Current Derating For Yaskawa 1000-Series Drives
Current Derating For Yaskawa 1000-Series Drives
Current Derating For Yaskawa 1000-Series Drives
A1000 Series Derating Factor According to Installation Method and Ambient Temperature
Table 2 A1000 Series Derating Factor According to Installation Method and Ambient Temperature (Da1)
70
55
L8-35 = 1: Side-by-Side Mounting
0 L8-12
-10 30 40 50 (Ambient temp: °C)
<1> The drive standard ratings are valid for installations up to 1000 m. Derate 1% for every 100 m higher than 1000 m.
Normal Duty
2A0004 to 2A0069
Heavy Duty
2A0081 to 2A0138
80% of HD
70% of HD
Normal Duty
2A0169 to 2A0415
Heavy Duty
80% of HD
Normal Duty
60% of HD
Normal Duty
4A0139 to 4A0362
Heavy Duty
70% of HD
4A0414
Normal Duty
Heavy Duty
0 2 kHz 5 kHz
Heavy Duty
83% of HD
0 2 kHz 5 kHz
4A0930,4A1200
Normal Duty
Heavy Duty
62.5% of HD
0 2 kHz 5 kHz
Note: Refer to V1000 Series Derating Curve According to Carrier Frequency on page 9 for other carrier frequency settings.
V1000 Series Derating Factor According to Installation Method and Ambient Temperature
Table 5 V1000 Series Derating Factor According to Installation Method and Ambient Temperature (Dv1)
Parameter L8-35 = 1
(Side-by-side Mounting)
0% Ambient temp o C
o o o o o Parameter L8-12
-10 30 35 40 50
<1> The drive standard ratings are valid for installations up to 1000 m. Derate 1% for every 100 m higher than 1000 m.
Drive
Rating
ND
HD
200 V Class:
80% of HD
400 V Class:
60% of HD
0
2 10 (8) 15
Carrier Frequency (C6-02)
Note: Refer to J1000 Series Derating Curve According to Carrier Frequency on page 11 for other carrier frequency settings.
J1000 Series Derating Factor According to Installation Method and Ambient Temperature
Table 8 J1000 Series Derating Factor According to Installation Method and Ambient Temperature (Dj1)
Parameter L8-35 = 1
(Side-by-side Mounting)
0% Ambient temp o C
o o o o o Parameter L8-12
-10 30 35 40 50
<1> The drive standard ratings are valid for installations up to 1000 m. Derate 1% for every 100 m higher than 1000 m.
Drive
Rating
ND
HD
200 V Class:
80% of HD
400 V Class:
60% of HD
0
2 10 (8) 15
Carrier Frequency (C6-02)
Note: Refer to Z1000 Series Derating Curves According to Carrier Frequency on page 13 for other carrier frequency settings.
Z1000 Series Derating Factor According to Installation Method and Ambient Temperature
Table 11 Z1000 Series Derating Factor According to Installation Method and Ambient Temperature (Dz1)
IP00/Open-Type
100%
IP20/NEMA Type 1
External Heatsink
80%
60%
0%
-10°C 40°C 50°C
Figure 13 Z1000 Series Ambient Temperature and Installation Method Derating
<1> The drive standard ratings are valid for installations up to 1000 m. Derate 1% for every 100 m higher than 1000 m.
100%
60%
Figure 14 Carrier Frequency Derating Models CIMR-Z2A0011 to 2A0114 and 4A0005 to 4A0096
100%
80%
Figure 15 Carrier Frequency Derating Models CIMR-Z2A0143 to 2A0273 and 4A0124 to 4A0180
Figure 16
100%
60%
0 4kHz 10kHz
Figure 16 Carrier Frequency Derating Models CIMR-Z4A0240 and 4A0302
Figure 17
100%
80%
0 2 kHz 5 kHz
Figure 17 Carrier Frequency Derating Models CIMR-Z2A0343 to 2A0396 and 4A0361 to 4A0590