For HXE310 CT & CTPT Meters
Introduction
This user manual covers all aspects of using the HexView software, which is specially designed for
User-friendly interface and convenient operation are the main features of this HexView software.
Obtain readings
Program meters
Table of Contents
INTRODUCTION .............................................................................................................................................................. 1
1 INSTALLATION ...................................................................................................................................................... 4
1 Installation
Hardware requirement
Software requirement
Other
Start installation
Selection
(g) Click button to select the desired disk drive for installing HexView software.
And then choose the access mode authorized to this PC software.
User
Confirm
Please wait some seconds, in order to complete installation of the PC software. After successful
Installation Complete
Please click button , at this time, a new icon appears on the desktop.
Double click this icon to operate.
HexView PC SW User Manual for HXE310 8 / 51
2 HexView Basic
2.1 Login
Before start-up this HexView PC software, please ensure that the PC connection with the electricity
meter via optical probe. After successful installation, the new icon will appears on the
desktop.
Login
Key in the User name and Password correctly, and then click button to enter into the
main window.
NOTE: The default administrator ID is „Hexing‟ and default password is 000000. This user
is in the highest security level, which cannot be deleted and can change the password only by itself.
HexView PC SW User Manual for HXE310 9 / 51
3.1 Overview
After logging in, the below interface appears. The interface is initial window interface.
The main menu consists of Title bar, Menu bar and Icon bar.
Title bar
Menu bar
Icon bar
Main menu
HexView PC SW User Manual for HXE310 10 / 51
(a) File menu: In this menu there are 5 functions: New, Open, Save, Save as, And Exit.
File menu
(b) System menu: In this menu there are 4 functions: User shift, Password change, User
HexView PC SW User Manual for HXE310 11 / 51
System menu
Password change Change password, which is user‟s password. The users can change
User management Add, edit or delete user account (Five levels of users are available.
User named Hexing is the supervisor and has the highest access
right who cannot be deleted), the user of level 1 has the right to
Level access Access Level, there are five levels totally. Level access defines
(c) Option: reference about communication, Parameters about meter type, protocol, media, port, and
baud rate, initial the communication parameters here before reading or programming the meter.
HexView PC SW User Manual for HXE310 12 / 51
Option menu
(d) Skin: there are more than 20 kinds of skin provided for HexView.
Skin menu
HexView PC SW User Manual for HXE310 13 / 51
Click „About…‟ of Help menu, and appear the below dialog box.
User management Add or delete user account (Five levels of users are available. User
named Hexing is the supervisor and has the highest access right
and has the highest access right who cannot be deleted), the user
Level access Access Level, there are five levels totally. Level access defines
HexView PC SW User Manual for HXE310 14 / 51
Reference Parameters about meter type, protocol, media, port, and baud rate,
3.2.2.2 Illumination
If there has been a meter parameter scheme, confirm dialog box will appear after clicking .
If there has never been opened a meter parameter scheme or click in confirm dialog box,
Login again
HexView PC SW User Manual for HXE310 15 / 51
Click shortcut or „Password change‟ in system menu and pop up the below dialog box.
Password change
Name Explanation
Old password Inputs the old password of current user into this text box.
New password Inputs the new password of current user into this text box
OK Saves amendment
Click „User management‟ to pop up the dialogue box as below, and you could get all kinds of work
Add user: Key in the „Username‟ and „Password‟ , select specific security level for the user and
click „Add‟ button; then click „Save‟ to store the latest data. There are two authentication level:
HLS and LLS, HLS has the right to read and write the meter, but LLS only can read meter.
Delete user: Select the user except „Hexing‟ in the user list, and click „Delete‟ button to delete it
Edit user:Select the user in the user list, and click „Edit‟ button, and then you can change the
content in the blank of Password/Level. After editing, the information of the user list will be
refreshed.
User management
There are 5 levels for users(3 levels for some meter type), and users in each level can have same or
different scope operations. The scope of each level can also be set by Level1.
