Approved Catalog A09-In November 2016

Download as pdf or txt
Download as pdf or txt
You are on page 1of 60

Axial Flow Fans

- Direct Driven
- Belt Driven

A09-IN
#
Wolter Ventilators India Pvt. Ltd. certifies that the
series AXV shown herein are licensed to bear the
AMCA Seal. The ratings shown are based on tests
and procedures performed in accordance with AMCA
Publication 211 and AMCA Publication 311 and
comply with the requirements of the AMCA Certified
Ratings Program.
Table of Content

Contents
Page 1

Fan Type Code


Page 2

Design Features
Page 2

Fan Selection and Installation


Page 4

Selection Sample
Page 4

AMCA FEG Rating


Page 5

Fan Performance Curves - 50Hz


Page 6~26

AMCA FEG Rating


Page 27

Fan Performance Curves - 60Hz


Page 28~48

Dimensions
Page 49~51

Accessories
Page 52

Sound Information
Page 53~55

Tubular sound attenuator for AXV


Page 56~57
Subject to change without prior notice.

A09-IN V2016/November 1
Axial Flow Fans AXV
Technical information
Fan type code

AXV 450-26° LH100 -2 AL SU 400°C/2Std


Smoke extract fan
400°C/120min, 300°C/120min

Air flow and form of running


S, D, SU, SO, DU, DO

Material of blade

number of poles

Casing version
SH = Short-cased
LH1 = Long-cased

Pitch angle

AXV: impeller-Ø
355...2800

Axial impeller blade type

Design features
Types and duty range
Wolter Axial flow fans can be used for various applications in ventilation and Casing LH
process air technology. Standard diameters range from 355 to 2800mm, with
airflow rates of up to 290 m³/s at static pressure increases of up to 1600 Pa.
Higher pressures can be achieved by using contra-rotating multi-stage fans.
Belt driven fans are designed for application that required motor to be iso-
lated from the airstreams.
Smoke spill operation
The AXV range of axial fans is designed and tested to operate at standard
temperatures as well as at elevated temperatures of 300°C for 60 (F300)
and 120 minutes and 400°C for at least 120 minutes (F400), according to
DIN EN ISO 12101, part 3. The following fan curves are valid for standard
temperatures and 300°/ 60 (F300) and 120 minutes operation. To select a Casing SH
fan for 400°C/120 minutes operation, please contact our technical support.
Casing
Fan casings are of hot-dip galvanized finishing. Flanges are rolled, the pitch
circles of holes are in accordance with DIN 24 154, R2.
> LH - Long-cased axial fan, with external terminal box
D DU DO
> SH - Short-cased axial fan
If motors require additional lubrication, tubes and grease-nipples are fitted
to the outside of the fan casing. An inspection hole, closed by a rubber plug,
allows technical personnel to view the direction of impeller rotation.
Impellers
AXV impellers, hubs and blades are made off pressure-cast aluminium alloy,
the aerodynamic profile guarantees high efficiency and low noise levels.
The blade pitch angle is adjustableduring standstill. The variable number
of blades the expands the performance range.
Motor
Wolter uses closed squirrel cage motors according to IEC 34, if required
also in accordance with EPACT. Standard motors are class F with IP 55
protection class. Multi speed versions with 2 or 3 speeds (Dahlander circuit or S SU SO
separate windings) are also available, as well as explosion-proof versions or
specific industrial executions such as marine-type fans. The motor bearings
have a L 10 life.
Forms of running
Wolter AXV axial flow fans are available for all forms of running. The right
chart shows all standard forms of running. Please indicate the required
configuration when ordering. Without specific instructions, fans will be
delivered in configuration S. Arrows outside the fan casing indicates the
correct direction of rotation and airflow.
Form D, DU and DO are not licensed by AMCA International.

2 A09-IN V2016/November
AXV DD

Fan performance curves


AXV BD !"
to suit the actual site condition. Belt driven fans are used for applications
to extract more heavily polluted air i.e. presence of corrosive or hazardous
The performance curves for these fan types have been established in fumes, or dirt-laden, moist air or hot air from professional kitchens. Various
mounting position D (according to AMCA 210, duct connected to inlet and mounting positions are illustrated.
outlet sides) and represent the total pressure increase Dpt as a function of
the volume flow. The dynamic pressure pd2 is related to the flange cross- Ordering designations
sectional area at the of the fan.
When ordering, please provide the following information:
Sound levels > fan type code (see above), casing version and form of running
The ascertaining of the sound level follows the Reverberant Room Method > duty required at standard air temperature
in accordance to AMCA 300. The A-weighted sound power levels is shown (air volume in m³/h at static pressure in Pa)
on the performance curves. > motor power rating in kW
Belt driven design > electrical supply
> required ancillary equipment
Belt driven fan with single / dual motors can be mounted in various positions

0 deg

Setups
315 deg 45 deg

Setups 270 deg

Nozzles
90 deg

225 deg 135 deg


Motor Mounting Nozzles
at Zero Position 180 deg
Motor Mounting Position - Specify in degree

Test Setups
Nozzles

Test Fan
Test Fan Auxilliary Fan
Settling
means

Settling
ISO 5801 Figure 73b means

AMCA 210 Figure 12 Settling


means

Outlet
5801chamber
AMCA 210 Figure 12

ISO Figure 73b ISO 5801 Figure 73b

ISO 5801 Figure 73b


A09-IN V2016/November AMCA
AMCA 210210 Figure
Figure 12 12 3

Outlet chamber
Axial Flow Fans AXV
Technical information
Fan selection and installation
Fan selection
Please select fans according to the nearest performance curve above
the required duty point. The middle range of each fan curve is the area
of highest efficiency. Do not select fans at the upper end of the fan
curve, as this might cause the fan to work in stall. In order to avoid motor
overloading, please select motors according to the peak power of the
respective performance curve. Please refer to the selection example
on the following page. Bad 1 Right

Fan installation
When installing the fan, please consider the following instructions:
> Fans with free inlet and outlet should be installed with an unobstructed duct length min. 1xØ
distance of at least 1,5 x fan diameter on suction and pressure sides.
Fans should have a bellmouth on the inlet side in order to assure optimal
incoming flow. A diffusor mounted on the pressure side will increase
efficiency.
> When installing fans in a ducted system, adequate distance to other
structural parts such as bends, filters and silencers should be provided Wrong 2 Right
for. A sharp bond radius of the duct near the suction or pressure side
of the fan is to be avoided. Flexible connections are to be installed in
a way that does not obstruct the outlet cross section of the fan (see
following page).

Selection example Wrong 3 Right


Required duty point
>> Volume flow : 5.000 m3/h
>> Static pressure: 110 Pa
>>

In order to calculate the total pressure, please add velocity pressure 1,5 x D
to static pressure (30 Pa dynamic pressure + 110 Pa static pressure
= 140 Pa total pressure)
>> Fan speed: 1.440 1/min (4-pole)
Using the fan curve Wrong 4 Right
Having chosen a fan with adequate performance range for the required
duty point, plot volume flow and pressure.

!"
At the point of intersection, the following data can be read:
>> Motor speed or number of poles 1.440 1/min - 4-pole Performance
Curve AXV 500, 50 Hz
>> Pitch angle: 18 degrees 0.8
�������������������

645004, AXV-AL 500, 2880, 1440, 960


6
>> FEG Rating: FEG71 (see page5) 0.2

>> Inlet sound power level: 80 dB(A) 0.6


30°
32 °

0.15 4 28°
26°
0.4 24°
0.1 22°
20°
2
16° 18°
0.2 14°
Calculation of motor power: 0.05

10°
12° ������������3

250 1000
There are two possibilities to calculate the motor power:
Total pressure pt [PA]

1) Calculation of absorbed power by using the fan curve in duty point: 100
k

0,338 kW 200 800 m

Motor power: 0,37 kW 80


a
e

2) Calculation according to peak absorbed power, see table below the


fan curve: 0,366 kW 150 600
f
60 b

Motor power: 0,37 kW n

32 °
g
100 400 30°

The given peak absorbed power is the maximum shaft absorbed power 40
c
28°

over the whole pitch angle curve in.


26°
24°
22°
50 200 h 20°
20
18 °
16°
14° Lwi(A) a b c d e f g h j k m n
d 12° �� ��� ��� �� 99 ��� 99 99 ��� ��� ��� ��� ��� Speed
Pd 10° �� �� �� �� �� �� �� �� �� �� �� ��

�� [min-1]
�� �� �� �� �� �� �� �� �� �� �� �� ��
0 0 0
2500 5000 7500 10000 12500 15000 17500 20000 2880
2880 1/min 2-pol
1 1.5 2 2.5 3 3.5 4 4.5 5 5.5

1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 1440
1440 1/min 4-pol
0.5 0.75 1 1.25 1.5 1.75 2 2.25 2.5 2.75

1000 2000 3000 4000 5000 6000 700 960


960 1/min
0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 6-pol
.
������������ [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min-1] 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
��� ����� ����� ����� ����� ����� ����� ����� ����� ����� ����� ����� ����� ����� � � � �
motor ����
����� ����� ����� ����� ����� ����� ����� ����� ����� ����� ����� ����� ����� ����� � � � �
motor ���� ���� ����
���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ���� � � � �
motor ��� 3 4 ��� ���

��������������������������������������������������������������������������� �������������������������������������������������������������������������������
��� ���� ������������� ����� �� �� ������� ������� ������� �������� ������������ �������� ��� ��������� ����� ������� ������ ���� ���� ������ ����� ������ ������ ������� ���� �������������
��������������������������������������������������������������������������������� ����������������������������������������������������������������������������������������

A09 V2013/November ��

4 A09-IN V2016/November
AMCA - FEG rating
Fan Efficiency
AXV DD
Grade - AXV
AXV BD !"
Certified FEGs are determined in accordance with AMCA 205-12 Energy Efficiency Classification
for fans. In conjunction with AMCA 211-13 (Rev. 2015) Certified Ratings Program, Product Rating
Manual for Fan Air Performance. This classification is based on fan peak (optimum) total efficiency
for a given fan speed, fan size and application category. For the purpose of energy classification,
the peak efficiency can be determined at a speed not higher than the maximum design speed of
the fan.

The AMCA Certified Ratings Seal applies to the Fan Efficiency Grade (FEG) for AXV series Axial
Fan model AXV 355 to AXV 2800 as shown in the table below.

Fan Fan Fan Fan Fan Fan


Fan Fan
Speed Outlet Area Efficiency Speed Outlet Area Efficiency
Model No. Model No.
(rpm) (m2) Grades (FEG) (rpm) (m2) Grade (FEG)
AXV 355 2880/1440/960 0,1012 FEG63 AXV 1250 1440/960/720 1,2272 FEG71
AXV 400 2880/1440/960 0,1269 FEG67 AXV 1400 960/720/576 1,5504 FEG75
AXV 450 2880/1440/960 0,1590 FEG63 AXV 1600 960/720/576 1,9981 FEG67
AXV 500 2880/1440/960 0,2003 FEG71 AXV 1800 960/720/576 2,5588 FEG75
AXV 560 2880/1440/960 0,2516 FEG67 AXV 2000 960/720/576 3,1573 FEG75
AXV 630 2880/1440/960 0,3167 FEG63 AXV 2200 720/576/480 3,8186 FEG75
AXV 710 1440/960/720 0,3982 FEG67 AXV 2400 720/576/480 4,5428 FEG75
AXV 800 1440/960/720 0,5001 FEG67 AXV 2500 720/576/480 4,9284 FEG75
AXV 900 1440/960/720 0,6333 FEG63 AXV 2600 720/576/480 5,3297 FEG75
AXV 1000 1440/960/720 0,7980 FEG71 AXV 2800 720/576/480 6,1795 FEG75
AXV 1120 1440/960/720 0,9978 FEG71

90
FEG90

FEG85
80
FEG80

FEG75
Fan Peak Total Efficiency (%)

70 FEG71
FEG67
FEG63
60
FEG60
FEG56
FEG53
50 FEG50

40

30
Fan sizes in preferred numbers
125160 200 250 315 355 400 450 500 560 630 710 800 900 1000
20
0 100 200 300 400 500 600 700 800 900 1000 1100
Fan size (mm)

A09-IN V2016/November 5
Notes:
AbsorbedPower [kW]
power(kw)
Performance
Curve
0.2
1.5
645024, AXV-AL 355, 2880, 1440, 960
AXV 355, 50 Hz !" Hub: 150-7

40°
38°
0.15 36°
Absorbed

0.04 34°
1 32°
30°
0.1 28°

24° 26°
22°
0.02 20°
18°
0.5 14°
16°
12°
0.05 10 °
ρ = 1,2 kg/m3

125 500
[PA]
∆p(Pa)

h
t
Pressure

50
pressure

j
d
Total

100 400
Total

k
e
40 a

m
75 300 f
40°
30 38°
b
36°
34°
50 200 32°
20 30°
g 28°
26°
24°
25 100 22°
10 20°
18°
16° Lwi(A) a b c d e f g h j k m n
c 14° 2P 96 93 93 98 103 103 104 100 104 105 106 - Speed
Pd 12°
10° 4P 75 74 74 77 81 82 83 79 83 84 84 - [min-1]
6P 62 62 62 65 68 69 70 67 70 71 71 -
0 0 0
1000 2000 3000 4000 5000 6000 7000 8000 2880
2880 1/min 2-pol
0.5 0.75 1 1.25 1.5 1.75 2 2.25

500 1000 1500 2000 2500 3000 3500 4000 1440


1440 1/min 4-pol
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1

500 750 1000 1250 1500 1750 2000 2250 2500 2750 960
960 1/min
0.1 0.2 0.3 0.4 0.5 0.6 0.7 6-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
960 - 0,018 0,020 0,022 0,024 0,026 0,028 0,031 0,033 0,035 0,038 0,041 0,044 0,047 0,050 0,053 0,056
motor 0,37
1440 - 0,061 0,068 0,075 0,082 0,089 0,096 0,103 0,110 0,117 0,127 0,137 0,148 0,158 0,169 0,180 0,190
motor 0,37
2880 - 0,488 0,544 0,600 0,656 0,712 0,768 0,824 0,880 0,936 1,01 1,10 1,18 1,267 1,352 1,44 1,52
motor 0,55 0,75 1,1 1,5 2,2
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

6 A09-IN V2016/November
AbsorbedPower [kW]
power (kw)
Performance
Curve
0.3
2.5
AXV 400, 50 Hz
645023, AXV-AL 400-7, 2880, 1440, 960
!" Hub: 150-7

0.08 40°
0.25 2
38°
Absorbed

36°
0.06 0.2
1.5 34°
32°
0.15
0.04 30°
1
28°
0.1
22° 24° 26°
0.02 18° 20°
0.5 14° 16° ρ = 1,2 kg/m3
0.05 10° 12°
[PA]
∆pt(Pa)

g
60
Pressure

h
pressure

125 500
j
Total
Total

50

100 400
k
d
40 a 40°

38°
75 300 e
36°
30
34°
b
32°

50 200 30°
20 f 28°
26°
24°
22°
25 100 20°
10 18°
16°
c 14° Lwi(A) a b c d e f g h j k m n
Pd 12° 2P 100 97 93 98 97 98 99 98 99 98 - - Speed
10° 4P 79 79 75 79 78 79 80 80 80 81 - - [min-1]
6P 70 68 65 69 68 69 70 69 69 71 - -
0 0 0
2000 4000 6000 8000 10000 2880
2880 1/min 2-pol
0.5 1 1.5 2 2.5 3

1000 2000 3000 4000 5000 1440


1440 1/min
0.4 0.6 0.8 1 1.2 1.4 1.6 4-pol

1000 1500 2000 2500 3000 3500 960


960 1/min
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 6-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
960 - 0,021 0,022 0,024 0,025 0,027 0,029 0,031 0,033 0,035 0,042 0,049 0,057 0,064 0,071 0,078 0,085
motor 0,37
1440 - 0,072 0,076 0,080 0,085 0,092 0,098 0,105 0,111 0,118 0,142 0,166 0,191 0,215 0,240 0,264 0,288
motor 0,37
2880 - 0,576 0,607 0,638 0,679 0,733 0,784 0,838 0,892 0,946 1,14 1,33 1,53 1,72 1,92 2,11 2,31
motor 0,75 1,1 1,5 2,2 3
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

A09-IN V2016/November 7
[kW]
power (kw)
Performance
Curve
0.3 645003, AXV-AL 450, 2880, 1440, 960
AXV 450, 50 Hz !" Hub: 150-7

0.08
AbsorbedPower

0.25 3
32°
Absorbed

30°
0.06 0.2
28°
26°
2
0.15 24°
0.04 22°
20°
0.1 18°
14° 16°
1 12°
0.02 8° 10°
ρ = 1,2 kg/m3
0.05
[PA]
∆pt(Pa)

j
Pressure

80
175 700
pressure
Total

70 k
Total

150 600
e

60 m
125 500
f
50 a

100 400
b
40 n
g 32°
75 300 30°
30 28°
26°
50 200 c 24°
20 22°
h 20°
18°
10 25 100 16°
14° Lwi(A) a b c d e f g h j k m n
d 12° 2P 102 103 98 99 100 97 99 98 98 100 101 101 Speed
Pd 10° 4P 81 82 80 80 82 78 79 79 79 80 81 82 [min-1]
8° 6P 68 69 69 69 71 67 68 69 68 68 69 70
0 0 0
2500 5000 7500 10000 12500 2880
2880 1/min 2-pol
0.5 1 1.5 2 2.5 3 3.5 4

1000 2000 3000 4000 5000 6000 7000 1440


1440 1/min 4-pol
0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2

500 1000 1500 2000 2500 3000 3500 4000 4500 960
960 1/min
0.2 0.4 0.6 0.8 1 1.2 6-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
960 0,043 0,049 0,054 0,059 0,065 0,070 0,079 0,088 0,097 0,106 0,114 0,123 0,132 - - - -
motor 0,37
1440 0,146 0,164 0,182 0,200 0,218 0,237 0,267 0,297 0,327 0,356 0,386 0,416 0,446 - - - -
motor 0,37 0,55
2880 1,17 1,31 1,45 1,60 1,75 1,90 2,14 2,38 2,61 2,852 3,09 3,33 3,567 - - - -
motor 1,5 2,2 3 4
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

8 A09-IN V2016/November
AbsorbedPower [kW]
power(kw)
Performance
Curve
0.8
6
645004, AXV-AL 500, 2880, 1440, 960
AXV 500, 50 Hz !" Hub: 150-7

