to the computer you select. Once
Database Manager connects to the selected SCADA server, the program opens the server's current database.
From the Database Manager, you can open databases from SCADA nodes with iFIX 3.0 or greater installed. You cannot add,
modify, or delete blocks in databases from earlier versions of iFIX, such as iFIX 2.5 or FIX32.
To exit from the program, in Classic view, select Exit from the File menu or in Ribbon view, click the Database Manager button,
and then click Exit.
NOTE: Connections to remote SCADA servers are established with a physical node name, not logical node names. Logical and phys-
ical node names are identical unless you enable SCADA redundancy. For more information about this feature, refer to the Mastering
iFIX manual.
Each process database you open appears as a spreadsheet in Database Manager. Blocks appear as rows, and block fields
appear as columns. Click to select a row or field. You can also select multiple rows and columns by clicking and dragging.
The following topics provide more information about the database spreadsheet:
By configuring these properties you can customize the spreadsheet as needed. To learn more about these properties, refer to
the chapters Locating and Displaying Data and Querying and Sorting Data.
In addition to the properties you can configure, the spreadsheet lets you right-click any row, column, or cell to display a menu
containing a list of frequently-accessed commands. These commands are identical to commands you can access from the
menu bar. For example, Cut on the pop-up menu is identical to Cut on the Edit menu. Similarly, Add Block on the pop-up menu is
identical to Add on the Blocks menu.
You can edit most spreadsheet cells by selecting them and entering the data you want to display, allowing you to change indi-
vidual items quickly. Cells in certain columns, such as the Tagname column, are read-only and cannot be modified.
To change multiple fields for a particular block, you can double-click the block to display its dialog box. To change the same field
for multiple blocks, you can find and replace data in a spreadsheet column. Refer to the chapter Locating and Displaying Data to
learn more about finding and replacing data.
Exchanging Data
Database Manager also lets you edit blocks by copying or exporting them. Whenever you complete these tasks, the program
converts the selected blocks into comma separated value (CSV) format, enabling you to paste or import the data into your favor-
ite text editor or spreadsheet. Once you edit the data, you can copy or import the data back to Database Manager.
Often a quicker way to convert blocks into CSV format is by holding down the Control key and dragging and dropping the blocks
from Database Manager and into Microsoft® Excel. The blocks you move appear in CSV format, allowing you to edit them.
When you finish, you can drag them back. To learn more about using Excel with the Database Manager, refer to the section
Copying and Pasting Blocks.
Across the top of the spreadsheet is the Database Manager Ribbon. The Ribbon, shown in the following figure, provides access
to common database operations such as saving a database or adding a block.
Setting Database Manager Preferences
Database Manager provides preferences for printing, saving, displaying, and editing the database. These preferences let you
adjust how Database Manager handles certain operations. The following table summarizes the preferences you can enable.
You also have the option to set the automatic refresh rate.
Editing pref- Open block dialog boxes in view or modify mode when you double-click a cell in the spreadsheet. In view mode,
erences you can examine the block configuration but not modify it. The block and its chain remain on scan at all times. In
modify mode, you can examine and change the block configuration. The block and its chain are placed off scan
even if you do not modify the block.
You also have the option to place edited blocks and chains on scan automatically when you finish editing them.
By default, this option is disabled and Database Manager prompts you to place modified blocks on scan.
After you have this data, you are ready to design a database. To help illustrate how to do this, this chapter walks you through the
process of designing a chain for the Enviro company, introduced in the section Sample Application. Using these examples, you
should be able to create your own blocks and chains for your process database.
As you read this chapter, you may find it helpful to skip ahead and learn how to add a block with Database Manager so that you
can create the sample chains described here. By creating sample chains, working with Database Manager, and correcting
errors, you learn how to avoid mistakes before you create your actual database.
The first step in designing a database is to examine the application that you want to automate. Next, assign specific processing,
maintenance, and monitoring tasks. For example, the Enviro company identified the following tasks, the specific iFIX features
they would use to accomplish them, and the economic benefits.
The key elements of this application also apply to processes in other industries, such as chemical processing, food processing,
and even discrete parts manufacturing.
Designing a Chain
Once you know the tasks you want to accomplish, you can design the chains for your database. The easiest and most efficient
way to design a functional chain is to use the following design steps:
To design a chain:
1. Analyze your process and make a record of the data you need, including:
l I/O addresses of the device controller (a wiring list)
l Device types
l Signal conditioning
l The EGU range
2. Design an automation strategy that explains how you want your process automated. For example:
l What types of alarms and alarm limits do you want to establish?
l How often do you want the chain processed?
l When do you want operators notified of process events?
l How do you want process disruptions handled?
3. Create an algorithm that combines your process analysis and automation strategy. This determines how iFIX automates
your process and provides the specific processing instructions you will enter into block dialog boxes.
4. Match the steps in your algorithm to blocks capable of performing these steps.
5. Draw a flowchart listing the block types that perform each step along with the specific processing instructions for each
block.
The example presented in the following subsections illustrates the thought process involved in designing a simple chain.
Sludge from the collection tank is periodically pumped into a large tank where water is added to make the sludge easier to mix. A
sensor in the tank registers the sludge's pH level. If the sludge is acidic, a device controller turns on a pump that adds an
alkaline solution into the tank to raise the pH; if the sludge is alkaline, the device controller turns on a pump that adds an acidic
solution into the tank to lower the pH. In either case, the sludge's pH is properly adjusted according to the grade of fertilizer that
is needed before it is pumped to the filter press. The following figure shows the pH adjustment tank and its equipment.
pH Adjustment Tank
The next step is to design a chain that examines and adjusts the sludge's pH by:
Once you complete these tasks, you can add blocks to monitor pH fluctuations, chemical usage, pump usage, down time, and
other statistical information. You can also historically trend this information, print it in reports, and display it to operators.
The first step in automating your process is analyzing how the process works. By developing a detailed process analysis first,
you save time because you isolate the tasks that simple chains can complete and identify those tasks that require more com-
plex chain designs. For example, a task in the Enviro company might be "if the pH is greater than 8.5, add the acidic solution
until it reaches 7.5."
Although this analysis describes how the process works, it lacks important information about your control devices. You need to
add detailed information on I/O driver or OPC server addresses, the type of controller equipment, signal conditioning, and max-
imum ranges the equipment can accept. In short, record all detailed information on how the process equipment operates.
After you obtain this information, you can go on to write a detailed analysis of your process. The following table presents a
sample analysis of the pH monitoring and adjustment process.
The next step in designing a database chain is planning a successful automation strategy. This requires you to determine how
you want to automate the steps recorded in your process analysis. The following steps provide a sample automation strategy for
the pH adjustment process.
Notice how this automation strategy incorporates an alarming plan for handling process upsets, such as extreme pH fluc-
tuations (rate of change). This helps to assure that empty drums of acidic and alkaline solutions do not go unnoticed and equip-
ment failures do not interrupt your treatment process.
The next and most important step in designing the pH adjustment chain is writing an algorithm that combines both the process
analysis and automation strategy. The following figure shows how the technical specifications outlined in the process analysis
are combined with the automation needs listed in the automation strategy.
Creating an Automation Algorithm
The algorithm forms the basis of your chain; it identifies the order in which the process proceeds, where each step acquires
information, and how iFIX gathers, processes, and verifies information.
The next step is finding the right database blocks to perform the steps outlined in the algorithm. This process transforms the
algorithm from written steps into a chain schematic. Moreover, this step ensures that you incorporate iFIX capabilities into your
processing plans. Once you complete this design step, you can enter your designs into your SCADA server's database.
When matching blocks to steps, select a block that can perform the function of a step. In many cases, one block type can
handle more than one step, whereas some steps may include too many functions or too many complex operations for any one
block.
For your pH adjustment process, the following blocks satisfy the algorithm:
1. An Analog Input block can receive analog signals from the pH sensor's address.
2. The Analog Input block can also accommodate the alarming requirements, so this task is assigned to this block.
3. The pumps are turned on or off based upon the value that the Analog Input block receives from the pH sensor. The block
required for this step must be able to monitor an analog input and, depending on the value of the input, open or close a
digital output point.
The digital outputs are sent directly to the acid and alkali pump addresses. The On-Off Control block can perform this
function.
Since the On-Off Control block can turn the pumps on and off without the use of any other block, this completes step 3.
At this point you've identified the blocks that can perform all the steps in your algorithm.
The flowchart is a visual representation of the chain and shows the instructions you will enter into each block as you add them to
the database. The following figure shows a flowchart for the pH adjustment process.
Chain Flowchart
Typically, your chain designs are seldom perfect the first time you implement them. With Database Manager, you can always
re-evaluate the design of your chain, add blocks, remove blocks, modify block configurations, or change block types to those
that accommodate more sophisticated automation functions.
The best approach to re-evaluating the design of your chain is to examine the original automation algorithm and determine if
other blocks provide more flexibility or features over the existing blocks. For example, after testing the sample chain, Enviro
engineers found it works well most of the time, but every so often the adjustment process exceeds acceptable pH limits by
pumping in too much acidic solution, which lowers the pH beyond acceptable limits. The following figure illustrates this problem.
Sample pH Problem
You want the capability of pumping in acid at short intervals. In the original design, iFIX scans the chain every four minutes. This
allows the acid more time to react with the sludge before more acid enters the tank. An additional improvement would be to
shorten the chain's scan time, providing more pH sampling to determine which solution needs to be pumped into the tank.
By re-examining the automation algorithm, you can determine where to make improvements to the chain. Reproduced below is
the original automation algorithm that called for the On-Off Control block.
l If the pH is below 5.5, turn on the pump to add an alkaline solution. If the pH is above 8.5, turn on the pump to add an acid
solution.
l Acid pump digital address: 1:1:40004:8
l Alkaline pump digital address: 1:1:40004:5
l If the pH is between 5.5 and 8.5, stop all pumps.
What you want to do is modify this algorithm to run the acid pump for shorter intervals, giving the acid time to decrease the pH
before the acid is turned on again. To do this, you need to examine if other blocks can perform this task.
One block capable of turning a pump on or off is the Program block. You can replace the On-Off Control block with the Program
block. However, the Program block cannot establish direct digital contact with the acid and alkali pumps. For this you need to
use two Digital Output blocks, one for each pump.
The following figure shows the replacement of the On-Off Control block with the Program block and the two Digital Output
blocks, and represents how information passes from one block to the next.
Chain Modification
NOTE: The figure Chain Modification illustrates how the data flows from one block to another, not the actual chain structure.
The following figure provides the new programming instructions required to operate the Program and Digital Output blocks.
Modified Flowchart
With this modification and with the Analog Input block's scan time reduced to one minute, the chain handles pH adjustment
more efficiently by allowing the Program block to run short programs that adjust the pH. The following figure shows how the mod-
ified chain handles pH adjustment.
