NGR Panel - Rev 01 PDF
NGR Panel - Rev 01 PDF
NGR Panel - Rev 01 PDF
Quantity: 01 NO.
X6
L1 L2 L3
X6
VIEWING
1000
WINDOW MARSHALLING
X3 CHAMBER
X6
DRAWING
POUCH
2000
2000
PROVISION FOR
MANUAL REAR FRONT
OPERATION
900
X6
X6
E
100
Appd By : D.R.JAYARAM CLIENT : M/s. TEHKHAND WASTE TO ELECTRICITY PROJECT LIMITED. SCALE : NTS
Description: CONSULTANT : M/s. KORUS ENGINEERING SOLUTIONS PVT LTD., JOB No : VV19-295 REV.No.
Chkd By : D.R.JAYARAM PROJECT NAME : 30 MW BLEED CONDENSING TURBINE. 01
01 REVISED AS PER CUSTOMER COMMENTS RAJ DRJ 23.06.2020 M/s. VEEVEE CONTROLS GENERAL ARRANGEMENT EQUIPMENT : NGR PANEL (C-3643) DRG SUB No. : VVC 2019-295B/GA
Drawn By : Sudha PVT.LTD.,
Rev Revision comment Prep Appd Date DATE : 16.03.2020 Sheet : 3 OF 20 Total Pages: 20
1000
X6
X7
X6
2000
2000
FRONT REAR
X7
900
X6
EARTH BUS
E
1500
NOTE:-
1. INTERNAL GA SHOWN IS TENTATIVE ONLY.
IT MAY CHANGE SUBJECT TO PRACTICAL IMPLEMENTATION.
Appd By : D.R.JAYARAM CLIENT : M/s. TEHKHAND WASTE TO ELECTRICITY PROJECT LIMITED. SCALE : NTS
Description: CONSULTANT : M/s. KORUS ENGINEERING SOLUTIONS PVT LTD., JOB No : VV19-295 REV.No.
Chkd By : D.R.JAYARAM PROJECT NAME : 30 MW BLEED CONDENSING TURBINE. 01
01 REVISED AS PER CUSTOMER COMMENTS RAJ DRJ 23.06.2020 M/s. VEEVEE CONTROLS GENERAL ARRANGEMENT EQUIPMENT : NGR PANEL (C-3643) DRG SUB No. : VVC 2019-295B/GA
Drawn By : Sudha PVT.LTD.,
Rev Revision comment Prep Appd Date DATE : 16.03.2020 Sheet : 4 OF 20 Total Pages: 20
1000
2000
900
DLS3 PL2
CABLE TROUGH
CABLE TROUGH
F1 F2 F4
X1
X4
F3
CABLE TROUGH
CABLE TROUGH
CABLE TROUGH
CABLE TROUGH
NISX
X2
CABLE TROUGH
PS
100
X3
700 800
(IGA OF MARSHALLING
CHAMBER)
FRONT VIEW WITHOUT DOOR
NOTE:-
1. INTERNAL GA SHOWN IS TENTATIVE ONLY.
IT MAY CHANGE SUBJECT TO PRACTICAL IMPLEMENTATION.
Appd By : D.R.JAYARAM CLIENT : M/s. TEHKHAND WASTE TO ELECTRICITY PROJECT LIMITED. SCALE : NTS
Description: CONSULTANT : M/s. KORUS ENGINEERING SOLUTIONS PVT LTD., JOB No : VV19-295 REV.No.
Chkd By : D.R.JAYARAM PROJECT NAME : 30 MW BLEED CONDENSING TURBINE. 01
01 REVISED AS PER CUSTOMER COMMENTS RAJ DRJ 23.06.2020 M/s. VEEVEE CONTROLS GENERAL ARRANGEMENT EQUIPMENT : NGR PANEL (C-3643) DRG SUB No. : VVC 2019-295B/GA
Drawn By : Sudha PVT.LTD.,
Rev Revision comment Prep Appd Date DATE : 16.03.2020 Sheet : 5 OF 20 Total Pages: 20
SEAL OF BUSHING
CT1
1RX50X10mm AL
CT2
2000
2000
INTERNAL SIDE VIEW-AA INTERNAL SIDE VIEW-BB
NOTE:-
1. INTERNAL GA SHOWN IS TENTATIVE ONLY.
IT MAY CHANGE SUBJECT TO PRACTICAL IMPLEMENTATION.