0.2
0.6 32 °
Absorbed

30°
0.15 4 28°
26°
0.4 24°
0.1 22°
20°
2
16° 18°
0.2 14°
0.05 10°
12° ρ = 1,2 kg/m3

250 1000
Pressure t
[PA]
∆p(Pa)

j
100
pressure

k
Total

200 800 m
Total

a
80 e

150 600
f
60 b

32 °
g
100 400 30°
40 28°
c
26°
24°
22°
50 200 h 20°
20
18 °
16°
14° Lwi(A) a b c d e f g h j k m n
d 12° 2P 100 100 98 99 100 99 99 100 100 101 101 103 Speed
Pd 10° 80 82 80 81 81 80 80 81 82 82 82 83

4P [min-1]
6P 69 71 69 70 71 69 69 70 71 71 71 72
0 0 0
2500 5000 7500 10000 12500 15000 17500 20000 2880
2880 1/min 2-pol
1 1.5 2 2.5 3 3.5 4 4.5 5 5.5

1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 1440
1440 1/min 4-pol
0.5 0.75 1 1.25 1.5 1.75 2 2.25 2.5 2.75

1000 2000 3000 4000 5000 6000 7000 960


960 1/min
0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 6-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW] * Out of Range

n Pitch angle [°]


[min-1] 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
960 0,058 0,068 0,078 0,088 0,098 0,108 0,124 0,141 0,155 0,171 0,187 0,202 0,218 - - - -
motor 0,37
1440 0,194 0,228 0,262 0,297 0,331 0,366 0,419 0,471 0,524 0,577 0,630 0,683 0,736 - - - -
motor 0,37 0,55 0,75
2880 1,55 1,83 2,10 2,37 2,65 2,93 3,35 3,77 4,19 4,61 5,04 5,46 5,89 - - - -
motor 2,2 3 4 -*
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

A09-IN V2016/November 9
[kW]
power (kw)

0.4
Performance
Curve
645021, AXV-AL 560, 2880, 1440, 960
AXV 560, 50 Hz !" Hub: 200-9

1.25 10
Absorbed Power

32°
0.3
Absorbed

1 30°
7.5
28°
0.75 26°
0.2 24°
5
22°
0.5
18° 20°
0.1 16°
2.5 14°
12°
0.25 8°
10°
ρ = 1,2 kg/m3
∆pt (Pa)
[PA]

j
Pressure

250 1000
pressure

100
Total
Total

a
m
200 800 e

f
75

150 600 n
b
g 32°
30°
50 28°
100 400 26°
c
24°
h 22°

25 20°
50 200 18°
16°
14°
Lwi(A) a b c d e f g h j k m n
d 12°
10° 2P 107 105 106 104 109 107 106 108 110 111 112 112 Speed
Pd 8° 4P 87 87 89 85 90 88 87 88 91 91 91 92 [min-1]
6P 75 76 78 73 79 76 76 77 79 79 79 80
0 0 0
5000 10000 15000 20000 25000 2880
2880 1/min 2-pol
1 2 3 4 5 6 7 8

2000 4000 6000 8000 10000 12000 14000 1440


1440 1/min 4-pol
0.5 1 1.5 2 2.5 3 3.5 4

1000 2000 3000 4000 5000 6000 7000 8000 9000 960
960 1/min
0.5 0.75 1 1.25 1.5 1.75 2 2.25 2.5 6-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
960 0,104 0,119 0,133 0,148 0,163 0,178 0,194 0,228 0,261 0,295 0,329 0,362 0,396 - - - -
motor 0,37 0,55
1440 0,351 0,401 0,450 0,500 0,551 0,602 0,655 0,769 0,882 0,995 1,11 1,22 1,34 - - - -
motor 0,37 0,55 0,75 1,1 1,5
2880 2,81 3,21 3,60 4,01 4,41 4,82 5,24 6,15 7,06 7,96 8,87 9,78 10,7 - - - -
motor 3 4 5,5 7,5 11
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

10 A09-IN V2016/November
[kW]
power (kw)

1
Performance
Curve
25
645002, AXV-AL 630, 2880, 1440, 960
AXV 630, 50 Hz !" Hub: 200-9

3 40 °
AbsorbedPower

0.8 38°
20 36°
Absorbed

34°
0.6 2 32°
15
30°
28°
0.4
10 26°
24°
1 20°
22°
18°
0.2 5 16°
14° ρ = 1,2 kg/m3
12°
10 °
1500
[PA]
∆pt(Pa)

j
350
Pressure

k
150
pressure

1250
Total

300 e
Total

125
f
a
n
250 1000
40°
100 38°
g
200 36°
750 b 34°

75 32°
30°
150
h 28°
500 26 °
50 24°
100 c 22°
20°
18°
250
25 16°
50 14°
d Lwi(A) a b c d e f g h j k m n
12°
Pd 10° 2P 109 108 106 107 112 108 109 111 111 111 112 113 Speed
4P 89 91 87 88 94 90 90 91 93 93 93 94 [min-1]
6P 78 80 76 76 83 79 78 79 82 82 82 83
0 0 0
10000 15000 20000 25000 30000 35000 40000 45000 2880
2880 1/min 2-pol
2 4 6 8 10 12

5000 7500 10000 12500 15000 17500 20000 22500 1440


1440 1/min 4-pol
1 2 3 4 5 6

2000 4000 6000 8000 10000 12000 14000 16000 960


960 1/min
1 1.5 2 2.5 3 3.5 4 6-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW] * Out of Range

n Pitch angle [°]


[min-1] 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
960 - 0,183 0,219 0,256 0,292 0,329 0,367 0,405 0,443 0,481 0,545 0,610 0,675 0,739 0,804 0,868 0,934
motor 0,37 0,55 0,75 1,1
1440 - 0,618 0,741 0,863 0,986 1,11 1,24 1,37 1,49 1,62 1,84 2,06 2,28 2,50 2,71 2,93 3,15
motor 0,75 1,1 1,5 2,2 3 4
2880 - 4,94 5,92 6,90 7,88 8,88 9,90 10,9 12,0 13,0 14,7 16,5 18,2 20,0 21,7 23,4 25,2
motor 5,5 7,5 11 15 18,5 -*
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

A09-IN V2016/November 11
AbsorbedPower [kW]
power (kw)

0.6
Performance
Curve
1.5 5 645006, AXV-AL 710 , 1440, 960, 720
AXV 710, 50 Hz !" Hub: 250-9

36°
4 34°
Absorbed

32°
1
0.4 30°
3
28°
26°
2 24°
0.2 0.5 22°
20°
18°
16°
1 14°
12°
10° ρ = 1,2 kg/m3

125 500
[PA]
∆pt(Pa)
Pressure

h
200
pressure

j
Total

100 400 k
Total

d
150

75 300 e
m
36°
34°
f
100 a 32°

50 200 30°
28°

b 26°
g 24°
22°
50
25 100 20°
18°
16°
14°
Lwi(A) a b c d e f g h j k m n
c 12°
10° 4P
2P 94 93 90 93 92 92 94 96 96 97 98 - Speed
Pd
8° 6P
4P 84 83 79 83 81 81 83 85 85 86 87 - [min-1]
8P
6P 76 76 71 75 73 73 75 77 77 77 78 -
0 0 0
5000 10000 15000 20000 25000 30000 1440
2880
1440 1/min 4-pol
2-pol
2 3 4 5 6 7 8 9

5000 7500 10000 12500 15000 17500 20000 960


1440
960 1/min 6-pol
4-pol
1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6

2000 4000 6000 8000 10000 12000 14000 16000 720


960
720 1/min 8-pol
1 1.5 2 2.5 3 3.5 4 4.5 6-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
720 0,125 0,149 0,175 0,201 0,228 0,255 0,282 0,309 0,353 0,397 0,440 0,484 0,528 0,572 0,616 - -
motor 0,37 0,55 0,75
960 0,295 0,353 0,414 0,477 0,541 0,604 0,668 0,732 0,836 0,940 1,04 1,15 1,25 1,36 1,46 - -
motor 0,37 0,55 0,75 1,1 1,5
1440 0,996 1,19 1,40 1,61 1,83 2,04 2,26 2,47 2,82 3,17 3,52 3,87 4,22 4,58 4,93 - -
motor 1,1 1,5 2,2 3 4 5,5
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

12 A09-IN V2016/November
[kW]
power(kw)

1
Performance
Curve
2.5 645012, AXV-AL 800, 1440, 960, 720
AXV 800, 50 Hz !" Hub: 250-9

7.5
AbsorbedPower

2 36 °
34°
0.75
Absorbed

32°
1.5 5 30°
28°
0.5 26°
1 24°

2.5 22°
20°
0.25 18°
16°
0.5 14°
12° ρ = 1,2 kg/m3
10°

[PA]

j
∆p(Pa)
t

k
125 500
Pressure
pressure

200
m
Total
Total

100 400 a e

f n
150 b 36°
34°
75 300
32°
g
30°

100 28°
c
50 200 26°
h 24°
22°
20°
50 18°
25 100 16°
14°
d
12° Lwi(A) a b c d e f g h j k m n
10°

4P
2P 95 95 99 92 101 95 95 95 99 99 99 101 Speed
Pd 6P 84 84 88 82 91 84 84 84 89 88 88 89
4P [min-1]
8P
6P 76 76 81 74 83 76 76 77 81 81 81 81
0 0 0
5000 10000 15000 20000 25000 30000 35000 40000 45000 1440
2880
1440 1/min 4-pol
2-pol
2 4 6 8 10 12

5000 10000 15000 20000 25000 30000 1440


960
960 1/min 6-pol
4-pol
1 2 3 4 5 6 7 8

2500 5000 7500 10000 12500 15000 17500 20000 22500 720
960
720 1/min
1 2 3 4 5 6 8-pol
6-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
720 0,186 0,225 0,265 0,306 0,348 0,390 0,432 0,474 0,549 0,624 0,699 0,774 0,849 0,924 0,999 - -
motor 0,37 0,55 0,75 1,1
960 0,440 0,533 0,628 0,726 0,825 0,925 1,02 1,12 1,30 1,48 1,66 1,83 2,01 2,19 2,37 - -
motor 0,55 0,75 1,1 1,5 2,2 3
1440 1,49 1,80 2,12 2,45 2,79 3,12 3,46 3,79 4,39 4,99 5,59 6,19 6,79 7,39 7,99 - -
motor 1,5 2,2 3 4 5,5 7,5 11
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

A09-IN V2016/November 13
Absorbed power [kW]
Performance
Curve
15
645011, AXV-AL 900, 1440, 960, 720
AXV 900, 50 Hz !" Hub: 300-10
4
1.5
32°
3 10 30°
28°
1 26°
2 24°
22°
5 20°
0.5 18°
1 16°
14°
12°
10° ρ = 1,2 kg/m3

175 700
Total pressure ∆pt [PA]

300 h

j
150 600
250

a k
125 500
d

200

100 400 e
m
b
32°
150 30°
75 300 f 28°

26°
100 24°
50 200 22°
g 20°
18 °
50 16°
25 100 14°
12° Lwi(A) a b c d e f g h j k m n
c
10° 4P
2P 99 101 97 100 97 97 98 100 100 100 101 - Speed
Pd
8° 6P
4P 88 91 87 90 87 86 87 90 89 90 91 - [min-1]
8P
6P 80 83 80 83 80 79 79 82 82 82 83 -
0 0 0
10000 20000 30000 40000 50000 60000 1440
2880
1440 1/min 4-pol
2-pol
2.5 5 7.5 10 12.5 15

10000 15000 20000 25000 30000 35000 40000 1440


960
960 1/min 6-pol
4-pol
2 4 6 8 10

5000 10000 15000 20000 25000 30000 720


960
720 1/min 8-pol
2 3 4 5 6 7 8 6-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
720 0,376 0,456 0,536 0,617 0,699 0,780 0,914 1,05 1,18 1,32 1,45 1,59 1,72 - - - -
motor 0,55 0,75 1,1 1,5 2,2
960 0,891 1,08 1,27 1,46 1,66 1,85 2,17 2,49 2,80 3,12 3,44 3,76 4,08 - - - -
motor 1,1 1,5 2,2 3 4 5,5
1440 3,01 3,64 4,30 4,93 5,59 6,24 7,31 8,39 9,46 10,5 11,6 12,7 13,8 - - - -
motor 4 5,5 7,5 11 15
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

14 A09-IN V2016/November
Absorbed power [kW]

3
Performance
Curve
645000, AXV-AL 1000, 1440, 960, 720
AXV 1000, 50 Hz !" Hub: 300-10

6 20
32°
30°
2
15 28°
4 26°
24°
10 22°
1 20°
2 18°
16°
5 12°
14°
10° ρ = 1,2 kg/m3

225 400 900
Total pressure ∆pt [PA]

200 800 k
350

175 700
300 m

a e

150 600
250 f

n
125 500
32°
200
b 30°
100 400 g
28°

150 26°

75 300 24°
22°
100 h 20°
c
50 200 18°
16°
14°
25 50 100 12° Lwi(A) a b c d e f g h j k m n
d
10° 4P 102 105 99 100 103 101 100 102 104 103 104 105
2P Speed
Pd 8° 6P 91 95 89 89 93 91 90 91 94 93 94 94
4P [min-1]
8P 83 88 81 82 86 83 83 84 87 86 87 87
6P
0 0 0
10000 20000 30000 40000 50000 60000 70000 80000 1440
2880
1440 1/min 4-pol
2-pol
2.5 5 7.5 10 12.5 15 17.5 20 22.5

10000 15000 20000 25000 30000 35000 40000 45000 50000 55000 1440
960
960 1/min 6-pol
4-pol
2 4 6 8 10 12 14

5000 10000 15000 20000 25000 30000 35000 40000 720


960
720 1/min
2 3 4 5 6 7 8 9 10 11 8-pol
6-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
720 0,654 0,798 0,942 1,09 1,23 1,38 1,59 1,80 2,01 2,22 2,44 2,65 2,86 - - - -
motor 0,75 1,1 1,5 2,2 3
960 1,55 1,89 2,23 2,58 2,92 3,26 3,76 4,26 4,77 5,27 5,77 6,27 6,78 - - - -
motor 2,2 3 4 5,5 7,5
1440 5,23 6,38 7,54 8,69 9,85 11,0 12,7 14,4 16,1 17,8 19,5 21,2 22,9 - - - -
motor 5,5 7,5 11 15 18,5 22 30
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

A09-IN V2016/November 15
[kW]
power (kw)
Performance
Curve
645196
AXV-AL AXV-AL 1120,
1120, 1440, 1440,
960, 720 960, 720
AXV 1120, 50 Hz !" Hub: 300-5
40°
10 38°
AbsorbedPower

4
36°
30
34°
Absorbed

32°
7.5
3 30°
28°
20
26°
2 5 24°
22°
20°
10
2.5 18°
1 16°
14° ρ = 1,2 kg/m3
12°
10°
200 800
[PA]
∆pt(Pa)

350
Pressure
pressure

175 a
300 h
j
Total

e
Total

k
150 600
40°
250 b
38°

f 36°
125
34°
200 32°

100 400 30°


28°
c 26°
150
24°
75
22°
g 20°
100 18°
50 200 16°
14°
d 12°
50 10°
25
Lwi(A) a b c d e f g h j k m n
Pd 4P
2P 106 106 105 102 110 101 102 110 111 111 - - Speed
6P
4P 95 95 95 92 100 91 92 99 100 100 - - [min-1]
8P
6P 88 87 88 85 92 84 85 92 92 92 - -
0 0 0
20000 40000 60000 80000 100000 1440
2880
1440 1/min 4-pol
2-pol
5 10 15 20 25 30

10000 20000 30000 40000 50000 60000 70000 960


1440
960 1/min 6-pol
2.5 5 7.5 10 12.5 15 17.5 20 4-pol

10000 20000 30000 40000 50000 720


960
720 1/min
2.5 5 7.5 10 12.5 15 8-pol
6-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
720 - 0,789 0,98 1,17 1,37 1,57 1,78 2,04 2,32 2,59 2,87 3,15 3,43 3,71 3,99 4,27 4,56
motor 1,1 1,5 2,2 3 4 5,5
960 - 1,87 2,32 2,78 3,25 3,73 4,23 4,85 5,49 6,14 6,79 7,46 8,13 8,79 9,46 10,1 10,8
motor 2,2 3 4 5,5 7,5 11
1440 - 6,31 7,85 9,39 11,0 12,6 14,3 16,4 18,5 20,7 22,9 25,2 27,4 29,7 31,9 34,2 36,4
motor 7,5 11 15 18,5 22 30 37
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

16 A09-IN V2016/November
[kW]
power (kw)
Performance
Curve
20 645100 1250,
AXV-AL AXV-AL 1250,
1440, 1440,
960, 720 960, 720
AXV 1250, 50 Hz !" Hub: 370-6
40°
7.5 60
AbsorbedPower

38°
36°
15 34°
Absorbed

32°
30°
5 40 28°
10 26°
24°
22°
20°
2.5 20
5 18°
16°
12° 14° ρ = 1,2 kg/m3
10°
[PA]
∆pt(Pa)

225 400
Pressure
pressure

h
200 350 800 j
Total

a e
Total

k
175 40°
300
38°

150 600 36°


250 34°
b f
125 32°
30°
200
28°
100 400
26°
150 c 24°
75 22°
20°
18°
100 g
50 200 16°
14°
d 12°
50 10°
25 Lwi(A) a b c d e f g h j k m n
Pd 4P
2P 106 110 105 106 110 109 105 112 112 113 - - Speed
6P
4P 96 100 95 96 99 99 95 102 102 102 - - [min-1]
8P
6P 88 92 88 88 92 92 88 95 95 95 - -
0 0 0
20000 40000 60000 80000 100000 120000 140000 1440
2880
1440 1/min
5 10 15 20 25 30 35 40 4-pol
2-pol

20000 40000 60000 80000 100000 1440


960
960 1/min
5 10 15 20 25 6-pol
4-pol

10000 20000 30000 40000 50000 60000 70000 720


960
720 1/min
2.5 5 7.5 10 12.5 15 17.5 20 8-pol
6-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
720 - 1,38 1,61 1,86 2,18 2,63 3,11 3,59 4,08 4,57 5,07 5,57 6,06 6,55 7,05 7,54 8,03
motor 1,5 2,2 3 4 5,5 7,5 11
960 - 3,26 3,82 4,40 5,17 6,23 7,37 8,51 9,66 10,8 12,0 13,2 14,4 15,5 16,7 17,9 19,0
motor 4 5,5 7,5 11 15 18,5 22
1440 - 11,0 12,9 14,8 17,5 21,0 24,9 28,7 32,6 36,6 40,6 44,5 48,5 52,4 56,4 60,3 64,3
motor 11 15 18,5 22 30 37 45 55 75
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