Data trended by a chart is not stored. To store the real-time data use a Trend block. Then with a chart you can view these values
directly on an operator display. The following figure shows the same control chain with a Trend block added to the chain.
Trend Block Insertion
Adding other blocks, such as the Statistical Data block, allows you to display statistical data in a graph.
The chain shown from the sample application performs data acquisition and control. These types of chains usually receive
inputs from an I/O driver or OPC server through an input block, manipulate the inputs with secondary blocks, and return an adjus-
ted value to the I/O driver or OPC server through an Analog Output, Digital Output, or On-Off Control block, as the following fig-
ure shows.
With Database Manager you can create very large databases. If you do this, keep in mind:
l The size of the database that you can construct is limited by the amount of memory you have available in your computer.
l Plan your database carefully. A database that implements a good scan time and phasing scheme will provide better sys-
tem performance than the same database that has its blocks scanned all at once.
l iFIX provides a number of features that can aid in processing large databases:
l Exception-based processing (triggered by a change at the I/O address).
l One shot processing.
l Long scan times (up to 24 hours with phasing configurations of up to HRS:HRS, HRS:MIN, MIN:MIN, MIN:SEC,
and so forth).
l Subsecond processing.
For more information on these topics, refer to the section Scan Times.
Make sure you have enough disk space available when saving your database to disk. If your SCADA server does not have
enough disk space, you may lose the changes you have just made. For example, if you build a 3MB database, make sure you
have 3MB of free disk space available.
When planning your automation strategy you may want to consider using Analog Input and Digital Input blocks, or Analog
Register and Digital Register blocks. All four blocks combine read/write capabilities and eliminate the need for separate output
blocks.
Analog Register and Digital Register blocks also have specific addressing and configuration requirements:
Your main task when setting up a SCADA server is creating blocks for your process database. In general, you can create a
block by completing its dialog box. However, in order to configure a block, you should understand the basic database concepts,
such as scan times and phasing. This chapter discusses these and other database concepts.
Typically, every SCADA server comes with two types of blocks: primary and secondary. The main difference between these
block types is that primary blocks have scan times and are first in a chain. Secondary blocks do not have scan times and are
never first in a chain.
Database Options
The option... Provides... Refer to the section...
Control Continuous, PID, direct, and digital control. Understanding Control Blocks to learn more
about control blocks.
Statistical Pro- Statistical data analysis and calculations, alarming, Understanding Statistical Process Control
cess Control supervisory control, and display of statistical data. Blocks to learn more about SPC blocks.
(SPC)
Batch State-driven, interlocked, and batch control. Understanding Batch Blocks to learn more
about batch blocks.
SQL Read and write access to a relational database on a Understanding SQL Blocks to learn more
remote server. about SQL blocks.
The following table summarizes the differences among all the blocks. For detailed information on blocks, refer to the iFIX Data-
base Reference.
Block Summary
Block Type Primary Secondary Standard Optional
Analog Alarm (AA) x x
Analog Input (AI) x x
Analog Output (AO) x x
Analog Register (AR) x x
Boolean (BL) x x
Calculation (CA) x x
Dead Time (DT) x x (Control)
Device Control (DC) x x (Batch)
Digital Alarm (DA) x x
Digital Input (DI) x x
Digital Output (DO) x x
Digital Register (DR) x x
Event Action (EV) x x
Extended Trend (ETR) x x
Fanout (FN) x x
Histogram (HS) x x (SPC)
Lead Lag (LL) x x (Control)
Multistate Digital Input (MDI) x x
On-Off Control (BB) x x (Control)
Pareto (PA) x x (SPC)
PID (PID) x x (Control)
Program (PG) x x (Batch)
Ramp (RM) x x (Control)
Ratio/Bias (RB) x x (Control)
Signal Select (SS) x x (Control)
SQL Data (SQD) x x (SQL)
SQL Trigger (SQT) x x (SQL)
Statistical Control (SC) x x (SPC)
Statistical Data (SD) x x (SPC)
Text (TX) x x
Timer (TM) x x
Totalizer (TT) x x
Trend (TR) x x
NOTE: The tag count limit per tag type is 32,767.
Primary blocks receive data from an I/O driver or OPC server and generate alarms based upon this information. Primary blocks
are usually associated with one or more pieces of process hardware. For example, a pump, a tank, a temperature sensor, a
photo cell, a limit switch are all process hardware with which you might associate a primary block.
Most primary blocks, listed in the following table, also include a scan time. The scan time controls when SAC scans the blocks
in the database. Refer to the section Scan Times to learn more about them.
Secondary blocks manipulate data according to your instructions. Secondary blocks usually receive input from an upstream or
primary block and perform a specific function with that input, such as perform a calculation or store several successive input val-
ues. Therefore, a secondary block cannot be the first block of a chain. However, you can connect secondary blocks to create a
chain like the one shown in the following figure.
Control blocks provide continuous, direct, or digital control capability. The following table lists the available control blocks.
Control Blocks
The Function:
block...
Dead Delays the transfer of an input value to the next block in the chain for up to 255 seconds. It can store up
Time (DT) to 60 values of incoming variables and sends values on a first in/first out basis.
Lead Lag Lets you simulate process dynamics and includes a digital approximation of the exponential equations
(LL) for lead lag. This block is useful in feed-forward strategies.
PID (PID) Compares analog inputs to a user-defined set point and sends out incremental adjustments to bring the
process variable closer to the set point.
On-Off Receives analog values and outputs digital values.
Control
(BB)
Ramp Increases or decreases values to a target value at a specified rate. You can enter the target values
(RM) manually or they can be retrieved from other blocks. You can define three distinct stages for the ramp
process.
Ratio/Bias Lets you change incoming signals by adding a constant (bias) and/or by multiplying a constant (ratio)
(RB) after subtracting an offset from the signal. This block uses less memory and executes faster than the
Calculation block.
Statistical Process Control (SPC) provides statistical data analysis and calculations, alarming, supervisory control, and display
of statistical data. The following table lists the available SPC blocks.
Batch Blocks
The block... Function:
Device Control (DC) Coordinates the opening and closing of digital devices based upon user-defined conditions.
Program (PG) Runs short programs for batch operations or to increase the degree of automation in an application.
SQL blocks read and write data to a relational database. The following table lists the available SQL blocks.
SQL Blocks
The block... Function:
SQL Data Identifies the data to send and retrieve between the process database and your relational database.
(SQD)
SQL Trigger Triggers the execution of SQL commands and defines how your relational database interacts with the pro-
(SQT) cess database.
For more information about how these blocks work and how to use them, refer to the Using SQL manual and the iFIX Database
Reference.
iFIX can process information from one or more Database Dynamo objects, also known as loadable blocks. Each Database
Dynamo is an optional block that adds functionality to the process database. By using Database Dynamos, you can create new
blocks tailored to your needs. For example, you might create a Dynamo that provides a custom PID or other control algorithm.
You can create a Database Dynamo by using the Database Dynamo Toolkit. After you create one, iFIX treats your Database
Dynamo like any other block in the process database. This feature enables iFIX to process alarms from the Dynamo, along with
the other alarms in the system. Database Dynamos also enable you to:
GE also makes the following Database Dynamos available in the iFIX product:
Use the Database Dynamo Configuration Utility (BTKCFG.exe) to add the Database Dynamos in the above table to iFIX. After
iFIX is restarted, you will then be able to add blocks of these types in the iFIX Database Manager.
To add a Database Dynamo:
1. Double-click the Btkcfg.exe file to launch the Database Dynamo Configuration Utility. By default, this file is located in
the iFIX install folder, C:\Program Files (x86)\GE\iFIX.
2. In the Available Database Dynamos list, select the Dynamo that you want to add and click Add (or optionally, click Add
All). This moves the specified Database Dynamos to the Configured Database Dynamos list.
3. On the File menu, click Save.
4. Restart iFIX. After iFIX restarts, you will then be able to add the blocks in the above table within the iFIX Database Man-
ager.
IMPORTANT: Use caution in removing Database Dynamos (loadable blocks). If you use the Database Dynamo Configuration Utility
(BTKCFG.exe) to remove a loadable block but do not remove the block from the iFIX database, an error message appears in the Alarm
History that a block type is missing and the blocks are not loaded.
To remove a Database Dynamo:
1. Double-click the Btkcfg.exe file to launch the Database Dynamo Configuration Utility. By default, this file is located in
the iFIX install folder, C:\Program Files (x86)\GE\iFIX.
2. In the Configured Database Dynamos list, select the Dynamo that you want to remove and click Remove (or optionally,
click Remove All). This moves the specified Database Dynamos to the Available Database Dynamos list.
3. On the File menu, click Save.
4. Restart iFIX.
To change a slot number of a Database Dynamo:
1. Double-click the Btkcfg.exe file to launch the Database Dynamo Configuration Utility. By default, this file is located in
the iFIX install folder, C:\Program Files (x86)\GE\iFIX.
2. In the Configured Database Dynamos list, select the Dynamo that you want to change the slot number for.
3. In the Slot Number field, enter a new number. You can enter any number between 50 to 149 that is not in use. For more
information on slot numbers, refer to the Understanding Slot Numbers section.
4. On the File menu, click Save.
5. Restart iFIX.
The database contains approximately 100 slots into which Database Dynamo blocks can be added. These slots are numbered
from 50 to 149. Slots 1 to 49 are reserved for GE database blocks.
The Database Dynamo Configuration Utility generates a default slot for the Database Dynamo that you are adding to the data-
base. Use this slot. If you must change the Database Dynamo slot, select the Dynamo in the configured column and enter a
new value for the slot in the Slot field.
NOTE: Once a slot is selected, it should never be changed. If you must change the slot, export the database to an ASCII file first.
Change the slot of the block. Delete the database and import the ASCII file into a new database.
Block Fields
Whenever you add a block, its configuration dialog box appears. The dialog box fields and controls represent locations in the
block called fields. These fields store the information you enter into the dialog box. This information includes such data as the
block's name, description, scan time, I/O address, and scan status.
Other block fields receive information from your process hardware or from other blocks. For example, a primary block's current
value comes from an I/O device. However, a secondary block receives its current value from an upstream block.
The format indicates the type of data that the field stores. The following table lists the available formats:
Field Formats
Format: Description: Used in...
A_ ASCII Format. Data links and objects in pictures.
F_ Floating-point Data links, objects in pictures, and block-to-block references.
Format.
E_ 15-Digit Precision Data links, objects in pictures, and block-to-block references. Valid values range from +/-
Format. 3.40282300000000e+/-38, with 15 digits of accuracy.
T_ Graphic Format. Charts.
Refer to the Creating Pictures manual for more information on Data links, objects in pictures, and charts.