Appd By : D.R.JAYARAM CLIENT : M/s. TEHKHAND WASTE TO ELECTRICITY PROJECT LIMITED. SCALE : NTS
Description: CONSULTANT : M/s. KORUS ENGINEERING SOLUTIONS PVT LTD., JOB No : VV19-295 REV.No.
Chkd By : D.R.JAYARAM PROJECT NAME : 30 MW BLEED CONDENSING TURBINE. 01
01 REVISED AS PER CUSTOMER COMMENTS RAJ DRJ 23.06.2020 M/s. VEEVEE CONTROLS GENERAL ARRANGEMENT EQUIPMENT : NGR PANEL (C-3643) DRG SUB No. : VVC 2019-295B/GA
Drawn By : Sudha PVT.LTD.,
Rev Revision comment Prep Appd Date DATE : 16.03.2020 Sheet : 6 OF 20 Total Pages: 20
1200
1250
250
600
RGP(400X200)
50
2 Nos.-14
SUITABLE FOR
175 175 SUITABLE FOR M12 BOLT
75 75 M12 BOLT 1Rx50x10mm, Al.
75
175
1Rx50x10mm AL
400
500
175
75
400 PANEL
500
12MM
Appd By : D.R.JAYARAM CLIENT : M/s. TEHKHAND WASTE TO ELECTRICITY PROJECT LIMITED. SCALE : NTS
Description: CONSULTANT : M/s. KORUS ENGINEERING SOLUTIONS PVT LTD., JOB No : VV19-295 REV.No.
Chkd By : D.R.JAYARAM PROJECT NAME : 30 MW BLEED CONDENSING TURBINE. 01
01 REVISED AS PER CUSTOMER COMMENTS RAJ DRJ 23.06.2020 M/s. VEEVEE CONTROLS GENERAL ARRANGEMENT EQUIPMENT : NGR PANEL (C-3643) DRG SUB No. : VVC 2019-295B/GA
Drawn By : Sudha PVT.LTD.,
Rev Revision comment Prep Appd Date DATE : 16.03.2020 Sheet : 7 OF 20 Total Pages: 20
CONSTRUCTION DETAILS & GENERAL NOTES:-
1. ENCLOSURE DETAILS:
5. CABLE DETAILS:
a) ENCLOSURE DIMENSION 2000(H)X1500(W)x1250(D) a) GRADE 1.1kV FRLS FLEXIBLE MULTISTRAND COPPER
b) LOAD BEARING MEMBER 2.5mm, CRCA
b) CABLES FOR CT SEC. WIRING 2.5Sq.mm BLACK
c) NON LOAD BEARING MEMBER 2mm, CRCA
c) CABLES FOR CONTROL & AUX. 2.5Sq.mm BLACK
d) GLAND PLATE THICKNESS FOR 3mm, CRCA
CIRCUIT (230V AC)
MARSHALLING CHAMBER
e) BASE FRAME HEIGHT 100mm, ISMC d) CABLES FOR CONTROL 1.5Sq.mm GREY
f) ANTI VIBRATION PAD 15mm THICK CIRCUIT (110V DC)
g) ENCLOSURE PROTECTION FOR CT IP 54 e) POTENTIAL FREE CONTACTS 1.5Sq.mm GREY
COMPARTMENT
f) CABLES FOR EARTHING 2.5Sq.mm YELLOW WITH GREEN STRIP LINE
h) ENCLOSURE PROTECTION FOR IP 44 4Sq.mm YELLOW WITH GREEN STRIP LINE FOR CT
RESISTOR COMPARTMENT BODY EARTHING
6. LABELS & LEGEND DETAILS:
h) PANEL TYPE SIMPLEX, FLOOR MOUNTING
i) GASKET MATERIAL PU a) PATTERN LETTERS ENGRAVED ON BLACK
j) WEIGHT OF THE ENCLOSURE apprx. 800kgs. BACK GROUND
k) FRONT DOOR HINGED & FIXED b) MATERIAL ANODISED ALUMINIUM STRIPS
Appd By : D.R.JAYARAM CLIENT : M/s. TEHKHAND WASTE TO ELECTRICITY PROJECT LIMITED. SCALE : NTS
Description: CONSULTANT : M/s. KORUS ENGINEERING SOLUTIONS PVT LTD., JOB No : VV19-295 REV.No.