A09-IN V2016/November 17
[kW]
power (kw)
Performance
Curve
6451941400,
AXV-AL AXV-AL
960,1400,
720, 960,
576 720, 576
AXV 1400, 50 Hz !" Hub: 420-6

30 40°
AbsorbedPower

38°
6
36°
34°
Absorbed

10 32°
30°
20
4 28°
26°
24°
22°
5
20°
2 10
18°
16°
12° 14° ρ = 1,2 kg/m3
10°
600
[PA]
∆pt(Pa)

a
Pressure

200
pressure

300

500 j k
Total

175 e
m
Total

250 n

150 40°
400 b
38°
f
125 200 36°

34°

300 32°
100 30°
150
c 28°
g 26°
75 24°
200
100 22°
20°
50 18°
h 16°
100 14°
50 d 12°
25 10° Lwo(A) a b c d e f g h j k m n
Pd 6P 102 99 103 100 101 105 98 99 108 107 105 106 Speed
8P 95 92 96 93 94 97 91 92 100 100 98 99 [min-1]
10P 90 87 91 87 88 92 86 87 94 94 93 94
0 0 0
20000 40000 60000 80000 100000 120000 140000 2880
960
960 1/min 6-pol
2-pol
5 10 15 20 25 30 35 40

20000 40000 60000 80000 100000 1440


720
720 1/min
5 10 15 20 25 30 8-pol
4-pol

576
10000 20000 30000 40000 50000 60000 70000 80000 90000 960
576 1/min 10-
2.5 5 7.5 10 12.5 15 17.5 20 22.5 25 6-pol
pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
576 - 1,08 1,33 1,58 1,81 2,20 2,62 3,04 3,46 3,88 4,30 4,72 5,13 5,56 5,98 6,41 6,83
motor 1,1 1,5 2,2 3 4 5,5 7,5
720 - 2,10 2,59 3,09 3,54 4,31 5,11 5,94 6,76 7,58 8,40 9,21 10,0 10,9 11,7 12,5 13,3
motor 2,2 3 4 5,5 7,5 11 15
960 - 4,98 6,14 7,32 8,40 10,2 12,1 14,1 16,0 18,0 19,9 21,8 23,8 25,7 27,7 29,7 31,6
motor 5,5 7,5 11 15 18,5 22 30 37
Fan test laboratory AMCA 210/99 Fig.15,Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation
installation type
type D
A - Ducted inlet,
Free inlet, Ducted
Free outlet.
outlet. Performance
Performance ratings
ratings do
do not Standard 301.
301. Values
Values shown
shown are
areforforoutlet LwoAsound
inlet LwiA sound power
power levels
levels for installation
not include
include the effects
the effects of appurtenances
of appurtenances (accessories-belt
(accessories-belt cover,
cover, pulley
pulley & belt).
& belt). Type A:
D: free inlet,
ducted freeducted
inlet, outlet.outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

18 A09-IN V2016/November
[kW]
power (kw)
Performance
Curve
60
6452031600,
AXV-AL AXV-AL
960,1600,
720, 960,
576 720, 576
AXV 1600, 50 Hz !" Hub: 420-6
40°
38°
AbsorbedPower

36°
20 34°
10
Absorbed

32°
40 30°
28°
26°
24°
5 10 22°
20 20°
18°

14°
16° ρ = 1,2 kg/m3
12°
10°
450 800
[PA]
∆pt(Pa)

275
Pressure
pressure

400 700
250
a e
Total
Total

225 350 j
600 k
f
200
300 m
b
500 40°
175
38°
250 g
36°
150
400 34°

200 32°
125 c
30°
300 28°
100 26°
150
24°
22°
75 200 20°
100 h
18°
50 16°
14°
100 d 12°
50 Lwo(A) a b c d e f g h j k m n
25 10°
6P 102 104 106 104 108 107 108 109 111 110 111 - Speed
Pd 8P 95 96 98 97 104 100 100 101 103 103 103 - [min-1]
10P 89 90 92 92 95 93 94 95 97 97 97 -
0 0 0
25000 50000 75000 100000 125000 150000 175000 200000 2880
960
960 1/min 6-pol
2-pol
10 20 30 40 50

20000 40000 60000 80000 100000 120000 140000 160000 1440


720
720 1/min
5 10 15 20 25 30 35 40 8-pol
4-pol

576
20000 40000 60000 80000 100000 120000 960
576 1/min 10-
5 10 15 20 25 30 35 6-pol
pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
576 - 2,13 2,60 3,07 3,55 4,07 4,77 5,53 6,32 7,13 7,95 8,78 9,61 10,5 11,3 12,1 13,0
motor 2,2 3 4 5,5 7,5 11 15
720 - 4,16 5,08 6,00 6,94 7,94 9,32 10,8 12,3 13,9 15,5 17,1 18,8 20,4 22,0 23,8 25,4
motor 5,5 7,5 11 15 18,5 22 30
960 - 9,86 12,0 14,2 16,4 18,8 22,0 25,6 29,3 33,0 36,8 40,6 44,5 48,4 52,3 56,3 60,3
motor 11 15 18,5 22 30 37 45 55 75
Fan test laboratory AMCA 210/99 Fig.15,Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation
installation type
type D
A - Ducted
Free inlet,
inlet,
Free
Ducted
outlet.
outlet.
Performance
Performance
ratings
ratings
do not
do Standard 301.
301. Values
Values shown
shown are
areforforoutlet LwoAsound
inlet LwiA sound power
power levels
levels for installation
not include
include the the
effects
effects
of appurtenances
of appurtenances
(accessories-belt
(accessories-belt
cover,
cover,
pulley
pulley
& belt).
& belt). Type A:
D: free inlet,
ducted freeducted
inlet, outlet.outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

A09-IN V2016/November 19
[kW]
power (kw)
Performance
Curve
645302, AXV-AL 1800, 960, 720, 576
AXV 1800, 50 Hz !" Hub: 540-6

40°
AbsorbedPower

100 38°
20 40 36°
Absorbed

34°
32°
30°
28°
26°
50 24°
10 20
22°
20°
18°
16°
ρ = 1,2 kg/m3
12° 14°
10°
1000
[PA]
∆pt(Pa)

350
a
Pressure
pressure

500

300 j k
Total

800 e m
Total

n
400
250 40°
b
38°
600 f
36°
200 34°
300
32°
30°
150 c 28°
400
g 26°
200
24°
22°
100 20°
18°
h 16°
200
100 14°
50 d 12°
10° Lwo(A) a b c d e f g h j k m n
Pd 6P 109 107 111 107 108 112 106 107 116 115 113 114 Speed
8P 103 100 103 100 101 105 99 100 108 107 106 107 [min-1]
10P 97 94 97 95 95 99 93 94 102 102 100 101
0 0 0
5.0x10
4
1.0x10
5
1.5x10
5
2.0x10
5
2.5x10
5
3.0x10
5
2880
960
960 1/min 6-pol
2-pol
10 20 30 40 50 60 70 80

4 4 4 5 5 5 5 5 5
2.50x10 5.00x10 7.50x10 1.00x10 1.25x10 1.50x10 1.75x10 2.00x10 2.25x10 1440
720
720 1/min
10 20 30 40 50 60 8-pol
4-pol

576
2.50x10
4
5.00x10
4
7.50x10
4
1.00x10
5
1.25x10
5
1.50x10
5
1.75x10
5
960
576 1/min 10-
5 10 15 20 25 30 35 40 45 50 6-pol
pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
576 - 3,76 4,64 5,54 6,36 7,73 9,17 10,6 12,1 13,6 15,0 16,5 18,0 19,5 20,9 22,4 23,9
motor 4 5,5 7,5 11 15 18,5 22 30
720 - 7,35 9,07 10,8 12,4 15,0 17,9 20,8 23,7 26,6 29,4 32,3 35,1 38,0 40,9 43,8 46,7
motor 7,5 11 15 18,5 22 30 37 45 55
960 - 17,4 21,5 25,6 29,4 35,8 42,4 49,3 56,1 62,9 69,7 76,5 83,2 90,2 97,0 103,8 110,7
motor 18,5 22 30 37 45 55 75 90 110 132
Fan test laboratory AMCA 210/99 Fig.15,Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation
installation type
type D
A - Ducted inlet,
Free inlet, Ducted
Free outlet.
outlet. Performance
Performance ratings
ratings do
do not Standard 301.
301. Values
Values shown
shown are
areforforoutlet LwoAsound
inlet LwiA sound power
power levels
levels for installation
not include
include the effects
the effects of appurtenances
of appurtenances (accessories-belt
(accessories-belt cover,
cover, pulley
pulley & belt).
& belt). Type A:
D: free inlet,
ducted freeducted
inlet, outlet.outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

20 A09-IN V2016/November
[kW]
power(kw)
Performance
Curve
200 645402, AXV-AL 2000, 960, 720, 576
AXV 2000, 50 Hz !" Hub: 600-6
40
75 40°
AbsorbedPower

38°
36°
150 34°
Absorbed

30
32°
50 30°
28°
100 26°
20
24°
22°
25 20°
10 50 18°
16°
14° ρ = 1,2 kg/m3
12°
10°
450 1250
[PA]

700
∆p(Pa)
Pressure t

a
pressure

400
600
j k
Total

1000
Total

350 e m

500 n

300 40°
b
38°
750 f
36°
250 400
34°
32°
200 30°
300
500 c 28°
g
26°
150 24°
200 22°
20°
100 18°
250 h 16°
14°
100 d 12°
50 10° Lwo(A) a b c d e f g h j k m n
6P 113 110 114 110 111 115 109 110 119 118 116 117 Speed
Pd 8P 106 103 106 104 104 108 102 103 111 111 109 110 [min-1]
10P 100 97 101 98 99 102 96 98 105 105 104 104
0 0 0
5.0x10
4
1.0x10
5
1.5x10
5
2.0x10
5
2.5x10
5
3.0x10
5
3.5x10
5
4.0x10
5
2880
960
960 1/min 6-pol
2-pol
20 40 60 80 100 120

4 5 5 5 5 5
5.00x10 1.00x10 1.50x10 2.00x10 2.50x10 3.00x10 1440
720
720 1/min 8-pol
4-pol
10 20 30 40 50 60 70 80 90

576
4
2.50x10 5.00x10
4
7.50x10
4 5
1.00x10 1.25x10
5
1.50x10
5
1.75x10
5
2.00x10
5
2.25x10 2.50x10
5 5
960
576 1/min 10-
10 20 30 40 50 60 70 6-pol
pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
576 - 6,37 7,85 9,36 10,7 13,1 15,5 18,0 20,5 23,0 25,5 27,9 30,4 32,9 35,4 37,9 40,4
motor 7,5 11 15 18,5 22 30 37 45
720 - 12,4 15,3 18,3 21,0 25,5 30,3 35,2 40,0 44,9 49,8 54,6 59,4 64,4 69,2 74,1 79,0
motor 15 18,5 22 30 37 45 55 75 90
960 - 29,5 36,3 43,3 49,8 60,5 71,8 83,4 94,9 106,4 117,9 129,4 140,8 152,5 164,1 175,7 187,3
motor 30 37 45 55 75 90 110 132 160 200
Fan test laboratory AMCA 210/99 Fig.15,Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation
installation type
type D
A - Ducted
Free inlet,
inlet,
Free
Ducted
outlet.
outlet.
Performance
Performance
ratings
ratings
do not
do Standard 301.
301. Values
Values shown
shown are
areforforoutlet LwoAsound
inlet LwiA sound power
power levels
levels for installation
not include
include the the
effects
effects
of appurtenances
of appurtenances
(accessories-belt
(accessories-belt
cover,
cover,
pulley
pulley
& belt).
& belt). Type A:
D: free inlet,
ducted freeducted
inlet, outlet.outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

A09-IN V2016/November 21
[kW]
power (kw)
Performance
Curve
645502, AXV-AL 2200, 720, 576, 480
AXV 2200, 50 Hz !" Hub: 660-6
40°
60 38°
AbsorbedPower

36°
30 100 34°
Absorbed

32°
30°
40
28°
20 26°
24°
50 22°
20°
20
10 18°
16°
ρ = 1,2 kg/m3
12° 14°
10°
800
[PA]
∆pt(Pa)

350 500 a
Pressure
pressure

700 j k
300 e
m
Total
Total

400
n
600
40°
250 b
38°
f
500 36°
300
200 34°

32°
400
30°
c 28°
150
g
200 26°
300
24°
22°
100 20°
200 18°
h
16°
100
14°
d 12°
50
100 10° Lwo(A) a b c d e f g h j k m n
8P
6P 109 106 109 107 107 111 105 106 114 114 112 113 Speed
Pd 10P
8P 103 100 103 101 101 105 99 101 108 108 107 107 [min-1]
12P
10P 99 96 99 97 97 100 95 96 103 103 102 103
0 0 0
5.0x10
4
1.0x10
5
1.5x10
5
2.0x10
5
2.5x10
5
3.0x10
5
3.5x10
5
4.0x10
5
720
2880
960
720 1/min
20 40 60 80 100 120 6-pol
2-pol
8-pol

576
4 5 5 5 5 5 5
5.00x10 1.00x10 1.50x10 2.00x10 2.50x10 3.00x10 3.50x10 1440
720
576 1/min
10 20 30 40 50 60 70 80 90 8-pol
4-pol
10-pol

576
480
960
4 5 5 5 5
5.00x10 1.00x10 1.50x10 2.00x10 2.50x10
480 1/min 10-
10 20 30 40 50 60 70 80 12-pol
6-pol
pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
480 - 5,92 7,30 8,70 9,99 12,1 14,4 16,7 19,1 21,4 23,7 26,0 28,3 30,6 32,9 35,3 37,6
motor 7,5 11 15 18,5 22 30 37 45
576 - 10,2 12,6 15,0 17,3 21,0 24,9 28,9 32,9 36,9 40,9 44,9 48,8 52,9 56,9 60,9 64,9
motor 11 15 18,5 22 30 37 45 55 75
720 - 20,0 24,6 29,4 33,7 41,0 48,6 56,5 64,3 72,1 79,9 87,6 95,4 103,3 111,1 119,0 126,8
motor 22 30 37 45 55 75 90 110 132
Fan test laboratory AMCA 210/99 Fig.15,Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation
installation type
type D
A - Ducted inlet,
Free inlet, Ducted
Free outlet.
outlet. Performance
Performance ratings
ratings do
do not Standard 301.
301. Values
Values shown
shown are
areforforoutlet LwoAsound
inlet LwiA sound power
power levels
levels for installation
not include
include the effects
the effects of appurtenances
of appurtenances (accessories-belt
(accessories-belt cover,
cover, pulley
pulley & belt).
& belt). Type A:
D: free inlet,
ducted freeducted
inlet, outlet.outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

22 A09-IN V2016/November
[kW]
power(kw)
Performance
Curve
100 200 645602, AXV-AL 2400, 720, 576, 480
AXV 2400, 50 Hz !" Hub: 720-6
40°
38°
AbsorbedPower

50 36°
150 34°
75
Absorbed

32°
40
30°
28°
30 100 26°
50
24°
22°
20 20°
25 50 18°

10
16° ρ = 1,2 kg/m3
12° 14°
10°
[PA]
∆p(Pa)

600 a
t

400
Pressure
pressure

j k
350 800 e m
500
Total
Total

300 40°
b
38°
400
600 f
36°
250
34°
32°
300
200 30°

400 c 28°
g 26°
150 24°
200
22°
20°
100 18°
h 16°
200
14°
100 d 12°
50 10° Lwo(A) a b c d e f g h j k m n
6P
8P 111 109 112 109 110 113 107 109 117 116 115 115 Speed
Pd 8P
10P 106 103 106 104 104 107 102 103 111 111 109 110 [min-1]
10P
12P 101 98 101 99 100 102 97 99 106 106 105 106
0 0 0
1.0x10
5
2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5 720
2880
960
720 1/min 6-pol
2-pol
8-pol
25 50 75 100 125 150

5.00x10
4
1.00x10
5
1.50x10
5
2.00x10
5
2.50x10
5
3.00x10
5
3.50x10
5
4.00x10
5
4.50x10
5
576
1440
720
576 1/min 8-pol
4-pol
20 40 60 80 100 120 10-pol

576
5.00x10
4
1.00x10
5
1.50x10
5
2.00x10
5
2.50x10
5
3.00x10
5
3.50x10
5
480
960
480 1/min 10-
10 20 30 40 50 60 70 80 90 100 12-pol
6-pol
pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
480 - 9,14 11,3 13,4 15,4 18,7 22,2 25,8 29,4 33,0 36,5 40,1 43,6 47,3 50,9 54,4 58,0
motor 11 15 18,5 22 30 37 45 55 75
576 - 15,8 19,5 23,2 26,7 32,4 38,4 44,6 50,8 57,0 63,2 69,3 75,4 81,7 87,9 94,1 100,3
motor 18,5 22 30 37 55 75 90 110
720 - 30,8 38,0 45,3 52,1 63,3 75,0 87,2 99,3 111,3 123,3 135,3 147,3 159,5 171,6 183,7 195,8
motor 37 45 55 75 90 110 132 160 200
Fan test laboratory AMCA 210/99 Fig.15,Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation
installation type
type D
A - Ducted
Free inlet,
inlet,
Free
Ducted
outlet.
outlet.
Performance
Performance
ratings
ratings
do not
do Standard 301.
301. Values
Values shown
shown are
areforforoutlet LwoAsound
inlet LwiA sound power
power levels
levels for installation
not include
include the the
effects
effects
of appurtenances
of appurtenances
(accessories-belt
(accessories-belt
cover,
cover,
pulley
pulley
& belt).
& belt). Type A:
D: free inlet,
ducted freeducted
inlet, outlet.outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

A09-IN V2016/November 23
[kW]
power (kw)

75
Performance
Curve
645702, AXV-AL 2500, 720, 576, 480
AXV 2500, 50 Hz !" Hub: 750-6

40°
AbsorbedPower

38°
100 200 36°
34°
Absorbed

50 32°
30°
28°
26°
24°
50 100 22°
25 20°
18°
16°
ρ = 1,2 kg/m3
12° 14°
10°
[PA]
∆pt(Pa)