For example, the below figure means that Level4 can have operations of Parameters, Energy,
Level access
It can change communication parameter here, and be sure that the meter type and COM port are
correct before communication with meter. Make sure that no parameter scheme is opened before
changing the meter type. The threshold of over time is provided for you to modify when the
communication is not very good. Some meters support more than one protocol, for example
DLMS(Mode E) and DLMS(Direct HDLC for RS485), in HexView the default protocol is
DLMS(Mode E), if DLMS(Direct HDLC for RS485) is selected when communication, the
SubStation No. should be changed to four bytes, see detail information in chapter about option .
HexView PC SW User Manual for HXE310 18 / 51
Reference
4.1 Overview
When adding a new file or open existing file, the main communication interface will appear:
HexView PC SW User Manual for HXE310 19 / 51
This HexView, PC software, is major in configuration and readout data tool. Each tree node is
corresponding to relevant command. The main command is read, write and execute their function
separately are data readout, parameter writing into and the execute operation.
The main window splits into main three parts of the main window.
Main command area The left area It is major in main command selection
Data display area The top right area It is used for display readout data information
Communication state area The bottom right area It is designed for review communication state
Option Get knowledge of or change Sub station No. and password or AES key.
Clear Delete the data of selected items ( the data are displayed in the Data
Display Area in HexView and not in Meter), and then the data becomes
default values.
NOTE: After clicking (Option), Meter Parameters will appear. See or change sub station
No. and keys.
HexView PC SW User Manual for HXE310 21 / 51
Meter Parameters
Parameters
Name Explanation
If you is going to communicate with one meter, input the correct sub
station No. For protocol DLMS(Mode E) the length of sub station No.
the last 2 bytes of the meter serial number in the nameplate add „0001‟.
save the keys, If the authentication Key of the meter is not the default
„Modify keys‟.
Global key is the key for ciphering. The default Global Key of the meter
is 16 bytes of hex. HexView will not save the keys, If the global Key of
00 00 00 00), you should input the correct authentication key here. It can
Click symbol in the left column, the relevant electronic values will be displayed.
Parameters operation tools on meter parameters scheme can separately operate option on the left, and
also operate multi-options or all the options depending on user‟s choice. User has chosen all the read
HexView PC SW User Manual for HXE310 22 / 51
operations and Basic parameters option of write operation, so that when click all the parameters of
NOTE: HexView for different types of meters may contains some special parameter items, e.g.
for direct connection meter it do not contain CT/PT item.
When clicking , read all the selected parameters, and show and save the data readout. Symbol
When reading and writing, it will appear relevant communication information in the textbox at the
bottom of window, and error information will be marked with red. Click on the right to save
5.1 Read
The Meter Read is used for readout the register data in the meter by HexView.
5.1.1 Parameters
Current parameters of the meter which are read only. Such as current tariff number, firmware
version.
Parameters
5.1.2 Energy
Energy
Instantaneous Values of meter, such as voltage, current, frequency, active power. For three phase, the
Instantaneous values
Billing data, you can select all to read all billing data, also you can select the data range to read part
of billing data.
Billing data
HexView PC SW User Manual for HXE310 26 / 51
5.1.5 Profile
Read the profile log, there are 17 channels totally, the parameters of each channel can be modified in
menu „profile configuration‟. The records of a channel can be read out totally or partly.
Profile
5.1.6 Event
There are several types of event. You can choose reading some of them, also you can read the events
Standard event log records all general events, e.g changes of the clock, changes of the configuration,
clearing of profiles, all kind of self check errors, activation of new parameters, activation of new time
of use, etc.
Fraud detection log records events related to fraud attemps, e.g removal of terminal cover, removal
of meter cover.
Disconnector control log records the events related to the disconnector, e.g connect, disconnect,
Grid event records the events related to power outages, low voltage, overvoltage, etc. Long power
failure log records the occurring time and duration of long power outages.
Long power outage event log records End of long power outage and Duration of long power
outages.
