Bored Pile Capacity

Grade, fcu 35 N/mm² Concrete Density 25


Factor, γ 0.25 Pile Length (m) 30
Cover 75 mm
4 0 200

Working Cap Workign Cap Safe Bearing


Min Pile cap d Socket Length
Diameter (mm) Perimeter (mm) A (mm2) γ*fcu*A (kN) -selfweight(kN) Cap
(mm) (safe skin 200kPA)
@30m ignored
500 1571 196350 1718 1571 410 0 5.5
600 1885 282743 2474 2262 492 0 6.6
750 2356 441786 3866 3534 615 0 8.2
800 2513 502655 4398 4021 656 0 8.8
900 2827 636173 5567 5089 738 0 9.8
1000 3142 785398 6872 6283 820 0 10.9
1200 3770 1130973 9896 9048 984 0 13.1
1350 4241 1431388 12525 11451 1107 0 14.8
1500 4712 1767146 15463 14137 1230 0 16.4
1800 5655 2544690 22266 20358 1477 0 19.7
2000 6283 3141593 27489 25133 1641 0 21.9

Reinforcement
Min Bar (NOS)
Diameter (mm) Link (mm) Rebar (mm) Perimeter* (mm) Proposed NOS 0.40% Diameter Required
Required
500 10 12 999 6.7 8 785 11.2
600 10 12 1313 8.8 10 1131 12.0
750 10 16 1772 11.8 12 1767 13.7
800 10 16 1929 12.9 14 2011 13.5
900 10 32 2193 14.6 16 2545 14.2
1000 10 32 2507 16.7 18 3142 14.9
1200 10 25 3157 21.0 22 4524 16.2
1350 10 25 3629 24.2 26 5726 16.7
1500 10 20 4115 27.4 28 7069 17.9
1800 10 20 5058 33.7 34 10179 19.5
2000 10 20 5686 37.9 40 12566 20.0
*Perimeter at centre of main reinforcement

Proposed Test Nos

Bi-Dir (with
instrument - 4 (1 for each size)
vibration
strain gauge for
skin friction
reading)
PDA 4 (1 for each size)
PIT (Sonic Logging) 10
Point Load Test 30

Cost
PDA cost on BP RM/nos
1.2 5000
1.35 5500
1.8 7000

Bi-dir mobilisatio 5000

Instrumented Bi-dir
4 instrument/late 5000 around 4 Nos x 1.2k/instrument

Bi-dir cost (test RM/t


<1000 80
1000-2000 75
2000-3000 70
3000 65

Test & Monitoring 5000

PIT 650 M88


Point Load Test 150
Sonic Logging 6000 from Semporna
Spring H/V 5%

mm mm
10 25

Spring Vertical Spring


Horizontal H/V
kN/m
kN/m
157080 3142 0.02
226195 4524 0.02
353429 7069 0.02
402124 8042 0.02
508938 10179 0.02
628319 12566 0.02
904779 18096 0.02
1145111 22902 0.02
1413717 28274 0.02
2035752 40715 0.02
2513274 50265 0.02

Based on Min M (e=100) Asprov (mm2)

905
1131
2413
2815
2.45% 12868 15616
1.66% 14476 13020
0.66% 10799 7440
0.64% 12763 9192
0.40% 8796
0.40% 10681
0.40% 12566
Bored Pile Capacity
Grade, fcu 40 N/mm²
Factor, γ 0.25
Cover 75 mm
3000 100
Adopted Safe Bearing
γ*fcu*A (kN) Socket Length
Diameter (mm) Perimeter (mm) A (mm2) Workign Load Cap
(skin 100kPA)
(kN) (3000kPA)
500 1571 196350 1963 1950 589 8.7
600 1885 282743 2827 2800 848 10.5
750 2356 441786 4418 4400 1325 13.1
800 2513 502655 5027 5000 1508 14.0
900 2827 636173 6362 6350 1909 15.8
1000 3142 785398 7854 7850 2356 17.5
1200 3770 1130973 11310 11300 3393 21.0
1350 4241 1431388 14314 14300 4294 23.6
1500 4712 1767146 17671 17600 5301 26.3
1800 5655 2544690 25447 25400 7634 31.5
2000 6283 3141593 31416 31400 9425 35.0