450 1000 a
Pressure

600
pressure

400 j k
e m
Total
Total

350 800 n
500
40°
b
38°
300
f
36°
400
600 34°
250
32°
30°
300
200 c 28°
g
400 26°
24°
150 22°
200
20°
18°
100 h 16°
200 14°
100 d 12°
50 10° Lwo(A) a b c d e f g h j k m n
8P
6P 112 110 113 110 111 115 109 110 118 117 116 117 Speed
Pd 10P
8P 107 104 107 105 105 109 103 104 112 112 110 111 [min-1]
12P
10P 102 100 103 101 101 104 98 100 107 107 106 107
0 0 0
1.0x10
5
2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5
6.0x10
5
720
2880
960
720 1/min
25 50 75 100 125 150 175 6-pol
2-pol
8-pol

576
4 5 5 5 5 5 5 5 5 5
5.00x10 1.00x10 1.50x10 2.00x10 2.50x10 3.00x10 3.50x10 4.00x10 4.50x10 5.00x10 1440
720
576 1/min
20 40 60 80 100 120 140 8-pol
4-pol
10-pol

576
480
960
4 5 5 5 5 5 5 5
5.00x10 1.00x10 1.50x10 2.00x10 2.50x10 3.00x10 3.50x10 4.00x10
480 1/min 10-
20 40 60 80 100 120 12-pol
6-pol
pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
480 - 11,2 13,8 16,5 18,9 23,0 27,3 31,7 36,1 40,4 44,8 49,2 53,5 57,9 62,4 66,8 71,2
motor 15 18,5 22 30 37 45 55 75
576 - 19,4 23,9 28,5 32,7 39,7 47,1 54,7 62,3 69,9 77,4 84,9 92,4 100,1 107,7 115,3 122,9
motor 22 30 37 45 55 75 90 110 132
720 - 37,8 46,6 55,6 63,8 77,6 92,1 106,9 121,7 136,5 151,2 165,9 180,6 195,6 210,4 225,3 240,1
motor 45 55 75 90 110 132 160 200 250
Fan test laboratory AMCA 210/99 Fig.15,Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation
installation type
type D
A - Ducted inlet,
Free inlet, Ducted
Free outlet.
outlet. Performance
Performance ratings
ratings do
do not Standard 301.
301. Values
Values shown
shown are
areforforoutlet LwoAsound
inlet LwiA sound power
power levels
levels for installation
not include
include the effects
the effects of appurtenances
of appurtenances (accessories-belt
(accessories-belt cover,
cover, pulley
pulley & belt).
& belt). Type A:
D: free inlet,
ducted freeducted
inlet, outlet.outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

24 A09-IN V2016/November
[kW]
power(kw)
Performance
Curve
150 300 645802, AXV-AL 2600, 720, 576, 480
AXV 2600, 50 Hz !" Hub: 780-6
40°
38°
AbsorbedPower

75
36°
34°
Absorbed

32°
100 200
30°
50 28°
26°
24°
22°
50 100 20°
25 18°
16°
ρ = 1,2 kg/m3
12° 14°
10°
[PA]
∆p(Pa)

500
700 a
t
Pressure
pressure

1000
j k
600
Total

e m
Total

400
n

40°
500 b
750 38°
f
36°
300
400 34°
32°
30°
500
c 28°
300
200 g 26°
24°
22°
200 20°
18°
250 h 16°
100
14°
d 12°
100
10° Lwo(A) a b c d e f g h j k m n
6P
8P 114 111 114 112 112 116 110 111 119 119 117 118 Speed
Pd 8P
10P 108 105 109 106 107 110 104 106 113 113 112 112 [min-1]
10P
12P 104 101 104 102 102 105 100 101 109 108 107 108
0 0 0
1.0x10
5
2.0x10
5
3.0x10
5
4.0x10
5
5.0x10
5
6.0x10
5
7.0x10
5 720
2880
960
720 1/min 6-pol
2-pol
8-pol
25 50 75 100 125 150 175 200

1.00x10
5
2.00x10
5
3.00x10
5
4.00x10
5
5.00x10
5
576
1440
720
576 1/min 8-pol
4-pol
25 50 75 100 125 150 10-pol

576
5.00x10
4
1.00x10
5
1.50x10
5
2.00x10
5 5
2.50x10 3.00x10
5
3.50x10
5
4.00x10
5
4.50x10
5
480
960
480 1/min 10-
25 50 75 100 125 12-pol
6-pol
pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
480 - 13,6 16,8 20,0 23,0 28,0 33,2 38,5 43,9 49,2 54,5 59,8 65,1 70,5 75,8 81,2 86,5
motor 15 18,5 22 30 37 45 55 75 90
576 - 23,5 29,0 34,6 39,8 48,3 57,3 66,6 75,8 85,0 94,2 103,3 112,4 121,8 131,1 140,3 149,5
motor 30 37 45 55 75 90 110 132 160
720 - 46,0 56,7 67,6 77,6 94,4 112,0 130,1 148,1 166,0 184,0 201,8 219,6 237,9 255,9 274,0 292,1
motor 55 75 90 110 132 160 200 250 315
Fan test laboratory AMCA 210/99 Fig.15,Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation
installation type
type D
A - Ducted
Free inlet,
inlet,
Free
Ducted
outlet.
outlet.
Performance
Performance
ratings
ratings
do not
do Standard 301.
301. Values
Values shown
shown are
areforforoutlet LwoAsound
inlet LwiA sound power
power levels
levels for installation
not include
include the the
effects
effects
of appurtenances
of appurtenances
(accessories-belt
(accessories-belt
cover,
cover,
pulley
pulley
& belt).
& belt). Type A:
D: free inlet,
ducted freeducted
inlet, outlet.outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

A09-IN V2016/November 25
[kW]
power (kw)

125
Performance
Curve
645902, AXV-AL 2800, 720, 576, 480
AXV 2800, 50 Hz !" Hub: 840-6

200 400 40°


AbsorbedPower

38°
36°
100 34°
Absorbed

150 300 32°


30°
75 28°
26°
100 200 24°
50 22°
20°
18°
50 100
25 16°
ρ = 1,2 kg/m3
12° 14°
10°
600
[PA]
∆pt(Pa)

a
Pressure

800 1250
pressure

500 j k
Total

700 e m
Total

1000 n
600 40°
400 b
38°
f
36°
500
750 34°
300 32°
400 30°
c 28°
g
500 26°
300 24°
200
22°
20°
200 18°
h 16°
250 14°
100
d 12°
100 10° Lwo(A) a b c d e f g h j k m n
8P
6P 116 113 117 114 114 118 112 114 122 121 119 120 Speed
Pd 10P
8P 110 108 111 108 109 112 106 108 116 115 114 115 [min-1]
12P
10P 106 103 106 104 104 107 102 103 111 111 110 110
0 0 0
1.0x10
5
2.0x10
5
3.0x10
5
4.0x10 5.0x10
5
6.0x10
5 5
7.0x10
5
8.0x10
5
9.0x10
5
720
2880
960
720 1/min
25 50 75 100 125 150 175 200 225 250 6-pol
2-pol
8-pol

576
5 5 5 5 5 5 5
1.00x10 2.00x10 3.00x10 4.00x10 5.00x10 6.00x10 7.00x10 1440
720
576 1/min
25 50 75 100 125 150 175 200 8-pol
4-pol
10-pol

576
480
960
5 5 5 5 5
1.00x10 2.00x105 3.00x10 4.00x10 5.00x10 6.00x10
480 1/min 10-
25 50 75 100 125 150 12-pol
6-pol
pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
480 - 19,7 24,3 29,0 33,3 40,5 48,0 55,8 63,5 71,2 78,9 86,6 94,2 102,1 109,8 117,6 125,3
motor 22 30 37 45 55 75 90 110 132
576 - 34,1 42,0 50,1 57,6 70,0 83,0 96,4 109,8 123,1 136,4 149,6 162,8 176,4 189,8 203,1 216,5
motor 37 45 55 75 90 110 132 160 200 250
720 - 66,6 82,1 97,9 112,4 136,6 162,1 188,3 214,4 240,4 266,4 292,2 318,0 344,5 370,6 396,8 422,9
motor 75 90 110 132 160 200 250 315 355 450
Fan test laboratory AMCA 210/99 Fig.15,Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation
installation type
type D
A - Ducted inlet,
Free inlet, Ducted
Free outlet.
outlet. Performance
Performance ratings
ratings do
do not Standard 301.
301. Values
Values shown
shown are
areforforoutlet LwoAsound
inlet LwiA sound power
power levels
levels for installation
not include
include the effects
the effects of appurtenances
of appurtenances (accessories-belt
(accessories-belt cover,
cover, pulley
pulley & belt).
& belt). Type A:
D: free inlet,
ducted freeducted
inlet, outlet.outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

26 A09-IN V2016/November
AMCA - FEG rating
Fan Efficiency Grade - AXV !"
Certified FEGs are determined in accordance with AMCA 205-12 Energy Efficiency Classification
for fans. In conjunction with AMCA 211-05 (Rev. 6/12) Certified Ratings Program, Product Rating
Manual for Fan Air Performance. This classification is based on fan peak (optimum) total efficiency
for a given fan speed, fan size and application category. For the purpose of energy classification,
the peak efficiency can be determined at a speed not higher than the maximum design speed of
the fan.

The AMCA Certified Ratings Seal applies to the Fan Efficiency Grade (FEG) for AXV series Axial
Fan model AXV 355 to AXV 2800 as shown in the table below.

Fan Fan Fan Fan Fan Fan


Fan Fan
Speed Outlet Area Efficiency Speed Outlet Area Efficiency
Model No. Model No.
(rpm) (m2) Grades (FEG) (rpm) (m2) Grade (FEG)
AXV 355 3456/1728/1152 0,1012 FEG63 AXV 1250 1728/1152/864 1,2272 FEG71
AXV 400 3456/1728/1152 0,1269 FEG67 AXV 1400 1152/864/691 1,5504 FEG75
AXV 450 3456/1728/1152 0,1590 FEG63 AXV 1600 1152/864/691 1,9981 FEG67
AXV 500 3456/1728/1152 0,2003 FEG71 AXV 1800 1152/864/691 2,5588 FEG75
AXV 560 3456/1728/1152 0,2516 FEG67 AXV 2000 1152/864/691 3,1573 FEG75
AXV 630 3456/1728/1152 0,3167 FEG63 AXV 2200 864/691/576 3,8186 FEG75
AXV 710 1728/1152/864 0,3982 FEG67 AXV 2400 864/691/576 4,5428 FEG75
AXV 800 1728/1152/864 0,5001 FEG67 AXV 2500 864/691/576 4,9284 FEG75
AXV 900 1728/1152/864 0,6333 FEG63 AXV 2600 864/691/576 5,3297 FEG75
AXV 1000 1728/1152/864 0,7980 FEG71 AXV 2800 864/691/576 6,1795 FEG75
AXV 1120 1728/1152/864 0,9978 FEG71

90
FEG90

FEG85
80
FEG80

FEG75
Fan Peak Total Efficiency (%)

70 FEG71
FEG67
FEG63
60
FEG60
FEG56
FEG53
50 FEG50

40

30
Fan sizes in preferred numbers
125160 200 250 315 355 400 450 500 560 630 710 800 900 1000
20
0 100 200 300 400 500 600 700 800 900 1000 1100
Fan size (mm)

A09-IN V2016/November 27
Notes:
[kW]
power(kw)

0.1
Performance
Curve AXV 355, 60 Hz
645024, AXV-AL 355, 3456, 1728, 1152
!" Hub: 150-7
2.5
0.3
AbsorbedPower

40°
0.08 38°
Absorbed

2 36°
34°
32°
0.06 0.2
1.5 30°
28°

24° 26°
0.04 22°
1 20°
18°
16°
0.1 12°
14° ρ = 1,2 kg/m3
10°
80
[PA]

h
∆p(Pa)

175 700
Pressure t
pressure

70
j
150 600 d
Total
Total

k
60 e
a
125 500

50 m
f
100 400 40°
38°
40 b
36°
34°
75 300
32°
30
30°
g 28°
50 200 26°
20
24°
22°
20°
10 25 100 18°
16° Lwi(A) a b c d e f g h j k m n
Pd c 14° 2P 101 99 99 103 108 108 109 106 109 110 110 - Speed
12° 4P 81 80 79 83 87 87 88 85 89 90 90 - [min-1]
10°
6P 70 68 68 72 77 77 78 74 78 79 80 -
0 0 0
2000 3000 4000 5000 6000 7000 8000 9000 10000 3456
2880
3456 1/min 2-pol
0.5 0.75 1 1.25 1.5 1.75 2 2.25 2.5 2.75

1000 1500 2000 2500 3000 3500 4000 4500 5000 1728
1440
1728 1/min
0.2 0.4 0.6 0.8 1 1.2 1.4 4-pol

500 1000 1500 2000 2500 3000 1152


960
1152 1/min
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 6-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW] * Out of Range

n Pitch angle [°]


[min-1] 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
1152 - 0,031 0,035 0,038 0,042 0,046 0,049 0,053 0,056 0,060 0,065 0,070 0,076 0,081 0,087 0,092 0,097
motor 0,37
1728 - 0,105 0,118 0,130 0,142 0,154 0,166 0,178 0,190 0,202 0,219 0,237 0,255 0,274 0,292 0,310 0,329
motor 0,37
3456 - 0,843 0,940 1,04 1,13 1,23 1,33 1,42 1,52 1,62 1,75 1,90 2,04 2,19 2,34 2,48 2,63
motor 1,1 1,5 2,2 -*
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

28 A09-IN V2016/November
Absorbed Power [kW]
power (kw)

0.15
Performance
Curve
0.5 4
AXV 400, 60 Hz
645023, AXV-AL 400, 3456, 1728, 1152
!" Hub: 150-7

40°
38°
0.4
Absorbed

3 36°
0.1 34°
0.3
32°
2 30°
0.2 28°
0.05
26°
22° 24°
1 18° 20°
0.1 14° 16° ρ = 1,2 kg/m3
10° 12°
∆pt (Pa)
[PA]

200 800
g
Pressure
pressure

h
80
j
Total
Total

150 600

60 k
d
a 40°

38°
e
36°
100 400
34°
40
b
32°

30°

f 28°
26°
50 200 24°
20
22°
20°
18°
16°
Lwi(A) a b c d e f g h j k m n
c 14°
Pd 12° 2P 110 103 100 104 105 106 107 106 106 106 - - Speed
10° 4P 89 85 81 85 85 87 87 86 87 89 - - [min-1]
6P 75 73 70 74 73 74 74 74 74 75 - -
0 0 0
2000 4000 6000 8000 10000 12000 14000 2880
3456
3456 1/min
1 1.5 2 2.5 3 3.5 4 2-pol

1000 2000 3000 4000 5000 6000 7000 1440


1728
1728 1/min
0.5 0.75 1 1.25 1.5 1.75 2 4-pol

1000 1500 2000 2500 3000 3500 4000 4500 1152


960
1152 1/min
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3 6-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW] * Out of Range

n Pitch angle [°]


[min-1] 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
1152 - 0,037 0,039 0,041 0,043 0,047 0,050 0,054 0,057 0,061 0,073 0,085 0,098 0,110 0,123 0,135 0,148
motor 0,37
1728 - 0,124 0,131 0,138 0,147 0,158 0,169 0,181 0,193 0,204 0,246 0,288 0,330 0,372 0,414 0,456 0,498
motor 0,37 0,55
3456 - 0,995 1,05 1,10 1,17 1,27 1,35 1,45 1,54 1,63 1,97 2,30 2,64 2,98 3,31 3,65 3,99
motor 1,1 1,5 2,2 3 -*
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

A09-IN V2016/November 29
[kW]
power(kw)
Performance
Curve
0.8
645003, AXV-AL 450, 3456, 1728, 1152
AXV 450, 60 Hz !" Hub: 150-7
6
AbsorbedPower

0.2

0.6 32°
Absorbed

30°
0.15 4 28°
26°
24°
0.4
22°
0.1 20°

16° 18°
2 14°
0.2 10°
12° ρ = 1,2 kg/m3

0.05
[PA]
∆p(Pa)

120 j
t
Pressure
pressure

250 1000
Total

100 k
Total

e
200 800
m
80
f
a
150 600
60 b
n
g 32°
30°
100 400
28°
40
26°
c 24°
22°
h 20°
50 200
20 18°
16°
14° Lwi(A) a b c d e f g h j k m n
d 12° 2P 108 108 103 104 106 103 105 104 104 106 106 107 Speed
Pd 10° 4P 87 87 85 85 87 84 85 85 85 86 87 87 [min-1]
8° 6P 77 78 75 74 76 73 74 74 74 75 76 76
0 0 0
2500 5000 7500 10000 12500 15000 3456
2880
3456 1/min 2-pol
0.5 1 1.5 2 2.5 3 3.5 4 4.5

1000 2000 3000 4000 5000 6000 7000 8000 1728


1440
1728 1/min
0.25 0.5 0.75 1 1.25 1.5 1.75 2 2.25 4-pol

500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 1152
960
1152 1/min
0.2 0.4 0.6 0.8 1 1.2 1.4 6-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW] * Out of Range
n Pitch angle [°]
[min-1] 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
1152 0,075 0,084 0,093 0,102 0,112 0,121 0,137 0,152 0,167 0,182 0,198 0,213 0,228 - - - -
motor 0,37
1728 0,252 0,283 0,314 0,345 0,377 0,410 0,461 0,513 0,564 0,616 0,667 0,719 0,770 - - - -
motor 0,37 0,55 0,75 1,1
3456 2,02 2,26 2,51 2,76 3,02 3,28 3,69 4,10 4,52 4,93 5,34 5,75 6,16 - - - -
motor 2,2 3 4 -*
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

30 A09-IN V2016/November
[kW]
power (kw)
AbsorbedPower
Performance
Curve
1.25 10
AXV 500, 60 Hz
645004, AXV-AL 500, 3456, 1728, 1152
!" Hub: 150-7

