Analogue Addressable Control Panel: Product Data

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

PS1278.

3 11/04/2005 PAGE 1/2


ZP3 ANALOGUE ADDRESSABLE CONTROL PANEL Product Data

PS1278.3
The Ziton ZP3 is an analogue addressable fire
detection and alarm system, based upon advanced
technology developed to provide maximum
flexibility through a comprehensive range of
modular hardware, supported by highly
configurable software.
Advanced panel design, combined with high
sensitivity smoke and fire sensing, enables ZP3 not
only to identify and disregard conditions, which
would result in false or unwanted alarms - but to
recognise real fires sooner.
Scaleable in every aspect, the ZP3 system offers
tailor made engineered solutions for all
applications, from single panel systems to large
multi panel networks. Modular design backed by
powerful software enables ZP3 systems to be
configured exactly to the needs of any commercial
or industrial site.
Control panels are available in 1, 2, and 4 loop
sizes, accommodating up to 508 sensing
addresses. For sites requiring above four loops,
panels can be networked together to form systems
capable of controlling over 32000 devices from 64
control panels.
Up to 127 line devices (sensors, callpoints,
sounders or interface units) can be connected to
each of the control panel loops. All loop devices
incorporate switch settings enabling them to be
assigned a unique address, the location of which is
ZP3
pinpointed and polled by the panel every two
seconds. Variations in the sensors environment Analogue Addressable
caused by increases of temperature or products of
combustion, are reported to the panel, where they
are processed and compared to known fire data,
Control Panel
prior to any alarm output being activated.
Constant communication between control panel
and sensor, enables ZP3 to provide a wide range of • ZP analogue addressable system
user facilities including pre alarm, constant • Complies fully with EN 54 parts 2 and 4
sensitivity adjustment and service and near service
listings for all sensor types. • Advanced sensing techniques

Software flexibility enables facilities such as alarm • Extensive networking ability


organisation, evacuation procedures and complex • Loop powered sounders
cause and effect requirements to be easily
programmed into any system.
All customer and site data is held in non volatile
flash memory, ensuring both ease of initial system
data input and subsequent on site amendments
and modifications should they occur.
PS1278.3 11/04/2005 PAGE 2/2
ZP3 ANALOGUE ADDRESSABLE CONTROL PANEL Product Data

Features
The ZP3 panel supports, fire and non fire functions, loop powered sounders, remote control and remote
display panels, up to 128 zones with 768 programmable inputs and outputs per panel, all covered by
comprehensive programming facilities.
ZP3 'active' protocol provides complete reliability at all times. Systems feature the continuous monitoring of
wiring and sensors, corrupt data detection and disconnection of faulty or corrupt loop sections.
Built in system diagnostics improves levels of maintenance and reduces service costs. Included are remote
diagnostic support (optional), sensor and sounder testing, statistics and status reports, sensor contamination
and near service reports and 'one man - zone walk test'

Other features include -


Ease of Operation - user interface incorporating Radio Loop Interface - full analogue system facilities
both large, 160 character LCD display and via wireless interface enables equipment to be sited
traditional LED indicators provide clear, easy to where access is difficult or cable runs impossible.
understand information at all levels.
Automatic contamination adjustment for each
Service and near service facility - compensates for sensor - maintains constant sensitivity.
sensitivity drifting over time period listing sensors
Intelligent loop isolation - maintains system integrity
that are due for cleaning and others that may be
against partial or full short circuit faults and
approaching the service condition.
monitors for data corruption.
Sophisticated alarm verification - offers two time
Self test sounder - loop wired sounder range
integration levels for each address, selectable to suit
features built in microphone circuit to automatically
sensor environment.
test sounder output by loop, zone or individual unit.
Automatic Self Test - all sensors are functionally
Password protection - provides multilevel access,
tested every 24 hours ensuring full functionality and
complying with BS EN54 Part 2.
correct calibration at all times.
Event Log - all system events for example alarms,
Day / night control - separate programmes for day
faults and disablements are held in the control
and night operation. Different sensor sensitivity,
panel memory. Up to 1000 events can be displayed
alarm selection, alarm delays and fire brigade
or printed in order.
response can be configured.

Remote Manned Centre Wired analogue sensors/devices


Radio analogue sensors/devices
Thermal sensors
Smoke sensors
Combination sensors
High-sensitivity aspirating sensors
Volumetric beam sensors
Loop sounders
Loop relay
Loop interface units
Loop isolators
Callpoints
Local and remote I/O
Data ports
To other To other Remote display units and mimics
ZP3 Panels ZP-NET ZP3 Panels Colourgraphic computers and printers
PS1278.3 11/04/2005 PAGE 3/2
ZP3 ANALOGUE ADDRESSABLE CONTROL PANEL Product Data

Networking and Software Support Packages


Optional facilities
An onboard printer module together with a series of facility boards can be added to the standard panel to
extend any system up to a maximum of 768 programmable inputs and outputs.

