AUMA Electric Actuator (DALIAN DV Valve)
AUMA Electric Actuator (DALIAN DV Valve)
AUMA Electric Actuator (DALIAN DV Valve)
129166-1651G-EADS.doc 3/6
Actuator Type4
No. DESCRIPTION UNITS SELLER's DATA
11HAC10AA502, 11HAD10AA502
11HAD10AA504, 11HAH10AA502
11HAH20AA402, 11HAH30AA502
11HAH01AA502, 11HAH01AA504
1 Customer's Tag (KKS) Number* 11HAH01AA506, 11HAH01AA508
11HAH01AA402, 11HAH01AA404
11HAH01AA406, 11HAH01AA412
11HAH01AA414, 11HAH01AA422
11HAH01AA424, 11HAH20AA502
2 Equipment Service Description
3 Purchaser's Requisition No.
4 Quantity of Actuators of same rating/design 18
5 Electric Actuator Manufacturer AUMA
6 Actuator Type SA14.2/AM02.1‐F14‐B1
7 Service Type (shut‐off / inching / modulating) shut‐off
8 Manufacturer's Model number SA+AM
9 Enclosure Classification (IEC 60529)
10 Rated output kW 0.45
11 Rated voltage V 400VAC
12 Current at rated output A 1.5
13 Insulation System Class F
14 Weight Kg 58
15 Rotation Speed at rated power rpm 11‐32
16 Rated Output Torque N‐m 30‐500
16 Travel Operation Time s DN25/DN40/DN50 23/27/27
17 Number of starts per hour
18 Heating Element (Voltage / phase / power) V/_/W 24VDC/5W
19 Motor Protection
20 Handwheel w/ clutch Yes/No YES
o
21 Actuator Temperature Rating C ‐40 oC‐+70 oC
o
22 Temperature Rating of Controls C ‐40 oC‐+70 oC
23 Integral Starter Yes/No YES
24 Remote Electronics Yes/No YES
25 Limit Switches (OPEN/CLOSED) Yes/No YES
26 Limit Switch Type
27 Limit Switch Rating V/A/VA Max.250VAC/0.5A 24VDC/2A
28 Torque Switches (OPEN/CLOSED) Yes/No yes
29 Thermal Overload alarm contact Yes/No yes
129166-1651G-EADS.doc 4/6
No. DESCRIPTION UNITS SELLER's DATA
30 REMOTE mode status contact Yes/No yes
31 OPEN/CLOSE command inputs Yes/No yes
32 Integral Control power V 24VDC
33 Position Transmitter ( 4 – 20 mADC) Yes/No no
34 Analog Input ( 4 – 20 mADC) Yes/No no
129166-1651G-EADS.doc 5/6
Actuator Type 5
No. DESCRIPTION UNITS SELLER's DATA
1 Customer's Tag (KKS) Number* 11HAH30AA402
2 Equipment Service Description
3 Purchaser's Requisition No.
4 Quantity of Actuators of same rating/design 1
5 Electric Actuator Manufacturer AUMA
6 Actuator Type SA14.6/AM02.1‐F14‐B1
7 Service Type (shut‐off / inching / modulating) shut‐off
8 Manufacturer's Model number SA+AM
9 Enclosure Classification (IEC 60529)
10 Rated output kW 0.8
11 Rated voltage V 400VAC
12 Current at rated output A 3.6
13 Insulation System Class F
14 Weight Kg 63
15 Rotation Speed at rated power rpm 11‐32
16 Rated Output Torque N‐m 30‐500
16 Travel Operation Time s 23
17 Number of starts per hour
18 Heating Element (Voltage / phase / power) V/_/W 24VDC/5W
19 Motor Protection
20 Handwheel w/ clutch Yes/No YES
o
21 Actuator Temperature Rating C ‐40 oC‐+70 oC
o
22 Temperature Rating of Controls C ‐40 oC‐+70 oC
23 Integral Starter Yes/No YES
24 Remote Electronics Yes/No YES
25 Limit Switches (OPEN/CLOSED) Yes/No YES
26 Limit Switch Type
27 Limit Switch Rating V/A/VA Max.250VAC/0.5A 24VDC/2A
28 Torque Switches (OPEN/CLOSED) Yes/No yes
29 Thermal Overload alarm contact Yes/No yes
30 REMOTE mode status contact Yes/No yes
31 OPEN/CLOSE command inputs Yes/No yes
32 Integral Control power V 24VDC
33 Position Transmitter ( 4 – 20 mADC) Yes/No no
34 Analog Input ( 4 – 20 mADC) Yes/No no
129166-1651G-EADS.doc 6/6
Multi-turn actuators
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
with actuator controls
AUMA MATIC AM 01.1/AM 02.1
Reference documents:
Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA
(refer to <Addresses>).
2
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Table of contents
3
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Table of contents AM 01.1/AM 02.1
4
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Safety instructions
1. Safety instructions
1.1 Basic information on safety
Standards/directives AUMA products are designed and manufactured in compliance with recognised
standards and directives. This is certified in a Declaration of Incorporation and an
EC Declaration of Conformity.
The end user or the contractor must ensure that all legal requirements, directives,
guidelines, national regulations and recommendations with respect to assembly,
electrical connection, commissioning and operation are met at the place of installation.
Safety instructions/war- All personnel working with this device must be familiar with the safety and warning
nings instructions in this manual and observe the instructions given. Safety instructions
and warning signs on the device must be observed to avoid personal injury or property
damage.
Qualification of staff Assembly, electrical connection, commissioning, operation, and maintenance must
be carried out exclusively by suitably qualified personnel having been authorised by
the end user or contractor of the plant only.
