Fault Location and Diagnosis in A Medium Voltage EPR Power Cable
Fault Location and Diagnosis in A Medium Voltage EPR Power Cable
Fault Location and Diagnosis in A Medium Voltage EPR Power Cable
Power Cable
A. J. Reid, C. Zhou and D. M. Hepburn
School of Engineering and Built Environment
Glasgow Caledonian University
Glasgow, G4 0BA, UK
P. Withers
Manchester X-ray Imaging Facility
Materials Science Centre
University of Manchester, M13 9PL, UK
ABSTRACT
This paper presents a case study on fault location, characterisation and diagnosis in
a length of shielded 11 kV medium voltage ethylene-propylene rubber (EPR) power
cable. The defect was identified on-site as a low resistance fault occurring between the
sheath and the core. A 43 m section was removed for further analysis. The fault
resistance was characterised and the location of the defect pinpointed to within a few
cm using a combination of time-difference-of-arrival location and infra-red imaging. A
combination of X-ray computed tomography, scanning electron microscopy and energy
dispersive X-ray spectroscopy were then applied to characterise any abnormalities in
the dielectric surrounding the breakdown region. A significant number of high density
contaminants were found to be embedded in the dielectric layer, having an average
diameter of the order of 100 μm, a maximum diameter of 310 μm and an average
density of 1 particle per 2.28 mm3. Scanning electron microscopy and energy-dispersive
X-ray spectroscopy were used to determine the geometry and elemental composition of
some initial contaminant samples. It was concluded that contamination of the EPR
layer, combined with an observed eccentricity of the cable’s core and sheath resulting
in a reduced insulation gap, may have led to an electric field concentration in the
region of the defect sufficient to initiate breakdown. Preventative strategies are
discussed for similar families of cables, including more stringent dielectric testing
requirements at the manufacturing stage and PD monitoring to detect incipient failure.
Index Terms — Power cable insulation, power system faults, condition monitoring,
dielectric breakdown.
Figure 4. Fault location using infra red imaging. The location is 1.8 m from
the cable datum end. For clarity, this composite image consists of the
thermal image superimposed on a photograph of the experimental setup.
Figure 3. Measured traces at the respective HFCTs arising from breakdown
at the site of the cable fault. Δt = 261 ns. The cable had been placed in a spiral arrangement so that
the entire cable length was within the field of view. The site of
Fault location was then calculated using the equation: the fault was apparent on the inner coil of the spiral
arrangement as evidenced by increased temperature in the
region. Once thermal equilibrium was reached the peak cable
l − Δt ⋅ u p
d= (1) temperature was found to be 21.7oC (2.5oC above the ambient
2 level).
It was of interest to characterise parameters of the fault. For
where Δt is the time-difference-of-arrival between measured example, since the cable voltage, current and phase could be
signals at HFCTs 1 and 2. This was achieved by identifying measured, fault resistance could be evaluated in terms of its
similar features on the respective waveforms arriving at each variation with applied voltage. The resistance of the active
HFCT, such as the initial peaks, and estimating the time fault region is related to its reflection coefficient. Knowledge
difference between these features. Taking into account of this resistance is therefore useful in determining the
measurement errors in Δt and ΔT, the signals shown in Figure accuracy of reflection-based location methods. This will be
3 correspond to a fault location of d = 2.18 ± 0.56 m from discussed further in the next section.
HFCT1 (see Figure 1).
3 DEFECT ANALYSIS applied voltages. Fault resistance fluctuated between 2 kΩ and
6.5 kΩ at the minimum applied voltage. The variation in fault
3.1 CHARACTERISATION OF RESISTANCE resistance was plotted against the voltage across the cable (test
The voltage across and current through the cable were object). This is shown in Figure 7.
measured as indicated in Figure 5, where, Ip is the primary
current, Is is the secondary current, Vs is the secondary voltage
and Ccable is the capacitance of the cable under test from inner Increasing primary
applied voltage
to outer conductor.
