145kV GTP BPDB
145kV GTP BPDB
145kV GTP BPDB
Page 1|4
Minimum Requirement of BPDB Guaranteed
S. No. Description
Unit Data
Rated peak withstand current Ip (equal
2.8 kA 100kA 100kA
short-circuit making current)
D.C. component of the rated short-circuit
2.9 % > 30 > 30
breaking current
2.10 Rated operating sequence O-0.3 s-CO-3 min-CO O-0.3 s-CO-3 min-CO
Page 2|4
Minimum Requirement of BPDB Guaranteed
S. No. Description
Unit Data
3.7 Total height mm To be mentioned
3.8 Pole weight kg To be mentioned
3.9 Weight of operating mechanism kg To be mentioned
3.10 Total weight (with metal structure) of CB kg To be mentioned Please refer attached OGA
3.11 Minimum clearance
3.12 Between poles mm To be mentioned
3.13 To ground mm To be mentioned
Operating mechanism
3.14 Operating mechanism Manufacturer To be mentioned Spring - Spring
3.15 Is lockout facility fitted? Yes/No Yes Yes
3.16 Motor - auxiliary supply voltage V, Hz 230, 50 230, 50
Page 3|4
Minimum Requirement of BPDB Guaranteed
S. No. Description
Unit Data
Weather proof, corrosion resistance
4.12 IP55 IP55, Material: Al
enclosure, Al or stainless steel
Cu earthing rails inside central control Al. Earth pad provided
4.13 Yes
cabinet externally
Detachable plates, the bottom of central
4.14 Yes Yes
control cabinet
Set of cables for connection of operating
4.15 mechanism and central control panel of Yes NA
circuit breaker
Galvanized horizontal and vertical metal
4.16 Yes Yes
structure with minimum 85 μm zinc layer
4.17 Supporting structure Shall be provided Shall be provided
4.18 Gas filling equipment shall be provided shall be provided
4.19 SF6 Gas Cylinder , 20 Kg Shall be provided 10kg Shall be provided
4.20 Name plate rating Shall be provided Shall be provided
Page 4|4