Table of Relay Outputs With tYPE 1-2-3-4-13 (Variable Speed Control)
Table of Relay Outputs With tYPE 1-2-3-4-13 (Variable Speed Control)
Table of Relay Outputs With tYPE 1-2-3-4-13 (Variable Speed Control)
Lamp.
The lights situated at the bottom of the display show the state of the relay.
Table of relay Outputs with tYPE= 1-2-3-4-13 (Variable speed control)
Output relay N° Relay
HP54 SL 3.1
HEAT 0 1 2 3 4 4 step ventilation + thermoreg.
HEAT 1 0 0 0 0 0 5 Handbook
VENT 1 0 0 1 0 0 0 1
VENT 2 0 0 0 1 0 0 2 MAIN SETTINGS (Run Mode)
VENT 3 0 0 0 0 1 0 3
HEAT TEMPERATURE SETTING.
VENT 4 0 0 0 0 0 1 4
Press HEAT:
This message will be displayed instead of the
Table of relay Outputs with tYPE = 14 (On-Off regulation type)
°Set Heat temperature value .
Lamp. Output relays with tYPE = 14 (see COSt) N° Relay Press + or - to modify, press HEAT to exit.
HEAT 0 1 2 3 4
VENTILATION TEMPERATURE SETTING.
HEAT 1 0 0 0 0 0 5 Press VENT:
VENT 1 0 0 1 0 0 0 1 This message will be displayed instead of the
VENT 2 0 0 1 1 0 0 2 °Set Ventilation temperature value (start first step).
VENT 3 0 0 1 1 1 0 3 Press + or - to modify, press VENT to confirm.
VENT 4 0 0 1 1 1 1 4 At this point: this message will be displayed instead of the
Minimum Ventilation Step (*).
INSTALLATION Press + or - to modify, press VENT to confirm.
How to connect the line At this point: this message will be displayed instead of the
Connect 230V line on terminals L-N. Maximum Ventilation Step.
Protect supply with adequate fuse.
How to connect the sensors HP54 Press + or - to modify, press VENT to confirm.
COOL
Connect the provided sensor as shown in the
diagram. For remote connections use a COMMON (*) If the minimum speed is set to 0, this message appears
standard 0.5-square millimeter two-pole wire HEAT instead of the Set Shutter Running Time (seconds).
, taking great care over the connections, by Press + or - to modify, press VENT to confirm.
insulating and sealing the joins carefully. -O.C.-
is displayed when the temperature sensor wiring At this point: this message will be displayed instead of the
is open, -S.C.- is displayed when the
Shutter Dwell Time (seconds.).
temperature sensor wiring is short circuit.
Press + or - to modify, press VENT to confirm.
How to connect the contacts
SX TEMPER.
230V LINE *
Output contacts are N.O. (Normally At this point: this message will be displayed instead of the
COMMON
You can press ALARM for at least 2 seconds to exit and return to the Run Mode. If Minimum speed is programmed to 0
CONDIZIONATED
d.FAn V4 BY SP. - -
Mess. Valore Meaning Note (SP._ _=0), when the ventilation is off it is
d.HEA 0.2 ° °HEAT differential *1 possible to insert a cyclical operation of
minimum speed, composed of a turn-on V3 With tYPE = 13 :
rEL.1 0.0 ° ° Temperature set of step 1 referred to the vEnt set *1 time fans (t.on), by a switch-off time fans d.FAn
1.0 ° ° Temperature set of step 2 referred to the Step 1 start *1 V0 V4
rEL.2 (t.oF), and the selected speed during
rEL.3 1.0 ° ° Temperature set of step 3 referred to the Step 1 start *1 an’s shuttering operation (SP- -). V1 V3
V2
rEL.4 1.0 ° ° Temperature set of step 4 referred to the Step 1 start *1
d.FAn V2 V2
d.FAn 0.2 ° ° Ventilation differential *1 V3 V1
V1 V4 V0
r.COL 6.0 ° ° COOL setting shift referring to vEnt set *1 Heater mode ventilation
d.COL 0.2 ° ° COOL differential *1
tEnP =1 Temperature unit (=1: °C, =2: °F) t.on t.oF t.on t.of rEL.2 rEL.3 rEL.4
Option 13 permits Heater mode ventilation (low temperature = higt speed; in other options high d.HEA 0.2° 0.2°
temperature= high speed). HEAT ON MIN ON MAX ON
Option 14 permits On-Off regulation mode (in other condition regulation is for variable speed control).
MIN MAX
PRESET PROGRAMS (bootstrap) HEAT ALARM ALARM
This processor is already programmed with the following (variable) settings.
To return to these settings at any time you may:
HEAT OFF MIN OFF MAX OFF
Power off the processor, press MAX VENT key and keep it pressed giving power on: boot
message will be displayed (release now MAX VENT key).
HEAt AL._ _ AL.- -
HEAt = 20.0° vEnt = 25.0° SP._ _= 0 SP.- - = 4 AL._ _= 10.0° AL.- - = 40.0° AMB. TEMP. AMB. TEMP. AMB. TEMP.
t.on = 10" t.oF = 60" SP.-- = 0 The COSt values are shown in COSt Promagramming.