PILC 3 Core Paper/Lead/SWA/PVC 6350/11000V BS6480

Applications: Mains power distribution cable


Conductor: Plain annealed stranded compacted copper. Class 2.
25sq.mm – 35sqmm: circular compacted conductors
50sq.mm and above are shaped conductors
Core identification: Numbered cores
Insulation: M.I.N.D (Mass impregnated non-draining) paper insulated, lead or lead
alloy sheathed
Screen: Belted or Screened
Bedding: Textile compound
Armour/Protection: SWA (Single wire armour)
Sheath/Jacket: PVC (Polyvinyl chloride)
Colour: Red
Voltage: 6350/11000v
Operating temperature: Maximum 80°C, minimum bending 0°C
Minimum bending radius: 12 x overall diameter
Standards: BS6480: Power cables, impregnated paper insulated, lead or lead alloy
sheathed electric cables
For current ratings refer to Table BEC107

Size Thickness Thickness Nominal RT of Nominal Diameter Nominal Approx. Weight BATT
sq.mm insulation insulation diameter lead diameter of diameter overall kg/km part no
between between over sheath over armour over diameter
conductor conductor paper mm lead wire mm armour mm
mm and lead belt mm sheath mm
mm mm
25 5.6 3.4 29.4 1.5 32.4 2.0 39.4 43.6 5100 72008
35 5.6 3.4 32.1 1.6 35.3 2.0 38.3 46.7 5300 72009
50 5.6 3.4 30.2 1.7 33.6 2.5 41.6 46.2 6500 72010
70 5.6 3.4 33.3 1.8 36.9 2.5 44.9 49.7 7600 72011
95 5.6 3.4 36.5 1.9 40.3 2.5 48.3 53.3 9000 72012
120 5.6 3.4 39.1 1.9 43.0 2.5 52.0 56.2 10100 72013
150 5.6 3.4 41.8 2.0 45.8 2.5 53.8 59.2 11500 72014
185 5.6 3.4 45.0 2.1 49.2 2.5 57.2 62.8 13200 72015
240 5.6 3.4 49.4 2.3 54.0 2.5 62.0 67.8 16000 75016
300 5.6 3.4 53.5 2.4 58.3 3.15 67.6 73.6 19400 72026
400 5.6 3.4 58.5 2.6 63.7 3.15 73.0 79.4 23100 -