The name indicates the specific information in the field. For example, the current value of a block is identified by the name:
CV
The combination of the field format and the field name provides you with the information you want. For example, if you want the
current value of a block displayed as a number, you select the field F_CV. If you want the current value of a block displayed as
text, you select the field A_CV.
You can display a list of fields for the currently selected block using the Expression Builder or the iFIX Database Reference
help. Using this information, you can configure Data links or other objects in your operator displays to extract block field data by
specifying a data source. Alternatively, you can write a Visual Basic for Applications (VBA) script or an Easy Database Access
program to extract and display block field data. For more information about the Expression Builder, specifying data sources, and
adding Data links and objects, refer to the Creating Pictures manual.
The iFIX Database Reference provides information to help you complete block dialog boxes. The remainder of this chapter
provides related information for completing common block fields, such as the scan time, phase, and I/O driver fields. Refer to
these sections to learn how to configure these fields for your blocks.
Scan Times
All primary blocks have a scan time. The scan time determines how often SAC processes the block and sends the current value
to the next block in the chain. SAC processes all secondary blocks chained to a primary block according to the primary block's
scan time.
Time-based processing is best used when you want to regularly scan a block. If you only need to scan a block when its value
changes, use exception-based processing instead. Similarly, you can use one shot processing if you need to scan a block when
the process database initially loads.
In time-based processing, SAC processes a block at a set time. The following table lists the scan time ranges you can enter for
time-based chains.
SAC scans chains with hour and minute scan times based on the system clock of the local SCADA server. Scan times are set
relative to midnight (00:00:00 hours). SAC scans chains with second and subsecond scan times based on the computer's start
up time, as the following tables describes.
You can assign a time-based scan time to a block by completing its Scan Time field with the following format:
time unit
The following table lists the valid units and their abbreviations. If you do not enter a unit of time, iFIX assumes the unit is
seconds.
Unit Entry
Minutes M
Hours H
l Assign scan times larger than the poll rate assigned in the I/O driver. This ensures that the I/O driver has time to read and
send new values to SAC before SAC scans each block again. See your I/O driver manual for more information about the
poll rate.
l Phase (stagger) scan times to reduce the risk of overloading the CPU. Refer to the section Phasing to learn more about
phasing.
l Assign critical process chains a more frequent scan time than non-critical chains. If you need to have a chain scanned
every 2 minutes, assign a 2-minute scan time, not a 5-second scan time. Remember that very short scan times require
more CPU time and SAC processing than longer scan times.
l If a chain does not need processing at a set time, assign exception-based processing. Doing so will require less CPU
time and improve performance.
Exception-based processing lets SAC scan a block or chain by exception, not at scheduled time intervals. An exception is:
l A change in a process value greater than the defined exception dead band; or
l An unsolicited message from your process hardware.
Using exception-based processing generally requires less CPU time and improves performance because SAC does not have to
scan blocks at defined intervals. However, if a block's value changes very frequently, time-based processing may be more effi-
cient.
You can use exception-based processing only if your I/O driver supports it. Consult your I/O driver client manual to learn if your
I/O driver supports exception-based processing.
NOTE: The SM2 driver supports exception-based processing; the SIM driver does not support exception-based processing.
CAUTION: Do not assign the same I/O address to exception-based and time-based blocks. Doing so will cause the exception-based
blocks to occasionally miss an incoming value.
While you can use exception-based processing with most blocks, certain blocks perform better with exception-processing than
others. You can use the following blocks in exception-based chains as needed:
l Analog l On-Off
Input Control
l Analog l Pareto
Output
l Digital l Ratio/Bias
Input
l Digital l SQL Data
Output
l Fanout l Timer
l Histogram l Totalizer
Using Program and Statistical Data Blocks
Typically, the blocks listed in the following table are used as stand-alone blocks and have limitations when incorporated in an
exception-based chain.
The Boolean, Calculation, Event Action, and Signal Select blocks can use values from multiple blocks, but SAC only processes
them according to their upstream primary block's scan time. Therefore, use these blocks with care in exception-based chains.
For example, the following figure shows a sample chain containing a Calculation block that receives values from Analog Input
blocks outside the chain.
The following figure shows an improved chain design using the blocks from the previous figure. This chain allows CA1 to recal-
culate its value whenever an exception occurs to any of the Analog Input blocks and ensures all blocks are processed before the
recalculating the output.
PID, Lead Lag, and Dead Time blocks use the local computer's system time to define a time constant. For this reason, it is
recommended not using them in exception-based chains.
Using Analog Alarm and Digital Alarm Blocks
Analog Alarm and Digital Alarm blocks support exception-based processing. However, you must leave the Re-alarm Time and
the Delay Time fields unmodified; otherwise, SAC places these blocks (and their chains) off scan when iFIX starts or when you
reload the database. SAC processes exception-based Analog Alarm and Digital Alarm blocks only when an operator
acknowledges an alarm from the iFIX WorkSpace. If an operator acknowledges the alarm with the Remote Acknowledge field,
SAC does not process the block.
Assigning Exception-Based Scan Times
You can assign an exception-based scan time to a block by selecting Process by Exception from the block's dialog box. If you
are configuring an exception-based chain with multiple primary blocks, you must enter 0 in the Scan Time field of every primary
block that does not start the chain, and select the Off Scan option button.
Configuring the primary blocks that do not start the chain in this manner ensures that SAC processes the chain properly.
You can configure any primary block or chain to be scanned once on start-up by setting the scan time to zero and placing the
block on scan. Once scanned, SAC does not scan the block or chain again until it restarts, the database is reloaded, or you
place the block off scan and then on scan.
Any block with a scan time may be configured for one shot processing. However, the same restrictions that apply to exception-
based chains also apply to one shot-based chains.
Phasing
Phasing staggers the time at which SAC scans your blocks. This is particularly important for large databases because it can dra-
matically improve performance. Even for small databases, phasing blocks results in more efficient use of CPU time.
For example, if you have 3 unphased blocks with a 5-second scan time, SAC processes all 3 blocks at the same time. The fol-
lowing figure shows the CPU usage when SAC processes these blocks simultaneously.
You can define the phase time by entering it into the Phase field. The phase you enter must have the same unit or one unit lower
than the scan time unit, as the following table describes.
Phase Time Formats
If the Scan Time is in... The Phase Time must be in...
Hours Hours:Minutes
Minutes Minutes:Seconds
Seconds Seconds
Subseconds Subseconds
For example, if the scan time is 5 minutes, you enter a phase of 1 minute and 30 seconds as follows:
1:30
Overphasing
You can also overphase your blocks. An overphased block is one that has a larger phase than scan time. For example, assume
you have the chain shown in the Exception-Based Chain Processing figure. In this chain, AI2 and AI3 have 5-second scan
times. AI1 is overphased with a 5-second scan time and a 10-second phase. This delays AI1 by 10 seconds and ensures that
SAC scans AI2 and AI3 before AI1. This means that the Calculation block receives the most recent values on which to perform
its functions.
SAC only lets you overphase blocks with second or subsecond scan times. For blocks with a scan time of a minute or more,
you can create an initial offset from the time that SAC would normally scan the block. For example, assume you want to scan a
block every 6 hours with an offset of 2 hours and 10 minutes. You can configure the offset by entering the following phase in the
Phase field:
2:10
Because the scan time is linked to the system clock, SAC always scans the block at 2:10, 8:10, 14:10, and 20:10 regardless of
when it was placed on scan. Also remember, SAC scans blocks with scan times of one minute or longer immediately when iFIX
starts or when the database is reloaded. To forego this initial scan, start SAC with the S command line parameter. Refer to the
section Controlling SAC Startup in the Setting up the Environment manual for more information on specifying SAC command
line parameters.
Block Modes
l Other blocks.
l An I/O driver or OPC server.
l The keyboard (using Data links).
l Recipes.
l Easy Database Access programs.
l Visual Basic for Applications (VBA) scripts.
You can control from where a block receives data by setting its mode, as the following figure shows:
Placing a block in Manual mode does not place it off scan; SAC still processes the block using its last value. Manual mode only
prevents a block from receiving data from an I/O driver, an OPC server, or the upstream block. SAC also scans exception-
based blocks when they change mode (from Automatic to Manual mode or vice versa). While in Manual mode, SAC accepts
any input within the EGU range and immediately scans the block. No deadband checking is made on these values.
You can toggle a block's mode from an operator display by adding an object to the display and then using the Toggle Tag
Auto/Manual Expert from the Task Wizard. To display a block's mode from an operator display, add a Data link that references
the block's A_AUTO field. If you have enabled in-place data entry when configuring the data link, you can then modify that
block's mode from the operator display by clicking on the Data link and entering AUTO or MANL. You can also modify a block's
mode from the Database Manager by entering AUTO or MANL in the Curr Mode column for the selected block.
NOTE: Blocks perform alarming in both Automatic and Manual modes.
The exact function of certain blocks depends on their mode, as the following table describes
As blocks change from Automatic and Manual modes, they enter a pending state. This state indicates that SAC has acknow-
ledged the mode switch and will change it on the next scan.
Blocks placed into Manual mode enter PMAN mode. The block remains in this state until SAC scans the block again. While in
PMAN mode, SAC continues to scan the block according to its scan time and phase. Manual entries from an operator or a Pro-
gram block force SAC to scan the block immediately and put it into Manual mode. Scans after a manual entry depend on the
block's scan time.
For blocks with short scan times, the next scan time occurs relative to the manual entry. For example, suppose SAC scans the
block AI1 at 1:15:30. This block has a 30-second scan time and a 5-second phase. If an operator puts AI1 into Manual mode and
enters a value at 1:15:45, SAC scans the block immediately and resets AI1's next scan to 1:16:15 and every 30 seconds there-
after. If the operator subsequently enters another value at 1:15:50, SAC scans AI1 again and reset AI1's next scan to 1:16:20
and every 30 seconds thereafter.
For blocks with scan times of a minute or longer, SAC synchronizes the next scan to the system clock. For example, assume
AI2 has a one hour scan time and a 30-minute phase. If an operator placed the block into Manual mode and enters a value at 15
minutes past the hour, SAC scans AI2 immediately and on the half hour.
Blocks placed in Automatic mode enter PAUT mode. The block remains in this state until SAC scans the block again. While in
PAUT mode, SAC scans the block as if it were in Automatic mode.