HexView PC SW User Manual for HXE310 27 / 51
Meter cover removed records occurring time when meter cover removed.
Terminal cover removed records occurring time when terminal cover removed.
Event
A predefined selection of events set and clear flags in the error register. The error register can be read
and displayed at anytime to see, if there is a malfunction in the device. Depending on the type of
error, some errors clear themselves if the reason for the error has disappeared. Other must be cleared
via CAS. Nevertheless the events are stored in one of the event logs.
All alarm flags in the alarm register remain active until the alarm register is cleared via CAS
(acknowledgment). Typically fraud attempts are selected as alarm triggers. Typically fraud attempts
and critical errors are selected as alarm triggers. Power outages normally can't be selected since the
When some events such as power down, clock adjusted, daylight saving, data not valid, clock invalid
and critical error occur in E-meter, the corresponding bit of AMR profile status code will be set.
5.2 Write
The Meter Write is used for setting the parameters in the meter. Also the parameters to configure can
be read.
5.2.1 Meter ID
They are information about identification numbers. Here you can change the parameters about meter
location.
HexView PC SW User Manual for HXE310 29 / 51
Meter ID
Format of Billing date is „dd hh‟ („date hour‟, dates are from 01 to 28 and hours are from 01 to 23),
Billing date
Display items: it can set the contents displayed on the LCD and the scrolling interval between
Display configuration
HexView PC SW User Manual for HXE310 30 / 51
(b) Auto scroll display items: get or set the contents displayed on the LCD in Auto scroll sequence.
(c) Manual display items: get or set the contents displayed on the LCD in manual scroll.
read button to read the configurations in the meter first. The items that are already
configured in the meter will display in the left column.
2. Select before items in the right column and click . The selected items will display in
the left column.
3. If some items in the left column are considered unnecessary to display in auto scroll display
mode, select these items and click or double click the selected item, they will be
removed from the display list.
4. Check if the display items list in the left column is correct. If there is no mistake, click
to write this configuration to the meter.
5. Repeat the first step to see if the items are successfully written to the meter.
HexView PC SW User Manual for HXE310 31 / 51
Items setup
Name Explanation
Auto scroll display interval Set Scrolling interval [sec]. The range of it is from1s to 99s.
Auto scroll display items Get or set the contents displayed on the LCD in Auto scroll
Manual display items Get or set the contents displayed on the LCD in Manual scroll
Manual display items with Get or set the contents displayed on the LCD in Manual display
NOTE: If need delete some items in Data Display Area, click or double click the
Define the interface of Optical port and RS-485. If optical communication is disabled, the baud rate
NOTE:If the communication address of RS-485 is changed when meter communicates through
Communication interface
There are 17 channels provided (less than 17 for some type meter), the capture objects, capture
HexView PC SW User Manual for HXE310 33 / 51
period, start address and entries size of each channel can be read or write. Max number of records is
read only. The max number of capture objects for every channel is 9(item 1-item 9), any item
It should be noted that the start address of channel 1 for single phase meter should be greater than
16476, and it should be greater than 22134 for three phase. The maximum address for profile is
540671. The start address of one channel should not less the value that start address of former
Profile configuration
It contains all data necessary to set up the TCP or UDP sub-layer of the COSEM TCP or UDP based
transport layer of a TCP-UDP/IP based communication profile. The GPRS module can be configured
GPRS
5.2.7 RTC
you can set the time according PC time or input time by yourself. When set the new time, the meter
will compare with the new time, if the time shift is more than the limit value, the new time will be
ignored by the meter, and the CAD bit of AMR profile status code E meter will be set.
HexView PC SW User Manual for HXE310 35 / 51
Date/time
5.2.8 Tariff
Four tariffs can be configurable, named T1, T2, T3, and T4.