Prior to working on this product, the staff must have thoroughly read and understood
these instructions and, furthermore, know and observe officially recognised rules
regarding occupational health and safety.
Commissioning Prior to commissioning, it is important to check that all settings meet the requirements
of the application. Incorrect settings might present a danger to the application, e.g.
cause damage to the valve or the installation. The manufacturer will not be held
liable for any consequential damage. Such risk lies entirely with the user.
Maintenance To ensure safe device operation, the maintenance instructions included in this manual
must be observed.
Any device modification requires prior consent of the manufacturer.
1.2 Range of application
AUMA multi-turn actuators are designed for the operation of industrial valves, e.g.
globe valves, gate valves, butterfly valves, and ball valves.
Other applications require explicit (written) confirmation by the manufacturer.
5
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Safety instructions AM 01.1/AM 02.1
● Escalators
● Continuous duty
● Buried service
● Permanent submersion (observe enclosure protection)
● Potentially explosive areas, with the exception of zone 22
● Radiation exposed areas in nuclear power plants
No liability can be assumed for inappropriate or unintended use.
Observance of these operation instructions is considered as part of the device's
designated use.
Information These operation instructions are only valid for the "clockwise closing" standard
version, i.e. driven shaft turns clockwise to close the valve.
1.3 Applications in Ex zone 22 (option)
Actuators of the indicated series basically meet the requirements for applications in
dust hazardous locations of ZONE 22 in compliance with the ATEX directive 94/9/EC.
The actuators are designed to meet enclosure protection IP 68 and fulfil the
requirements of EN 50281-1-1:1998 section 6 - Electrical apparatus for use in
presence of combustible dust, requirements for category 3 electrical equipment -
protected by enclosures.
To comply with all requirements of EN 50281-1-1:1998, it is imperative that the
following points are observed:
● In compliance with the ATEX directive 94/9/EC, the actuators must be equipped
with an additional identification – II3D IP6X T150 °C.
● The maximum surface temperature of the actuators, based on an ambient
temperature of +40 °C in accordance with EN 50281-1-1 section 10.4, is +150
°C. In accordance with section 10.4, an increased dust deposit on the equipment
was not considered for the determination of the maximum surface temperature.
● The correct connection of the thermoswitches or the PTC thermistors as well
as fulfilling the requirements of the duty type and the technical data are prere-
quisites for compliance with the maximum surface temperature of devices.
● The connection plug may only be plugged in or pulled out when device is dis-
connected from the mains.
● The cable glands used also have to meet the requirements of category II3 D
and must at least comply with enclosure protection IP 67.
● The actuators must be connected by means of an external ground connection
(accessory part) to the potential compensation or integrated into an earthed
piping system.
● The threaded plug (part no. 511.0) or the stem protection tube with protective
cap (part nos. 568.1 and 568.2) for sealing the hollow shaft must imperatively
be mounted to guarantee tightness and therefore the combustible dust hazard
protection.
● As a general rule, the requirements of EN 50281-1-1 must be respected in dust
hazardous locations. During commissioning, service, and maintenance, special
care as well as qualified and trained personnel are required for the safe opera-
tion of actuators.
1.4 Warnings and notes
6
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Safety instructions
Information The term Information preceding the text indicates important notes and information.
7
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Identification AM 01.1/AM 02.1
2. Identification
2.1 Name plate
Each device component (actuator, controls, motor) is equipped with a name plate.
Figure 1: Arrangement of name plates
8
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Identification
Commission number An order-specific commission number is assigned to each device. This commission
number can be used to directly download the wiring diagram, inspection records and
further information regarding the device from the Internet: http://www.auma.com.
Control
24 V DC = Control via parallel interface at 24 V DC control voltage.
115 V AC = Control via parallel interface at 115 V AC control voltage.
0/4 – 20 mA = Control via parallel interface via analogue input 0/4 – 20 mA.
2.2 Short description
9
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Transport, storage and packaging AM 01.1/AM 02.1
Hovering load!
Risk of death or serious injury.
→ Do NOT stand below hovering load.
→ Attach ropes or hooks for the purpose of lifting by hoist only to housing and NOT
to handwheel.
→ Actuators mounted on valves: Attach ropes or hooks for the purpose of lifting
by hoist to valve and NOT to actuator.
→ Actuators mounted to gearboxes: Attach ropes or hooks for the purpose of lifting
by hoist only to the gearbox using eyebolts and NOT to the actuator.
→ Actuators mounted to controls: Attach ropes or hooks for the purpose of lifting
by hoist only to the actuator and NOT to the controls.
3.2 Storage
Long-term storage If the device must be stored for a long period (more than 6 months) the following
points must be observed in addition:
1. Prior to storage:
Protect uncoated surfaces, in particular the output drive parts and mounting
surface, with long-term corrosion protection agent.
2. At an interval of approx. 6 months:
Check for corrosion. If first signs of corrosion show, apply new corrosion protec-
tion.
3.3 Packaging
Our products are protected by special packaging for transport when leaving the
factory. The packaging consists of environmentally friendly materials which can easily
be separated and recycled. We use the following packaging materials: wood,
cardboard, paper, and PE foil. For the disposal of the packaging material, we
recommend recycling and collection centres.
10
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Assembly
4. Assembly
AUMA actuators and actuator controls can be operated without restriction in any
mounting position.
Figure 4: Handwheel
[1] Spacer
[2] Input shaft
[3] Handwheel
[4] Circlip
11
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Assembly AM 01.1/AM 02.1
4.3.1.1 Multi-turn actuator (with output drive types B1 – B4 or E): mount to valve/gearbox
12
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Assembly
✔ This working step is only required if stem nut is supplied unbored or with pilot
bore.