240V / 50kV
(a)
(b) (a)
(c) (b)
REFERENCES
[1] L. Renforth, R. Mackinlay and M. Michel, “MV cable diagnostics - Alistair J. Reid (M’11) graduated from the University of Strathclyde, UK, in
applying online PD testing and monitoring,” in Proc. MNC-CIRED Asia 2004 with a B.Eng. (Hons) degree in Electrical and Mechanical Engineering
Pacific Conference on MV Power Cable Technologies, September 2005. and received the Ph.D. degree in 2007 for research on partial discharge
[2] H. E. Orton, “Diagnostic testing of in-situ power cables: An overview,” monitoring. He conducted post-doctoral research within the Institute for
in Proc. Asia Pacific Transmission and Distribution Conference and Energy and Environment at the University of Strathclyde, from 2007-2011,
Exhibition. Yokohama, Japan: IEEE/PES, October 2002, pp. 1420– studying advanced radiometric techniques for partial discharge detection and
1425. diagnostics on underground power cables. He is presently a Research Fellow
[3] S. Boggs and J. Densley, “Fundamentals of partial discharge in the within the School of Engineering and Built Environment at Glasgow
context of field cable testing,” IEEE Electrical Insulation Magazine, vol. Caledonian University. Alistair is a Member of both the IET and IEEE.
16, no. 5, pp. 13–18, September/October 2000.
[4] J. C. Chan, P. Duffy, L. J. Hiivala, and J. Wasik, “Partial discharge VII: Martin D. Judd (M’02-SM’04) was born in Salford, England, in 1963. He
PD testing of solid dielectric cable,” IEEE Electrical Insulation graduated from the University of Hull in 1985 with a B.Sc. (Hons) degree in
Magazine, vol. 7, no. 5, pp. 9–16, Sep–Oct 1991. electronic engineering. His employment experience includes four years
[5] B. Clegg, “Underground Cable Fault Location”. McGraw Hill Book working for Marconi Electronic Devices Ltd followed by four years with EEV
Company Europe, 1993. Ltd, both in Lincoln, England. Martin received the Ph.D. degree from the
[6] British Standard BS6622: Specification for cables with extruded University of Strathclyde in 1996 for his research into the excitation of UHF
crosslinked polyethylene or ethylene propylene rubber insulation for signals by partial discharges in gas insulated switchgear. From 1999 to 2004
rated voltages from 3800/6600 V up to 19000/33000 V. London, UK: he held an EPSRC Advanced Research Fellowship concerned with
British Standards Institution (BSI), 1985. electrodynamics of electrical discharge phenomena. His fields of interest
[7] L. J. Lewis, “Traveling wave relations applicable to power-system fault include high frequency electromagnetics, generation and measurement of fast
locators,” Trans. American Institute of Electrical Engineers, vol. 70, no. transients, and partial discharges and energy harvesting. Dr. Judd is a Reader
2, pp. 1671–1680, July 1951. in the Institute for Energy and Environment at the University of Strathclyde.
[8] A. O. Ibe and B. J. Cory, “A travelling wave-based fault locator for two- He is a Chartered Engineer, a Member of the IET and Senior Member of the
and three-terminal networks,” IEEE Trans. Power Delivery, vol. 1, no. 2, IEEE.
pp. 283–288, April 1986.