For blocks with short scan times, this means that the next scan time occurs relative to the last scan. For example, suppose
SAC scans AI1 at 1:15:30. This block has a 30-second scan time. If an operator changes the block's mode to Automatic, SAC:
SAC processes all database blocks placed on scan when it starts or a database is loaded. By default, Database Manager
prompts you to place on scan each block you add. SAC stops processing a block or a chain when:
l From the iFIX WorkSpace, you select an object connected to a primary block and you run a script that places the block
off scan.
l You modify a block with Database Manager. Modifying a block while SAC is processing that block's chain places the
entire chain off scan. As an option, you can set up Database Manager to automatically place the modified block and its
chain on scan when you finish editing it. Refer to the section Setting Database Manager Preferences to learn more about
Database Manager options.
l You delete any block within a chain. Refer to the section Deleting Blocks to learn more about removing blocks from the
process database.
l Statements in Program blocks, Event Action blocks, or an EDA program place a chain's primary block off scan.
l You connect the blocks in a chain incorrectly and SAC cannot scan the chain. Use Database Manager's Verify command
to determine which blocks are improperly chained. Refer to the section Verifying Databases to learn about examining
your database for errors.
l A Program block finishes processing its statements and exits, the Program block does not execute again until the data-
base is reloaded or the block is turned off and placed back on scan.
l You can place a block off scan from the Scan Status column displayed in the spreadsheet.
l An operator clicks an object with a VBA script that places a block off scan. You can quickly add such a script to an object
with the Turn Tag Off Scan button. To use this button, you must first drag it from the CommandTasks toolbar category
onto a toolbar. To learn how to display toolbar categories and add a button to a toolbar, refer to the section Customizing
Toolbars in the Understanding iFIX manual.
Placing a primary block off scan turns that block's entire chain off scan. You can put the chain back on scan by:
l Opening an operator display, selecting an object connected to the chain's primary block, and running a script that places
the block on scan.
l Setting up a Program or an Event Action block that places the chain back on scan.
l Changing the text in the Scan status column from OFF to ON.
l Adding or modifying a block with Database Manager or the iFIX WorkSpace. Depending on the options selected, both pro-
grams can automatically place the block on scan.
l An operator clicks an object with a VBA script that places a block on scan. You can quickly add such a script to an object
with the Turn Tag On Scan button. To use this button, you must first drag it from the CommandTasks toolbar category
onto a toolbar. To learn how to display toolbar categories and add a button to a toolbar, refer to the section Customizing
Toolbars in the Understanding iFIX manual.
Blocks with Long Scan Times
Blocks that have long scan times react differently to on/off scan changes than blocks that have short scan times. If you change
the block's scan status, it enters a pending state: PON (pending on) or POFF (pending off). This state indicates that a scan
status change was requested and is pending, but SAC has not placed the block off or on scan. While a block is in PON, new val-
ues are ignored.
Example: Placing Blocks with Long Scan Times On Scan
Assume you have a block with a one hour scan time and you place it on scan 45 minutes into its scan cycle. The block enters
the PON state and remains there for 15 minutes in order to synchronize it with SAC. Once synchronized, SAC changes the
block's state and places it on scan.
Using the S Parameter
By default, SAC changes a block's scan status shortly after entering the pending state. However, if SAC was started with the
"S" command line parameter, the block remains in the pending state until SAC is ready to scan it.
I/O Drivers
In order for each primary block in the database to receive data, you must connect to your I/O using an I/O driver. The driver you
select depends on your process hardware. GE sells drivers for many types of hardware. Contact your GE Sales Representative,
or refer to our web site at at https://digitalsupport.ge.com for a list of available drivers.
After you purchase a driver and install it, you can start specifying I/O points you want the current block to use. If the I/O point
does not exist, Database Manager starts your I/O driver configuration program so you can add it. Refer to your I/O driver doc-
umentation to learn how to add an I/O point to your driver configuration.
iFIX supplies an OPC Client I/O driver, as well as two simulation drivers.
l Provide a matrix of addresses that database blocks can read from and write to.
l Support analog and digital database blocks.
l Support text blocks.
The OPC Client I/O driver allows you to bring OPC data into and out of iFIX. It is automatically installed with iFIX; however, if
you choose to create a customized install program, the OPC Client I/O driver is an optional component.
To use the OPC I/O Driver:
1. In the Database Manager, in the Driver field for the primary block, select OPC - OPC Client vx.xx from the list.
2. Click the Browse button next to the I/O Address field. The Browse I/O Address dialog box appears.
3. Select an I/O point from an available server and group, and then click OK to exit the dialog box. The I/O Address field will
display the following:
Server;Group;ItemID[;AccessPath]
When you click out of the I/O Address field, ;No Access Path will be appended to the existing text, like this:
Server;Group;ItemID;NoAccessPath
4. If applicable, from the Signal Conditioning list, select a format for mapping the values coming from your process hard-
ware.
5. If applicable, from the Hardware Options list, select a device control addressing format for the database block. This selec-
tion is overridden if you select a datatype from the Requested Datatype list on the Item Configuration page of the OPC
Client I/O driver Power Tool.
For detailed information, refer to the OPC Client Driver online help.
You may prefer to use the SIM driver over the SM2 driver for one or more of the following conditions:
l Generating a repeating pattern of random and predefined values to help you test your chains.
l Using alarm counters to show the general alarm state of your SCADA server.
To use the SIM driver:
For analog values, the register ranges from 0 to 1999. The bit is not used.
For digital values, the register ranges from 0 to 1999. The bit is 0 to 15. The full range of register/bit settings is 0:0 to 1999:15.
NOTE: The SIM driver does not support analog scaling (A_SCALE_* and F_SCALE_* database fields).
Examples: SIM Addresses
0:0
50:2
63:15
The SIM driver shares only one set of registers for Analog and Digital blocks. As a result, you can address all 2000 registers as
analog or digital values. The following table shows the digital bit values when a SIM register contains an analog value.
Database Manager does not accept entries into the Hardware Options and Signal Conditioning fields when using the SIM driver.
In addition, the SIM driver supports:
To help you test your database with simulated input, the SIM driver provides a set of registers that generate a repeating pattern
of random and predefined values. For example, you could ramp a value to simulate the performance of specific chains or you
might generate a series of random numbers to test the entire database.
To assign one of these registers to a block:
To ramp a value with the RA register, enter the following text in the I/O Address field:
RA
All SIM registers support Analog Input, Analog Register, Digital Input, and Digital Register blocks. However, as the following
table describes, certain blocks provide optimum performance when used with certain registers.
NOTE: The RB and RC registers support Digital Register offsets of A_0 to A_15.
You may prefer to use the SM2 driver over the SIM driver when one or more of the following conditions occur:
l You have more test data than the SIM driver can hold.
l You want to determine how the database responds to 32-bit values.
l You need to access the driver from a C program.
The SM2 driver matrix consists three independent sets of registers, one for analog values, one for digital values, and one for text
values. Analog database blocks read from and write to analog registers only. Once a block writes a value, other analog blocks
can read the value from the register written to. Digital database blocks work the same way, reading and writing from the digital
registers. iFIX clears all SM2 values when iFIX starts.
The SM2 driver does not use the Hardware Options or Signal Conditioning fields.
To use the SM2 register:
The SM2 driver provides an S register to simulate a communication error. Using this register, all analog and digital reads return
an error as if communication to the process hardware has been lost.
You can access SM2 analog, digital, and text values through the C API that the driver supplies. The file SM2API.H describes
the API and the functions reside in the file SM2API.LIB. You can link this library file to your C application to access the API's
functions. You can find both files in your Base path. By default, this path is C:\Program Files (x86)\GE\iFIX\ or C:\IFIX\, depend-
ing where you installed iFIX.
NOTE: You must have the iFIX Integration (EDA) Toolkit installed to use this API.
Example
Suppose you are using the SM2 driver to store data from a legacy system. Using the C API and a number of preconfigured ana-
log blocks, you can extract your data from the legacy system and store it in your process database.
C API Functions
Syntax Values read, written, and returned
UINT16 GetAn- GetAnalog reads an analog value (32-bit float) to the register indicated by 'index'.
alog(UINT16
FE_OK is returned if the operation succeeds.
index, FLOAT
*data); FE_IO_ADDR is returned if the register index is out of range.
FE_RANGE is returned if the analog value exceeds the range of a 32-bit float.
NOTE: GetAnalog and GetDouble access the same table in the SM2.
UINT16 SetAn- SetAnalog writes an analog value (32-bit float) to the register indicated by 'index' and causes an exception for
alog(UINT16 the specified register even if the data has not changed.
index, FLOAT
FE_OK is returned if the operation succeeds.
data);
FE_IO_ADDR is returned if the register index is out of range.
NOTE: SetAnalog and SetDouble access the same table in the SM2.
UINT16 GetDouble reads an analog value (64-bit float) to the register indicated by 'index.'
GetDouble
FE_OK is returned if the operation succeeds.
(UINT16 index,
DOUBLE *data); FE_IO_ADDR is returned if the register index is out of range.
NOTE: GetAnalog and GetDouble access the same table in the SM2.
UINT16 SetDouble writes an analog value (64-bit float) to the register indicated by 'index' and causes an exception
SetDouble for the specified register even if the data has not changed.
(UINT16 index,
FE_OK is returned if the operation succeeds.
DOUBLE data);
FE_IO_ADDR is returned if the register index is out of range.
NOTE: SetAnalog and SetDouble access the same table in the SM2.
UINT16 GetDi- GetDigital reads 16 digital values (all 16 bits in one of the 20,000 digital registers) to the register indicated by
gital(UINT16 'index'.
index, UINT16
FE_OK is returned if the operation succeeds.
*data);
FE_IO_ADDR is returned if the register index is out of range.
NOTE: The API can only read and write the entire 16 bit digital register at one time. If you want to change 1
bit, you can read the register, modify the desired bit and write the register. However, when you modify a
single bit, ensure that only one thread in one application is accessing a digital register at one time.
UINT16 SetDi- SetDigital writes 16 digital values (all 16 bits in one of the 20,000 digital registers) to the register indicated by
gital(UINT16 'index' and causes an exception for all 16 bits of the specified register even if the data has not changed.
index, UINT16
FE_OK is returned if the operation succeeds.
data);
FE_IO_ADDR is returned if the register index is out of range.
NOTE: The API can only read and write the entire 16 bit digital register at one time. If you want to change 1
bit, you can read the register, modify the desired bit and write the register. However, when you modify a
single bit, ensure that only one thread in one application is accessing a digital register at one time.
UINT16 SetDi- SetDigitalEx writes 16 digital values (all 16 bits in one of the 20,000 digital registers) to the register indicated
gitalEx(UINT by 'index' and causes an exception for specific bits selected from a mask. An exception is triggered for the
index, UINT16 bits set in the mask even if the data has not changed.
data, UINT16
FE_OK is returned if the operation succeeds.
mask)
FE_IO_ADDR is returned if the register index is out of range.
NOTE: The API can only read and write the entire 16 bit digital register at one time. If you want to change 1
bit, you can read the register, modify the desired bit and write the register. However, when you modify a
single bit, ensure that only one thread in one application is accessing a digital register at one time.