Figure 6: Design of output drive type A
13
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Assembly AM 01.1/AM 02.1
4.3.2.2 Multi-turn actuator (with output drive type A): mount to valve
1. If the output drive type A is already mounted to the multi-turn actuator: Loosen
screws [3] and remove output drive type A [2].
2. Check if the flange of output drive type A matches the valve flange [4].
3. Apply a small quantity of grease to the valve stem [1].
4. Place output drive type A on valve stem and turn until it is flush on the valve
flange.
5. Turn output drive type A until alignment of the fixing holes.
6. Screw in fastening screws [5], however do not completely tighten.
7. Fit multi-turn actuator on the valve stem so that the stem nut dogs engage into
the output drive sleeve.
➥ The flanges are flush with each other if properly engaged.
8. Adjust multi-turn actuator until alignment of the fixing holes.
9. Fasten multi-turn actuator with screws [3].
10. Fasten screws [3] crosswise with a torque according to table.
11. Turn multi-turn actuator with handwheel in direction OPEN until valve flange
and output drive A are firmly placed together.
12. Tighten fastening screws [5] between valve and output drive type A crosswise
applying a torque according to table.
14
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Assembly
The mounting position of the local controls is selected according to the order. If, after
mounting the actuator to the valve or the gearbox on site, the local controls are in
an unfavourable position, the mounting position can be changed at a later date. Four
mounting positions are possible.
Figure 9: Mounting positions A and B
15
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Assembly AM 01.1/AM 02.1
Hazardous voltage!
Risk of electric shock.
→ Disconnect device from the mains before opening.
16
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Electrical connection
5. Electrical connection
5.1 Basic information
Wiring diagram/terminal
The pertaining wiring diagram/terminal plan (in German and English language) is
plan attached to the device in a weather-proof bag, together with these operation
instructions. It can also be obtained from AUMA (state commission no., refer to name
plate) or downloaded directly from the Internet (www.auma.com).
Protection on site
For short-circuit protection and for disconnecting the actuator from the mains, fuses
and disconnect switches have to be provided by the customer.
The current values for respective sizing is derived from the current consumption of
the motor (refer to electrical data sheet) plus the current consumption of the controls.
If controls are mounted separately from actuator (controls on wall bracket): Consider
length and cross section of connecting cable when defining the protection required.
Power supply for the
If the controls (electronics) are supplied externally with 24 V DC, the power supply
controls (electronics) is smoothed via an internal 1,000 µF capacitor). When selecting a power supply,
care must be taken to consider the capacitor inrush current upon powering the unit
up.
Safety standards All externally connected devices shall comply with the relevant safety standards.
Cable installation in ac-
Signal and bus cables are susceptible to interference.
cordance with EMC
Motor cables are interference sources.
● Lay cables being susceptible to interference or sources of interference at the
highest possible distance from each other.
● The interference immunity of signal and bus cables increases if the cables are
laid close to the earth potential.
● If possible, avoid laying long cables and make sure that they are installed in
areas being subject to low interference.
17
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Electrical connection AM 01.1/AM 02.1
● Avoid long parallel paths with cables being either susceptible to interference or
interference sources.
● For the connection of remote position transmitters, screened cables must be
used.
Type of current, mains Type of current, mains voltage and mains frequency must match the data on the
voltage and mains fre- motor name plate.
quency
Figure 11: Motor name plate (example)
● Power terminals (U1, V1, W1, U2, V2, W2): max. 6 mm² flexible/10 mm² solid
●
PE connection : max. 6 mm² flexible/10 mm² solid
● Control contacts (1 to 50): max. 2.5 mm²
18
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Electrical connection
[1] Cover
[2] Screws for cover
[3] O-ring
[4] Screws for socket carrier
[5] Socket carrier
[6] Cable entry
[7] Blanking plug
[8] Cable gland (not included in delivery)
Hazardous voltage!
Risk of electric shock.
→ Disconnect device from the mains before opening.
4. Seal unused cable entries [6] with suitable blanking plugs [7].
5. Insert the cables into the cable glands [8].
5.2.2 Cable connection
19
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Electrical connection AM 01.1/AM 02.1
Information Some actuators are equipped with an additional motor heater. The motor heater
minimises condensation within the motor and improves the start-up behaviour for
extremely low temperatures.
20
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Electrical connection
[1] Cover
[2] Screws for cover
[3] O-ring
[4] Screws for socket carrier
[5] Socket carrier
[6] Cable entry
[7] Blanking plug
[8] Cable gland (not included in delivery)
1. Insert the socket carrier [5] into the cover [1] and fasten with screws [4].
2. Clean sealing faces of cover [1] and housing.
3. Check whether O-ring [3] is in good condition, replace if damaged.
4. Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
5. Fit cover [1] and fasten screws [2] evenly crosswise.
6. Fasten cable glands [8] applying the specified torque to ensure the required
enclosure protection.
5.3 Accessories for electrical connection
— Option —
5.3.1 Controls mounted to wall bracket
The wall bracket allows separate mounting of controls and actuator.
Application ● If the actuator cannot be accessed safely.
● If the actuator is subjected to high temperatures.
● In case of heavy vibration of the valve.
21
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Electrical connection AM 01.1/AM 02.1
22
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Electrical connection
The open terminal compartment can be closed using a protective cover (not
illustrated).
5.3.4 Double sealed intermediate frame
When removing the electrical connection or due to leaky cable glands, ingress of
dust and water into the housing may occur. This is prevented effectively by inserting
the double sealed intermediate frame [2] between the plug/socket connector [1] and
the housing of the device. The enclosure protection of the device (IP 68) will not be
affected, even if the electrical connection [1] is removed.