Reinforcement
Min Bar (NOS)
Diameter (mm) Link (mm) Rebar (mm) Perimeter* (mm) Proposed NOS 0.40% Diameter Required
Required
500 10 12 999 6.7 8 785 11.2
600 10 12 1313 8.8 10 1131 12.0
750 10 16 1772 11.8 12 1767 13.7
800 10 16 1929 12.9 14 2011 13.5
900 10 16 2243 15.0 16 2545 14.2
1000 10 16 2557 17.0 18 3142 14.9
1200 10 20 3173 21.2 22 4524 16.2
1350 10 20 3644 24.3 26 5726 16.7
1500 10 20 4115 27.4 28 7069 17.9
1800 10 20 5058 33.7 34 10179 19.5
2000 10 20 5686 37.9 40 12566 20.0
*Perimeter at centre of main reinforcement
Asprov (mm2)

905
1131
2413
2815
3217
3619
6912
8168
8796
10681
12566
Bored Pile Capacity
Grade, fcu 40 N/mm²
Factor, γ 0.25
Cover 75 mm

Adopted
Diameter (mm) Perimeter (mm) A (mm2) γ*fcu*A (kN) Workign Load
(kN)
500 1571 196350 1963 1950
600 1885 282743 2827 2800
750 2356 441786 4418 4400
800 2513 502655 5027 5000
900 2827 636173 6362 6350
1000 3142 785398 7854 7850
1200 3770 1130973 11310 11300
1350 4241 1431388 14314 14300
1500 4712 1767146 17671 17600
1800 5655 2544690 25447 25400
2000 6283 3141593 31416 31400

Reinforcement
Min Bar (NOS) Asprov (mm2)
Diameter (mm) Link (mm) Rebar (mm) Perimeter* (mm) Proposed NOS 0.40% Diameter Required
Required
500 10 12 999 6.7 8 785 11.2 905
600 10 12 1313 8.8 10 1131 12.0 1131
750 10 16 1772 11.8 12 1767 13.7 2413
800 10 16 1929 12.9 14 2011 13.5 2815
900 10 16 2243 15.0 16 2545 14.2 3217
1000 10 16 2557 17.0 18 3142 14.9 3619
1200 10 20 3173 21.2 22 4524 16.2 6912
1350 10 20 3644 24.3 26 5726 16.7 8168
1500 10 20 4115 27.4 28 7069 17.9 8796
1800 10 20 5058 33.7 34 10179 19.5 10681
2000 10 20 5686 37.9 40 12566 20.0 12566
*Perimeter at centre of main reinforcement
Bored Pile Capacity
Grade, fcu 40 N/mm²
Factor, γ 0.25
Cover 75 mm

Adopted
Diameter (mm) Perimeter (mm) A (mm2) γ*fcu*A (kN) Workign Load
(kN)
500 1571 196350 1963 1950
600 1885 282743 2827 2800
750 2356 441786 4418 4400
800 2513 502655 5027 5000
900 2827 636173 6362 6350
1000 3142 785398 7854 7850
1200 3770 1130973 11310 11300
1350 4241 1431388 14314 14300
1500 4712 1767146 17671 17600
1800 5655 2544690 25447 25000
2000 6283 3141593 31416 31000

Reinforcement
Min Bar (NOS) Asprov (mm2)
Diameter (mm) Link (mm) Rebar (mm) Perimeter* (mm) Proposed NOS 0.40% Diameter Required
Required
500 8 12 1012 6.7 8 785 11.2 905
600 8 12 1326 8.8 10 1131 12.0 1131
750 8 16 1784 11.9 12 1767 13.7 2413
800 8 16 1942 12.9 14 2011 13.5 2815
900 8 16 2256 15.0 16 2545 14.2 3217
1000 8 16 2570 17.1 18 3142 14.9 3619
1200 8 20 3186 21.2 22 4524 16.2 6912
1350 8 20 3657 24.4 26 5726 16.7 8168
1500 8 20 4128 27.5 28 7069 17.9 8796
*Perimeter at centre of main reinforcement