Networking
The ZP3 peer to peer network enables up to 64 stand alone ZP3 control panels to be integrated into a single
co-coordinated fire detection and alarm system. The network facility features system wide alarm reporting, co-
coordinated evacuation and cross panel cause and effect operation, making it ideal for large systems and
multi building sites.
System control and graphics display computers can be included on the network. Display and control functions
are fully programmable and alarms and events, including zone, location and individual address detail, can be
displayed from the system of origin to any other networked panel. In addition alarms from any control panel
can be programmed to operate sounders and outputs on panels across the network.
One or more control panels can be assigned as system masters, displaying complete system status. System
control and graphics display computers also show complete network status and allow control functions to be
operated remotely.

Maestro
Designed specifically for connection to ZP3 fire detection systems Maestro is a P.C. based monitoring system,
providing the user with a complete system overview.
Graphically presenting alarms and events, Maestro provides system control, colour graphics and event
logging with archive facilities. Running on Windows NT, the software can be used either with stand alone
control panels or as an integrated network facility.

Planner
Planner software package enables system designers to fully configure ZP3 systems either directly into the panel
via a PC, or off site for subsequent downloading at the system commissioning stage. The package checks that
equipment parameters entered are within the ranges allowed and prompts the user on allowable options.

Remote diagnostics
Designed to provide the user with full facilities for both fault diagnosis and system configuration off site, the
remote diagnostics hardware and software package makes information available to service personnel, prior to
visiting site for remedial action or maintenance activity.
PS1278.3 11/04/2005 PAGE 4/2
ZP3 ANALOGUE ADDRESSABLE CONTROL PANEL Product Data
Specification
Model No Indicators
ZP3 - 4L 4 loop panel System status - 87 light emitting diodes
ZP3 - 2L 2 loop panel Text display - 4 line, 160 character, LCD (back lit)
ZP3 - 1L 1 loop panel Optional printer
Description 24 character (built into front door)
Analogue addressable fire detection and alarm control panel Software
Specification Firmware and site configuration programming - Flash memory
Control panel EN 54 Pt 2 Communications ports:
Integral power supply unit EN 54 Pt 4 Z-Port 1 Planner RS 232
Meets recommendations in systems to BS 5839 Pt1 Z-Port 2 Network RS 485 / fibre optic
EMC Repeater Panel
CE marked (EEC89/336) ZP3 RDUB1-24 remote display unit
Configuration Selectable features
Loops 1, 2, and 4. Common sounders Coincidence alarm
Addresses Up to 127 per loop RMC fire RMC fault
Compatibility Zone walk test Control output
All ZP analogue addressable equipment Output delays Alarm counter
Mounting Sounder silence delay Alarm verification
Surface or recessed (with ZP3 flushing collar) Standby batteries
Power Requirements 2 x 12 volt sealed lead acid
Panel (Quiescent at 24 VDC) 4 loops 420mA Up to 28 Ah (Panasonic) accommodated inside panel enclosure
Load of panel only, excluding any external devices Temperature range
Panel (Alarm at 24 VDC) 820mA -5OC to +40OC
25% of zones in alarm Humidity range
Per Loop (Quiescent at 24 VDC) 70mA 10% to 90% RH (non condensing)
Fully loaded loop, with 127 ZP devices, not in alarm Environmental
Power Supply IP 30 (indoor applications)
Input 230 Vac 50 Hz + or -10% Construction
0.75 Amps Enclosure - Back box and hinged door - sheet steel
Optional input DC 24 to 50 volts Dimensions
load dependent 540 mm (H) x 410 mm (W) x 137 mm (D)
User output 24 Vdc (nominal) up to 3.0 Amps Overall dimensions when mounted in flushing collar:
Battery charge 28.2 Vdc 1.2 Amps 623 mm (H) x 512 mm (W)
Wiring 15 mm projection when recessed
2 core screened (to local codes and standards) Colour
Switched outputs (standard) Pantone 428c Cool grey
Sounder circuits (programmable) 2 x dual (monitored) Weight
Fire (common) 1 volt free N/O or N/C 11.0 Kg with printer (batteries excluded)
(software set)
Fault (common) 1 volt free N/O or N/C
(software set)
Remote manned centre (fire) 1 monitored
Remote manned centre (fault) 1 monitored
Monitoring
Loop wiring Open and short circuit fault, earth leakage,
sensor removed and wrong device type
Switched outputs & inputs (optional & programmable)
Non loop devices:
Sounder circuits
Relay outputs Total max
Transistor outputs 768
Monitoring inputs

Ziton Copyright © Ziton


8 Newmarket Court Chippenham Drive Kingston Milton Keynes MK 10 0AQ United Kingdom Ziton reserves the right to change specifications without notice in order to
Telephone +44 (0) 1908 281981 Fax +44 (0) 1908 282554 email [email protected] improve products or manufacturing methods. Although every effort is made to
avoid errors, we reserve the right to correct typographical, photographic, clerical
Ziton (Pty) Ltd or printing errors.
Ziton House 555 Voortrekker Road Maitland 7405 PO Box 181 Maitland 7404 South Africa
Telephone +27 (0)21 506 6000 Fax +27 (0)21 506 6100 email [email protected]

501-127800-0-03, Published April 2005

You might also like