Figure 18: Electrical connection with double sealed intermediate frame
23
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Operation AM 01.1/AM 02.1
6. Operation
✔ Perform all commissioning settings and the test run prior to motor operation.
24
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Operation
➥ The actuator can now be operated using the push buttons [1 – 3]:
- Run actuator in direction OPEN: Press push button [1] .
- Stop actuator: Press push button [2] Stop.
- Run actuator in direction CLOSE: Press push button [3] .
Information The OPEN - CLOSE operation commands can be given either in push-to-run opera-
tion mode or in self-retaining mode. In self-retaining mode, the actuator runs to the
defined end position after pressing the button, unless another command has been
received beforehand.
➥ Now, it is possible to operate the actuator via remote control, via operation
commands (OPEN, STOP, CLOSE) or analogue setpoints (e.g. 0 – 20 mA).
25
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Operation AM 01.1/AM 02.1
Information For actuators equipped with positioner, it is possible to optionally select between
open-close duty (REMOTE OPEN-CLOSE) and modulating duty (REMOTE
SETPOINT). Selection is made via REMOTE MANUAL input, e.g. based on a 24 V
DC signal (refer to wiring diagram).
26
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Indications
7. Indications
7.1 Indication lights
The colours of the 3 indication lights on the local controls and the assignment of the
signals are specified in the order.
Figure 25: Local controls with indication lights (default signalling)
Collective fault signal The collective fault signal (red indication light) will be activated if one of the following
events occurs (default configuration):
● Torque fault: The set torque was exceeded before reaching an end position.
(This signal can be activated/deactivated via a switch in the controls.)
● Thermal fault: Motor protection has tripped, i.e. the motor is overheated.
● Phase failure: One phase is missing (3-ph AC motors only).
● PTC tripping device: Test complete
Running indication If the actuator is equipped with a blinker transmitter (wiring diagram designation:
S5), indication lights [1] and [3] can be used as running indication. The running
indication can be activated/deactivated via a switch in the controls. If the running
indication is active, the respective indication light blinks during operation.
7.2 Mechanical position indicator/running indication
— Option —
Mechanical position indicator:
● Continuously indicates the valve position
(For complete travel from OPEN to CLOSED or vice versa, the indicator disc
[2] rotates by approximately 180° to 230°.)
● Indicates whether the actuator is running (running indication)
● Indicates that the end positions are reached (via indicator mark [3])
27
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Indications AM 01.1/AM 02.1
[1] Cover
[2] Indicator disc
[3] Mark
[4] Symbol for position OPEN
[5] Symbol for position CLOSED
28
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Signals
8. Signals
8.1 Feedback signals via output contacts (binary)
The output contacts can be used to indicate operation modes of the actuator or the
controls as binary signals.
The signals are assigned according to the order. Example:
Output contact open = end position CLOSED not reached
Output contact closed = end position CLOSED reached
29
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Commissioning (basic settings) AM 01.1/AM 02.1
The switch compartment must be opened to perform the following settings (options).
30
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Commissioning (basic settings)
1. Loosen screws [2] and remove cover [1] from the switch compartment.
Figure 29:
31
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Commissioning (basic settings) AM 01.1/AM 02.1
Black section:
[1] Setting spindle: End position CLOSED
[2] Pointer: End position CLOSED
[3] Mark: End position CLOSED is set
White section:
[4] Setting spindle: End position OPEN
[5] Pointer: End position OPEN
[6] Mark: End position OPEN is set
32
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Commissioning (basic settings)
Black section:
[1] Setting spindle: Running direction CLOSE
[2] Pointer: Running direction CLOSE
[3] Mark: Intermediate position CLOSED is set
White section:
[4] Setting spindle: Running direction OPEN
[5] Pointer: Running direction OPEN
[6] Mark: Intermediate position OPEN is set
33
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Commissioning (basic settings) AM 01.1/AM 02.1
Information After 177 turns (control unit for 1 – 500 turns/stroke) or 1,769 turns (control unit for
1 – 5,000 turns/stroke), the intermediate switches release the contact.
9.5.1 Running direction CLOSE (black section): set
34
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Commissioning (basic settings)
35
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Commissioning (basic settings) AM 01.1/AM 02.1
➥ If the PTC tripping device is working properly, the tripping of the motor protection
is signalled via the red indication light "collective fault signal" on the local con-
trols.
2. Turn selector switch to position Reset.
Information Due to the ratio of the reduction gearing the complete resistance range/stroke is not
always passed. Therefore, external adjustment (setting potentiometer) must be pro-
vided.
[1] Potentiometer
36
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Commissioning (basic settings)
37
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Commissioning (basic settings) AM 01.1/AM 02.1
Information If the maximum value cannot be reached, the selection of the reduction gearing must
be checked. (The max. possible turns/stroke are indicated on the order-related
technical data sheet for the actuator.)
38
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Commissioning (basic settings)
3. Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
39
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Commissioning – controls settings AM 01.1/AM 02.1
Hazardous voltage!
Risk of electric shock.
→ Disconnect device from the mains before opening.
The type of seating can be set via two DIP switches on the logic board.
Limit seating
The limit switching is set in such a way that the actuator switches off at the desired
switching points. The torque switching acts as overload protection for the valve.
Torque seating
The torque switching is set to the desired tripping torque. After reaching the tripping
torque, the actuator is turned off.
40
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Commissioning – controls settings
The limit seating is used to signal that the limit switching will trip shortly before
reaching the set tripping torque. If this is not the case, either the indication light on
the local controls or the alarm contact K9 (collective fault signal) will signal a fault.
