Setting Calculation Protocol For IDMT Overcurrent Relay Settings

This document provides the calculation protocol for setting the IDMT overcurrent and earth fault relay settings for the protection of an outgoing feeder. It includes the feeder details, relay and CT data, fault current data, and calculations to determine the Plus Setting Multiplier (PSM), Time Multiplier Setting (TMS), and high set elements based on the minimum fault current values to achieve coordination. The settings are checked to ensure coordination with upstream and downstream protection.

Uploaded by

sherub wangdi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
636 views3 pages

Setting Calculation Protocol For IDMT Overcurrent Relay Settings

This document provides the calculation protocol for setting the IDMT overcurrent and earth fault relay settings for the protection of an outgoing feeder. It includes the feeder details, relay and CT data, fault current data, and calculations to determine the Plus Setting Multiplier (PSM), Time Multiplier Setting (TMS), and high set elements based on the minimum fault current values to achieve coordination. The settings are checked to ensure coordination with upstream and downstream protection.

Uploaded by

sherub wangdi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 3

ADDC Testing and Protection Section

Setting Calculation Protocol for IDMT Overcurrent Relay Settings


Station:

Contract:

Consultant:

Contractor:

Feeder ID: Outgoing Feeder (Typical)

Relay: Relay Type: Numerical Relay Model: Delta Relay Make: VATECH

CT Ratio Prim. Current Sec. Current Burden, VA Class Rct


CT Data:
600/400/1 100 1 15 - 10 5P15 -

Fault Current, If L-L Fault L-G Fault

Fault Data: Min. Fault Current, A 6975 699.83

Max. Fault Current, A

FAULT SETTING CALCULATION FOR IDMT O/C

General Data:

Overload Current: 75.6 (125% of Full load current of Protected Object)

PMS (Plug Multiplier Setting): 0.756

Curve Selected: Normal Inverse (NI)

Operating time at TMS 1, sec '=0.14/


1.48 sec .........Eq. 1
[(PSM)0.02 - 1]:

PSM (Plus Setting Multiplier):


'=[(Ifmin/Prim.Current) * (Sec.Rated 92.26 1.09 .........Eq. 2
Current/PMS)]

Assuming Prot. Op. time, sec:


0.1 sec
(0.3sec)

Grading Margin (0.3sec) 0.5 sec

Hence TMS: ('= (0.3+0) / (Result


0.406 .........Eq. 3
from Eq.1)

Final TMS set at: 0.5


Operating time at TMS 0.125, sec
0.739 sec
'=0.14*0.125/[(PSM)0.02 - 1]:
Operating time at TMS 0.2, sec
0.296 sec (for Sample)
'=0.14*0.2/[(PSM)0.02 - 1]:

PMS: 0.756

Adopted Settings: TMS: 0.5


High Set
10xIn
(I>>):
Is settings co-ordinated with downstream side: Yes/No

482415926.xls/IDMT OC-Outgoing 1/3


ADDC Testing and Protection Section

Is settings co-ordinated with upstream side: Yes/No

482415926.xls/IDMT OC-Outgoing 2/3


ADDC Testing and Protection Section

Setting Calculation Protocol for IDMT Earth Fault Relay Settings


Station:

Contract:

Consultant:

Contractor:

Feeder ID: Outgoing Feeder (Typical)

Relay: Relay Type: Numerical Relay Model: Delta Relay Make: VATECH

CT Ratio Prim. Current Sec. Current Burden, VA Class Rct


CT Data:
600/400/1 100 1 15 - 10 5P15 -

Fault Current, If L-L Fault L-G Fault

Fault Data: Min. Fault Current, A 6975 699.83

Max. Fault Current, A

FAULT SETTING CALCULATION FOR IDMT O/C

General Data:

Earth Fault Current: 0.189 (25% of OC PMS)

PMS (Plug Multiplier Setting): 0.189

Curve Selected: Normal Inverse (NI)

Operating time at TMS 1, sec '=0.14/


1.87 sec .........Eq. 1
[(PSM)0.02 - 1]:

PSM (Plus Setting Multiplier):


'=[(Ifmin/Prim.Current) * (Sec.Rated 37.03 1.07 .........Eq. 2
Current/PMS)]
Assuming Prot. Op. time, sec:
0.1 sec
(0.3sec)
Grading Margin (0.3sec) 0 sec
Hence TMS: ('= (0.3+0) / (Result
0.054 .........Eq. 3
from Eq.1)
Final TMS set at: 0.2
Operating time at TMS 0.2, sec
0.374 sec
'=0.14*0.2/[(PSM)0.02 - 1]:

PMS: 0.189

Adopted Settings: TMS: 0.2


High Set
8xIn
(I0>>):
Is settings co-ordinated with downstream side: Yes/No

Is settings co-ordinated with upstream side: Yes/No

482415926.xls/IDMT EF-Outgoing 3/3