UINT16 GetText GetText reads the text specified by `data' from text registers starting at the register indicated by `index'. The
(UINT16 index, number of characters to read is indicated by `size'. GetText does not automatically add a null terminator to
char *data, int the text being read. If you require null-terminated strings, make sure your program adds a null terminator after
size) reading text.
iFIX can process alarm status information from I/O drivers. This information complements the alarms generated by iFIX data-
base blocks. When an alarm is returned from a driver, iFIX compares the driver alarm against the block alarm. The alarm with
the higher severity is used as the block alarm and the other alarm is ignored.
NOTE: As of iFIX 4.5, only the alarm statuses IA_OK and IA_COMM are supported for use through the SM2 driver.
Using the preceding table, you can see that if a driver returns a HIHI alarm to a block that is in HI alarm, iFIX changes the alarm
state to HIHI because the driver alarm is more severe. However, if the alarms are of equal severity, iFIX does not change the
alarm state of the block. For example, if the block is in HI alarm and the driver returns a LO alarm, the block's alarm state does
not change because both alarms have equal severity. Once an operator acknowledges the HI alarm, iFIX changes the block's
alarm state.
NOTE: If you set a communication error to the S register with the SetCommError function, then all SM2 registers show a COMM alarm
status. When examining the alarm status of text, only the status of the first character (byte) is read. You can control the alarm status
functions of the SM2 driver using its C API only. Refer more information about this API, refer to the Using the SM2 C API section.
In addition to I/O drivers, the WorkSpace can send and receive data with an OLE for Process Control (OPC) server. You can
configure any database block to receive or send OPC data by completing the block's I/O driver fields. To do this, select OPC
from the Driver field, and then click the I/O Address field's Browse button to specify an OPC address.
where ServerName is the name of your OPC server, GroupName is the name of the OPC group you want to access, and ItemID
is the name of the OPC item you want to read or write. Including the AccessPath is optional and instructs the server how to
access its data. For more information about connecting to your OPC server, refer to your OPC PowerTool documentation.
Very often raw values from your process hardware are not meaningful to operators. This is particularly true when the hardware
reports values in a numeric format, such as an unsigned integer, to indicate how full a tank is. In this situation, what is needed is
a way to map the range of values you receive into a different range of values. Many I/O drivers provide this ability by applying sig-
nal conditioning.
Signal conditioning converts the data received from the process hardware into a format that is easily recognizable by operators.
You can apply signal conditioning by selecting the type you want to use from a block's Signal Conditioning field.
Example: Understanding Signal Conditioning
Suppose you have a 700-gallon water tank and you want to display how much water is in the tank. You can display the tank's
water level as:
For this example, assume the I/O driver sends an unsigned integer to the process database (that is, 0 to 65535). The following
table lists sample high and low EGU limits you could assign to the input block. These settings scale the incoming values to dis-
play the tank's water level in percent filled and in gallons.
The following figure shows the values that are displayed when the tank is full, half full, and empty.
Scaling Values
EGU limits have a precision and range. The precision is the number of digits after the decimal point. The range is the span of val-
ues. For example, the default range for blocks is 0 to 100.
Changing the EGU Limit Precision
You can change the EGU limits' precision by editing the High Limit and Low Limit fields. When you change the precision, Data-
base Manager modifies all references to the current block throughout the database. For example, if you create an Analog Input
block with EGU limits of 0.0 to 100.0 and then change the precision to 0.00 to 100.00, Database Manager searches the data-
base for all references to this block and makes the appropriate changes. In this case, a Program block that contains the fol-
lowing step:
SETOUT AI1 50.0
is adjusted to read:
SETOUT AI1 50.00
Changing the EGU Limit Range
To change the EGU limits' range, you must change all references to this block manually. For example, if you create an Analog
Input block with limits of 0.0 to 100.0 and then change the range to 0.0 to 700.0, all references to this block's EGU limits are unaf-
fected until you edit them. In this case, assume you have a Program block that outputs a value equal to half of this block's ori-
ginal range, as shown below:
SETOUT AI1 50.0
You must modify this Program block's SETOUT statement to reflect the new range, as shown below:
SETOUT AI1 350.0
EGU Limit Formats
Database Manager accommodates the EGU limit formats listed in the table Available EGU Limits. Each format is accurate to
six digits. Because of compiler limitations, round-off errors may occur in the seventh digit. The following figure shows sample
values and their accuracy.
As you develop your process databases, you need to complete many basic operations including:
One of your first tasks when developing a process database is to create a new database. Creating a new database loads the
empty database, EMPTY.PDB, into memory and removes any existing database that may be loaded. If the existing database
has unsaved changes, Database Manager prompts you to save them before the new database loads.
Before Database Manager can open and display a database, the program establishes a connection to a SCADA server (either
local or remote) on the network. It accomplishes this by prompting you to select the SCADA server to which you want to con-
nect. Once you select the server, Database Manager establishes the connection and opens the server's current database.
You can establish a connection with a different server by opening a different database. Once you select the new server you want
to connect to, Database Manager disconnects from the existing server and opens the selected server's current database.
NOTE: From the Database Manager, you can open databases from SCADA nodes with iFIX 3.0 or greater installed. You cannot add,
modify, or delete blocks in databases from earlier versions of iFIX, such as iFIX 2.5 or FIX32.
You can also disconnect from a SCADA server by closing the database. If the database has unsaved changes, Database Man-
ager prompts you to save them before breaking the connection.
Adding Blocks
After you open or create a new database, you can begin adding blocks to your database. Database Manager lets you add blocks
by:
When any of the first four methods are used, you can select the type of block you want to add. Once you do this, a block con-
figuration dialog box appears. By completing the dialog box and clicking OK, you can add the block to the database. For more
information on completing a block configuration dialog box, refer to the iFIX Database Reference help.
NOTE: Whenever you add or delete a block in the database, we recommend you resolve your pictures. For more information about
resolving pictures, refer to the Creating Pictures manual.
The Generate Wizard lets you add many similar blocks to the database quickly, saving development time. You simply select the
type of block you want to create and the block names you want to use.
For the block type, you can select an existing or a new block. This selection determines the specific values assigned to each
block created. For example, when you select a new block, the Wizard creates blocks with default values. However, when you
select an existing block, the Wizard creates blocks with values of the selected block. This option lets you create many similar
blocks quickly without having to reconfigure them later.
When specifying the block names, you must enter a prefix, suffix, starting number, ending number, and increment value. The
Generate Wizard uses this information to systematically assign names to the blocks it creates. For example, the following val-
ues create blocks with the names F1T1 through F20T1.
The Generate Wizard cannot create a block with a name that already exists. If the information you specify results in an existing
block name, the Wizard skips that block and continues on to the next one.
Using the Generate Wizard, you also have the option of customizing up to 5 fields. Customizing these fields lets you fine tune
the block's configuration. For example, if you need to create 50 Digital Input blocks, each one will have a different I/O address.
You can use the Generate Wizard to assign these addresses if they occur in a sequential order.
You can customize a field by selecting it and entering a prefix, suffix, starting number, ending number, and increment value. The
Wizard handles this information identically to the block name values you entered. If the resulting sequence of field values ends
before the Wizard creates all the new blocks, the sequence repeats from the beginning. For example, suppose you want to cre-
ate 10 Analog Input blocks, AI1 through AI10 and you customize the I/O address of each block with the following information:
Block Address
AI1 N10:7
AI2 N20:7
AI3 N30:7
AI4 N40:7
AI5 N50:7
AI6 N10:7
AI7 N20:7
AI8 N30:7
AI9 N40:7
AI10 N50:7
You also have the option of enabling the Use Custom Format check box. When you enable this check box, the Wizard lets you
enter multiple patterns for the five fields you have selected. A pattern acts as a programming statement for generating a range of
numeric or string values. The following table lists the syntax for each type of pattern.
Pattern Types
Type Syntax Example
Numeric <start:end:increment> <1:10:1> generates a range of numbers from
1 to 10.
where start is the initial value of the pattern,
<1:20:3> generates the numbers
end is the ending value, and
1,4,7,10,13,16, and 19.
increment is the amount to add to the current pattern value.
Alphanumeric <"string1", "string2",... "string"> <"A", "B", "C", "D">
List
where string1 is the first string, <"Area A", "Area B", "Area C">
string2 is the second string, and <"Pump 1", "Pump 2", "Pump 3">
Analog Input
Constants "string" "Curr Value > 100"
where string is up to 40 alphanumeric characters, including the "I/O Addr < 500"
quotation marks.
"PLC:N7:"<766:780:1>"/15"
Notice that the difference between literals and constants is minor. Both are strings and can be up 40 characters. However, quo-
tation marks (" ") are required for constants when the string contains any mark of punctuation or non-alphanumeric symbol such
as an angle bracket or a colon. If the string contains only numbers or letters, the quotation marks are optional.
Also notice that negative and floating point numbers are not supported within patterns. You can generate these types of numbers
by enclosing a minus sign or a decimal point in quotation marks outside of the pattern. Negative increments are not supported.
Consider the following examples:
By combining different pattern types, you can generate a wide range of block field entries. For example, if you want to customize
the Description field for a group of blocks, you could enter a pattern such as Alarm Status from Area <"A", "B", "C">. Notice that
the text outside the pattern does not require quotation marks.
Duplicating Blocks
Another way you can add similar blocks to the database is by duplicating them. Like the Generate Wizard, you can duplicate
multiple blocks. However, you cannot customize specific block fields; you can only specify a new name for the duplicated
blocks. As a result, the new blocks are identical to the original ones.
For example, suppose you have an Analog Input block monitoring the speed of a pump and want to monitor five other pumps in a
similar way. By duplicating the block, you can reproduce it and create the additional blocks you need.
Database Manager lets you share block information among your process databases and third-party applications by copying and
pasting them to the clipboard. Copying and pasting blocks between two databases is a quick way to create new ones. This
works best when the database you want to create contains blocks similar to existing blocks in other databases. By copying
existing blocks, you save time because you only need to change the information that differs between the original block and the
new copy.
Copying and pasting between Database Manager and a third-party application lets you quickly modify a block from your text
editor or spreadsheet. You can also create new blocks with your third-party application and paste them into Database Manager.
This feature can be helpful when you do not have access to iFIX and you want to create new blocks for later inclusion into the
process database.
When you copy blocks to the clipboard, Database Manager converts and saves them in comma separated value (CSV) format.
Once saved on the clipboard, you can paste the blocks into any application that supports CSV files.
Pasting blocks into Excel requires you to configure the program so that it converts and displays the data correctly. You also
need to configure Excel when you drag and drop data from Database Manager or import a database saved in CSV format.
To configure Excel:
Pasting CSV-based blocks into Database Manager converts and adds them to the process database in memory. If the names of
these blocks are already in use, Database Manager prompts you to replace the existing blocks with the ones you are pasting. If
you do not replace them, Database Manager generates an error for each duplicate block. You can avoid creating these errors by
loading a database that does not contain the blocks you are pasting or by modifying the names of the blocks prior to pasting
them into Database Manager.