→ Set type of seating for end positions via DIP switches [S1] and [S3].
Figure 46: DIP switches on logic board
41
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Commissioning – controls settings AM 01.1/AM 02.1
Information If the controls are equipped with a positioner, switches 1 and 2 (operation commands
from remote) must be in position OFF (push-to-run operation).
➥ Switch 6 in lower position (position ON): The signal "Torque fault in collective
fault signal" is activated.
➥ Switch 6 in upper position (position OFF): The signal "Torque fault in collective
fault signal" is deactivated.
10.6 Positioner
— (Option) —
42
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Commissioning – controls settings
→ Prior to positioner setting, set limit and torque switching as well as potentiometer
or electronic position transmitter.
10.6.1 Input ranges (signal type) for setpoint and actual value
The input range (signal type) for setpoint E1 and actuator value E2 is set in the
factory and marked with a label on the cover plate of the positioner.
The type of signal can be modified at a later date exclusively for versions with setpoint
E1 ≠ 0/4 – 20 mA and split-range version. For these versions, the positioner board
is equipped with an additional contact.
Figure 50: Version with additional switch on the positioner board
0–5V
0 – 10 V
0 – 5 V2)
Information When changing the setting, a new label [5] indicating the set signal type must be
provided. Furthermore, the wiring diagram indicated on the name plate of the actuator
controls also changes.
10.6.2 Behaviour on loss of signal (actuator reaction)
In case of a loss of signal of setpoint E1 or actual value E2, the reaction of the actuator
can be programmed via switch [S2-7]. The complete selection range, however, is
only available for signals 4 – 20 mA.
43
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Commissioning – controls settings AM 01.1/AM 02.1
Fail close
Fail open
0 – 20 mA 4 – 20 mA
0 – 20 mA 0 – 20 mA
0–5V 0–5V
0 – 10 V
Fail close 0 – 20 mA 4 – 20 mA
0–5V
Fail as is 0 – 20 mA 4 – 20 mA
0 – 10 V
Fail open 4 – 20 mA 0 – 20 mA
0–5V
44
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Commissioning – controls settings
End position CLOSED 1. Set selector switch to position Local control (LOCAL).
2. Move valve to end position CLOSED.
3. Connect lower setpoint to customer connection XK (terminals 2/3). The lower
setpoint (0 V, 0 mA or 4 mA) is indicated on the label [5].
4. If the red LED [V10] E1/E2 <4 mA is illuminated:
4.1 Verify polarity of setpoint E1.
4.2 Check whether external load is connected to customer connection XK
(terminals 23/24) (observe max. load RB), or
4.3 Connect terminals 23/24 across customer connection XK (terminals 23/24).
5. Measure setpoint E1: Connect measuring device for 0 – 5 V to measuring points
[MP3/MP4].
➥ For a setpoint E1 of 0 V or 0 mA, the voltmeter shows 0 V.
➥ For a setpoint E1 of 4 mA, the voltmeter shows 1 V.
6. If measured value is not correct: Correct setpoint E1.
7. Measure actual value E2: Connect measuring device for 0 – 5 V to measuring
points [MP1/MP2].
➥ For an actual value E2 of 0 mA, the voltmeter shows 0 V.
➥ For an actual value E2 of 4 mA, the voltmeter shows 1 V.
8. If measured value is not correct: Re-set potentiometer or electronic position
transmitter and perform adjustment once again, starting from step 1.
45
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Commissioning – controls settings AM 01.1/AM 02.1
[P3] Potentiometer 0
[P4] Potentiometer max
[V27] Yellow LED: End position CLOSED reached
[V28] Green LED: End position OPEN reached
➥ The setting is correct if the yellow LED [V27] is switched on when reaching end
position CLOSED.
End position OPEN 10. Move valve to end position OPEN.
11. Measure actual value E2 (measuring points [MP1/MP2]):
➥ For an actual value E2 of 20 mA, the voltmeter shows 5 V.
12. If measured value is not correct: Re-set potentiometer or electronic position
transmitter and perform adjustment once again, starting from step 1.
13. Set maximum setpoint E1 (5 V or 20 mA, refer to label [5]).
14. Measure setpoint E1 (measuring points [MP3/MP4]):
➥ For a setpoint E1 of 5 V or 20 mA, the voltmeter shows 5 V.
15. If measured value is not correct: Verify setpoint E1.
16. Adjust positioner using potentiometer max [P4].
16.1 If both LEDs are OFF or the yellow LED [V27] is illuminated: Turn poten-
tiometer max [P4] slightly counterclockwise until the green LED [V28] is
illuminated.
16.2 If the green LED [V28] is illuminated: Turn potentiometer max [P4] clock-
wise until the green LED [V28] goes out. Then turn potentiometer 0 [P3]
slightly counterclockwise until the green LED [V28] is illuminated again.
➥ The setting is correct if the green LED [V28] is switched on when
reaching end position OPEN.
Dead band The dead band determines the sensitivity between switch-on point and switch-off
point. The smaller the dead band, the higher the sensitivity of the positioner.
46
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Commissioning – controls settings
Dead time The dead time prevents the operation to a new setpoint within a pre-determined time
(0.5 to 10 seconds). The number of starts can be reduced by setting the dead time
to a sufficiently high value.
Figure 54: Sensitivity setting
Dead band setting 1. Set selector switch to position Remote control (REMOTE).
2. Connect setpoint E1 to customer connection XK (terminals 2/3).
3. Set dead band using potentiometer Δ E [P9]:
→ Reduce dead band (increase sensitivity): Turn potentiometer counter-
clockwise.