0.3 32°
1
Absorbed

7.5 30°
28°
0.75 26°
0.2 24°
5
22°
0.5 20°

16° 18°
0.1 2.5 14°
0.25 10°
12° ρ = 1,2 kg/m3

350 1400
[PA]
∆pt(Pa)

j
Pressure

k
140
pressure

300 1200
m
Total
Total

120 a
e
250 1000

100
f
200 800
b
80 n

32°
150 600 g
30°
60
28°
c
26°
100 400 24°
40
22°
h 20°
18°
50 200 16°
20
14° Lwi(A) a b c d e f g h j k m n
d 12° 2P 106 105 103 105 105 104 105 106 106 106 107 108 Speed
10°
Pd
8° 4P 86 87 85 86 87 85 86 87 87 87 88 89 [min-1]
6P 76 76 75 75 76 74 75 76 76 76 77 78
0 0 0
2500 5000 7500 10000 12500 15000 17500 20000 22500 2880
3456
3456 1/min 2-pol
1 2 3 4 5 6

2000 4000 6000 8000 10000 12000 1440


1728
1728 1/min
0.5 1 1.5 2 2.5 3 4-pol

1000 2000 3000 4000 5000 6000 7000 8000 1152


960
1152 1/min
0.25 0.5 0.75 1 1.25 1.5 1.75 2 2.25 6-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW] * Out of Range

n Pitch angle [°]


[min-1] 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
1152 0,099 0,117 0,135 0,152 0,170 0,187 0,214 0,241 0,268 0,295 0,322 0,350 0,377 - - - -
motor 0,37 0,55
1728 0,336 0,395 0,454 0,514 0,573 0,633 0,723 0,814 0,905 0,997 1,09 1,18 1,27 - - - -
motor 0,37 0,55 0,75 1,1 1,5
3456 2,69 3,16 3,64 4,11 4,59 5,06 5,79 6,51 7,24 7,97 8,71 9,44 10,2 - - - -
motor 3 4 -*
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

A09-IN V2016/November 31
AbsorbedPower [kW]
power (kw)
Performance
Curve
2.5 20 645021, AXV-AL 560, 3456, 1728, 1152
AXV 560, 60 Hz !" Hub: 200-9

0.6 2
15 32°
Absorbed

30°
1.5 28°
0.4 26°
10
24°
1 22°

18° 20°
0.2 5 16°
14°
0.5 12°

10° ρ = 1,2 kg/m3

400
[PA]
∆pt (Pa)

175 j

1500
Pressure
pressure

k
350
150
Total
Total

1250 a
m
300
e
125

f
250 1000

100
b n

200 g 32°
750
30°
75
28°
150
26°
500 c
24°
50
100 h 22°
20°
18°
250 16°
25
50 14°
12° Lwi(A) a b c d e f g h j k m n
d 2P 112 110 110 109 113 112 111 113 114 115 115 116 Speed
10°
Pd 8° 4P 92 92 93 90 95 93 92 94 95 95 95 96 [min-1]
6P 81 81 83 79 85 82 81 82 85 85 85 85
0 0 0
5000 10000 15000 20000 25000 30000 35000 2880
3456
3456 1/min 2-pol
2 3 4 5 6 7 8 9

2000 4000 6000 8000 10000 12000 14000 16000 1728


1440
1728 1/min
1 1.5 2 2.5 3 3.5 4 4.5 4-pol

2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 1152
960
1152 1/min
0.5 0.75 1 1.25 1.5 1.75 2 2.25 2.5 2.75 3 6-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
1152 0,180 0,205 0,231 0,256 0,282 0,308 0,336 0,394 0,452 0,510 0,568 0,626 0,684 - - - -
motor 0,37 0,55 0,75
1728 0,607 0,692 0,778 0,864 0,952 1,04 1,13 1,33 1,52 1,72 1,92 2,11 2,31 - - - -
motor 0,75 1,1 1,5 2,2 3
3456 4,85 5,54 6,23 6,91 7,61 8,33 9,06 10,6 12,2 13,8 15,3 16,9 18,4 - - - -
motor 5,5 7,5 11 15 18,5
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

32 A09-IN V2016/November
[kW]
power (kw)
Performance
Curve
645002, AXV-AL 630, 3456, 1728, 1152
AXV 630, 60 Hz !" Hub: 200-9

1.5 5 40 40°
AbsorbedPower

38°
36°
Absorbed

4
30 34°
1 32°
3 30°
20 28°

2 26°
24°
0.5 22°
20°
18°
10 16°
1 14°
10°
12° ρ = 1,2 kg/m3
[PA]
∆pt(Pa)

j
225 500 2000
Pressure

k
pressure

200 450
1750
Total

e
Total

175 400 f
1500 a
n
350
150 40°
1250 38°
g
300
36°
125
b 34°
250 1000 32°
100 30°
200 h 28°
750
26°
75
24°
150
c 22°
500
50 20°
100 18°
16°
250 14°
25 d Lwi(A) a b c d e f g h j k m n
50 12°
Pd 10° 2P 114 113 110 111 116 113 113 115 116 116 116 118 Speed
4P 95 96 92 93 99 95 94 96 98 98 98 99 [min-1]
6P 83 85 81 82 88 84 83 85 87 87 87 88
0 0 0
10000 15000 20000 25000 30000 35000 40000 45000 50000 55000 2880
3456
3456 1/min 2-pol
2 4 6 8 10 12 14

5000 7500 10000 12500 15000 17500 20000 22500 25000 27500 1440
1728
1728 1/min
1 2 3 4 5 6 7 4-pol

2500 5000 7500 10000 12500 15000 17500 1152


960
1152 1/min
1 1.5 2 2.5 3 3.5 4 4.5 5 6-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW] * Out of Range

n Pitch angle [°]


[min-1] 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
1152 - 0,316 0,379 0,442 0,505 0,568 0,624 0,699 0,765 0,831 0,942 1,05 1,17 1,28 1,39 1,50 1,63
motor 0,37 0,55 0,75 1,1 1,5 2,2
1728 - 1,07 1,28 1,49 1,70 1,92 2,14 2,36 2,58 2,80 3,18 3,56 3,93 4,31 4,69 5,06 5,44
motor 1,1 1,5 2,2 3 4 5,5
3456 - 8,54 10,2 11,9 13,6 15,3 17,1 18,9 20,7 22,4 25,4 28,5 31,5 34,5 37,5 40,5 43,6
motor 11 15 18,5 -*
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

A09-IN V2016/November 33
[kW]
power (kw)
Performance
Curve
2.5 645006, AXV-AL 710, 1728, 1152, 864
AXV 710, 60 Hz !" Hub: 250-9
1 8
AbsorbedPower

36°
2 34°
Absorbed

0.75 6 32°
30°
1.5
28°

0.5 4 26°

1 24°

20°
22°
18°
0.25 2 16°
0.5 14°
10°
12° ρ = 1,2 kg/m3

175 700
[PA]
∆pt(Pa)

300
h
Pressure

j
pressure

150 600
k
Total

250
Total

d
125 500

200
e
m
100 400
36°
34°
150 f
a 32°
75 300
30°
28°

100 b 26°
50 200 g 24°
22°
20°
18°
50 16°
25 100
14°
12° Lwi(A) a b c d e f g h j k m n
c 4P
2P 99 97 95 98 97 97 99 102 102 103 105 - Speed
Pd 10°
8° 6P
4P 89 87 84 88 86 86 88 90 90 91 92 - [min-1]
8P
6P 81 80 76 80 78 79 80 83 83 83 85 -
0 0 0
5000 10000 15000 20000 25000 30000 35000 1728
1440
2880
1728 1/min 4-pol
2-pol
2 3 4 5 6 7 8 9 10

5000 7500 10000 12500 15000 17500 20000 22500 25000 1152
960
1440
1152 1/min 6-pol
4-pol
1 2 3 4 5 6 7

2500 5000 7500 10000 12500 15000 17500 720


864
960
864 1/min
1 1.5 2 2.5 3 3.5 4 4.5 5 8-pol
6-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
864 0,215 0,257 0,302 0,348 0,394 0,441 0,487 0,534 0,610 0,685 0,761 0,837 0,912 0,988 1,06 - -
motor 0,37 0,55 0,75 1,1
1152 0,510 0,609 0,715 0,825 0,935 1,04 1,15 1,27 1,45 1,62 1,80 1,98 2,16 2,34 2,52 - -
motor 0,55 0,75 1,1 1,5 2,2 3
1728 1,72 2,06 2,41 2,78 3,15 3,52 3,90 4,27 4,88 5,48 6,09 6,69 7,30 7,91 8,51 - -
motor 2,2 3 4 5,5 7,5 11
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

34 A09-IN V2016/November
[kW]
power (kw)
Performance
Curve
15 645012, AXV-AL 800, 1728, 1152, 864
AXV 800, 60 Hz !" Hub: 250-9
4
AbsorbedPower

1.5 36°
34°
Absorbed

3 10 32°
30°
1 28°
2 26°
24°
5
20°
22°
0.5 18°
1 16°
14°
10°
12° ρ = 1,2 kg/m3

[PA]
∆pt(Pa)

k
Pressure

175 700
pressure

300
m
Total
Total

150 600
a e
250

f n
125 500
b 36°
200 34°

100 400 32°


g
30°
150 28°
c
75 300 26°
h 24°
100 22°
50 200 20°
18°
16°
50 14°
25 100 12°
d Lwi(A) a b c d e f g h j k m n
10°
Pd 8°
4P 100 100 103 97 106 100 100 100 105 105
2P 105 106 Speed
6P 89 89 93 87 96 89 89 90 94 94
4P 94 94 [min-1]
8P 81 81 86 79 88 81 81 82 86 86
6P 86 87
0 0 0
5000 10000 15000 20000 25000 30000 35000 40000 45000 50000 2880
1440
1728
1728 1/min 2-pol
4-pol
2 4 6 8 10 12 14

5000 10000 15000 20000 25000 30000 35000 1440


1152
960
1152 1/min
1 2 3 4 5 6 7 8 9 10 4-pol
6-pol

2500 5000 7500 10000 12500 15000 17500 20000 22500 25000 960
720
864
864 1/min
1 2 3 4 5 6 7 6-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
864 0,321 0,388 0,458 0,529 0,602 0,674 0,747 0,820 0,949 1,08 1,21 1,34 1,47 1,60 1,73 - -
motor 0,37 0,55 0,75 1,1 1,5 2,2
1152 0,761 0,921 1,08 1,26 1,43 1,60 1,77 1,94 2,25 2,56 2,86 3,17 3,48 3,78 4,09 - -
motor 1,1 1,5 2,2 3 4 5,5
1728 2,57 3,11 3,66 4,23 4,81 5,39 5,97 6,56 7,59 8,63 9,66 10,7 11,7 12,8 13,8 - -
motor 3 4 5,5 7,5 11 15
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

A09-IN V2016/November 35
Absorbed power [kW]

3
Performance
Curve
25
645011, AXV-AL 900, 1728, 1152, 864
AXV 900, 60 Hz !" Hub: 300-10

6 20
32°
30°
2 28°
15
4 26°
24°
10 22°

1 20°
2 18°
16°
5 14°
12°
10° ρ = 1,2 kg/m3

250 1000
Total pressure ∆pt [PA]

400
j

200 800

a k
d
300

150 600
e
m
b
32°
30°
200
f 28°
100 400
26°
24°
22°
g 20°
100
50 200 18°
16°
14°
12° Lwi(A) a b c d e f g h j k m n
c 4P
2P 104 106 102 105 102 102 103 105 105 106 106 - Speed
Pd 10°
8° 6P
4P 93 96 92 95 92 91 92 95 94 95 96 - [min-1]
8P
6P 85 88 85 88 84 84 85 87 87 87 88
0 0 0
10000 20000 30000 40000 50000 60000 70000 1728
1440
2880
1728 1/min 4-pol
2-pol
5 7.5 10 12.5 15 17.5 20

10000 15000 20000 25000 30000 35000 40000 45000 1152


960
1440
1152 1/min 6-pol
4-pol
2 4 6 8 10 12

5000 10000 15000 20000 25000 30000 35000 720


864
960
864 1/min
2 3 4 5 6 7 8 9 10 8-pol
6-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW] * Out of Range

n Pitch angle [°]


[min-1] 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
864 0,649 0,787 0,926 1,07 1,21 1,35 1,58 1,81 2,04 2,28 2,51 2,74 2,97 - - - -
motor 0,75 1,1 1,5 2,2 3
1152 1,54 1,87 2,19 2,53 2,86 3,20 3,74 4,29 4,84 5,39 5,95 6,50 7,05 - - - -
motor 2,2 3 4 5,5 7,5
1728 5,19 6,30 7,41 8,53 9,66 10,8 12,6 14,5 16,3 18,2 20,1 21,9 23,8 - - - -
motor 5,5 7,5 11 15 18,5 22 30
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

36 A09-IN V2016/November
Absorbed power [kW]

5
Performance
Curve
40
AXV 1000, 60 Hz
645000, AXV-AL 1000, 1728, 1152, 864
!" Hub: 300-10

10
4 32°
30
30°
7.5 28°
3
26°
20 24°

2 5 22°
20°
18°
10 16°
1 2.5 14°
10°
12° ρ = 1,2 kg/m3

Total pressure ∆pt [PA]

300 1200
k
500

250 1000
m
a e
400

200 800 f

300 32°
b 30°
150 600
g
28°

26°
200 24°
100 400
22°
h 20°
c
18°
100 16°
50 200 14°
12° Lwi(A) a b c d e f g h j k m n
d
10°

4P 108 109 103 105 108 106 106 107 109 108 109 110
2P Speed
Pd 6P 96 100 93 94 98 95 95 96 99 98 99 99
4P [min-1]
8P 89 93 86 87 91 88 88 89 92 91 92 92
6P
0 0 0
20000 40000 60000 80000 100000 2880
1440
1728
1728 1/min 2-pol
4-pol
5 10 15 20 25

10000 20000 30000 40000 50000 60000 1440


1152
960
1152 1/min
2 4 6 8 10 12 14 16 18 4-pol
6-pol

5000 10000 15000 20000 25000 30000 35000 40000 45000 50000 960
720
864
864 1/min
2 4 6 8 10 12 14 6-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
864 1,13 1,38 1,63 1,88 2,13 2,38 2,74 3,11 3,47 3,84 4,21 4,57 4,94 - - - -
motor 1,5 2,2 3 4 5,5
1152 2,68 3,27 3,86 4,45 5,04 5,63 6,50 7,37 8,24 9,10 9,97 10,8 11,7 - - - -
motor 3 4 5,5 7,5 11 15
1728 9,05 11,0 13,0 15,0 17,0 19,0 21,9 24,9 27,8 30,7 33,7 36,6 39,5 - - - -
motor 11 15 18,5 22 30 37 45
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

A09-IN V2016/November 37
[kW]
power (kw)

8
Performance
Curve
20 645196
AXV-AL AXV-AL 1120,
1120, 1728, 1728,
1152, 8641152, 864
AXV 1120, 60 Hz !" Hub: 300-5

60 40°
AbsorbedPower

38°
36°
15 34°
6
Absorbed

32°
40 30°
28°
4 10 26°
24°
22°
20 20°
2 5 18°
16°
14°
12° ρ = 1,2 kg/m3
10°
[PA]
∆pt(Pa)

500
Pressure
pressure

a
250 1000 h
j
Total
Total

400 e k

40°
b
200 800 38°

f 36°

300 34°
32°
150 600 30°
28°
c 26°
200 24°
100 400 22°
g 20°
18°
16°

100 14°
50 200 d 12°
10°
Lwi(A) a b c d e f g h j k m n
4P
2P 110 110 110 106 115 106 107 115 116 116 - - Speed
Pd
6P
4P 100 100 100 97 104 96 97 104 105 105 - - [min-1]
8P
6P 92 92 93 89 97 88 89 96 97 97 - -
0 0 0
20000 40000 60000 80000 100000 120000 140000 1728
1440
2880
1728 1/min 4-pol
2-pol
5 10 15 20 25 30 35 40

10000 20000 30000 40000 50000 60000 70000 80000 90000 1152
960
1440
1152 1/min 6-pol
4-pol
2.5 5 7.5 10 12.5 15 17.5 20 22.5 25

10000 20000 30000 40000 50000 60000 70000 720


864
960
864 1/min 8-pol
2.5 5 7.5 10 12.5 15 17.5 20 6-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
864 - 1,36 1,70 2,03 2,37 2,72 3,08 3,53 4,00 4,48 4,95 5,44 5,93 6,41 6,90 7,39 7,88
motor 1,5 2,2 3 4 5,5 7,5 11
1152 - 3,23 4,02 4,81 5,62 6,44 7,31 8,37 9,48 10,6 11,7 12,9 14,0 15,2 16,3 17,5 18,7
motor 4 5,5 7,5 11 15 18,5 22
1728 - 10,9 13,6 16,2 19,0 21,7 24,7 28,3 32,0 35,8 39,6 43,5 47,4 51,3 55,2 59,1 63,0
motor 11 15 18,5 22 30 37 45 55 75
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

38 A09-IN V2016/November
(kw)
Power [kW]

15
Performance
Curve
645100 AXV-AL
AXV-AL 1250,
1250, 1728, 1728,
1152, 8641152, 864
AXV 1250, 60 Hz !" Hub: 370-6
40°
Absorbed power

30 100 38°
36°
34°
Absorbed

10 32°
30°
20 28°
26°
50 24°
22°
5 20°
10 18°
16°
12° 14° ρ = 1,2 kg/m3
10°
350
(Pa)
∆pt [PA]

600
Pressure

1250
pressure

300
h
j
Total

500
Total

a e
k
250 1000 40°
38°
400
36°
200 34°
750
b f 32°
300 30°
150 28°
26°
500 24°
c
200 22°
100 20°
18°
g 16°
250 14°
100 d 12°
50
10°
Lwi(A) a b c d e f g h j k m n
Pd 4P 111 114 109 110 115 114 110 117 117 118 -
2P - Speed
6P 100 104 100 100 104 104 100 107 107 107 -
4P - [min-1]
8P 93 97 93 93 97 96 93 99 100 100 -
6P -
0 0 0
25000 50000 75000 100000 125000 150000 175000 2880
1440
1728
1728 1/min
5 10 15 20 25 30 35 40 45 50 2-pol
4-pol

