Armature Reaction: The Current in The Armature Produces A Flux
The document discusses armature reaction in generators. It can be summarized as:
1) Current flowing in the generator armature produces an magnetic field that interacts with the main field, called armature reaction.
2) The armature field has two effects - it demagnetizes the main field, reducing voltage, and cross-magnetizes, causing sparking at the brushes.
3) Shifting the brushes to align with the new flux direction caused by armature reaction introduces a demagnetizing component, further reducing the main field. Various methods are discussed to minimize armature reaction without shifting brushes.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
67 views21 pages
Armature Reaction: The Current in The Armature Produces A Flux
The document discusses armature reaction in generators. It can be summarized as:
1) Current flowing in the generator armature produces an magnetic field that interacts with the main field, called armature reaction.
2) The armature field has two effects - it demagnetizes the main field, reducing voltage, and cross-magnetizes, causing sparking at the brushes.
3) Shifting the brushes to align with the new flux direction caused by armature reaction introduces a demagnetizing component, further reducing the main field. Various methods are discussed to minimize armature reaction without shifting brushes.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 21
Armature reaction
The current in the armature produces a flux.
So, the interaction between this flux and the main field flux is called armature reaction. The armature magnetic field has two effects: (i) it demagnetizes or weakens the main flux which leads to reduced generated voltage, and (ii) it cross-magnetizes, which leads to the sparking at the brushes, or distorts it. When there is no load connected to the generator, the current in the armature conductors is zero. Under these conditions there is only one magnetic field in the generator, and that field is produced by the main- field poles of the generator. The main field is represented by an arrow, which indicates the direction of the magnetic flux from the north pole to south pole as shown in Fig. 6.1.
A load is now connected to the generator, and of course
current flow exists. The current to the load is the current in the armature conductors and is equal to the sum of the currents from the parallel paths in the armature. Consider Fig. 6.2, which allows the armature rotating in the magnetic field and the resulting armature current when a load is connected to the generator. When the current flows through a conductor a magnetic field is set up around the conductor as indicated in Fig. 6.2.
The flux from the conductors on
the left side of the armature and the flux from the conductors on the right side of the armature cause a resultant flux in the center of the armature that is downward in direction. This resultant flux can be represented by an arrow as indicated, noting that the arrow passes through both top and bottom brushes. There are now two fluxes inside the generator, one produced by the main field poles of the generator and the other by the current in the armature conductors. These two fluxes now combine to form a new resultant flux as shown in Fig. 6.3. This new resultant flux is not in the same direction as the original main field flux but runs from the tip of one of the poles, across the armature, to the tip of the other pole. The armature conductors are now cutting this new resultant flux that is not the same direction as the main field flux which conductors were originally cutting. The brushes are supposed to be located at the point of minimum flux, which of courses at right angles to the direction of the flux.
Since the brushes were at right angles to the main-field
flux, they certainly cannot be at right angles to the new resultant flux. With the brushes in their present location they will be short-circuiting coils in which there is a voltage induced, thereby producing sparking at the brushes, undue brushes wear, and other unfavorable conditions. Effect of Brush Shifting If the brushes are no longer at the points of minimum flux, or magnetic neutral, as the points of minimum flux are known, it might appear to be a simple solution to shift the brushes until they do fall on the magnetic neutral, and then the brushes will once again be at the points of minimum flux. It has just been seen that the direction of resultant flux depends upon both the flux from the main-field poles and the flux produces by the current in the armature conductors. The flux from the main-field poles is fairly constant and will remain constant even though the generator is supplying current to a load. Effect of Brush Shifting If the load current is small, the armature current will be small and the flux produced by the armature conductors will be small; hence the shift in the resultant flux will be small as compared with the main-field flux. The greater the current delivered by the generator, the greater the current in the armature conductors, and therefore the greater the flux produced by the armature conductors, ending with greater shift in the direction of the resultant flux. Hence if the brushes are to be moved to a new neutral position, the new position will depend upon the load. With the load on a generator constantly varying, it would be impossible to preset the position of the brushes and expect satisfactory result. Fig. 6.4 shows a new position of brushes at the minimum flux point. Referring Fig. 6.4, it is seen by Fleming’s right-hand rule that the conductors under the north pole carry current away from the observer and the conductors under the south pole carry current toward the observer.