Database Manager also displays errors if you attempt to paste a block from Excel that is not in the correct format. The easiest
way to ensure the block is in the correct format is to export a block of that type from the process database or paste a block into
Excel, modify it, and paste the modified block back into Database Manager.
Moving Blocks
In addition to sharing blocks by copying and pasting them, you can cut and paste them. Cutting blocks from the database is sim-
ilar to copying them; the main difference is that cut blocks are physically moved and placed on the clipboard, allowing you to
move blocks to other databases.
Prior to removing blocks from their chains, Database Manager takes each chain off scan. Make sure you place the chain on
scan when you finish editing it. iFIX provides several ways to do this. For more information about placing a block or chain on
scan, refer to the section Placing Blocks On and Off Scan.
If you cut a block from the middle of the chain, Database Manager attempts to connect the two portions of the chain, as the fol-
lowing figure shows.
Removing a Block from a Chain
Modifying Blocks
You can modify any database block displayed in the spreadsheet. Typically, you need to modify a block:
Before you modify a block, you can determine the exact fields to change by displaying the block's configuration dialog box.
Unlike modifying a block, displaying a block's dialog box leaves the block and its chain on scan.
Deleting Blocks
Whenever you find that specific blocks are no longer needed, you can delete them from the database. Database Manager lets
you delete blocks by selecting:
l The blocks you want to remove and cutting them without subsequently pasting them
l The Delete button from Database Manager's toolbar (Classic view)
l The Delete button from the Blocks group on the Home tab (Ribbon View).
The difference between these methods is the Delete button in Classic View or Delete in Ribbon view removes the selected
blocks completely and does not let you retrieve them if you change your mind. By cutting blocks, you instruct Database Man-
ager to save a copy on the clipboard allowing you to paste them back into the database until the next copy or cut occurs.
Regardless of the method you choose to remove the blocks, Database Manager displays a message box with the following text:
Following tag(s) selected for deletion from database
Click Cancel to retain the blocks and continue using Database Manager. If you click Delete All, Database Manager deletes the
blocks and takes the chains containing them off scan. Make sure you place the chain on scan when you finish editing it. iFIX
provides several ways to do this. For more information about placing a block or chain on scan, refer to the section Placing
Blocks On and Off Scan.
If the deleted block was in the middle of the chain, Database Manager attempts to connect the two portions of the chain as the
Removing a Block from a Chain figure shows.
Saving a Database
When you finish making changes to a database, you can save the database to disk. By saving the database, you enable the
SCADA server to reload the database in memory when you restart iFIX.
Make sure you have enough disk space available when saving your database to disk. If your SCADA server does not have
enough disk space, you may lose the changes you have just made. For example, if you build a 3MB database, make sure you
have 3MB of free disk space available.
You can also save a database automatically using the RUNTASK command from a Program block or a script. When you save a
database using the Program block, use the following syntax:
RUNTASK DBBSAVE -Nnodename -Ddatabase
The -N command line parameter enables you to save a database on a remote SCADA server. The -D command line parameter
enables you to save a database to another PDB file name. Both command line parameters are optional; if you do not use them,
you save the current database on the local SCADA server.
When you save a database from a VBA script, use routines similar to the following:
Private Sub FixEvent1_OnTrue()
Dim save_pdb As String
Dim return_value As Double
Dim nodename As String
Dim database As String
nodename = "MIXER1"
database = "BACKUP"
save_pdb = System.ProjectPath + "\DBBSAVE" + " -N" + nodename + " -D" + database
return_value = Shell (save_pdb, 0)
End Sub
End SubRefer to the Database Manager online help system for more information about the RUNTASK from the Program block.
For information about the Shell function, refer to the iFIX Automation Interfaces Help file.
Using Database Manager, you can locate and display data in the spreadsheet. This chapter explains how to accomplish these
tasks. Refer to the following topics for detailed information:
As you develop and test your process database, you may find it necessary to locate specific spreadsheet values. For example,
you may want to locate and adjust the scan times of your primary blocks.
With Database Manager, you can search in any spreadsheet column for text by selecting the column head of the column you
want to search in. You must also enter a search string. The string is the text you want to locate in the selected column. You can
enter up to 29 alphanumeric characters for the search string.
Once you enter the text you want to locate, Database Manager locates the first occurrence of the string in the selected column.
To locate subsequent occurrences, you can repeat this process.
Find Options
You can toggle the case sensitivity of a search using the Match Case option. When this option is enabled, Database Manager
searches for the exact text and case you enter. The search string is not case sensitive when you disable the option. For
example, selecting the Tag Name column and entering the search string:
AI
is the same as entering any of the following search strings:
l ai
l Ai
l aI
You can also find whole or partial words with the Match Whole Word Only option. Database Manager treats the search string as
a whole word when you enable the option. By disabling the option, you can find the specified string inside other words. For
example, if you search for the string "line" with the Match Whole Word Only option disabled, Database Manager matches the fol-
lowing descriptions with the search string:
Replacing Data
In addition to finding text, you can find and replace it. Finding and replacing text is similar to just finding it. Both tasks require you
to select the cell or column you want to search in and enter a search string. However, when finding and replacing data, you can
also enter a replacement string. This text is the data with which you want to replace the search string.
Find Options
You can enter up to 29 alphanumeric characters for both the search and replacement strings. Both strings also accept the Match
Case and Match Whole Words Only options. However, while you can toggle the case sensitivity of the search string with the
Match Case option, the replacement string is always case sensitive. This means that when replacing data, Database Manager
inserts text exactly as you enter it.
You also have the option to replace the text in the current selection (a cell or column) or the current column. The Selection option
button lets you replace text in the current selection. The Entire Column option button lets you replace text in the entire column.
Using Go To
While working with your database, you may want to display the text in a specific row or column. When the number of rows or
columns is small, using the scroll bars to move through the spreadsheet is a quick way to display the necessary information.
However, as the spreadsheet grows, you may find scrolling through it slow and time-consuming. To speed up locating inform-
ation, you can jump to any row or column. You can also jump to any block in the spreadsheet when do not know the block's row
number by entering its name instead.
By automatically updating the spreadsheet, you can troubleshoot your database by monitoring specific blocks. Should you
identify an error, you can correct it and immediately see your change's effect.
You can temporarily disable the automatic refresh option by pausing the spreadsheet. Pausing updates instructs the Database
Manager to stop updating the screen. It does not affect SAC or the scan status of the blocks in the database.
NOTE: Database Manager automatically pauses updating the screen when you add, modify, delete, or generate blocks or when you
print, reload, or import the database.
In addition to automatically refreshing the screen, you can manually update it whenever you want to refresh the values in the
spreadsheet. Manually updating the screen can be particularly helpful when you automatically update the spreadsheet infre-
quently, and can be used in conjunction with the automatic refresh option to update the screen more frequently than every 5
seconds.
By completing these tasks, you can create a custom display for yourself and other database developers.
Changing spreadsheet colors is like changing the colors of a window with the Display dialog box in the Control Panel. First, you
select the item whose color you want to change and then you select the color for it.
l Cell text
l Spreadsheet grid
l Row and column head background and text
As its name suggests, a non-scrolling column is one that does not move when you scroll left or right, as the following figure
shows.
Defining a Non-Scrolling Column
Using this feature, you can display related information without resizing or rearranging the spreadsheet columns. For example, if
you configure the Type column to stop scrolling, you can easily relate block values, names, and types, allowing you to identify
the block containing the values in each column.
When you create a non-scrolling column, all columns to the left of it no longer scroll until you unlock them.
The columns you can select correspond to common and block-specific fields. Columns corresponding to common block fields
appear with only the field name. For example, the following text appears for the common field Current Value:
Curr Value
AI is the block abbreviation and identifies the field as an Analog Input specific field. The text Smooth indicates the field name
and corresponds to a block field (in this case the A_SMOTH field). The Block Type Abbreviations table lists the abbreviations for
each block.
NOTE: If you remove a column from the spreadsheet that Database Manager uses to sort data, the column is also removed from the
sort order.
If you display database information in different ways, you may want to save your spreadsheet layouts to a format file. Format
files define the following information for each spreadsheet column:
By saving spreadsheet layouts, you eliminate the need to recreate them. Database Manager saves your spreadsheet layout in
format files residing in the FIX Local path by default. These files have the extension .FMT.
Loading a format file is like creating a spreadsheet layout. It appears in the Properties dialog box, allowing you to modify it as
needed. In addition, when Database Manager opens the format file, the program replaces the current set of spreadsheet
columns with the ones listed in the format file. If a block does not include a field that corresponds to one of the new columns, the
text "----" appears in that cell.
The first time you run Database Manager, it loads its preset default spreadsheet layout stored in the format file, DEFAULT.FMT.
The following table lists the preset default columns and the corresponding fields that appear.
If the Database Manager displays tag values, but the fields for an open block appear empty in the block display, try re-registering
the Fixdb32egu.ocx, Fixdb32IOAddress.ocx, and Fixdb32Tagname.ocx files. This should resolve the issue with the tag display.
Use the steps below.
5. Click OK. A message should appear indicating that the "DllUnregisterserver" succeeded.
6. Click OK.
7. Repeat steps 3-6 to properly unregister these files:
l Fixdb32IOAddress.ocx
l Fixdb32Tagname.ocx (making the appropriate substitution for the file name)
8. From the Start menu, click Run. The Run dialog box appears.
9. In the Open field, enter:
REGSVR32 "C:\Program Files (x86)\GE\iFIX\Fixdb32egu.ocx"
10. Click OK. A message should appear indicating that the "DllRegisterserver" succeeded.
11. Click OK.
12. Repeat steps 8-11 to properly register these files:
l Fixdb32IOAddress.ocx
l Fixdb32Tagname.ocx (making the appropriate substitution for the file name)
13. Restart the iFIX WorkSpace.
14. Start the iFIX Database Manager, open a tag, and confirm all of the proper tag information appears.
Querying and Sorting Data
One of the most powerful features that Database Manager provides is querying a database. A query is a request to display spe-
cific information. For example, you might want to display all the Analog Input blocks with a scan time of five seconds or less.
Alternatively, you might want to display every block in security area Packaging for a specific device driver. After you create a
query, Database Manager selects the blocks from the database that match the request and displays them, replacing any pre-
viously displayed blocks.
The following topics provide more detailed information about querying and sorting a database.
Before you can create a query, you must know the information you want to retrieve from the database. For example, you might
want to display all the Analog Input blocks with a current value greater than 50. Alternatively, you might want to display every
block in alarm area Line5 for a specific I/O driver.
Once you know the information you want to display, you can construct the query using the following syntax:
{column} operator "value"
or
"value" operator {column}
where column is a column heading you want to display, enclosed in curved brackets, operator is one of the relational operators
listed in the table Relational Operators, and value is a number or string enclosed with quotation marks (" ").