20000 40000 60000 80000 100000 120000


1152 1/min 1440
1152
960
5 10 15 20 25 30 35 4-pol
6-pol

10000 20000 30000 40000 50000 60000 70000 80000 90000 960
720
864
864 1/min
2.5 5 7.5 10 12.5 15 17.5 20 22.5 25 6-pol
8-pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
864 - 2,38 2,79 3,21 3,77 4,54 5,37 6,20 7,05 7,90 8,76 9,62 10,5 11,3 12,2 13,0 13,7
motor 3 4 5,5 7,5 11 15
1152 - 5,63 6,60 7,60 8,93 10,8 12,7 14,7 16,7 18,7 20,8 22,8 24,8 26,8 28,9 30,9 32,5
motor 7,5 11 15 18,5 22 30 37
1728 - 19,0 22,3 25,7 30,2 36,3 43,0 49,6 56,4 63,2 70,1 76,9 83,8 90,6 97,4 104,2 109,6
motor 22 30 37 45 55 75 90 110
Fan test laboratory AMCA 210/99 Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do Standard 301. Values shown are for inlet LwiA sound power levels for installation
not include the effects of appurtenances (accessories-belt cover, pulley & belt). Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

A09-IN V2016/November 39
[kW]
power(kw)

12.5
Performance
Curve
25 60 645194 AXV-AL
AXV-AL 1400,
1400, 1152, 1152,
864, 691 864, 691
AXV 1400, 60 Hz !" Hub: 420-6

40°
AbsorbedPower

38°
10 20 36°
34°
Absorbed

40 32°
7.5 15 30°
28°
26°
24°
5 10
22°
20 20°
18°
2.5 5 16°
14° ρ = 1,2 kg/m3
12°
10°
[PA]

300
∆pt(Pa)

a
800
Pressure
pressure

j k
400
250 e m
Total
Total

n
600 40°
b
200 38°
300 f
36°

34°

32°
150
400 30°

200 c 28°
g
26°
24°
100
22°
20°
200 18°
100 h 16°
50 14°
d 12°
10° Lwo(A) a b c d e f g h j k m n
Pd 6P 106 104 107 104 106 109 102 104 113 111 109 110 Speed
8P 99 97 100 97 98 102 95 97 105 104 103 103 [min-1]
10P 94 91 95 92 93 96 90 91 99 99 97 98
0 0 0
25000 50000 75000 100000 125000 150000 175000 2880
1152
960
1152 1/min 6-pol
2-pol
5 10 15 20 25 30 35 40 45 50

20000 40000 60000 80000 100000 120000 1440


720
864
864 1/min
5 10 15 20 25 30 35 8-pol
4-pol

576
20000 40000 60000 80000 100000 691
960
691 1/min 10-
5 10 15 20 25 30 10-pol
6-pol
pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
691 - 1,86 2,29 2,73 3,13 3,81 4,52 5,25 5,98 6,70 7,42 8,15 8,86 9,60 10,3 11,0 11,8
motor 2,2 3 4 5,5 7,5 11 15
864 - 3,63 4,47 5,33 6,13 7,45 8,84 10,3 11,7 13,1 14,5 15,9 17,3 18,8 20,2 21,6 23,0
motor 4 5,5 7,5 11 15 18,5 22 30
1152 - 8,60 10,6 12,6 14,5 17,6 20,9 24,3 27,7 31,1 34,4 37,7 41,1 44,5 47,9 51,2 54,6
motor 11 15 18,5 22 30 37 45 55
Fan test laboratory AMCA 210/99 Fig.15,Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation
installation type
type D
A - Ducted
Free inlet,
inlet,
Free
Ducted
outlet.
outlet.
Performance
Performance
ratings
ratings
do not
do Standard 301.
301. Values
Values shown
shown are
areforforoutlet LwoAsound
inlet LwiA sound power
power levels
levels for installation
not include
include the effects
the effects
of appurtenances
of appurtenances
(accessories-belt
(accessories-belt
cover,
cover,
pulley
pulley
& belt).
& belt). Type A:
D: free inlet,
ducted freeducted
inlet, outlet.outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

40 A09-IN V2016/November
[kW]
power (kw)
Performance
Curve
645203 1600,
AXV-AL AXV-AL 1600,
1152, 864,1152,
691 864, 691
AXV 1600, 60 Hz !" Hub: 420-6
40°
100
38°
AbsorbedPower

40
20 36°
34°
Absorbed

75 32°
15 30 30°
28°
26°
20 50 24°
10
22°
20°
18°
5 10 25
14°
16° ρ = 1,2 kg/m3
12°
10°
[PA]
∆pt(Pa)

400
Pressure

600
pressure

1000
350 a e
Total
Total

500 j

300 f k
800
m
b
400 40°
250
38°
g
36°
600
34°
200
300 32°
c 30°
28°
150
400 26°
200 24°
22°
100 20°
h 18°
200 16°
100 14°
d 12°
50
10° Lwo(A) a b c d e f g h j k m n
6P 106 108 110 109 109 112 112 113 116 115 116 - Speed
Pd
8P 99 101 103 102 102 104 105 106 108 108 108 - [min-1]
10P 94 95 97 96 96 99 99 100 102 102 102 -
0 0 0
50000 100000 150000 200000 250000 2880
1152
960
1152 1/min 6-pol
6-pol
2-pol
10 20 30 40 50 60 70

25000 50000 75000 100000 125000 150000 175000 1440


720
864
864 1/min
10 20 30 40 50 8-pol
8-pol
4-pol

576
25000 50000 75000 100000 125000 150000 691
960
691 1/min 10-
5 10 15 20 25 30 35 40 10-pol
6-pol
pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
691 - 3,68 4,49 5,31 6,13 7,02 8,24 9,55 10,9 12,3 13,7 15,2 16,6 18,1 19,5 21,0 22,5
motor 4 5,5 7,5 11 15 18,5 22 30
864 - 7,19 8,77 10,4 12,0 13,7 16,1 18,5 21,3 24,1 26,8 29,6 32,4 35,3 38,1 41,0 43,9
motor 7,5 11 15 18,5 22 30 37 45
1152 - 17,0 20,8 24,6 28,4 32,5 38,2 44,3 50,6 57,0 63,6 70,2 76,9 83,6 90,4 97,3 104,1
motor 18,5 22 30 37 45 55 75 90 110
Fan test laboratory AMCA 210/99 Fig.15,Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation
installation type
type D
A - Ducted
Free inlet,
inlet,
Free
Ducted
outlet.
outlet.
Performance
Performance
ratings
ratings
do not
do Standard 301.
301. Values
Values shown
shown are
areforforoutlet
inlet LwiA
LwoAsound
sound power
power levels
levels for installation
not include
include the the
effects
effects
of appurtenances
of appurtenances
(accessories-belt
(accessories-belt
cover,
cover,
pulley
pulley
& belt).
& belt). Type A:
D: free
ducted
inlet,
inlet,
freeducted
outlet.outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

A09-IN V2016/November 41
[kW]
power(kw)

40
Performance
Curve
200 645302, AXV-AL 1800, 1152, 864, 691
AXV 1800, 60 Hz !" Hub: 540-6

75 40°
AbsorbedPower

38°
36°
150 34°
Absorbed

30 32°
30°
50
28°
100 26°
20 24°
22°
25 20°
50 18°
10
16°
12° 14° ρ = 1,2 kg/m3
10°
[PA]

500
∆pt(Pa)

a
Pressure
pressure

450 700 1250


j k
e m
Total

400
Total

600 n
1000 40°
350 b
38°
500 f
36°
300
34°
750
400 32°
250
30°
c 28°
200 g
300 26°
500 24°
150 22°
20°
200 18°
h
100 16°
250 14°
d 12°
100
50 10° Lwo(A) a b c d e f g h j k m n
Pd 6P 114 112 115 111 113 117 110 111 121 120 117 118 Speed
8P 107 105 108 105 105 109 103 105 113 112 111 111 [min-1]
10P 102 99 102 99 100 104 98 99 107 106 105 106
0 0 0
5.0x10
4
1.0x10
5
1.5x10
5
2.0x10
5
2.5x10
5
3.0x10
5
3.5x10
5
2880
1152
960
1152 1/min 6-pol
2-pol
20 40 60 80 100

4 5 5 5 5
5.0x10 1.0x10 1.5x10 2.0x10 2.5x10 1440
720
864
864 1/min
10 20 30 40 50 60 70 80 8-pol
4-pol

576
2.50x10
4
5.00x10
4
7.50x10
4
1.00x10
5
1.25x10
5
1.50x10
5
1.75x10
5
2.00x10
5
2.25x10
5
691
960
691 1/min 10-
10 20 30 40 50 60 10-pol
6-pol
pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
691 - 6,50 8,01 9,56 11,0 13,3 15,8 18,4 20,9 23,5 26,0 28,5 31,0 33,6 36,2 38,7 41,3
motor 7,5 11 15 18,5 22 30 37 45
864 - 12,7 15,7 18,7 21,4 26,1 30,9 35,9 40,9 45,9 50,8 55,8 60,7 65,7 70,7 75,7 80,7
motor 15 18,5 22 30 37 45 55 75 90
1152 - 30,0 37,0 44,3 50,8 61,8 73,3 85,2 97,0 108,7 120,5 132,2 143,8 155,8 167,6 179,5 191,3
motor 30 37 45 55 75 90 110 132 160 200
Fan test laboratory AMCA 210/99 Fig.15,Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation
installation type
type D
A - Ducted
Free inlet,
inlet,
Free
Ducted
outlet.
outlet.
Performance
Performance
ratings
ratings
do not
do Standard 301.
301. Values
Values shown
shown are
areforforoutlet LwoAsound
inlet LwiA sound power
power levels
levels for installation
not include
include the effects
the effects
of appurtenances
of appurtenances
(accessories-belt
(accessories-belt
cover,
cover,
pulley
pulley
& belt).
& belt). Type A:
D: free inlet,
ducted freeducted
inlet, outlet.outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

42 A09-IN V2016/November
power [kW]
(kw) Performance
Curve
645402, AXV-AL 2000, 1152, 864, 691
AXV 2000, 60 Hz !" Hub: 600-6

300 40°
Absorbed Power

38°
60 36°
34°
Absorbed

100 32°
30°
200
40 28°
26°
24°
22°
50
100 20°
20 18°
16°
12° 14° ρ = 1,2 kg/m3
10°
1750
∆pt (Pa)
[PA]

600 a
Pressure
pressure

1500 j k
800 e
Total

m
500
Total

n
1250
40°
b
38°
400
f
600 36°
1000
34°
32°
300
30°
750 c 28°
400 g
26°
24°
200 22°
500
20°
18°
h
200 16°
14°
100 d
250 12°
10° Lwo(A) a b c d e f g h j k m n
6P 117 115 118 115 116 120 113 115 124 123 121 121 Speed
Pd 8P 110 108 111 108 109 113 106 108 116 115 114 114 [min-1]
10P 105 102 105 103 103 107 101 102 110 110 108 109
0 0 0
5 5 5 5 5
1.0x10 2.0x10 3.0x10 4.0x10 5.0x10 2880
1152
960
1152 1/min 6-pol
6-pol
2-pol
20 40 60 80 100 120 140

4 5 5 5 5 5 5 5
5.00x10 1.00x10 1.50x10 2.00x10 2.50x10 3.00x10 3.50x10 4.00x10 1440
720
864
864 1/min
20 40 60 80 100 8-pol
8-pol
4-pol

576
691
960
4 5 5 5 5 5
5.00x10 1.00x10 1.50x10 2.00x10 2.50x10 3.00x10
691 1/min 10-
10 20 30 40 50 60 70 80 10-pol
6-pol
pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
691 - 11,0 13,6 16,2 18,5 22,6 26,8 31,1 35,4 39,7 44,0 48,3 52,5 56,9 61,2 65,5 69,8
motor 11 15 18,5 30 37 45 55 75
864 - 21,5 26,5 31,6 36,3 44,1 52,3 60,8 69,2 77,6 86,0 94,3 102,6 111,2 119,6 128,1 136,5
motor 22 30 37 45 55 75 90 110 132 160
1152 - 50,9 62,8 74,9 86,0 104,5 124,1 144,1 164,0 183,9 203,8 223,6 243,3 263,6 283,6 303,6 323,6
motor 55 75 90 110 132 160 200 250 315 355
Fan test laboratory AMCA 210/99 Fig.15,Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation
installation type
type D
A - Ducted
Free inlet,
inlet,
Free
Ducted
outlet.
outlet.
Performance
Performance
ratings
ratings
do not
do Standard 301.
301. Values
Values shown
shown are
areforforoutlet
inlet LwiA
LwoAsound
sound power
power levels
levels for installation
not include
include the the
effects
effects
of appurtenances
of appurtenances
(accessories-belt
(accessories-belt
cover,
cover,
pulley
pulley
& belt).
& belt). Type A:
D: free
ducted
inlet,
inlet,
freeducted
outlet.outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

A09-IN V2016/November 43
power [kW]
Absorbed Power (kw)
Performance
Curve
645502, AXV-AL 2200, 864, 691, 576
AXV 2200, 60 Hz !" Hub: 660-6

60 40°
100 200 38°
36°
Absorbed

34°
32°
30°
40
28°
26°
50 100 24°
22°
20 20°
18°
16°
ρ = 1,2 kg/m3
12° 14°
10°
1200
∆pt (Pa)
[PA]

500 a
Pressure

700
pressure

1000
Total

e j k
Total

600
400 m

800 n
500 b
40°
f
38°
300
36°
400
600 34°
32°
30°
300 c
200 g 28°
400 26°
24°
22°
200
20°
18°
h
100 16°
200 14°
100 d 12°
10° Lwo(A) a b c d e f g h j k m n
8P
6P 113 111 114 111 112 115 109 111 119 118 117 117 Speed
Pd 10P
8P 108 105 108 106 106 110 104 105 113 113 111 112 [min-1]
12P
10P 103 100 103 101 101 105 99 101 108 108 107 107
0 0 0
2880
1152
960
864
5 5 5 5 5
1.0x10 2.0x10 3.0x10 4.0x10 5.0x10
864 1/min 8-pol
6-pol
2-pol
20 40 60 80 100 120 140

4 5 5 5 5 5 5 5
5.00x10 1.00x10 1.50x10 2.00x10 2.50x10 3.00x10 3.50x10 4.00x10 1440
720
864
691
691 1/min
20 40 60 80 100 10-pol
8-pol
4-pol

576
691
576
960
4 5 5 5 5 5 5
5.00x10 1.00x10 1.50x10 2.00x10 2.50x10 3.00x10 3.50x10
576 1/min 10-
10 20 30 40 50 60 70 80 90 100 10-pol
12-pol
6-pol
pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
576 - 10,2 12,6 15,0 17,3 21,0 24,9 28,9 32,9 36,9 40,9 44,9 48,8 52,9 56,9 60,9 64,9
motor 11 15 18,5 22 30 37 45 55 75
691 - 17,6 21,7 25,9 29,8 36,2 43,0 49,9 56,8 63,7 70,6 77,5 84,3 91,3 98,2 105,2 112,1
motor 18,5 22 30 37 45 55 75 90 110 132
864 - 34,5 42,5 50,7 58,3 70,8 84,0 97,6 111,1 124,6 138,0 151,4 164,8 178,5 192,1 205,6 219,2
motor 37 45 55 75 90 110 132 160 200 250
Fan test laboratory AMCA 210/99 Fig.15,Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation
installation type
type D
A - Ducted
Free inlet,
inlet,
Free
Ducted
outlet.
outlet.
Performance
Performance
ratings
ratings
do not
do Standard 301.
301. Values
Values shown
shown are
areforforoutlet LwoAsound
inlet LwiA sound power
power levels
levels for installation
not include
include the effects
the effects
of appurtenances
of appurtenances
(accessories-belt
(accessories-belt
cover,
cover,
pulley
pulley
& belt).
& belt). Type A:
D: free inlet,
ducted freeducted
inlet, outlet.outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

44 A09-IN V2016/November
power [kW]
(kw)

100
Performance
Curve
645602, AXV-AL 2400, 864, 691, 576
AXV 2400, 60 Hz !" Hub: 720-6

40°
Absorbed Power

300 38°
150
36°
34°
75
Absorbed

32°
30°
100 200 28°
50 26°
24°
22°
20°
50 100 18°
25
16°
12° 14° ρ = 1,2 kg/m3
10°
∆pt (Pa)
[PA]

600 a
Pressure
pressure

800 1250
j k
Total

e m
Total

500
n
1000 40°
600 b
38°
400
f
36°

34°
750
32°
300
30°
400
28°
c
g 26°
500 24°
200
22°
20°
18°
200 h
16°
250 14°
100 d 12°
10° Lwo(A) a b c d e f g h j k m n
8P
6P 116 113 117 114 114 118 112 113 122 121 119 120 Speed
Pd 10P
8P 110 108 111 108 109 112 106 108 116 115 114 114 [min-1]
12P
10P 106 103 106 104 104 107 102 103 111 111 109 110
0 0 0
5 5 5 5 5 5 5
1.0x10 2.0x10 3.0x10 4.0x10 5.0x10 6.0x10 7.0x10 2880
1152
960
864
864 1/min 6-pol
6-pol
2-pol
8-pol
25 50 75 100 125 150 175

4 5 5 5 5 5 5 5 5 5 5
5.00x10 1.00x10 1.50x10 2.00x10 2.50x10 3.00x10 3.50x10 4.00x10 4.50x10 5.00x10 5.50x10 1440
720
864
691
691 1/min
20 40 60 80 100 120 140 10-pol
8-pol
8-pol
4-pol

576
691
960
576
4 5 5 5 5 5 5 5 5
5.00x10 1.00x10 1.50x10 2.00x10 2.50x10 3.00x10 3.50x10 4.00x10 4.50x10
576 1/min 10-
20 40 60 80 100 120 10-pol
12-pol
6-pol
pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
576 - 15,8 19,5 23,2 26,7 32,4 38,4 44,6 50,8 57,0 63,2 69,3 75,4 81,7 87,9 94,1 100,3
motor 18,5 22 30 37 45 55 75 90 110
691 - 27,3 33,6 40,1 46,0 55,9 66,4 77,1 87,8 98,4 109,0 119,6 130,2 141,0 151,7 162,4 173,1
motor 30 37 45 55 75 90 110 132 160 200
864 - 53,3 65,7 78,3 89,9 109,3 129,7 150,7 171,5 192,4 213,1 233,8 254,5 275,7 296,6 317,5 338,4
motor 55 75 90 110 132 160 200 250 315 355
Fan test laboratory AMCA 210/99 Fig.15,Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation
installation type
type D
A - Ducted
Free inlet,
inlet,
Free
Ducted
outlet.
outlet.
Performance
Performance
ratings
ratings
do not
do Standard 301.
301. Values
Values shown
shown are
areforforoutlet
inlet LwiA
LwoAsound
sound power
power levels
levels for installation
not include
include the the
effects
effects
of appurtenances
of appurtenances
(accessories-belt
(accessories-belt
cover,
cover,
pulley
pulley
& belt).
& belt). Type A:
D: free
ducted
inlet,
inlet,
freeducted
outlet.outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