The flux from these conductors is indicated on the
diagram, and of course the combined flux from all the conductors is still in a direction from the top brush to the bottom brush. But the flux from the armature is not at right angles to the flux from thee main-field poles. The effects of the armature flux in the new position of brushes is illustrated in Fig. 6.5. It is seen from Fig. 6.5 that there have two components of armature flux that are at right angles to each other. One component is at right angles to the main field, and because this component crosses the main-field flux, it is known as cross-magnetizing component of the armature flux. The second component is in the same plane as the main-field flux. The direction of this component is opposite to the direction of the main-field flux, with the result that it tends to reduce the effect of the main-field flux. This component of the armature flux is known as the demagnetizing component of the armature flux. It now appears that the shifting of the brushes has not improved the situation. In fact, it seems to have become worse. Before the brushes were shifted, the armature flux was at right angles to the main-field flux and therefore produced only a cross-magnetizing field. With the brushes shifted to the new position, there is still a cross-magnetizing field, some what reduced in magnitude, but in addition there is now a demagnetizing field which tends to reduce the main- field flux, resulting in a lower generated voltage. This demagnetizing component was obtained only after the brushes were shifted, and the brushes were shifted because of the change in direction of the resultant flux, which was due to the armature conductors carrying current. The application of some means to prevent the shift of the resultant flux would eliminate the necessity of shifting the brushes, and hence no demagnetizing field would be produced. Demagnetizing and Cross-magnetizing Conductors The exact conductors which produce these distorting and demagnetizing effects are shown in Fig. 27.6 where the brush axis has been given a forward lead of so as to lie along the new position of magnetic neutral axis (M. N. A). All conductors lying with in the angles AOC=BOD=2 at the top and bottom of the armature, are carrying current in such a direction as to send the flux through the armature from right to left. It is these conductors which act in direct opposition to the main-field and are hence called the demagnetizing armature conductors. Now consider the remaining armature conductors lying between angles AOD and COB as shown in Fig. 27.7. These conductors carry current in such a direction as to produce a combined flux pointing at right angles to the main-field flux. This results in distortion of the main field. Hence, these conductors are known as cross-magnetizing conductors and constitute distorting ampere conductors. Without shifting the brush the armature effect can be minimized by using the following methods: (a) High-Reluctance Pole Tips (b) Horizontal Slots in Main-Field Pole (c) Compensating Windings
High-Reluctance Pole Tips
It can be seen that the flux from the current in the armature conductors causes the main-field flux to shift from the center of the main-field poles to the tips of the poles. Applying the knowledge that most of the flux flows the path of least reluctance, poles are designed where the reluctance at the ends of the poles is greater than the reluctance at the center. The variation of reluctance is obtained by constructing the poles that the greater the distance from the center of the pole, the greater the air gap between the pole and the armature. The greater the air gap, the greater the reluctance. With no current in the armature conductors, the flux will be concentrated at the center of the pole, and when current flows in the armature conductors, the flux will tend to shift the end of the pole. The air gap will offer an increase in reluctance to the flux as it moves from the center of the pole, thereby tending to keep the flux in the same original position.
The shape of this pole is shown in Fig. 6.6.
The reluctance of the center of pole can be reduced by
using lamination. Horizontal Slots in Main-Field Pole The high reluctance pole-tip construction reduced the effects of armature reaction by not allowing the flux to shift. The shift in the resultant flux was caused by the armature flux. If the armature flux could be reduced to a negligible value, then its cross-magnetizing effect upon the main- field flux would be small and the brushes would not have to be shifted. Fig. 6.8 shows that part of the path of the magnetic flux is through the field poles. By cutting horizontal slots in the poles, several air gaps are introduced in the path of the flux. These slots increase the reluctance to the armature flux while having very little effect on the main-field flux. The armature is materially reduced, and the brushes need not be shifted. Compensating Windings The compensating windings are placed in the pole faces of the filed pole can run parallel to the armature conductors. A connection is made from one of the brushes to one end of this winding, so that current from armature must first pass through the winding before going to the load. The direction of current through the winding is opposite to that of the current in the armature conductors under that pole.
The location of the compensating winding
and of the connection to the winding is shown in Fig. 27.8. Figure 27.8 indicates that the current in the armature conductors located under the north pole carry current away from the observer; therefore the direction of current flowing in that part of the compensating winding situated in the north pole is toward the observer. Since the current in the compensating winding is opposite in direction to the current in the armature conductors, the flux produced by the current in the compensating winding will be opposite in direction to the armature flux. The compensating flux, being opposite in direction to the armature flux, tends to cancel the armature flux. If the armature current increase, the compensating current increases, so that the armature flux is canceled for al load conditions.