Relational Operators
Operator Meaning
= Equal to
<= Less than or equal to
< Less than
!= Not equal to
>= Greater than or equal to
> Greater than
Case Sensitivity
Strings entered in a query are not case sensitive. For example, a query such as:
{Tag Name} = "AI*"
retrieves blocks with names that start with AI. It also retrieves blocks with names that start with:
l Ai
l ai
l aI
When entering a number, the block's EGU range determines the maximum and minimum values you can enter. The following
table lists these limits. To learn more about the EGU range, refer to the section Understanding EGU Limits.
You can combine two or more queries using one of the boolean operators in the following table. Using these operators you could
build a query such as:
{Scan time} = "3" AND {Security Area 1} = "Packaging"
to display all the blocks in security area Packaging with a scan time of 3 seconds.
Boolean Operators
The operator... Instructs Database Manager to... Example
AND Select the block when both query A and query B are true. A AND B
OR Select the block if either query A or query B is true. A OR B
NOT Invert query. If query A is true, its value becomes false. NOT A
NOR Select the block when both query A and query B are false. A NOR B
XOR Select the block if query A and query B are not both true or both false. A XOR B
NAND Select the block when query A and query B are not both true. A NAND B
You can also include the following wildcards in queries containing the equal to (=) operator.
The wildcard... Represents...
Asterisk (*) One or more characters.
Question mark (?) Any single character.
Examples: Query Wildcards
Other operators, such as the greater than (>) or less than (<) operators, treat wildcards literally.
Examples: Using Relational Operators
Grouping Queries
You can group queries together using parenthesis. For example, consider the following query:
{Tag name} = "A*" AND ({Type} = "AI" OR {Type} = "AO")
Database Manager evaluates this query from left to right. Expressions enclosed in parenthesis are treated as a unit. Con-
sequently, as Database Manager evaluates the above query, it retrieves every block that begins with an "A." From this list of
blocks, the program then displays all the Analog Input or Analog Output blocks.
Be careful where you place parenthesis in a query. The following query yields a very different spreadsheet compared to the
query given above.
({Tag name} = "A*" AND {Type} = "AI") OR {Type} = "AO"
This query displays every Analog Input block that begins with an "A" and every Analog Output block in the database.
Editing a Query
After you create a query, it remains the current query until you change it. Using this feature, you can append a new query to the
existing one and re-query the database. For example, suppose you create the following query:
{Type} ="AI" AND {Alarm Areas} ="Boston"
This query displays all the Analog Input blocks in the Boston alarm area. By appending the query:
AND {AI LOLO Alarm}<= "10"
you can display only those Analog Input blocks in the alarm area which have a LOLO alarm value less than or equal to ten.
To locate blank cells in the database:
For example, to find blank cells in the Description column use the query:
{TAG NAME} = "*" AND {Description}=""
This query displays all the blocks in the database that have no text in their Description fields.
The number of blocks that Database Manager retrieves from a query depends on how broad your request is. If the query is broad
(for example, display all Analog Input blocks) the program retrieves more blocks than if the query is narrow (for example, display
all Analog Input blocks with a scan time of five seconds and a name that begins with "Q"). You can adjust the number of blocks
retrieved by refining or expanding your query.
One way to refine a query is to start with a simple query and append other queries to it. For example, the following query displays
all the Analog Input blocks in the database.
{Type} = "AI"
Once Database Manager retrieves these blocks, you can refine the query by adding other queries to it. For example, you could
add the following query to display only the Analog Input blocks with a scan time of two seconds:
AND {Scan Time} = "2"
Similarly, you could increase the number of blocks in the spreadsheet by displaying all the Analog Input blocks and then, to the
original query, add all Analog Output blocks in the database with the following query:
OR {Type} = "AO"
If you find yourself frequently entering and re-entering the same query, you may want to save it to a file. By saving a query, you
cut down on frequent retyping and eliminate the possibility of mistyping the query. Database Manager saves your queries in sep-
arate files. These files reside in the FIX Local path by default and have the extension .QRY.
Loading a query is like entering one. It appears in the Enter Query field, allowing you to refine or expand the query as needed. In
addition, when Database Manager opens the query file, the program retrieves the blocks that match the specified criteria.
Database Manager automatically sorts all the blocks in the spreadsheet whenever you query or open a database. The blocks are
sorted according to the current sort order. A sort order defines:
For example, suppose you want to sort the spreadsheet by the Type and Scan Time columns in ascending order. Once you
select these columns:
l Database Manager sorts the spreadsheet by the Type column alphabetically (ascending order).
l Next, the program sorts the Scan Time column in numeric order.
If you sort your database in different ways, you may want to save each sort order to a file. By saving your sort orders, you elim-
inate the need to recreate it. Database Manager saves each sort order in a separate file. These files reside in the FIX Local path
by default and have the extension .SRT.
Loading a sort order is like entering one. It appears in the Properties dialog box, allowing you to modify it as needed. In addition,
when Database Manager opens the sort order file, the program re-sorts the spreadsheet.
Before loading a sort order, verify that the columns Database Manager sorts on appear in the spreadsheet. If the columns do not
appear, add them. For more information about adding columns to the spreadsheet, refer to the chapter Locating and Displaying
Data.
NOTE: Because the Tag Name column only contains unique data, Database Manager never needs to sort beyond this column. For
this reason, when you save or load a sort order containing the Tag Name column, Database Manager ignores any column that follows.
Ignored columns are not saved or loaded.
By default, Database Manager loads the sort order DEFAULT.SRT when you initially start the program. This sort order arranges
the blocks in the spreadsheet by block type and then by block name. If you prefer a different sort order, you can override the
default by saving the current settings. You can also restore the original sort order, DEFAULT.SRT, as the default, by loading the
sort order file and selecting Save Settings from the Tools menu.
Managing Databases
Database Manager lets you manage your process databases in many different ways. For example, you can verify them to
ensure they do not contain any errors. You can also reload, import, and export your databases as needed. This chapter
describes all these management tools.
l Verifying Databases
l Reloading Databases
l Displaying a Database Summary
l Exporting Databases
l Importing Databases
Verifying Databases
You can ensure a process database contains no configuration errors by verifying it. Verifying a database also ensures that iFIX
can process each block and that the database functions as you intend.
While verifying a process database, Database Manager ensures that each block:
To correct errors:
Reloading Databases
Even though you can create multiple databases for a SCADA server, Database Manager can load and display only one of them
at a time. You can load any database residing on the current SCADA server by selecting Reload from the Database menu.
Reloading a database lets you:
If you want operators to reload the database from the iFIX WorkSpace, you can create a script to reload the database using a
routine similar to the following:
Private Sub FixEvent1_OnTrue()
Dim load_pdb As String
Dim return_value As Double
Dim nodename As String
Dim database As String
nodename = "MIXER1"
database = "BACKUP"
load_pdb = System.ProjectPath + "\DBBLOAD" + " -N" + nodename + " -D" + database
return_value = Shell (load_pdb, 0)
End Sub
The -N command line parameter enables you to reload a database on a remote SCADA server. The -D command line parameter
enables you to reload a database other than the currently loaded one. Both command line parameters are optional; if you do not
use them, you reload the open database on the local SCADA server.
For information about using the Shell function from a script, see the Visual Basic help system.
CAUTION: The DBBLOAD system task does not prompt you to save changes to the database. Be sure you save your database before
executing a script that reloads the database. Otherwise, you will lose all your changes.
Database Manager lets you display a summary of the current database. This summary lists the database's:
l Size in bytes.
l Serial number.
l Contents.
l I/O count.
Using this information can help you manage your databases. For example, knowing the database's serial number can help you
determine if someone modified your database since its last save. The serial number is a unique code that Database Manager
creates whenever you add or delete a block. By writing down the serial number after you modify the database, you can sub-
sequently compare the current number to the previous one.
High-level documentation about the database can also help you manage your databases. You can provide this level of inform-
ation by displaying the database's contents. The contents lists by block type the number of blocks used and allocated. A used
block is one you have configured. An allocated block is a placeholder in memory. To make efficient use of memory and improve
performance, all SCADA servers pre-allocate 10 blocks at a time when you initially create a block of a specific type, as the fol-
lowing figure shows.
Exporting Databases
You can export the current process database to a comma separated value (CSV) or GDB text file. Typically, you export a data-
base when you want to:
For example, you could export your process database in CSV format and import the data into Microsoft Excel. By importing the
file into Excel, you can:
For more information using these features, refer to your Excel documentation.
Database Manager exports all the blocks displayed in the spreadsheet. As a result, you can query the database to display only
the blocks you want to export. For example, to export all the Analog Input blocks in the database, use the query:
{TYPE} = "AI"
For more information about querying the database, refer to the section Understanding Query Syntax.
The DBExporter.exe command allows you to export all tags currently loaded on local or remote node to a comma separated
value (CSV) or GDB text file. When no command parameters are specified, DBExporter.exe exports tags on local node to PDB
name.csv to local PDB path. Typically, this path is: C:\Program Files (x86)\GE\iFIX\PDB.
Syntax
DBExporter.exe [/NNodeName] [/OOutputFileName>] [/F] [/R]
Parameters
The following table lists the command line parameters available for the DBExporter.exe exporter tool.
Parameter Description
/NNodeName Optionally, specify the remote SCADA node name that you want to to export the database from.
Replace NodeName with the actual node name.
/OOut- Optionally, specify the output file name with full path or no path. If no path is specified, output file
putFileName is created in local PDB path. Typically, this path is: C:\Program Files (x86)\GE\iFIX\PDB. The file
name portion requires the file extension: .csv or .gdb.
Replace OutputFileName with the actual output file name. For example: MyFile.csv.
/F Optionally, allows you to run a fast export. The export runs as fast as possible, maximizing CPU
usage up to 100%.
/R Optionally, allows you to skip header information (that includes the node name, database name,
file name, and date and time of the export), in the output file.
Error Codes
The following table describes the error codes and descriptions DBExporter.exe exporter tool.
Code Result
0 Successfully exported.
1 General Failure. iFIX is not running; unable to load DatabaseManagerRes.dll, an so on.
2 Invalid commands.
3 Invalid node.
4 Invalid file name.
5 Invalid file extension.
6 Unable to open Export.err file used for recording error details.
7 Empty database.
8 Invalid output file.
9 Exporting failure. The export file had an open or write error, EDA call failure, or other similar type error during
the export process.
Once you export the database, you can edit it with any text editor. As you edit the export file, use the following guidelines:
l Verify that each block name is 256 characters or less.
l Ensure each block field is spelled correctly.
l Confirm the block type matches one of the types listed in the Block Type Abbreviations table.
You can also enter comments into the export file by typing an exclamation point (!) as the first character on a line.