A09-IN V2016/November 45
power [kW]
(kw)
Performance
Curve
645702, AXV-AL 2500, 864, 691, 576
AXV 2500, 60 Hz !" Hub: 750-6

200 400 40°


Absorbed Power

38°
36°
100
34°
Absorbed

32°
30°
28°
26°
100 200 24°
50 22°
20°
18°
16°
ρ = 1,2 kg/m3
12° 14°
10°
∆pt (Pa)
[PA]

700 1000
1500
Pressure

a
pressure

600
j k
Total

800
Total

1250 e m

500 n

40°
b
1000 38°
600 f
400 36°
34°
32°
750
30°
300
400 c 28°
g 26°
24°
500
200 22°
20°
18°
h
200 16°
250 14°
100 d 12°
10° Lwo(A) a b c d e f g h j k m n
8P
6P 117 114 118 115 115 119 113 115 123 122 120 121 Speed
Pd 10P
8P 112 109 112 109 110 114 108 109 117 116 115 116 [min-1]
12P
10P 107 104 107 105 105 109 103 104 112 112 110 111
0 0 0
5 5 5 5 5 5 5
1.0x10 2.0x10 3.0x10 4.0x10 5.0x10 6.0x10 7.0x10 2880
1152
960
864
864 1/min 8-pol
6-pol
2-pol
25 50 75 100 125 150 175 200

5 5 5 5 5 5
1.00x10 2.00x10 3.00x10 4.00x10 5.00x10 6.00x10 1440
720
864
691
691 1/min
25 50 75 100 125 150 10-pol
8-pol
4-pol

576
691
576
960
4 5 5 5 5 5 5 5 5 5
5.00x10 1.00x10 1.50x10 2.00x10 2.50x10 3.00x10 3.50x10 4.00x10 4.50x10 5.00x10
576 1/min 10-
25 50 75 100 125 12-pol
10-pol
6-pol
pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
576 - 19,4 23,9 28,4 32,7 39,7 47,1 54,7 62,3 69,9 77,4 84,9 92,4 100,1 107,7 115,3 122,9
motor 22 30 37 45 55 75 90 110 132
691 - 33,4 41,2 49,1 56,4 68,6 81,4 94,5 107,6 120,7 133,7 146,7 159,6 172,9 186,0 199,1 212,3
motor 37 45 55 75 90 110 132 160 200 250
864 - 65,3 80,5 96,0 110,3 134,1 159,1 184,7 210,3 235,9 261,3 286,7 312,0 338,0 363,6 389,3 414,9
motor 75 90 110 132 160 200 250 315 355 450
Fan test laboratory AMCA 210/99 Fig.15,Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation
installation type
type D
A - Ducted
Free inlet,
inlet,
Free
Ducted
outlet.
outlet.
Performance
Performance
ratings
ratings
do not
do Standard 301.
301. Values
Values shown
shown are
areforforoutlet LwoAsound
inlet LwiA sound power
power levels
levels for installation
not include
include the effects
the effects
of appurtenances
of appurtenances
(accessories-belt
(accessories-belt
cover,
cover,
pulley
pulley
& belt).
& belt). Type A:
D: free inlet,
ducted freeducted
inlet, outlet.outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

46 A09-IN V2016/November
power [kW]
(kw)

150
Performance
Curve
645802, AXV-AL 2600, 864, 691, 576
AXV 2600, 60 Hz !" Hub: 780-6
40°
38°
Absorbed Power

36°
200 400 34°
Absorbed

32°
100 30°
28°
26°
24°
100 200 22°
50 20°
18°
16°
14° ρ = 1,2 kg/m3
12°
10°
∆pt (Pa)
[PA]

700 1000 a
Pressure

1500
pressure

j k
600 e m
Total
Total

800 1250 n

40°
500 b
38°
f
1000 36°
600
400 34°
32°

750 30°
c 28°
300
g
400 26°
24°
500 22°
200 20°
18°
h
16°
200
14°
250 d 12°
100
10° Lwo(A) a b c d e f g h j k m n
8P
6P 118 116 119 116 117 121 114 116 124 123 122 122 Speed
Pd 10P
8P 113 110 113 111 111 115 109 110 118 118 116 117 [min-1]
12P
10P 108 105 109 106 107 110 104 106 113 113 112 112
0 0 0
2880
1152
960
864
5 5 5 5 5 5 5 5
1.0x10 2.0x10 3.0x10 4.0x10 5.0x10 6.0x10 7.0x10 8.0x10
864 1/min
25 50 75 100 125 150 175 200 225 6-pol
6-pol
2-pol
8-pol

5 5 5 5 5 5 5
1.00x10 2.00x10 3.00x10 4.00x10 5.00x10 6.00x10 7.00x10 1440
720
864
691
691 1/min
25 50 75 100 125 150 175 10-pol
8-pol
8-pol
4-pol

576
691
960
576
5 5 5 5 5
1.00x10 2.00x10 3.00x10 4.00x10 5.00x10
576 1/min 10-
25 50 75 100 125 150 10-pol
12-pol
6-pol
pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
576 - 23,5 29,0 34,6 39,8 48,3 57,3 66,6 75,8 85,0 94,2 103,3 112,4 121,8 131,0 140,3 149,5
motor 30 37 45 55 75 90 110 132 160
691 - 40,6 50,1 59,8 68,6 83,4 99,0 115,0 130,9 146,8 162,6 178,4 194,1 210,3 226,3 242,2 258,2
motor 45 55 75 90 110 132 160 200 250 315
864 - 79,4 98,0 116,8 134,2 163,1 193,5 224,7 255,9 286,9 317,9 348,7 379,5 411,1 442,3 473,5 504,7
motor 90 110 160 200 250 315 355 450 500 560
Fan test laboratory AMCA 210/99 Fig.15,Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation
installation type
type D
A - Ducted
Free inlet,
inlet,
Free
Ducted
outlet.
outlet.
Performance
Performance
ratings
ratings
do not
do Standard 301.
301. Values
Values shown
shown are
areforforoutlet
inlet LwiA
LwoAsound
sound power
power levels
levels for installation
not include
include the the
effects
effects
of appurtenances
of appurtenances
(accessories-belt
(accessories-belt
cover,
cover,
pulley
pulley
& belt).
& belt). Type A:
D: free
ducted
inlet,
inlet,
freeducted
outlet.outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

A09-IN V2016/November 47
[kW]
power(kw)
Performance
Curve
750 645902, AXV-AL 2800, 864, 691, 576
AXV 2800, 60 Hz !" Hub: 840-6
200 40°
38°
AbsorbedPower

36°
300
34°
Absorbed

150 32°
500
30°
28°
200 26°
100 24°
22°
250 20°
100 18°
50 16°
14° ρ = 1,2 kg/m3
12°
10°
2000
[PA]
∆pt(Pa)

1250
Pressure

a
800
pressure

j k
Total
Total

1000 e m
1500
n
600 40°
b
38°
750 f
36°
34°
1000
32°
400 30°

500 c 28°
g 26°
24°
22°
500 20°
200 18°
h
250 16°
14°
d 12°
10° Lwo(A) a b c d e f g h j k m n
8P
6P 120 118 121 118 119 123 116 118 127 126 124 125 Speed
Pd 10P
8P 115 112 116 113 113 117 111 112 121 120 118 119 [min-1]
12P
10P 110 108 111 108 109 112 106 108 116 115 114 115
0 0 0
2.0x10
5
4.0x10
5
6.0x10
5
8.0x10
5
1.0x10
6
2880
1152
960
864
864 1/min 8-pol
6-pol
2-pol
50 100 150 200 250 300

5 5 5 5 5 5 5 5
1.00x10 2.00x10 3.00x10 4.00x10 5.00x10 6.00x10 7.00x10 8.00x10 1440
720
864
691
691 1/min
25 50 75 100 125 150 175 200 225 10-pol
8-pol
4-pol

576
1.00x10
5
2.00x10
5
3.00x10
5
4.00x10
5
5.00x10
5
6.00x10
5
7.00x10
5
691
576
960
576 1/min 10-
25 50 75 100 125 150 175 200 12-pol
10-pol
6-pol
pol
.
Volume flow V [m³/h]
[m³/s]
Peak absorbed power [kW]
n Pitch angle [°]
[min ] -1
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
576 - 34,1 42,0 50,1 57,6 70,0 83,0 96,4 109,8 123,1 136,4 149,6 162,8 176,4 189,7 203,1 216,5
motor 37 45 55 75 90 110 132 160 200 250
691 - 58,8 72,6 86,5 99,4 120,8 143,3 166,4 189,5 212,5 235,4 258,3 281,1 304,5 327,6 350,7 373,8
motor 75 90 110 132 160 200 250 315 355 450
864 - 115,0 141,9 169,2 194,3 236,1 280,2 325,4 370,5 415,4 460,3 504,9 549,5 595,3 640,4 685,6 730,8
motor 132 160 200 250 315 355 450 500 560 630 710 -
Fan test laboratory AMCA 210/99 Fig.15,Fig.12, Test Chamber. Performance certified The A-weighted sound ratings shown have been calculated per AMCA International
is for installation
installation type
type D
A - Ducted
Free inlet,
inlet,
Free
Ducted
outlet.
outlet.
Performance
Performance
ratings
ratings
do not
do Standard 301.
301. Values
Values shown
shown are
areforforoutlet LwoAsound
inlet LwiA sound power
power levels
levels for installation
not include
include the effects
the effects
of appurtenances
of appurtenances
(accessories-belt
(accessories-belt
cover,
cover,
pulley
pulley
& belt).
& belt). Type A:
D: free inlet,
ducted freeducted
inlet, outlet.outlet. Ratings include the effects of duct end correction.
Sound power frequency spectrum Lwrel Page 54-55 Dimensions + Accessories Page 49-52

48 A09-IN V2016/November
Axial Flow Fans
Dimensions
Direct Driven
LH
s
!"
ØTk
SH

ØDa
ØDi
hF
z x Ød

bF
k1 k2 E
I1 I2 F
I max

Belt Driven

z x Ød
ØDa

ØTk
ØDi

hF2
hF

K1 bF E

I1 F

Model Da Di hF hF2 zxd Tk E F bF


size [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
355 438 359 225 750 8 x 12 405 305 355 60
400 484 401 250 810 12 x 12 448 350 400 60
450 534 450 280 860 12 x 12 497 400 450 60
500 584 504 315 1041 12 x 12 551 440 500 70
560 664 565 345 1094 16 x 14 629 500 560 70
630 734 634 400 1246 16 x 14 698 570 630 70
710 814 711 450 1454 16 x 14 775 650 710 70
800 904 797 500 1544 12* x 14 861 730 800 80
900 1004 894 580 1746 12* x 14 958 830 900 80
1000 1105 1003 630 1821 12* x 14 1067 930 990 80
1120 1245 1125 690 1990 16* x 18 1200 1050 1110 100
1250 1370 1250 750 2175 16* x 18 1337 1180 1240 100
1400 1525 1405 830 2362 16* x 18 1475 1330 1390 100
1600 1725 1605 930 2550 20* x 18 1675 1530 1590 100

LH/1 LH/2 SH
Model s k1 l1 motor s k1 l1 motor s k2 l2 lmax
size [mm] [mm] [mm] max. [mm] [mm] [mm] max. [mm] [mm] [mm] [mm]
355 2 356 420 80 2 161 225 350
400 2 371 435 90 2 161 225 400
450 2 371 435 112 2 161 225 500
500 2 396 470 112 2 151 225 600
560 2 396 470 112 3 624 700 160 3 224 300 750
630 2 396 470 112 3 624 700 160 3 224 300 750
710 2,5 395 470 112 2,5 490 565 132 2,5 225 300 600
800 2,5 385 470 112 3 614 700 160 3 214 300 750
900 3 479 565 132 4 612 700 160 4 212 300 750
1000 3 479 565 132 4 692 780 180 4 262 350 800
1120 4 592 700 160 4 892 1000 200 4 242 350 800
1250 4 592 700 160 4 892 1000 225 4 242 350 800
1400 4 892 1000 225 4 242 350 800
1600 4 892 1000 280 4 242 350 800

A09-IN V2016/November 49
AXD Abmessungen
Dimensions

SH PM LH

z-Ød

Ø Da
Ø Tk
Ø Di

hF

L2 E
L3 L1 F

Größe Da Di hF zxd Tk E F L1 L2 L3
Baugröße Da Di hF zxd Tk E F L1 L2 L3
size [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
size [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
1400 1590 1408 880 20 x 18 1510 1280 1400 310 850 1000
1800 2010 1805 1120 24x18 1920 1660 1800 400 1200 1400
1500
2000 1690
2210 1508
2005 980
1165 24 x 32x18
18 16102120 13801820 15002000 335 445 1000
1300 1165
1500
1600
2200 1790
2440 1608
2205 1050
1265 24 x 32x18
18 17102340 14602020 1600
2200 355 490 9801400 1150
1650
1800
2400 2010
2630 1810
2405 1120
1370 24 x 32x18
18 19202530 16602220 1800
2400 400 550 1200
1500 1400
1800
2000
2500 2210
2740 2010
2505 1165
1420 32 x 36x24
18 21202640 18202320 2000
2500 445 555 1300
1530 1550
1820
2100
2600 2340
2840 2110
2605 1215
1470 32 x 36x24
18 22402740 18802380 2100
2600 465 590 1350
1580 1600
1850
2200
2800 2440
3150 2210
2805 1265
1570 32 x 36x24
18 23403000 20202500 2200
2800 4901300 1400
1680 1650
1900
2400 2630 2410 1445 34 x 22 2530 2350 2550 550 1500 1820
2500 2740 2511 1420 36 x 24 2640 2320 2500 555 1530 1800
2600 2840 2612 1470 36 x 24 2740 2380 2600 590 1580 1850
2800 3150 2815 1570 36 x 24 3000 2500 2800 1300 1680 1900

63
50 A09-IN V2016/November
Axial Flow Fans
Dimensions
Square Wall Plate
4 x Ød1
A
!"
Air Flow

ØDb

A
B
I3 4 x Ød2
I4 B

Baugröße A B Db d1 d2 I3 I4
size [mm] [mm] [mm] [mm] [mm] [mm] [mm]
355 485 435 360 9 8,5 75 85
400 540 490 410 9 8,5 88 100
450 575 535 460 11 8,5 88 100
500 655 615 510 11 8,5 106 120
560 725 675 560 11 8,5 121 135
630 805 750 634 11 8,5 135 150
710 850 810 710 14,5 10,5 150 170
800 970 910 795 14,5 10,5 194 210
900 1070 1010 899 14,5 10,5 200 220
1000 1170 1110 999 14,5 10,5 200 220

Bifurcated Axial Fan hK

zxd

Air flow
Ø Tk
ØDa
ØDi

hF

bF
k1 E
l1 F

Größe ØDa ØDi ØTk E F zxd hF bF k1 l1 hK Motor max. Art.Nr.:


[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
AXV-BIF 400S 484 400 448 350 400 12x12 250 60 415 480 324 90(2.2 kW) 303719
AXV-BIF 450 534 450 497 400 450 12x12 280 60 415 480 331 90(2.2 kW) 303720
AXV-BIF 560 664 560 629 500 560 16x14 345 70 624 700 410 132(7.5 kW) 303721
AXV-BIF 630 734 630 698 570 630 16x14 400 70 624 700 435 100(2.2 kW) 303722
AXV-BIF 710 814 711 775 650 710 16x14 450 70 624 700 476 303723
AXV-BIF 800 904 800 861 730 800 12*x14 500 80 614 700 504 112(4.0 kW) 303716
AXV-BIF 900 1004 894 958 830 900 12*x14 580 80 612 700 572 132(7.5 kW) 303717
AXV-BIF1000 1105 1000 1067 930 990 12*x14 630 80 692 780 160(15.0kW) 303724

• We reserve the right to alter measurements without notice in case of technical improvements.
• The square wall plate and Bifurcated Axial Fan are not licensed by AMCA International.

A09-IN V2016/November 51
Accessories

ED LRK

Bellmouth inlet Air-operated damper

zx d

DDa
Da

Tk

Di

Da

Tk
Di
zx d

Ld
Lk U

GL-AXV EV-AXV GV-AXV

Matching flange Flexible connector compl. Up-stream guide vane


Ø Da
Ø Da
Ø Tk

Ø Tk
Ø Di

Ø Di

ØDa
ØDi

30 Le L

Model Da Di Tk zxd DDa L Ld Lk Le U


size [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
355 438 359 405 8 x 12 435 152 165 250 130 -
400 484 401 448 12 x 12 507 152 165 250 130 -
450 534 450 497 12 x 12 555 152 165 250 130 15
500 584 504 551 12 x 12 617 152 165 250 130 45
560 664 565 629 16 x 14 667 152 165 250 130 80
630 734 634 698 16 x 14 757 152 165 250 130 120
710 814 711 775 16 x 14 816 190 170 350 130 60
800 904 797 861 12* x 14 915 190 250 350 130 110
900 1004 894 958 12* x 14 1015 200 250 350 130 170
1000 1105 1003 1067 12* x 14 1115 200 250 350 130 225
1120 1245 1125 1200 16* x 18 1243 240 250 350 130 255
1250 1370 1250 1337 16* x 18 1364 240 250 400 170 375
1400 1525 1405 1475 16* x 18 1523 260 250 400 170 450
1600 1725 1605 1675 20* x 18 1723 260 250 400 170 550

52 A09-IN V2016/November
Sound Information

Sound power levels


This term refers to the power which a source radiates as sound. Sound power levels are expressed in decibels with a reference level of 1 picoWatt. The sound
power level of a source remains the same regardless of its environment and the distance to the listener.
!"
If the sound power frequency spectrum is needed, for as follows: example, the design of sound attenuators, the A- rated sound power levels at particular
octave band frequency LWA can be calculated by subtracting the relative sound Lwrel.