→ Increase dead band (reduce sensitivity): Turn potentiometer clockwise.
Fine tuning Information: Fine tuning is only useful for output speeds <16 rpm. For 1-phase
AC motors, fine tuning is not possible.
4. Reduce dead band further by up to 0.25 % (increase sensitivity): Turn potentio-
meter sens [P7] counterclockwise.
Dead time setting 5. Set dead time using potentiometer t-off [P10]:
→ Reduce dead time: Turn potentiometer t-off [P10] counterclockwise.
→ Increase dead time: Turn potentiometer t-off [P10] clockwise.
10.7 EMERGENCY command (EMERGENCY - OPEN/EMERGENCY - CLOSE)
— (Option) —
The EMERGENCY input (refer to wiring diagram) has to be connected to the control
voltage using an NC contact (closed circuit principle). In the event of an EMERGENCY
command (removal of the signal = NC contact is operated), the actuator runs to the
preset end position:
● EMERGENCY - CLOSE input: Actuator runs to end position CLOSED.
● EMERGENCY - OPEN input: Actuator runs to end position OPEN.
The EMERGENCY command is effective in all three selector switch positions (LOCAL,
OFF, REMOTE).
47
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Commissioning – controls settings AM 01.1/AM 02.1
Disable EMERGENCY Figure 55:Interface board for available option EMERGENCY - OPEN/EMERGENCY
command - CLOSE
48
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Corrective action
Switch check
The red test buttons [1] and [2] are used for manual operation of the switches:
1. Turn test button [1] in direction of the TSC arrow: Torque switch CLOSED trips.
The red indication light (fault) on the local controls is illuminated.
2. Press push button OPEN to reset the fault (indication light) by operating the
device in the opposite direction.
3. Turn test button [2] in direction of the TSO arrow: Torque switch OPEN trips.
4. Press push button CLOSE to reset the fault (indication light) by operating the
device in the opposite direction.
If the actuator is equipped with a DUO limit switching (option), the intermediate
position switches (LSA and LSB) will be operated at the same time as the torque
switches.
1. Turn test button [1] in direction of the LSC arrow: Limit switch CLOSED trips.
2. Turn test button [2] in direction of the LSO arrow: Limit switch OPEN trips.
11.2 Fuses
Hazardous voltage!
Risk of electric shock.
→ Disconnect device from the mains before opening.
49
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Corrective action AM 01.1/AM 02.1
F3 Internal 24 V DC supply
Information Only replace fuses with fuses of the same type and value.
50
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Corrective action
The actuator can be controlled again once the motor has cooled down (red indication
light goes out).
Version with thermoswitch and additional thermal overload relay within the
controls (option)
The operation may only be resumed once the fault signal (red indication light) has
been reset. The fault signal is reset via the overload relay integrated in the actuator
controls. Therefore the controls have to be opened at the cover and the relay held
down. The relay is located on the contactors.
Version with PTC thermistor (option)
The operation may only be resumed once the fault signal (red indication light) has
been reset. The fault signal is reset via selector switch position Reset of the local
controls.
Figure 59: Selector switch on local controls
51
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Servicing and maintenance AM 01.1/AM 02.1
AUMA
AUMA offer extensive service such as servicing and maintenance as well as customer
Service & Support product training. For the relevant contact addresses, please refer to <Addresses>
in this document or to the Internet (www.auma.com) .
52
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Servicing and maintenance
53
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Technical data AM 01.1/AM 02.1
54
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Technical data
55
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Technical data AM 01.1/AM 02.1
Power supply, mains frequency For mains voltage and mains frequency, refer to name plates at the controls and the motor
Permissible variation of the mains voltage: ±10 %
Permissible variation of the mains frequency: ±5 %
Option: Permissible variation of the mains voltage: –10 %
Current consumption Motor current consumption: Refer to motor name plate
Current consumption of the controls depending on the mains voltage:
100 to 120 V AC = max. 575 mA
208 to 240 V AC = max. 275 mA
380 to 500 V AC = max. 160 mA
External supply of the electro- 24 V DC +20 % / –15 %
nics (option) Current consumption: Basic version approx. 200 mA, with options up to 500 mA
Rated power The controls are conceived for the rated motor power, refer to motor name plate
Overvoltage category Category III according to IEC 60364-4–443
Switchgear 1) 2) Standard:
Reversing contactors (mechanically and electrically interlocked) for motor power up to power
class A1
Options:
● Reversing contactors (mechanically and electrically interlocked) for motor power up to
power classes A2 or A3
● Thyristor unit for mains voltage up to 500 V AC (recommended for modulating actuators)
for AUMA power classes B1, B2 and B3
Auxiliary voltage output Standard:
24 V DC ±5 %, max. 50 mA for supply of the control inputs, galvanically isolated from internal
voltage supply
Option:
115 V AC ±10 %, max. 30 mA for supply of the control inputs3), galvanically isolated from
internal voltage supply
Control Standard:
Control inputs 24 V DC, OPEN - STOP - CLOSE (via opto-isolator, one common), current
consumption: approx. 10 mA per input, observe minimum pulse duration for modulating ac-
tuators
Option:
Control inputs 115 V AC, OPEN - STOP - CLOSE - EMERGENCY (via opto-isolator, one
common), current consumption: approx. 15 mA input
Additional enable inputs for directions OPEN and CLOSE
Status signals Standard:
5 output contacts with gold-plated contacts:
● 4 potential-free NO contacts with one common, max. 250 V AC, 0.5 A (resistive load)
- Default configuration: End position OPEN, end position CLOSED, selector switch
REMOTE, selector switch LOCAL
● 1 potential-free change-over contacts, max. 250 V AC, 0.5 A (resistive load)
- Default configuration: Collective fault signal (torque fault, phase failure, motor protec-
tion tripped)
Options:
● Signals in combination with positioner:
- End position OPEN, end position CLOSED (requires tandem switch within actuator),
selector switch REMOTE, selector switch REMOTE, selector switch LOCAL via 2nd
level selector switch
● 1 potential-free change-over contact, max. 250 V AC, 0.5 A (resistive load)
- Default configuration: Collective fault signal (torque fault, phase failure, motor protec-
tion tripped)
Position feedback signal (option) Galvanically isolated analogue output E2 = 0/4 – 20 mA (load max. 300 Ω)
Local controls Standard:
● Selector switch LOCAL - OFF - REMOTE (lockable in all three positions)
● Push buttons OPEN, STOP, CLOSE
● 3 indication lights:
- End position CLOSED (yellow), collective fault signal (red), end position OPEN (green)
Options:
● Special colours for the 3 indication lights
● Protection cover, lockable
● Protection cover with indicator glass, lockable
56
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Technical data
Functions Standard:
● Switch-off mode adjustable
- Limit or torque seating for end position OPEN and end position CLOSED
● Overload protection against excessive torques over the whole travel
● Excessive torque (torque fault) can be excluded from collective fault signal.