Chkd By : D.R.JAYARAM PROJECT NAME : 30 MW BLEED CONDENSING TURBINE. 01
01 REVISED AS PER CUSTOMER COMMENTS RAJ DRJ 23.06.2020 M/s. VEEVEE CONTROLS CONSTRUCTION DETAILS EQUIPMENT : NGR PANEL (C-3643) DRG SUB No. : VVC 2019-295B/GA
Drawn By : Sudha PVT.LTD.,
Rev Revision comment Prep Appd Date DATE : 16.03.2020 Sheet : 8 OF 20 Total Pages: 20
NAME PLATE DETAIL
X1 : NEUTRAL GROUNDING RESISTOR PANEL
X2 : RESISTOR CHAMBER
X3 : NGR
VOLTAGE 11 kV/√3
RESISTANCE RATING:63.5Ω
RATED CURRENT:100A
DUTY CYCLE-30Sec
MATERIAL: PUNCHED STAINLESS STEEL
TEMP. RAISE OVER AMBIENT TEMP.:325°C
X4 : CT1
RATIO: 100/1-1A
11kV, 50Hz,
BIL: 12/28/75kV
CORE 1: 5P20, BURDEN: 10VA
CORE 2: 5P20, BURDEN: 10VA
STC: 40KA FOR 3Sec
X5 : CT2
RATIO: 100/1A
11kV, 50Hz,
BIL: 12/28/75kV
CORE 1: 5P20, BURDEN: 10VA
STC: 40KA FOR 3Sec
X6 : DANGER BOARD
X7 : CAUTION PLATE
X8 : MARSHALLING CHAMBER
L1 : NIS CLOSE
L2 : NIS OPEN
L3 : SPACE HEATER ON
Appd By : D.R.JAYARAM CLIENT : M/s. TEHKHAND WASTE TO ELECTRICITY PROJECT LIMITED. SCALE : NTS
Description: CONSULTANT : M/s. KORUS ENGINEERING SOLUTIONS PVT LTD., JOB No : VV19-295 REV.No.
Chkd By : D.R.JAYARAM PROJECT NAME : 30 MW BLEED CONDENSING TURBINE. 01
01 REVISED AS PER CUSTOMER COMMENTS RAJ DRJ 23.06.2020 M/s. VEEVEE CONTROLS RATING NAME PLATE DETAILS EQUIPMENT : NGR PANEL (C-3643) DRG SUB No. : VVC 2019-295B/GA
Drawn By : Sudha PVT.LTD.,
Rev Revision comment Prep Appd Date DATE : 16.03.2020 Sheet : 10 OF 20 Total Pages: 20
A2
1
= MINIATURE CIRCUIT BREAKER = SELECTOR SWITCH = TOGGLE SWITCH
A1
=EARTH
= CURRENT TRANSFORMER = PUSH BUTTON
= INDICATING LAMP PE
= MOTORISED ISOLATOR SWITCH = UTILITY SOCKET
2
= DIS-CONNECTING TYPE
= THERMOSTAT TERMINAL BLOCK
= LOADING RESISTOR
= STUD TYPE
= SPACE HEATER TERMINAL BLOCK
= NEUTRAL GROUNDING TRANSFORMER
A1
= AUX. CONTACTOR =DOOR LIMIT SWITCH
A2
BBT
11kV TAP OFF
A A
CT1 P1 1S1
100/1-1A, CORE 1: CL:5P20, EARTH FAULT CIRCUIT TO GPR-1
BURDEN : 10VA
P2 1S2
STC : 40KA FOR 3SEC
P1 2S1
100/1-1A, CORE 2: CL:5P20,
BURDEN : 10VA STAND BY EARTH FAULT CIRCUIT
STC : 40KA FOR 3SEC P2 2S2
B B
S1
CT2 P1
100/1A, CL:5P20, EARTH FAULT CIRCUIT TO GPR-2
BURDEN : 10VA P2 S2
STC : 40KA FOR 3SEC
NIS
ON LOAD SWITCH
11kV, 200A
MOTORIZED
STC : 40KA FOR 3SEC
C NGR C
11kV
RATED RESISTANCE:63.5 Ohms
RATED CURRENT:100A
DUTY RATING-30 Sec