LWA = Lwi + Lwrel

Sound pressure level


These are pressure fluctuations generated by a source expressed in decibels with a reference level of 20 µPa. The sound pressure level varies with the
distance of a sound source to the listener and its environment.
Sound level reduction half sphere
∆L [dB] L [dB]

30
a: without reflexion
25 b: with reflexion
/ noise reduction

c: full sphere without reflexion


c
20
a
Noise reduction

15 b
Pegelabnahme

10

0
0,5 0,6 0,8 1 2 3 4 5 6 7 8 9 10
Distance [m]
Entfernung / distance [m]

Frequencies
Sound is split into different frequencies. Frequencies of human hearing range from about 20 cycles per second (Hz) to 20.000 cycles per second (Hz). For
practical purposes, WOLTER publishes noise data in eight octave bands with the centre frequencies of (63,) 125, 250, 500, 1000, 2000, 4000 and 8000 Hz.
Each fan has its own specific correction factor which is to be deducted from sound power according to the octave band and is shown on the buttom line of
each perfomance curve.

A-weighted sound pressure level in dB (A)


The human ear is more sensitive to sound in some frequencies than in others. The A-weighting is an attempt to reflect this natural perception of sound. The
A-weighting is a set of figures which are applied to the sound pressure levels. The levels in each of the octave bands are added logarithmically to give a
single figure. The A-weighting over the octave band is as follows:
Table 1) Frequency [Hz] 63 125 250 500 1000 2000 4000 8000
A-weighting [dB] -26,2 -16,1 -8,6 -3,2 0 +1,2 +1,0 -1,1

Table 2)
Addition of sound levels Difference between two sound levels Add to the higher level
[dB] [dB]
0-1 3
2-3 2
4-9 1
>
=10 0

where:
L∑ = 10 · lg(10 0,1·L1 + 10 0,1·L2 + ... + 10 0,1·Ln ) L1 = sound level of a source 1
L∑ = resulting summation sound level

Summation of several congeneric sound levels


where:
L∑ = L1 + 10 · lg(z) z = number of sources
L1 = sound level of a single source
L∑ = resulting summation sound level

A09-IN V2016/November 53
Axial Flow Fans
Sound Information

Relative Sound Power Frequency Spectrum (Lwrel) [dB]

Fan Model Poles 63 125 250 500 1000 2000 4000 8000
Size [-] [Hz] [Hz] [Hz] [Hz] [Hz] [Hz] [Hz] [Hz]
2 -14 -10 -2 -10 -19 -26 -28 -33
355 4 -10 -1 -10 -18 -26 -28 -33 -37
6 -2 -5 -14 -22 -26 -30 -35 -39
2 -11 -8 -2 -12 -15 -17 -21 -26
400 4 -8 -2 -12 -14 -17 -21 -25 -34
6 -2 -7 -13 -15 -19 -23 -30 -39
2 -8 -5 -5 -13 -18 -22 -24 -26
450 4 -4 -4 -12 -17 -21 -24 -26 -27
6 -2 -7 -14 -18 -22 -23 -25 -27
2 -8 -5 -6 -10 -15 -18 -21 -26
500 4 -4 -5 -9 -14 -17 -21 -25 -26
6 -3 -6 -11 -14 -18 -22 -25 -24
2 -11 -8 -4 -7 -15 -18 -22 -26
560 4 -7 -4 -6 -14 -18 -21 -26 -31
6 -4 -4 -11 -16 -19 -23 -28 -33
2 -9 -6 -8 -5 -13 -15 -19 -22
630 4 -6 -8 -4 -12 -15 -18 -22 -27
6 -7 -4 -7 -13 -15 -19 -23 -29
4 -7 -4 -8 -12 -14 -18 -22 -28
710 6 -4 -5 -11 -12 -16 -20 -25 -31
8 -3 -7 -11 -13 -17 -21 -27 -33
4 -6 -6 -6 -11 -13 -17 -20 -26
800 6 -5 -5 -9 -11 -15 -18 -23 -30
8 -4 -5 -10 -12 -16 -19 -25 -32
4 -7 -7 -6 -10 -11 -14 -18 -25
900 6 -7 -5 -8 -10 -12 -16 -21 -29
8 -6 -5 -9 -10 -13 -17 -24 -32
4 -7 -5 -7 -12 -12 -13 -17 -22
1000 6 -5 -5 -10 -11 -12 -15 -19 -26
8 -4 -6 -11 -10 -12 -16 -21 -30
4 -7 -6 -9 -9 -12 -15 -19 -24
1120 6 -4 -7 -8 -10 -14 -17 -21 -28
8 -4 -7 -8 -11 -14 -17 -22 -31
4 -7 -5 -9 -11 -12 -14 -18 -23
1250 6 -5 -6 -10 -10 -12 -16 -19 -27
8 -4 -8 -10 -10 -13 -17 -22 -31
6 -9 -8 -10 -9 -10 -12 -15 -20
1400 8 -7 -9 -9 -9 -10 -13 -16 -23
10 -7 -9 -9 -9 -10 -13 -18 -25
6 -9 -7 -8 -9 -11 -15 -19 -24
1600 8 -7 -7 -8 -9 -12 -17 -21 -25
10 -7 -7 -8 -9 -13 -18 -22 -26
• Sound power frequency spectrum calculated with this Lwrel are not licensed by AMCA.

54 A09-IN V2016/November
Sound Information

Fan Model Poles


Relative Sound Power Frequency Spectrum (Lwrel) [dB]

63 125 250 500 1000


!"
2000 4000 8000
Size [-] [Hz] [Hz] [Hz] [Hz] [Hz] [Hz] [Hz] [Hz]
6 -9 -7 -10 -10 -10 -12 -16 -21
1800 8 -7 -8 -9 -9 -10 -13 -17 -23
10 -7 -9 -9 -9 -10 -13 -18 -25
6 -8 -7 -10 -10 -11 -13 -16 -21
2000 8 -6 -8 -10 -9 -10 -13 -17 -24
10 -7 -9 -9 -9 -10 -14 -18 -25
8 -6 -8 -10 -10 -10 -13 -17 -24
2200 10 -6 -9 -9 -9 -11 -14 -18 -26
12 -7 -9 -9 -9 -11 -15 -20 -27
8 -6 -8 -10 -10 -11 -13 -17 -24
2400 10 -6 -9 -9 -9 -11 -14 -19 -26
12 -7 -9 -9 -9 -11 -15 -20 -27
8 -6 -8 -10 -10 -11 -14 -17 -24
2500 10 -6 -9 -9 -9 -11 -14 -19 -26
12 -7 -9 -9 -9 -11 -15 -20 -27
8 -6 -8 -10 -10 -11 -14 -17 -24
2600 10 -6 -9 -9 -9 -11 -14 -19 -26
12 -6 -9 -9 -9 -11 -15 -20 -27
8 -5 -9 -10 -10 -11 -14 -17 -24
2800 10 -6 -9 -9 -9 -11 -14 -19 -26
12 -6 -9 -9 -9 -11 -15 -20 -28
• Sound power frequency spectrum calculated with this Lwrel are not licensed by AMCA.

A09-IN V2016/November 55
Tubular Sound Attenuator for AXV
SA, SPA

SPA 450 -1D


Length
z x Ød
Size
355...1600
Pod as option
Sound attenuator
SA - without pod
SPA - with pod

Attenuators made of galvanised sheet steel. Connecting flanges correspond


to those of the AXV axial fan series. ØDi
ls
ØTk

ØDSa

Size DSa Tk Di ls 1 Length Type Pitch angle Octave band mid-frequency [Hz]
x 1D x 2D SA-1D SPA-1D SA-2D SPA-2D
[mm] [mm] [mm] [mm] [mm] [kg] [kg] [kg] [kg] setting 63 125 250 500 1k 2k 4k 8k
1D SA-1D all 2 4 6 10 14 10 7 8
355 459 405 359 355 710 12 18 16 23 SPA-1D low 4 6 8 13 20 21 18 16
400 601 448 401 400 800 14 23 19 29 med 4 6 8 12 18 19 18 14
450 650 497 450 450 900 18 29 23 36 high 4 6 8 11 13 16 16 11
2D SA-2D low 4 7 12 18 22 17 12 13
med 4 7 11 17 21 17 13 12
high 4 7 10 15 19 16 13 10
SPA-2D low 7 10 15 24 32 35 30 28
med 7 10 15 21 26 26 24 22
high 7 10 15 16 15 17 13 13
500 704 551 504 500 1000 22 36 28 43 1D SA-1D all 3 4 8 14 14 9 8 7
560 765 629 565 560 1120 25 41 31 50 SPA-1D low 4 6 9 17 26 21 18 12
630 834 698 634 630 1260 29 47 37 59 med 4 6 9 17 23 20 18 11
710 911 775 711 710 1420 37 60 47 75 high 4 6 9 16 17 16 14 11
800 997 861 797 800 1600 69 108 90 141 2D SA-2D low 6 8 14 23 24 15 13 10
med 6 8 13 22 22 14 13 9
high 6 8 12 20 18 13 11 9
SPA-2D low 8 11 16 30 39 35 32 22
med 8 11 16 27 32 32 29 19
high 8 11 16 24 23 23 24 17
900 1094 958 894 900 1800 86 135 112 176 1D SA-1D all 3 4 9 14 12 8 7 7
1000 1203 1067 1003 1000 2000 125 190 156 234 SPA-1D low 4 6 11 22 21 16 14 11
1120 1325 1200 1125 1120 2240 132 210 169 260 med. 4 6 11 20 19 15 13 11
1250 1450 1337 1250 1250 2500 146 234 185 294 high 4 6 11 17 17 14 12 11
2D SA-2D low 6 8 14 22 20 13 12 10
med. 6 8 13 21 18 12 11 10
high 6 8 12 19 15 11 10 9
SPA-2D low 8 11 19 30 32 30 24 17
med. 8 11 19 26 27 26 22 17
high 8 11 19 21 20 22 20 16
1400 1605 1475 1405 1400 2800 197 316 250 397 1D SA-1D all 4 5 10 14 11 7 6 6
1600 1805 1675 1605 1600 3200 275 540 348 682 SPA-1D low 5 7 12 21 20 14 12 9
med. 5 7 12 19 18 13 11 9
high 5 7 12 15 16 12 10 8
2D SA-2D low 8 9 15 20 19 12 11 9
med. 8 9 14 20 17 11 10 9
high 8 9 13 19 14 10 9 9
SPA-2D low 10 14 22 28 31 29 18 15
med. 10 14 22 25 27 25 16 15
high 10 14 22 21 21 21 15 14
• Low, Medium and High Pitch Angle setting correspond to 10º, 22º and 35º pitch angle approximately: for other pitch angles use interpolation.

• Sizes 1800 - 2800 TBA.

56 A09-IN V2016/November
!"
Tubular Sound Attenuator for AXV
SPA - Pressure Loss

Pressure Loss SPA - 1D


.
Volume Flow V [CFM]
1000 2000 5000 10000 20000 50000 100000 200000
500 2

300
1
200

Pressure inches water gause [in.WG]


0.5
Pressure Loss [Pa]

100
0.3
315 355 400 450 500 560 630 710 800 900 1000
1120
50 1250
0.2
1400

30 1600
0.1
20

0.05
10
0.03

5 0.02
0.3 0.5 1 2 3 5 10 20 30 50 100
.
Volume Flow V [m3/s]

Pressure Loss SPA - 2D


.
Volume Flow V [CFM]
1000 2000 5000 10000 20000 50000 100000 200000
500 2

300
1
200
Pressure inches water gause [in.WG]

0.5
Pressure Loss [Pa]

100
0.3
315 355 400 450 500 560 630 710 800 900 1000
1120
50 1250
0.2
1400

30 1600
0.1
20

0.05
10
0.03

5 0.02
0.3 0.5 1 2 3 5 10 20 30 50 100
.
Volume Flow V [m3/s]

• Performance of sound attenuator are not licensed by AMCA International.

A09-IN V2016/November 57
Wolter Sales Network
Inland Poland: Hongkong:
Ing. Günther Rößler Wentoprodukt Wolter Asia Ltd.
D-07619 Schkölen 44-100 Gliwice Hong Kong
Tel. (+49) 03 66 94 / 22 359 Tel. (+48)32 331-34-24 Tel. (+852) 0 24 / 56 01 98
Fax (+49) 03 66 94 / 22 357 Fax (+48)32 729-76-53 Fax (+852) 0 24 / 56 02 90
[email protected] [email protected] [email protected]

Mattias Industrievertretungen Portugal: India:


D-16259 Bad Freienwalde Safe Park Ventilação Industrial Lda. Wolter Ventilators India Pvt. Ltd.
Tel. (+49)03344/301994 P-2675-240 Odivelas 867 D, Block-A, Sushant Lok, Phase-I,
Fax (+49)03344/301996 Tel. (+351) 21 93 / 75 265 Gurgaon - 122009 (Haryana)
[email protected] Fax (+351) 21 93 / 86 061 Tel. +91 124 2577797, 4261001-3
[email protected] [email protected]
Industrieservice Drexler
D-49080 Osnabrück Russia: Indonesia:
Tel. (+49) 0 541 / 20 04 88 3
Euroclimat-Prof PT. Agung Kipas Kastara.
Fax (+49) 0 541 / 20 04 88 4
RU-107082 Moskau ID-14440 Jakarta Indonesia
[email protected]
Tel. (+7) 4 95 / 97 57 530 Tel. +62 (0) 21 / 6667 6925, 6667 6926
Burkhardt Projekt GmbH Fax (+7) 4 95 / 97 57 530 Fax +62 (0) 21 / 6667 6927
D-67583 Guntersblum [email protected] [email protected]
Tel. (+49) 0 62 49 / 82 01 Korea:
Schweiz:
Fax (+49) 0 62 49 / 88 58
[email protected] Anson AG Zürich Kaceco-Wolter
CH-8055 Zürich 14-1, Dang-dong,Gunpo-shi, Gyeonggi-do
Friedrich Glock Tel. (+41) 0 44 / 46 11 111 Tel. +82 (0) 31 / 4773 104
D-97980 Bad Mergentheim Fax (+41) 0 44 / 46 13 111 Fax +82 (0) 31 / 4773 132
Tel. (+49) 0 79 31 / 37 44 [email protected] [email protected] / [email protected]
Fax (+49 )0 79 31 / 28 58
Ventra Technik AG Malaysia:
[email protected]
CH-8599 Salmsach
Tel. (+41) 0 71 / 46 11 447 Vibrantech (M) Sdn Bhd.
Europe Fax (+41) 0 71 / 46 11 448 47200 Petaling Jaya Selangor, Malaysia
[email protected] Tel. +603 (0) 7847 3500
Danmark: Fax +603 (0) 7847 3380
Air-Con Danmark A/S Turkey: [email protected]
DK-8400 Ebeltoft Air Trade Centre Ltd Sti Türkiye,
Tel. (+45)086/345111 Singapore:
TR-34418 Seyrantepe / Instanbul
Fax (+45)086/345810 Tel. (+90) 02 12 / 28 34 510 Wolter Pte. Ltd.
[email protected] Fax (+90) 02 12 / 27 83 964 SG-569738 Singapore
[email protected] Tel. (+65) 0 63 / 52 95 48
Hungary: Fax (+65) 0 63 / 52 95 47
Air-Technik Légtechnikal Kft. United Kingdom: [email protected]
HU-2040 Budaörs Wolter UK Ltd.
Tel. (+36)023/428533 Sri Lanka:
GB-B37 7UQ Solihull
Fax (+36)023/428544 Tel. (+44) 01 21 / 63 55 390 Sirocco Air Technologies (Pvt) Ltd.
[email protected] Fax (+44) 01 21 / 63 55 391 28/12, Gemunu Mawatha, Kotuwegoda,
[email protected] Rajagiriya, Sri Lanka
Ireland: Tel. +94 11 7 392 010
Finheat Ltd. Middle East and North Africa Fax +94 11 7 392 015
IE-Dublin 12, Walkinstown [email protected]
Tel. (+353)01/4564066 Egypt:
Fax (+353)01/4564071 Tiba Engineering Industries Co. Taiwan:
[email protected] Nasr City, Cairo Waxlink International Co., Ltd.
Tel. (+2) 02 / 40 22 866 8F No. 218 Roosevelt Rd., Sec. 6
Lithuania: Fax (+2) 02 / 40 44 771 Taipei, Taiwan
JSC Saldos Prekyba [email protected] Tel. (+886) 02 / 89 32 11 96
LT-78109 Siauliai Fax (+886) 02 / 89 32 11 97
Tel. (+37)041/540212 Israel: [email protected]
Fax (+37)041/596176 Lea Ventilation Industries Ltd.
[email protected] IL-27113 Kiriyat-Bialik, Israel Thailand:
Tel. (+972) 0 48 / 76 23 57 Wolter Ventilation Co., Ltd.
Netherlands: Fax (+972) 0 48 / 76 20 51 Thamai Kratumban Samutsakorn 74110
AirFan B. V. [email protected] Thailand
NL-7442 CX Nijverdal Tel. +66 (0) 3486 6555
Tel. (+31)054/8366366 United Arab Emirates, Kuwait, Fax +66 (0) 3486 6599
Fax (+31)054/8365320 Lebanon: [email protected]
[email protected] Wolter Ventilation LLC
Energy International Australia
Rucon B. V. Ventilatoren P.O. Box 3562 Sharjah, UAE
NL-3840 AG Harderwijk Tel. (+971) 06 / 53 43 477 The Sydney Fan Company.
Tel. (+31)034/1411670 Fax (+971) 06 / 53 43 756 NSW 2147, Sydney, Australia
Fax (+31)034/1411690 [email protected] Tel. +61 (0) 2 / 9624 4000
[email protected]
Fax +61 (0) 2 / 9624 4100
Österreich: Asia [email protected]
Wolter Werksvertretung Österreich China Mainland:
A-4040 Linz Taizhou Wolter Ventilation Co. Ltd.
Tel. (+43) 07 32 / 75 77 07 Hengjie, Luqiao District
Fax (+43)07 32 / 75 77 07 75 Taizhou City, Zhejiang
[email protected] Tel. (+86) 576 / 26 22 666 (26 52 888)
Fax (+86) 576 / 26 56 830

Wolter GmbH
Maschinen-und Apparatebau KG
Am Wasen 11
D-76316 Malsch / Germany
Tel. +49 (0) 7204/9201-0
Fax +49 (0) 7204/9201-11
www.wolter.eu
[email protected]
&
Air in Motion - Wolter Fans - www. wolterfans.de

Reference: A09-IN, V2016/November, Printed in November, 2016

Wolter Ventilators India Pvt. Ltd. • G1-793 (A), Riico Indl. Area, Road No.: - 20 A, Bhiwadi, Distt. Alwar,
Rajasthan (India) - 301019 • TeleFax. (+91)1493 515016 • www.wolterfans.com • [email protected]

You might also like