CSV File Format
For more intricate editing of the export file, you need to understand the file format. For example, an export file saved in CSV
format lists each row of the spreadsheet as one row in the CSV file. Each block's fields appear delimited by commas. The first
two fields of each block are:
A_NAME, A_TAG
You only need to enter values for these two fields when creating new blocks. If no additional field values are present, Database
Manager creates the block using the default block values. However, by adding these optional values to a block entry, you can
complete specific dialog box fields when the block is imported. For example, the following line creates an Analog Input block
with a scan time of 1 minute:
AI, AI2, , , , 1M
GDB File Format
The first two lines of each block entry are required and contain the block type and block name. Without these lines, Database
Manager will not add the block to the database when you subsequently import it.
Subsequent lines in a block entry appear for each field on the block's configuration dialog box. Including these additional lines is
optional. If no additional lines are present, Database Manager creates the block using the default block values. However, by
adding these optional lines to a block entry, you can complete specific dialog box fields when the block is imported. For
example, to set the scan time of the block AI1 to 5 seconds, the export file should contain the following information:
Block Type:: AI ;A_NAME
Tag Name :: AI1 ;A_TAG
Importing Databases
Using Database Manager, you can import any database into memory. Importing a database merges it with the database cur-
rently in memory.
NOTE: Before you import a database, stop any I/O drivers or OPC servers you may have running.
1. Export a database. For more information about exporting a database, refer to the section Exporting Databases.
2. Change the order in which the blocks are listed in the export file. For more information on a database's scanning order,
refer to the section Changing a Database's Scanning Order.
3. In Classic view, on Database Manager's toolbar, click the New button.
-Or-
In Ribbon view, click the Database Manager button, and then click New.
4. Import the edited export file.
This process ensures that only the original database resides in memory when Database Manager imports your database.
To combine two process databases:
Import errors encountered by Database Manager are stored in the file IMPORT.ERR. This file resides in the Database path.
Advanced Topics
After you put a database into production, you may find that SAC scans certain blocks in an order you did not intend. This chapter
explains how you can fine-tune your database and change the scanning order.
This chapter also describes how to customize Database Manager's toolbar and Tools menu. Customizing the toolbar lets you
select only the toolbar buttons you require. Customizing the Tools menu lets you add menu items that launch other applications
from Database Manager. Refer to sections Customizing the Toolbar and Customizing the Tools Menu for more information on
these features.
You can control the precise order you want SAC to scan your blocks and chains by adjusting the database's scanning order,
called the order of solve. Typically, you only need to adjust the order of solve when the value of one block depends on the value
of another. For example, suppose you are calculating a value from three Analog Input blocks as the following figure shows.
Changing the scanning order addresses this potential problem. By scanning AI1 last, you ensure SAC has updated values for
both AI2 and AI3 prior to computing the value of the Calculation block.
You can also phase the blocks so that SAC scans AI1 last. To learn more about phasing, refer to the Phasing section.
Understanding a Database's Scanning Order
1. Regardless of their order in the database, SAC processes blocks that output a value to an I/O device (using a Cold Start
value). SAC does not examine these values for alarm conditions.
2. SAC updates all primary blocks according to the scan time and phase. Blocks with the same scan time and phase
update in the following order.
a. Analog Input blocks
b. Analog Output blocks
c. Digital Input blocks
d. Digital Output blocks
e. Ramp blocks
f. Multistate Digital Input blocks
g. Statistical Data blocks
h. Boolean blocks
i. Device Control blocks
j. Analog Alarm blocks
k. Digital Alarm blocks
l. Pareto blocks
m. Text blocks
n. Program blocks
NOTE: Analog Register and Digital Register blocks do not require SAC processing. Instead, iFIX processes them only when an
operator opens a picture containing a link to either block or when a script that references either block runs. When either event
happens, iFIX processes the blocks before the Ramp block.
3. When SAC scans a primary block, it:
a. Processes that block's entire chain.
b. Scans the next primary block.
4. SAC scans primary blocks of the same type, scan time, and phase in the order these blocks occur in the database, as
the following example shows.
Suppose you create the five identical Analog Input blocks, shown in the following figure. SAC scans these blocks in the order
shown.
Blocks Assigned to a Scan Sequence
Now, assume you delete the third Analog Input block because you no longer need it. This creates an empty space in the data-
base, as the following figure shows. SAC now scans the blocks as shown.
You can change the order of solve by exporting the database and editing the export file. Database Manager exports primary
blocks in the order SAC scans all primary blocks. This results in all Analog Input blocks appearing first in the export file, followed
by all Analog Output blocks, and so on. Once the primary block types are exported, Database Manager exports the secondary
blocks.
For example, using the blocks in the Sample Calculation Chain figure, you can ensure SAC scans AI1 after AI2 and AI3 as fol-
lows:
For more information about completing these tasks, refer to the sections Exporting Databases and Importing Databases.
Customizing the Toolbar
As an option, Database Manager lets you customize its toolbar by arranging and removing the toolbar buttons. Customizing the
toolbar lets you display the buttons to frequently-used functions. For example, while developing a database you might display
the buttons that let you add, modify, and delete blocks. However, when the database is complete, you might want to remove
these buttons from the toolbar.
Once you remove a button, you can always add it back to the toolbar. Adding custom buttons is not supported. By default, the
toolbar comes pre-configured with all the available buttons added for you.
NOTE: This feature is not available in Ribbon view.
Depending on your needs, you may want to start other applications after launching Database Manager. For example, if you
routinely drag blocks to an Excel spreadsheet for modification, you may want to start Excel after Database Manager opens.
By customizing Database Manager's Tools menu, you can add menu items that launch any iFIX or third-party application. You
can also arrange and delete these menu items as needed.
Once you specify this information, Database Manager creates the menu item and saves it as part of its default configuration.
You can subsequently select the menu item to launch the associated application.
Index
adding
alarms 5
described 4
allocated blocks 73
archiving 5
database spreadsheet 61
automatic mode 36
described 35
batch blocks 25
block fields 28
block name 28
described 28
formats 28
locating 29
naming convention 28
block modes 35
described 35
abbreviations 76
blocks
adding 53
adding multiple 54
allocating memory 74
batch 25
configuring 3
control 25
copying 8
Database Dynamos 26
deleting 59
described 3
displaying information 58
duplicating 56
exception-based processing 31
function 3
importing 8
modifying 58
moving 57
off scan 38
on scan 38
optional 22
phasing 33
primary 22
saving 59
scan order 78
scan times 29
secondary 22
SQL 26
summary 26
time-based processing 30
chains 14
described 3
designing 12
drawing a flowchart 16
maximum size 3
scanning order 78
color 62
columns 63
adding in a spreadsheet 63
creating a non-scrolling 62
modifying in a spreadsheet 63
configuration errors 71
resolving 72
configuring blocks 3
control blocks 25
creating 9
process database 9
CSV 74
customizing 62
database spreadsheet 62
database
designing 11
displaying a summary 73
importing 77
order of solve 80
reloading 72
verifying 71
Database Dynamos 26
function 26
toolkit 26
Database Manager 14
adding blocks 3
block types 22
configuring blocks 3
customizing a spreadsheet 62
described 1
designing a chain 12
exiting 7
pausing a spreadsheet 61
queries 65
searching a spreadsheet 60
setting preferences 9
sort orders 70
starting 7
toolbar 8
updating a spreadsheet 61
using Go To in a spreadsheet 61
database spreadsheet 7
coloring 62
commands 8
customizing 62
editing 8
loading layouts 64
pausing 61
properties 7
replacing data 61
saving layouts 64
searching 60
updating 61
using Go To 61
designing 11
chains 12
process database 11
displaying
database summary 73
editing 8
EGU limit 50
errors
correcting verification 71
example 6
Excel 56
exception-based processing 31
PID considerations 31
understanding 31
export file
editing 75
field formats 29
GDB 74
Generate Wizard 54
adding blocks 53
entering patterns 54
Go To 61
using in a spreadsheet 61
historical trends 5
function 5
I
I/O data 4
I/O drivers
described 39
signal conditioning 49
SIM driver 41
SM2 driver 44
iFIX 7
installing 6
importing blocks 8
layout 63
loading 64
queries 69
spreadsheet layouts 64
manual mode 36
described 35
memory 21
non-scrolling column 62
creating in a spreadsheet 62
objects 26
Database Dynamo 26
on scan blocks 38
OPC server 49
optional blocks 22
list 22
order of solve 80
overphasing blocks 35
overriding 64
default query 69
pattern types 55
syntax 55
pausing a spreadsheet 61
PAUT mode 37
function 37
understanding 37
phasing 33
assigning 34
what it does 33
planning 10
PMAN mode 37
function 37
precision
EGU limits 50
preferences 9
Database Manager 9
primary blocks
described 22
function 23
scan times 29
standard 23
summary 26
process analyzing 13
process data
archiving 5
trending 5
process database
adding blocks 53
basic operations 52
closing 53
creating 9
customizing a spreadsheet 62
deleting blocks 59
described 1
describing 12
designing 11
designing a chain 12
displaying a summary 73
duplicating blocks 56
example 6
exporting 74
functions 2
importing 77
modifying blocks 58
moving blocks 57
opening 53
order of solve 80
overriding the default spreadsheet layout 64
pausing a spreadsheet 61
reloading 72
sample application 11
saving blocks 59
searching a spreadsheet 60
updating a spreadsheet 61
using 5
using Go to in a spreadsheet 61
verifying 71
queries 67
appending 68
boolean operators 67
described 65
editing 68
expanding 69
grouping 68
loading 69
overriding the default 69
refining 69
relational operators 66
saving 69
syntax 66
wildcard examples 67
wildcards 67
range
EGU limits 50
database spreadsheet 61
relational database 5
functions 5
reloading 72
process database 72
restoring 69
SAC 30
block phasing 33
exception-based processing 31
function 4
time-based processing 30
saving 64
queries 69
spreadsheet layouts 64
SCADA servers 5
scan time
described 29
examples 30
exception-based 31
one shot 33
time-based 30
scanning order
described 79
Scheduler 5
functions 5
SCU 7
described 22
function 24
standard 24
summary 26
signal conditioning 49
SIM driver 41
analog values 41
described 41
digital values 41
using 41
slot numbers 28
SM2 driver 45
C API 45
sort order 70
adding a column 70
arranging columns 70
described 70
loading 70
removing a column 70
saving 70
sorting
SQL blocks 26
standard blocks 26
summary 26
syntax 66
database query 66
time-based processing 30
examples 30
understanding 30
toolbar 8
Database Manager 8
Toolkit 26
Database Dynamo 26
Tools menu 81
trending 5
historical values 5
updating a spreadsheet 61
used blocks 73
VBA 73
functions 5
reloading a database from a script 73
verification messages 72
list 72
resolving 72
WorkSpace 5