Self Dehydrating Breather
Self Dehydrating Breather
The SDB maintenance free air breather was 1. Low environmental impact.
developed by COMEM with the goal of The SDB does not require periodical maintenance of the silica
achieving at least three important aims. gel salts, which effectively reduces the consumption of this
particularly precious natural raw material.
SDB
Moisture can be reliably absorbed, thanks to the double tank solution
The flow of hot air generated by the fan prevents any possible This exclusive patent pending system of drying with double
formation of ice in the entrance filter, if the air breather is tanks offers the advantage of ensuring that, during intake
installed in areas with glacial climate. of the air into the transformer conservator, the air breather
After regeneration of the salts in tank A, the solenoid valve is de- tank in function is always the one with dehydrated salts and
energized and the airflow through tank B is inhibited. NOT the one subject to simultaneous regeneration.
To ensure that the next time the salts in this tank are also
dehydrated, regeneration of the salts in tank B automatically follows.
2
Advantages Operating principle
• Continuous monitoring of the increased silicagel weight and con- In normal operation the outside air breathed by the conservator
trol at every cycle of correct salt regeneration. passes through the salt tanks “A” and in this passage any moisture is
• Overall reduction of the environmental impact with respect to eliminated.As they absorb the moisture in the air, the weight of the
conventional air breathers, as salt replacement is no longer salts increases which is constantly monitored by a weighing cell.
needed. The data collected is sent to an electronic control circuit (Patent
• Overall reduction of maintenance costs for the transformer, as the pending solution).
operation of salt replacement is eliminated. When the weight increase exceeds the preset value (value
• Reduction of the number of inspections to the new air breather, established with an experimental test process), a solenoid valve
that can be made together with normal maintenance of the trans- blocks the passage of air through the salt tank A and deviates it
former. through “plenum chamber” B. At the same time, a heating system
• Thanks to the double tank solution, we can drastically reduce any inside tank A is activated. The water vapor leaving the silicagel is
moisture entering the transformer. expelled outward by a fan, that also dissipates the heat. Inside the
salt, a probe controls the temperature of the heating element.
To conservator To conservator
Electroniccontrol Electroniccontrol
circuit circuit
3
Overall dimensions type SDB-030
302 (11.88")
88.5
CENTERING
12
SCREWS
711 (28")
753 (29.64")
M10
ANTIVIBRATION = = ANTIVIBRATION
INLET/ INLET/ 30 110 213 DEVICE
DEVICE 195 (7.68")
OUTLET AIR OUTLET AIR
323.5 (12.79")
X DETAIL
EYE-BOLT Ø42
The double tank solution is reliable and drastically reduces any moisture entering the transformer
4
Overall dimensions type SDB-015
CENTERING
SCREWS
12 (0.47")
721 (28.38")
764 (30.07")
M10
ANTIVIBRATION
DEVICE
DETAIL X
EYE-BOLT
100 (3.93")
EYE-BOLT
Ø42 (1.65")
Ø130 (5.12")
207 (8.15")
The coaxial tank allows you to have the advantages of the double tank while having a compact configuration
5
Overall dimensions type SDB-010
CENTERING
SCREWS
12 (0.47")
MAIN TANK
CONNECTION (1/4"G)
713 (28.07")
756 (29.76")
M10
ANTIVIBRATION
DEVICE 110(4.33") 213 (8.38")
INLET/
OUTLET AIR
30 (1.18") 323.5 (12.73")
DETAIL X
100 (3.93")
Ø42
Ø130 (5.12")
207 (8.15")
The single tank used in combination with the SDB-030 or SDB-015 allows you to have the same advantages
as the other models while reducing the total cost.
6
SDB-010 operating principle
During the normal operation the oil conservator intakes air that At the same time, a heating system inside tank 1 is activated. The
passes through the metallic filter. The metallic filter stops dust, water vapor leaving the silica gel is expelled outward by a fan
sand and other particles from the contaminating air. The air then that also dissipates the heat.
passes through the salt tank 1. Inside the salt, a probe controls the temperature of the heating
The salt tank is filled with silica gel that absorbs the moisture. element.
The dehydrated air goes through piping to the oil conservator. During the functioning of the device, the weighing cell
When the silica gel absorbs the moisture in the air, the weight temperature is monitored by a temperature sensor mounted in
of the salt increases and is constantly monitored by a weighing the upper part.
cell. When the weight increases and exceeds the pre-set value a After the salt regeneration in tank 1 (timed regeneration), the
solenoid valve blocks the passage of air through salt tank 1 and solenoid valve is de-energized.
deviates through the main self-dehydrating breather by the pipe No maintenance is required for replacement and regeneration of
connected on one of the two plug. the desiccant.
SDB-030 SDB-010
7
Self dehydrating breather type SDB
Maximum oil volume 45 m3, 40 tons oil, 12,000 gals 45 m3, 40 tons oil, 12,000 gals 90 m3, 80 tons oil, 24,000 gals
Power panel
Signal output 4-20 mA (dielectric strength between electronic card and analog output 1000 V)
Signal contacts
8
Wiring terminals
Standard:
- POWER FAILURE (terminals 22-24-21) - change-over contact:
NO contact: terminals 24-21
SYSTEM POWER POWER ANALOG RS 485
- POWER SUPPLY: 12 14 11 22 24 21 31 32 41 44 1 2 3 4
terminals 31-32
- SYSTEM FAILURE (terminal 12-14-11) - change-over contact:
NO contact: terminals 14-11
NC contact: terminals 11-12
- ANALOG OUTPUT 4÷20 mA:
terminals 41-44
- DIGITAL OUTPUT RS485 (optional): + - + - B A
- DATA LOG
9
Self dehydrating breather type SDB
Identification codes
1 (letter) E Air Breather
2 (letter) C Corrosion protection = moderate salinity areas acc. to ISO 12944
5 Corrosion protection = off-shore areas acc. to ISO 12944
3 (letter) A SDB-030
B SDB-015
C SDB-010
4 (letter) A With flange DN40 acc. to UNI EN 1092-1:2007
Model selection
The below number and size of Self Dehydrating Breathers are ‘Rule of Thumb’ recommendations for the devices in question. This is to
be considered as a guide only and should not replace good design and engineering practice and experience
10
11
Strada Regionale 11, Signolo 22 Due to technical product updates, the information
contained in this catalogue may be subject to change
36054 Montebello Vicentino (VI) - ITALY without notice.
Tel. +39 0444 449311
© Copyright 2013 COMEM.