0% found this document useful (0 votes)
879 views2 pages

Ulmcom & Ulmcom-S: UL Product Range

The document describes ULMCOM and ULMCOM-S mini single channel output units that provide solutions for most UL control panel design requirements. The ULMCOM and ULMCOM-S are compact single channel output units, with the ULMCOM identified as an input/output unit and the ULMCOM-S identified as a sounder. They have features such as quick and simple installation, compact size, soft addressing, and an integral short circuit isolator.

Uploaded by

mjay90
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
879 views2 pages

Ulmcom & Ulmcom-S: UL Product Range

The document describes ULMCOM and ULMCOM-S mini single channel output units that provide solutions for most UL control panel design requirements. The ULMCOM and ULMCOM-S are compact single channel output units, with the ULMCOM identified as an input/output unit and the ULMCOM-S identified as a sounder. They have features such as quick and simple installation, compact size, soft addressing, and an integral short circuit isolator.

Uploaded by

mjay90
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

UL Product Range

ULMCOM & ULMCOM-S Mini Single Channel Output Units

ULMCOM-S - Identified by panel as sounder

UL approved micro interface

Overview Features
An extensive range of interfaces are available to • Quick and simple to install
support the Cooper range of UL control panels, • Compact size
providing solutions for most design requirements. • Soft Addressed
• Integral short circuit isolator
The ULMCOM and ULMCOM-S are single channel
output units and are extremely compact and Benefits
therefore ideal for incorporation into other equipment.
• Plug and play no hard
The ULMCOM is identified by the panel as an addressing required
input/output unit. • No external short circuit
isolator required
The ULMCOM-S is identified by the panel as a
sounder.

The maximum number of ULMCOM-S units per loop


is 60, and is counted towards the total number of
sounders on the loop.

43
ULMCOM & ULMCOM-S - Mini Single Channel Output Units

Technical Specification Installation


Code ULMCOM and ULMCOM-S
1. Fit the box in position using the mounting
Description Single Channel Output Units
details below.
Standards UL864 9th edition 2. Connect the unit according to the diagram below.
Signalling Line Circuit 3. The ULMCOM & ULMCOM-S modules can be
Style 7, Class A, Supervised, Power Limited fitted inside a junction box.
Current 0.322 mA (max) 4. Up to 3 ULMCOM & ULMCOM-S modules can be
Output Relay fitted inside the FIBOX, as per diagram below.
Supervisory Programmable
Switching Voltage 24 V dc to 30 V dc Note:
Contact Rating 1 A Resistive, pf=1 (max) No addressing of the interface is required.
Max Line Impedance 16 Ω
(See control panel operation for details).
Power Factor 1
Environmental
Operating Temperature 0°C to 49°C
Humidity (Non Condensing) 0 to 93 %RH Standard Connections
Physical
Dimensions (H x W x D) 65mm x 35mm x 18.5mm
Weight >0.1kg
Ingress Protection IP40
Compatibility
Loop In
Suitable for use with Cooper analogue addressable fire systems

Relay Contacts Must Loop Out


Be Connected to a Addressable
Power Limited Source
Dimensions Loop

D Loop In

Relay Contacts Must Loop Out


Be Connected to a Addressable
W H Power Limited Source Loop

H (mm) W (mm) D (mm) Note:


65 35 18.5 1. Output relay are volt-free contacts and are
not monitored.
2. Recommended cable type FPLP (plenum cable),
type FPLR (riser cable), or type FPL.
Housing
Description SLC Field Wiring Circuit (input) Single Channel Output
Wiring Gauge 12 Max AWG 12 Max AWG
Wiring Class Class A Style 7
FR4 PCB Interface Plate
Secured to box with Ground Fault Impedance 0.1 ohm
2 self tapping screws. Supervised, Power Limited Yes Yes

Operation
60mm
Normal Standby, Alarm.
180mm
130mm

Product Codes
Code Description
ULMCOM Mini Single Channel Output Unit (recognised as output unit)
ULMCOM-S Mini Single Channel Output Unit (recognised as sounder)
ULBU Mini Module Box Unit (Empty box)

44