● Phase failure monitoring with automatic phase correction
● Push-to-run operation or self-retaining in REMOTE
● Push-to-run operation or self-retaining in LOCAL
● Running indication via blinker transmitter signal of actuator (option) can be activated or
deactivated
Options:
● Positioner
- Position setpoint via analogue input E1 = 0/4 – 20 mA
- Galvanic isolation for position setpoint (0/4 – 20 mA) and position feedback (0/4 – 20
mA)
- Adjustable behaviour on loss of signal
- Adjustable sensitivity (dead band) and pause time
● Positioner for Split Range operation
Motor protection evaluation Standard:
Monitoring of the motor temperature in combination with thermoswitches in the actuator
motor
Options:
● Additional thermal overload relay in the controls in combination with thermoswitches within
the actuator
● PTC tripping device in combination with PTC thermistors in the actuator motor
Electrical connection Standard:
AUMA plug/socket connector (S) with screw-type connection and M-threads
Options:
● Pg-threads, NPT-threads, G-threads, special threads
● Gold-plated control contacts (pins and sockets)
● Parking frame for wall mounting of the disconnected plug
● Protection cover for plug compartment (when plug is removed)
Wiring diagram Refer to name plate
1) The reversing contactors are designed for a lifetime of 2 million starts.
2) For the assignment of AUMA power classes, please refer to electrical data on actuator.
3) Not possible in combination with PTC tripping device
57
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Technical data AM 01.1/AM 02.1
58
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Spare parts
59
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Spare parts AM 01.1/AM 02.1
Information: Please state type and commission no. of the device (see name plate) when ordering spare parts.
Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts
AUMA from any liability. Delivered spare parts may slightly vary from the representation.
No. Designation Type No. Designation Type
001.0 Housing Sub-assembly 553.0 Mechanical position indicator Sub-assembly
002.0 Bearing flange Sub-assembly 554.0 Socket carrier with motor cable har- Sub-assembly
ness
003.0 Hollow shaft with worm wheel Sub-assembly 556.0 Potentiometer for position transmitter Sub-assembly
005.0 Drive shaft Sub-assembly 556.1 Potentiometer without slip clutch Sub-assembly
005.1 Motor coupling on output drive shaft 557.0 Heater Sub-assembly
005.3 Manual drive coupling 558.0 Blinker transmitter including pins at Sub-assembly
wires (without impulse disc and insula-
tion plate)
009.0 Planetary gear for manual drive Sub-assembly 559.0-1 Control unit with torque switching Sub-assembly
heads and switches
017.0 Torque lever Sub-assembly 559.0-2 Control unit with magnetic limit and Sub-assembly
torque transmitter (MWG) for Non-
intrusive version in combination with
AUMATIC integral controls
018.0 Gear segment 560.0-1 Switch stack for direction OPEN Sub-assembly
019.0 Crown wheel 560.0-2 Switch stack for direction CLOSE Sub-assembly
022.0 Drive pinion II for torque switching Sub-assembly 560.1 Switch for limit/torque switching Sub-assembly
023.0 Output drive wheel for limit switching Sub-assembly 560.2 Switch case
024.0 Drive wheel for limit switching Sub-assembly 566.0 Position transmitter RWG Sub-assembly
025.0 Locking plate Sub-assembly 566.1 Potentiometer for RWG without slip Sub-assembly
clutch
058.0 Wire for protective earth (pin) Sub-assembly 566.2 Electronic board RWG Sub-assembly
070.0 Motor (VD motor incl. no. 079.0) Sub-assembly 566.3 Wire harness for RWG Sub-assembly
079.0 Planetary gear for motor drive Sub-assembly 567.1 Slip clutch for potentiometer/RWG Sub-assembly
(SA/SAR 07.2 — 16.2 for VD motor)
155.0 Reduction gearing Sub-assembly 568.1 Stem protection tube (without cap)
500.0 Cover for switch compartment Sub-assembly 568.2 Cap for stem protection tube
501.0 Socket carrier (complete with sockets) Sub-assembly 568.3 V-seal
502.0 Pin carrier without pins Sub-assembly 574.1 Radial seal output drive A for ISO
flange
503.0 Socket for controls Sub-assembly 575.1 Stem nut type A
504.0 Socket for motor Sub-assembly 583.0 Motor coupling on motor shaft Sub-assembly
505.0 Pin for controls Sub-assembly 583.1 Pin for motor coupling
506.0 Pin for motor Sub-assembly 584.0 Retaining spring for motor coupling Sub-assembly
507.0 Plug cover Sub-assembly S1 Seal kit, small Set
511.0 Threaded plug Sub-assembly S2 Seal kit, large Set
514.0 Output drive form A (without stem nut) Sub-assembly
514.1 Axial needle roller bearing Sub-assembly
516.0 Output drive D Sub-assembly
535.1 Snap ring
539.0 Screw plug Sub-assembly
542.0 Handwheel with ball handle Sub-assembly
549.0 Output drive B1/B3/B4/C Sub-assembly
549.1 Output drive sleeve B1/B3/B4/C
60
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Spare parts
61
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Spare parts AM 01.1/AM 02.1
Information: Please state type and commission no. of the device (see name plate) when ordering spare parts.
Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts
AUMA from any liability. Delivered spare parts may slightly vary from the representation.
No. Designation Type
001.0 Housing
002.0 Local controls Sub-assembly
002.5 Selector switch Sub-assembly
003.0 Local controls board Sub-assembly
003.1 Primary fuse
003.2 Fuse cover
004.0 Carrier for contactors
006.0 Power supply including mounting plate Sub-assembly
006.1 Secondary fuse F3
006.2 Secondary fuse F4
008.0 Interface board Sub-assembly
008.1 Interface board
008.2 Cover plate for interface board
009.0 Logic board Sub-assembly
013.0 Adapter board
500.0 Cover Sub-assembly
501.0 Socket carrier (complete with sockets) Sub-assembly
502.0 Pin carrier without pins Sub-assembly
503.0 Socket for controls Sub-assembly
504.0 Socket for motor Sub-assembly
505.0 Pin for controls Sub-assembly
506.0 Pin for motor Sub-assembly
507.0 Plug cover Sub-assembly
508.0 Switchgear Sub-assembly
509.1 Padlock
S Seal kit Set
62
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Certificates
15. Certificates
15.1 Declaration of Incorporation and EC Declaration of Conformity
63
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Index AM 01.1/AM 02.1
I
Index Identification 8
Indication lights 27
A Indications 27
Accessories (electrical 21 Indicator disc 27 , 38
connection) Input ranges 43
Accessories for assembly 15 Inspection record 9
Actual value 43 Intermediate frame 23
Actuator operation from remo- 25 Intermediate positions 33
te
Ambient temperature 58 L
Analogue signals 29 Limit seating 40
Applications 5 Limit switching 32 , 35
Assembly 11 Local control 24
Local controls 24
B Loss of signal 43
Behaviour on loss of signal 43 Low temperature version 30
Blinker transmitter: activa- 42 Lubrication 52
te/deactivate
M
C Mains frequency 18
Cable set 21 Mains voltage 18
Collective fault signal 27 , 29 Maintenance 5 , 52 , 52
Commission number 9 Manual operation 24
Commissioning 5 Mechanical position indicator 27 , 38
Commissioning – controls 40 Motor heater 20
Connecting cable 21 Motor operation 24
Control 9
Corrective action 49 N
Corrosion protection 10 , 57 Name plate 8 , 18
Cross sections 18
Current consumption 17 O
Operation 5 , 24
D Output drive type A 12
DUO limit switching 33 Output drive types B, B1, B2, 11
Dead band 46 B3, B4, and E
Dead time 47
Declaration of Incorporation 63 P
Direction of rotation 34 PTC tripping device 36
Directives 5 Packaging 10
Disposal 53 Parking frame 22
Double sealed 23 Position indicator 38
Position transmitter RWG 37
E Positioner 43
EC Declaration of Conformity 63 Positioner adjustment 45
EMC 17 Positioner sensitivity 46
EMERGENCY command 47 Potentiometer 36
Earth connection 23 Power supply 17 , 18
Electrical connection 17 Protection cover 22
Electronic position transmitter 37 Protection on site 17
Enclosure protection 57 Protective measures 5
Push-to-run operation: set 41
H
Handwheel 11 Q
Heat-up time 30 Qualification of staff 5
64
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Index
R
RWG 37
Range of application 5
Recycling 53
Remote actuator operation 25
Running indication 27 , 27
Running indication: activa- 42
te/deactivate
S
Safety instructions 5
Safety instructions/warnings 5
Self-retaining: set 41
Service 52
Service conditions 57
Servicing 52
Setpoint 43
Short-circuit protection 17
Signal type 43
Signals 29
Signals (analogue) 29
Spare parts 59
Standards 5
Stem nut 13
Stem protection tube 15
Storage 10
Support 52
Switch check 49
T
Technical data 54
Technical data for switches 55
Terminal plan 17
Test run 34
Torque fault signal: activa- 42
te/deactivate
Torque seating 40
Torque switching 31
Transport 10
Type and size 8
Type of current 18
Type of seating: set 40
V
Valve stem 15
W
Wall bracket 21
Wiring diagram 9 , 17
65
AUMA worldwide
66
AUMA worldwide
Asia Australia
AUMA Actuators (Tianjin) Co., Ltd. BARRON GJM Pty. Ltd.
CN 300457 Tianjin AU NSW 1570 Artarmon
Tel +86 22 6625 1310 Tel +61 294361088
Fax +86 22 6625 1320 Fax +61 294393413
[email protected] [email protected]
www.auma-china.com www.barron.com.au
67
AUMA Riester GmbH & Co. KG
P.O.Box 1362
D 79373 Muellheim
Tel +49 7631 809 - 0
Fax +49 7631 809 - 1250
[email protected]
www.auma.com
Y004.903/003/en/4.12