There are active TOU and passive TOU, active TOU is the active calendar, passive TOU is passive
calendar, which can be active at passive TOU activation date. They contain day table, week table,
Name Explanation
Day table Sets to begin and end at specific times each day
Season table Is available for seasonal adjustments to the tariff schedule each year
Day table define the switching of Tariff during a 24 hour day, midnight to midnight. Each day can be
divided into maximum 8 periods with different tariff. Maximum 4 day tables can be defined. There
Day table
NOTE: Former time must be later than time set before, otherwise, „Note‟ dialog box will
appear.
Note
HexView PC SW User Manual for HXE310 37 / 51
Week table configures which Day table occurs by default each day of the week. Day table selection
is for every day of a week. Select the Day table for each day of the week using the drop down boxes
on the right.
Week table
It enables user to define tariff in different season. One year can be divided into 4 seasons at most.
HexView PC SW User Manual for HXE310 38 / 51
Season table
On the left are public holidays, which are on the same day each year and should not be set the year.
On the right are special holidays, which may be on the different day each year, and should be set the
year.
The total holidays (both public holidays and special holidays) can be set 50 at most.
HexView PC SW User Manual for HXE310 39 / 51
Holiday table
NOTE: Former date must be later than dates set before; otherwise, „Note‟ dialog box will
appear.
Number of voltage sags—Occurring counts of event that voltage sag. It is read only.
Number of voltage swells-- Occurring counts of event that voltage swells. It is read only.
Number of power failures—Occurring counts of event that power failures. It is read only.
Number of long power failures—Occurring counts of event that long time power failures. It is read
only.
Threshold for voltage sag—The value when voltage is higher than it, and the duration is longer than
„time threshold for voltage sag‟, event of voltage sag will be recorded.
Threshold for voltage swell—The value when voltage is lower than it, and the duration is longer than
„time threshold for voltage swell, event of voltage swell will be recorded.
HexView PC SW User Manual for HXE310 40 / 51
Time threshold for long power failure—The value which the duration of power failure is longer than,
Time threshold for current reverse—The value which the duration of current reverse is longer than,
5.2.10 Disconnector
You can get the output state, control mode,control state , the limiter threshold of disconnector and
information of emergency profile, also the control mode of disconnector and emergency profile can
be configured. Output state shows the actual physical state of the disconnect unit, i.e. if an electricity
breaker or a gas valve is open or closed, the state is „connected‟ or „disconnected‟. Control state
shows the internal state of the disconnect control object, the state is „disconnected‟, „connected‟ or
„ready for reconnection‟. Control mode configures the behavior of the disconnect control object for
all triggers, the possible state transitions are Mode 0 (None. The disconnect control object is always
in „connected‟ state) ,
Control Logic
HexView PC SW User Manual for HXE310 42 / 51
Disconnected(0)
(a)remote disconnect
(d)Reconnect time over
(b)Disconnect time over (b)Disconnect time over
(a)remote disconnect
(c)remote connect
(g)Manual disconnect
(h)remote connect
Connected(1)
(i)Reconnect time over
(e)Manual reconnect
(k)auto reconnect
(f)overload disconnect
Control status:
There are four statuses: disconnected (0), connected (1), ready for connected with lock (2), ready for
connected (3).
Disconnected (0): relay is disconnected. Relay is not permitted to execute any operation before
receiving connection order from Master Station/PC software or it is designated time for
connection.
Connected (1): relay is connected.
Ready for connected with lock (2): relay is disconnected. Relay won‟t connect automatically.
Ready for connected (3): relay is disconnected. Disconnected by overflow, relay will connect
automatically after a specific period.
If Master Station sends order (a) remote disconnect, status will switch to disconnected (0), no
matter which status is relay currently under. The physical status of relay is disconnected.
If it is time for disconnection, which is configurable on meter, (b) disconnect time over will be
executed. Status will switch to disconnected (0), no matter which status is relay currently under.
The physical status of relay is disconnected.
If Master Station sends order (c) remote connect, (c) or (h) will be executed based on current
HexView PC SW User Manual for HXE310 43 / 51
control mode.
If it is time for connection, which is configurable on meter, (d) or (i) will be executed based on
current control mode.