[9] P. F. Gale, P. A. Crossley, B. Xu, Y. Ge, B. J. Cory, and J. R. G. Barker, Wah Hoon Siew received the B.Sc. (Hons.) degree in electronic and electrical
“Fault location based on traveling waves,” in Proc. 5th International engineering, the Ph.D. degree in electrical engineering in 1982; and the
Conference on Developments in Power System Protection, York, UK, Master of Business Administration degree from the University of Strathclyde,
Mar-Apr 1993, p. 54. Glasgow, U.K., in 1978, 1982, and 1985, respectively. Currently, he is a
[10] Z. Q. Bo, G. Weller, and M. A. Redfern, “Accurate fault location Reader in the Department of Electronic and Electrical Engineering at the
technique for distribution system using fault-generated high-frequency University of Strathclyde, Glasgow, U.K. His research interests include
transient voltage signals,” IEE Proc. Generation, Transmission and lightning protection to aircraft and grounded structures, electromagnetic
Distribution, vol. 146, no. 1, pp. 73–79, Jan 1999. compatibility in large installations due to switching and lightning, lightning,
[11] A. J. Reid, X.Hu, and M. D. Judd and W. H Siew, “Defect investigation EMP and ESD; and cable diagnostics. Dr. Siew is a Chartered Engineer and a
in medium-voltage EPR cable,” in Proc. IEEE International Symposium member of the Institution of Engineering and Technology. He is also a
on Electrical Insulation, San Juan, Puerto Rico, 10-13 June 2012. member of several CIGRE Working Groups under C4 and a member of the
[12] S. V. Nikolajevic, “The behavior of water in XLPE and EPR cables and Technical Panel for the IET Professional Network on electromagnetics.
its influence on the electric characteristics of insulation,” IEEE
Transactions on Power Delivery, vol. 14, no. 1, pp. 39–45, January Chengke Zhou (M’07) received the B.Sc. and M.Sc. degrees in electrical
1999. engineering from Hua Zhong University of Science and Technology, China in
[13] M. A. Dakka, A. Bulinski, and S. Bamji, “Correlation between DC 1983 and 1986, respectively, and the Ph.D. degree at the University of
polarization and failure characteristics of XLPE and EPR aged with ac Manchester U.K., in 1994. Since then, he worked in Glasgow Caledonian
voltage in a wet environment,” IEEE Transactions on Dielectrics and University, U.K., as a Lecturer, Senior Lecturer and in Heriot-Watt University
Electrical Insulation, vol. 12, no. 4, pp. 700–708, August 2005. as a Reader until 2007 when he went back to Glasgow Caledonian University
[14] J. C. Chan, M. D. Havtley, and L. J. Hiivala, “Performance as a Professor. He has published more than 100 papers in the area of partial
characteristics of XLPE versus EPR as insulation for high voltage discharge based condition monitoring of MV/HV plant and power system
cables,” IEEE Electrical Insulation Magazine, Vol. 9, No. 3, pp. 8-12, analysis.
May-June 1993.
[15] G. Bahder, M. Sosnowski, C. Katz, R. Eaton, and K. Klein, “Electrical Donald Hepburn (M’08) is a Senior Lecturer in the School of Engineering
breakdown characteristics and testing of high voltage XLPE and EPR and Built Environment at Glasgow Caledonian University (GCU). He has
insulated cables,” IEEE Transactions on Power Apparatus and Systems, been involved in insulation materials research and in partial discharge
vol. PAS-102, no. 7, pp. 2173–2185, July 1983. diagnostics for HV and MV system components for over 19 years. He is a
[16] “Specification for Extruded Dielectric Shielded Power Cables Rated 5 member of CIGRE Joint Working Group A2-D1.46 on transformer solid
through 46 kV”, 3rd ed. Association of Edison Illuminating Companies insulation diagnostics and of the Universities High Voltage network
(AEIC), 2007. (UHVnet) within the UK. He holds a B.A. (hons) degree from the Open
[17] S. Shinoda, K. Hikino, and M. Marumo, “275kV XLPE insulated University and a Ph.D. from GCU. Dr Hepburn is a Chartered Engineer, a
aluminum sheathed power cable for Okuyahagi No.2 power station,” Member of the IEEE, a Member of the IET and a Member of the Institute of
IEEE Transactions on Power Apparatus and Systems, vol. PAS-100, no. Physics.
3, pp. 1298–1306, March 1981.