MATERIAL: PUNCHED SS
TEMPERATURE RAISE 325 DEG
ABOVE AMBIENT TEMPERATURE
GROUNDING
D D
BBT
11kV TAP OFF
A A
X1
1C10 1
P1 1S1
CT1 2
100/1-1A, CORE 1: CL:5P20, EARTH FAULT CIRCUIT TO GPR-1
BURDEN : 10VA P2 1S2 1C11 3
STC : 40KA FOR 3SEC
1C11
X2
2C10 1
100/1-1A, CORE 2: CL:5P20,
P1 2S1
BURDEN : 10VA 2
STC : 40KA FOR 3SEC STAND BY EARTH FAULT CIRCUIT
B P2 2C11 3 B
2S2
2C11
X3
3C10 1
P1 S1
CT2 2
EARTH FAULT CIRCUIT TO GPR-2
100/1A, CL:5P20,
BURDEN : 10VA P2 3C11 3
STC : 40KA FOR 3SEC S2
3C11
C C
13 21 31 43 53 61
NIS
ON LOAD SWITCH 14 22 32 44 54 62
11kV, 200A
/15.4:B
/15.5:B
/15.6:B
/15.6:B
/15.4:C
/15.5:C
MOTORIZED
STC: 40KA FOR 3SEC
NGR
11kV
RATED RESISTANCE:63.5 Ohms
RATED CURRENT:100A
DUTY RATING-30 Sec
MATERIAL: PUNCHED SS
TEMPERATURE RAISE 325 DEG ABOVE
AMBIENT TEMPERATURE
D D
GROUNDING
-F1
Ph. X4 1 H1 1 2 H3
Ph / 16.1:A
230V AC SUPPLY
A ACDB A
N 2 H2 3 4 H4
N / 16.1:B
MCB
16A, DP
1 2
MCB ILS
4A, DP K1 K1A
X4 5
SPARE TB X4 6
H6
11 11 REMOTE OPEN
L/R A2 H9 X4 3 X4 4 H6
43 43 LS LS
12 12 1
-C1 -C2
B /14.4:C 44 /14.4:C 44 H10 PB2 B
K9 K15
A1 NIS OPEN
K6 21 21
-C2 -C1
/14.4:C 22 /14.4:C 22
STARTING K11
K3
WINDING
H5
83
RUNNING 9
C -C1 H6
WINDING /14.4:C 84 X4 9 X4 10
10 SPARE TB
K17 H8
B2 H11 REMOTE CLOSE H8
L/R X4 7 X4
K5 H7 2 8
K3 83
11
-C2 H8
H12 PB1
/14.4:C 84 B1 NIS CLOSE
12
C 53 53 13 13 C
-C1 -C2 -C2 -C1
/14.4:C 54 /14.4:C 54 /14.4:C 14 /14.4:C 14
K11A K17A
A1 A1
C1 C2
A2 A2
K2 K2
13 14 /14.3:C 13 14 /14.2:C
21 22 /14.4:B 21 22 /14.4:B
43 44 /14.3:B 43 44 /14.3:B
D 53 54 /14.2:C 53 54 /14.2:C D
83 84 /14.3:C 83 84 /14.4:C
A A
F2
+VE X5 1 J1 1 2 J3
110V DC SUPPLY
FROM DCDB
-VE X5 2 J2 3 4 J4
MCB
10A, DP
NIS
U1 U3 U5 U7
13 14
NIS 13 21 31 43
AUXILIARY NIS NIS NIS NIS
SWITCH /13.3:C 14 /13.3:C 22 /13.3:C 32 /13.3:C 44
B 7 B
8
U2 U4 U6 U8
X5 3 X5 4 X5 5 X5 6 X5 7 X5 8 X5 9 X5 10
J5 J6 NEUTRAL ISOLATOR
SWITCH ON FEEDBACK SPARE CONTACT ON/OFF FEEDBACK SPARE CONTACT
TO MCSP TO DCS
J5
U9 U11 U9 U11
C A1 C
NISX L1 L2
53 61 13 21
A2
NIS NIS NISX NISX
/13.3:C 54 /13.3:C 62 /15.2:C 14 /15.2:C 22
D D
A A
H3 H3
Ph / 14.6:A
H4 F3 1
N / 14.6:A MCB 2
6A, SP
F4
MCB 2
6A, SP
B B
H17
11 11 11
1
TH DLS1 DLS2 DLS3
2 12 12 12
H15 H16
H4
PS
H4
1
x2 x2 PE
x1 x1
SH L3
x2
PL1 PL2 2
x2 CFL CFL
x1 x1
C C
H4 H4 H4 H4 H4
D D
11 SPARE
X2 Application
12 SPARE
2C10
1 STAND BY EARTH FAULT CIRCUIT