If status is connected (1) and load is over threshold, (f) overload disconnect will be executed
automatically and status will switch to ready for connected (3).
If status is ready for connected with lock (2) or ready for connected (3), (e) manual reconnect
can be executed through long press on key for 3 seconds, and status will switch to connect (1).
If status is ready for connected (3), it can switch to connected (1) through the execution of (k)
auto reconnect.
Generally, (j) N overtime will be executed after specific times of overflow disconnection, then,
status switches to ready for connect (2).
In emergency, (1) E overtime will be executed after specific times of overflow disconnection,
then, status switches to ready for connect (2), at the same time, E overtime flag will be set.
If status is ready for connect (2) and there is E overtime flag, (m) E to N will be executed, when
emergency switches to normal situation, then, status switches to connected (1).
If the working mode permits, (g) manual disconnect can be executed through long press on key
for 3 seconds, then, status switches to ready for connected with lock (2).
Control mode:
Power utilities can choose one of the four modes or switch from one mode to another while in
operation.
Active parameters:
Output state of disconnection: shows the actual physical state of the disconnection.
Control mode of disconnection: Configures the behavior of the disconnection for all triggers.
Normal mode
Min over threshold duration(s) is delayed time threshold, which means over limiter threshold “ Min
over threshold duration” seconds,relay will disconnected; and the default time is 30s;
Threshold for connection after disconnect is the delayed time of automatic connection after the relay
disconnected;
Allowed counts for auto reconnection [C1] is the allowed counts of automatic connection in the short
time;
Time threshold to clear C1 is the time after relay connected. C1 will clear if the relay no changing.
Therefore, Time threshold to clear C1 is a value must bigger than Min over threshold duration(s) and
HexView PC SW User Manual for HXE310 45 / 51
Threshold for connection after disconnect, otherwise the number of times will be cleared when the
relay not connects automatically yet after disconnection, and the allowed counts will be meaningless.
The objective of this function is let relay possesses the function of automatic connection, but the
Emergency mode
Table of normal limiter threshold: relay control threshold table under emergency mode
Min over threshold duration(s) is delayed time threshold under emergency mode, which means over
limiter threshold “ Min over threshold duration” seconds,relay will disconnected, and the default
time is 30s;
Threshold for connection after disconnect is the delayed time of automatic connection after relay
Allowed counts for auto reconnection[C1] is the allowed counts of automatic connection in the short
Time threshold to clear C1 is the time after relay connection under emergency mode; C1 will clear if
The emergency mode is activated via the emergency profile defined by emergency profile id,
emergency_activation_time, emergency_duration.
HexView PC SW User Manual for HXE310 46 / 51
An emergency profile is activated if the emergency_profile_id element matches one of the elements
emergency_duration element:
emergency_profile_id: long-unsigned,
emergency_activation_time: octet-string,
emergency_duration: double-long-unsigned
emergency_activation_time defines the date and time when the emergency_profile activated.
emergency_duration defines the duration in seconds, for which the emergency_profile is activated.
Master key is used for wrapping new Authentication key and Global key. It can not be changed.
Authentication key and Global key can be changed, before changing them be sure that the master key
is filled correctly. If the keys is changed, user should fill the new key when login HexView in menu
HexView PC SW User Manual for HXE310 47 / 51
The new image will not be active immediately after firmware update communication, it will be
active at activation time. Image version is the version of image wait to active.
If the set item is invalid, the meter will not record corresponding event.
HexView PC SW User Manual for HXE310 48 / 51
5.3 Execute
The Meter Execute is used for setting the special operations in the meter.
If execute some functions, click the Checkbox on the left of corresponding items, and click .
NOTE: Due to continuous improvement of the software, the screenshot shown in this user
manual might be slightly different with the actual software interface. Information in this document is
subject to change without notice. The information is accurate at the time of printing (March, 2013)
© Hexing Electrical
HexView PC SW User Manual for HXE310 50 / 51