2C11
2 STAND BY EARTH FAULT CIRCUIT
2C11
3 STAND BY EARTH FAULT CIRCUIT
X5 Application
J1
4 SPARE 1 110V DC SUPPLY FROM DCDB (+VE)
J2
2 110V DC SUPPLY FROM DCDB (-VE)
U1 NEUTRAL ISOLATOR SWITCH ON FEEDBACK
3
TO MCSP
U2 NEUTRAL ISOLATOR SWITCH ON FEEDBACK
X3 Application
4
TO MCSP
U3
5 SPARE CONTACT
3C10
1 EARTH FAULT CIRCUIT TO GPR-2
U4
6 SPARE CONTACT
3C11
2 EARTH FAULT CIRCUIT TO GPR-2
U5
7 ON/OFF FEEDBACK TO DCS
3C11
3 EARTH FAULT CIRCUIT TO GPR-2
U6
8 ON/OFF FEEDBACK TO DCS
4 SPARE
U7
9 SPARE CONTACT
U8
10 SPARE CONTACT
U9
11 SPARE CONTACT
X4 Application
U10
12 SPARE CONTACT
H1 U11
1 230VAC SUPPLY-FROM ACDB (Ph.) 13 SPARE CONTACT
H2 U12
2 230VAC SUPPLY-FROM ACDB (N) 14 SPARE CONTACT
H9 U9
3 REMOTE OPEN 15 SPARE CONTACT
H6 U10
4 REMOTE OPEN 16 SPARE CONTACT
H9 U11
5 SPARE TB 17 SPARE CONTACT
3 CURRENT TRANSFORMER RATIO: 100/1-1A, 11kV,50Hz, 40KA FOR 3Sec. CT1 INSTRANS 1
BASIC INSULATION LEVEL : 12/28/75KV
CORE 1 & 2 CL: 5P20, BURDEN: 10VA
APPLICATION:EARTH FAULT CIRCUIT TO GPR-1 & STAND BY EARTH FAULT CT, RESIN
CAST
4 CURRENT TRANSFORMER RATIO: 100/1A, 11kV,50Hz, 40KA FOR 3Sec. CT2 INSTRANS 1
BASIC INSULATION LEVEL : 12/28/75KV
CL: 5P20, BURDEN: 10VA
APPLICATION: EARTH FAULT CIRCUIT TO GPR-2 (RESIN CAST)
5 INDICATING LAMP 220V DC, 22.5mm DIA., LED TYPE, RED COLOUR L1 SIEMENS/TEKNIC 1
220V DC, 22.5mm DIA., LED TYPE, GREEN COLOUR L2 SIEMENS/TEKNIC 1
240V AC, 22.5mm DIA., LED TYPE, RED COLOUR L3 SIEMENS/TEKNIC 1
2 POLE, 2POSITION WITHOUT OFF, STAY PUT WITH 2NO+2NC CONTACT, 22.5mm
6 LOCAL / REMOTE SEL. SWITCH L/R SIEMENS 1
Dia.,230V AC,6A,
7 PUSH BUTTON 22.5mm dia, WITH 2NO ELEMENTS, CLOSE: :RED, OPEN: GREEN PB1,PB2 SIEMENS/TEKNIC 2
13 PANEL LAMP 230VAC,5W,LED TYPE WITH ONE FEET FITITNG PL1-2 PHILIPS/HAVELLS 2
01 OF 02
CUSTOMER: M/s.TRIVENI TURBINE LIMITED. PROJECT:30 MW BLEED CONDENSING TURBINE.
CLIENT:M/s. TEHKHAND WASTE TO ELECTRICITY DRG. No. : VVC 2019-295B/BOM
CONSULTANT : M/s. KORUS ENGINEERING SOLUTIONS JOB No. : VV19-295
BILL OF MATERIAL FOR NGR PANEL
PO NO:2000022822. DATE:11.03.2020 QTY: 1No.
REV. No. : 01, DT: 23.06.2020
15 SEAL OF BUSHING 12kV, EPOXY WITH RIBS SUITABLE FOR SEALED 1Rx50x10mm Al. BUSBAR ELCO INDUSTRIES 1
16 INSULATOR 12kV , SIZE 60mm DIA,130mm HIEGHT (EPOXY) , CREEPAGE DISTANCE -175mm ELCO INDUSTRIES AS REQ
02 OF 02